February 2, 2005 Mr. Michael Kansler President Entergy Nuclear Operations, Inc.
440 Hamilton Avenue White Plains, NY 10601
SUBJECT:
PILGRIM NUCLEAR POWER STATION - ISSUANCE OF AMENDMENT RE:
CHANGES TO TECHNICAL SPECIFICATION TABLE 3.2.C-1 (TAC NO. MC0838)
Dear Mr. Kansler:
The Commission has issued the enclosed Amendment No. 210 to Facility Operating License No. DPR-35 for the Pilgrim Nuclear Power Station (Pilgrim). This amendment is in response to your application dated August 19, 2003, as supplemented by your letter dated March 12, 2004.
This amendment approves changes to the Pilgrim Technical Specification Table 3.2.C-1 and lowers the rod block monitor low power setpoint to conform to the value used in plant procedures and the Core Operating Limits Report.
A copy of the related Safety Evaluation is also enclosed. Notice of Issuance will be included in the Commission's biweekly Federal Register Notice.
Sincerely,
/RA/
Robert J. Fretz, Project Manager, Section 2 Project Directorate I Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket No. 50-293
Enclosures:
- 1. Amendment No. 210 to License No. DPR-35
- 2. Safety Evaluation cc w/encls: See next page
February 2, 2005 Mr. Michael Kansler President Entergy Nuclear Operations, Inc.
440 Hamilton Avenue White Plains, NY 10601
SUBJECT:
PILGRIM NUCLEAR POWER STATION - ISSUANCE OF AMENDMENT RE:
CHANGES TO TECHNICAL SPECIFICATION TABLE 3.2.C-1 (TAC NO. MC0838)
Dear Mr. Kansler:
The Commission has issued the enclosed Amendment No. 210 to Facility Operating License No. DPR-35 for the Pilgrim Nuclear Power Station (Pilgrim). This amendment is in response to your application dated August 19, 2003, as supplemented by your letter dated March 12, 2004.
This amendment approves changes to the Pilgrim Technical Specification Table 3.2.C-1 and lowers the rod block monitor low power setpoint to conform to the value used in plant procedures and the Core Operating Limits Report.
A copy of the related Safety Evaluation is also enclosed. Notice of Issuance will be included in the Commission's biweekly Federal Register Notice.
Sincerely,
/RA/
Robert J. Fretz, Project Manager, Section 2 Project Directorate I Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket No. 50-293
Enclosures:
- 1. Amendment No. 210 to License No. DPR-35
- 2. Safety Evaluation cc w/encls: See next page DISTRIBUTION:
D. Roberts C. Anderson, RI OGC PUBLIC PDI-2 R/F C. Raynor R. Fretz G. Hill (2)
ACRS F. Akstulewicz T. Ford F. Arner, RI J. Bobiak, RI Accession Number: ML050050486 Package: Tech Specs:
- SE input provided. No major changes made.
OFFICE PDI-2/PM PDI-2/LA SRXB/SC*
OGC PDI-2/SC NAME RFretz CRaynor FAkstulewicz MZobler DRoberts DATE 1/11/05 1/12/05 05/12/04 1/19/05 1/26/05 OFFICIAL RECORD COPY
Pilgrim Nuclear Power Station cc:
Resident Inspector U. S. Nuclear Regulatory Commission Pilgrim Nuclear Power Station Post Office Box 867 Plymouth, MA 02360 Chairman, Board of Selectmen 11 Lincoln Street Plymouth, MA 02360 Chairman, Duxbury Board of Selectmen Town Hall 878 Tremont Street Duxbury, MA 02332 Office of the Commissioner Massachusetts Department of Environmental Protection One Winter Street Boston, MA 02108 Office of the Attorney General One Ashburton Place 20th Floor Boston, MA 02108 Dr. Robert M. Hallisey, Director Radiation Control Program Commonwealth of Massachusetts Executive Offices of Health and Human Services 174 Portland Street Boston, MA 02114 Regional Administrator, Region I U. S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406-1415 Mr. John M. Fulton Assistant General Counsel Entergy Nuclear Operations, Inc.
440 Hamilton Avenue White Plains, NY 10601 Mr. Steve Brennion Supt., Regulatory & Industry Affairs Entergy Nuclear Operations, Inc.
Pilgrim Nuclear Power Station 600 Rocky Hill Road, M/S 1 Plymouth, MA 02360-5508 Mr. Jack Alexander Manager, Reg. Relations and Quality Assurance Pilgrim Nuclear Power Station 600 Rocky Hill Road Plymouth, MA 02360-5599 Mr. David F. Tarantino Nuclear Information Manager Pilgrim Nuclear Power Station 600 Rocky Hill Road Plymouth, MA 02360-5599 Ms. Jane Perlov Secretary of Public Safety Executive Office of Public Safety One Ashburton Place Boston, MA 02108 Mr. Stephen J. McGrail, Director Attn: James Muckerheide Massachusetts Emergency Management Agency 400 Worcester Road Framingham, MA 01702-5399 Chairman Nuclear Matters Committee Town Hall 11 Lincoln Street Plymouth, MA 02360 Mr. William D. Meinert Nuclear Engineer Massachusetts Municipal Wholesale Electric Company P.O. Box 426 Ludlow, MA 01056-0426
Pilgrim Nuclear Power Station cc:
Mr. Gary J. Taylor Chief Executive Officer Entergy Operations 1340 Echelon Parkway Jackson, MS 39213 Mr. John T. Herron Sr. VP and Chief Operating Officer Entergy Nuclear Operations, Inc.
440 Hamilton Avenue White Plains, NY 10601 Mr. Michael A. Balduzzi Site Vice President Entergy Nuclear Operations, Inc.
Pilgrim Nuclear Power Station 600 Rocky Hill Road Plymouth, MA 02360-5508 Mr. Stephen J. Bethay Director, Nuclear Assessment Entergy Nuclear Operations, Inc.
Pilgrim Nuclear Power Station 600 Rocky Hill Road Plymouth, MA 02360-5508 Mr. Bryan S. Ford Manager, Licensing Entergy Nuclear Operations, Inc.
Pilgrim Nuclear Power Station 600 Rocky Hill Road Plymouth, MA 02360-5508 Mr. Danny L. Pace Vice President, Engineering Entergy Nuclear Operations, Inc.
440 Hamilton Avenue White Plains, NY 10601 Mr. Brian OGrady Vice President, Operations Support Entergy Nuclear Operations, Inc.
440 Hamilton Avenue White Plains, NY 10601 Mr. John F. McCann Director, Nuclear Safety Assurance Entergy Nuclear Operations, Inc.
440 Hamilton Avenue White Plains, NY 10601 Ms. Charlene D. Faison Manager, Licensing Entergy Nuclear Operations, Inc.
440 Hamilton Avenue White Plains, NY 10601 Mr. Michael J. Colomb Director of Oversight Entergy Nuclear Operations, Inc.
440 Hamilton Avenue White Plains, NY 10601 Senior Resident Inspector U.S. Nuclear Regulatory Commission Pilgrim Nuclear Power Station 600 Rocky Hill Road Mail Stop 66 Plymouth, MA 02360-5508 Ms. Stacey Lousteau Treasury Department Entergy Services, Inc.
639 Loyola Avenue New Orleans, LA 70113 Jim Sniezek 5486 Nithsdale Drive Salisbury, MD 21801 Mr. Kennety L. Graesser 38832 N. Ashley Drive Lake Villa, IL 60046 Mr. Ronald Toole 1282 Valley of Lakes Box R-10 Hazelton, PA 18202 Ms. Deb Katz, Executive Director Nuclear Security Coalition c/o Citizens Awareness Network Box 83 Shelburne Falls, MA 01370
ENTERGY NUCLEAR GENERATION COMPANY ENTERGY NUCLEAR OPERATIONS, INC.
DOCKET NO. 50-293 PILGRIM NUCLEAR POWER STATION AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 210 License No. DPR-35
- 1. The Nuclear Regulatory Commission (the Commission) has found that:
A.
The application for amendment filed by Entergy Nuclear Operations, Inc. (the licensee) dated August 19, 2003, as supplemented March 12, 2004, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act),
and the Commission's rules and regulations; B.
The facility will operate in conformity with the application, the provisions of the Act, and the rules and regulations of the Commission; C.
There is reasonable assurance: (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.
The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.
2.
Accordingly, the license is amended by changes to the Technical Specifications as indicated in the attachment to this license amendment, and paragraph 3.B of Facility Operating License No. DPR-35 is hereby amended to read as follows:
B.
Technical Specifications The Technical Specifications contained in Appendix A, as revised through Amendment No. 210, are hereby incorporated in the license. The licensee shall operate the facility in accordance with the Technical Specifications.
3.
This license amendment is effective as of the date of issuance and shall be implemented within 60 days.
FOR THE NUCLEAR REGULATORY COMMISSION
/RA/
Darrell J. Roberts, Chief, Section 2 Project Directorate I Division of Licensing Project Management Office of Nuclear Reactor Regulation
Attachment:
Changes to the Technical Specifications Date of Issuance: February 2, 2005
ATTACHMENT TO LICENSE AMENDMENT NO. 210 FACILITY OPERATING LICENSE NO. DPR-35 DOCKET NO. 50-293 Replace the following page of the Appendix A Technical Specifications with the attached revised page. The revised page is identified by amendment number and contains marginal lines indicating the areas of change.
Remove Insert 3/4.2-22 3/4.2-22
Enclosure SAFETY EVALUATION BY THE OFFICE OF NUCLEAR REACTOR REGULATION RELATED TO AMENDMENT NO. 210 TO FACILITY OPERATING LICENSE NO. DPR-35 ENTERGY NUCLEAR GENERATION COMPANY ENTERGY NUCLEAR OPERATIONS, INC.
PILGRIM NUCLEAR POWER STATION DOCKET NO. 50-293
1.0 INTRODUCTION
By letter dated August 19, 2003 (Reference 1), as supplemented March 12, 2004, Entergy Nuclear Operations, Inc. (ENO or the licensee) submitted a request for changes to the Pilgrim Nuclear Power Station (Pilgrim) Technical Specifications (TSs). The requested changes would revise the rod block monitor (RBM) low power setpoint (LPSP) allowable value from 29% to 25.9% in TS Table 3.2.C-1. The proposed change corrects the RBM LPSP (currently #29%)
that was incorrectly inserted into the Pilgrim TSs under License Amendment No. 138 (Reference 2). However, plant procedures and the Core Operating Limits Report (COLR)
(Reference 3) have enforced the correct setpoint value of #25.9% since issuance of License Amendment No. 138. The proposed amendment also makes Note 5 for Table 3.2.C-1 consistent with the value used in Pilgrims COLR. The March 12, 2004, letter provided clarifying information that did not change the initial proposed no significant hazards consideration determination.
2.0 REGULATORY EVALUATION
The proposed correction to the RBM LPSP allowable value is calculated in accordance with Regulatory Guide (RG) 1.105, Instrument Setpoints for Safety-Related Systems, and the Nuclear Regulatory Commission (NRC or the Commission) approved methodology in compliance with TS 5.6.5, Core Operating Limits Report (COLR).
3.0 TECHNICAL EVALUATION
During high power operation, the RBM provides protection for control rod withdrawal error events. During low power operations, control rod blocks from the rod worth minimizer enforce specific control rod sequences designed to mitigate the consequences of the control rod drop accident. During shutdown conditions, control rod blocks from the reactor mode switch shutdown position function ensure that all control rods remain inserted to prevent inadvertent criticalities. The purpose of the RBM is to limit control rod withdrawal if localized neutron flux exceeds a predetermined setpoint during control rod manipulations. An assumed function of the RBM is to block further control rod withdrawal to preclude a minimum critical power ratio (MCPR) safety limit violation.
General Electric (GE) Topical Report NEDC-31312-P describes the RBM setpoint development and rod withdrawal error (RWE) analysis process. The RBM setpoints are selected to limit the change in MCPR during a RWE event so that the core-wide transient power-dependent MCPR requirements are bounding. Therefore, the RWE event is expected to remain non-limiting from cycle to cycle. Three RBM setpoints are selected from the RWE analysis to cover three different power ranges (high, intermediate, and low). The combined span of the three ranges is from 30% to 100% power. The high power range covers operation above the analytical limit power level of 85%. The intermediate power range spans between 65% and 85%, and the low power range spans from 30% to 65%. In Reference 4, the licensee stated the RBM LPSP allowable value of #29% did not include adequate margin for instrument uncertainty based on RG 1.105 and, therefore, would not ensure the RBM LPSP analytical limit of 30% for the RWE event is not exceeded.
The licensee stated in its letter dated March 12, 2004, that the input value for the RWE analysis is the LPSP analytical limit of 30%, found in GE Topical Report NEDC-31312-P, Table 4-5a.
Therefore, the proposed change of the RBM LPSP allowable value from #29% to #25.9% has no impact on the RWE analysis. The RBM LPSP of 25.9% is not an input in the RWE analysis; however, it is derived from the RBM LPSP analytical limit of 30%, accounting for instrument loop uncertainties, in accordance with RG 1.105.
NEDC-31312-P also explains that the RBM setpoint in each range is a function of the operating limit MCPR (OLMCPR) used to select the setpoint. For example, Figure 4-9 of NEDC-31312-P depicts the RBM setpoint in each range for an OLMCPR of 1.20. If the OLMCPR is higher, each RBM setpoint can be raised in accordance with the RWE analysis. The bounding relationship between the analytical RBM setpoint and OLMCPR is depicted in Figure 4-8 of NEDC-31312-P. Pilgrim has established an RBM setpoint for each power range based on a low full power OLMCPR of 1.30. Pilgrim states the minimum full power OLMCPR for Cycle 15 is 1.37 as reported in the Supplemental Reload Licensing Report and the acceptability of the selected RBM setpoint is verified for each reload core design.
Pilgrim is required to operate within the core operating limits, as derived in accordance with NRC-approved methodology in compliance with TS 5.6.5. Accordingly, Pilgrim has submitted the COLR for fuel cycle 15. Section 2.3 of the COLR specifies the allowable values for the power-dependent rod block monitor trip setpoint and the LPSP specified is #25.9%. ENO also stated in Reference 1 that there is no impact on the initial Average Power Range Monitor, Rod Block Monitor and Technical Specifications (ARTS) improvement program approved by License Amendment No. 138 because Pilgrims procedures and COLR have been enforcing the correct RBM LPSP allowable value of #25.9% since the issuance of License Amendment No. 138.
Therefore, the Pilgrim ARTS program approved by License Amendment No. 138 remains valid.
3.1 NRC Staffs Conclusion The staff finds that the proposed change is more conservative than the current requirement since the proposed RBM LPSP allowable value of #25.9% provides rod block protection over a wider power range (from #25.9% to 100%, instead of #29% to 100%), therefore enforcing RBM protection against a RWE at an even lower power level. On the basis of the above review, the NRC staff concludes that the licensees proposed change to the RBM LPSP allowable value from #29% to #25.9% in Note 5 of TS Table 3.2.C-1 is acceptable.
4.0 STATE CONSULTATION
In accordance with the Commission's regulations, the Massachusetts State Official was notified of the proposed issuance of the amendment. The State official had no comments.
5.0 ENVIRONMENTAL CONSIDERATION
The amendment changes a requirement with respect to installation or use of a facility component located within the restricted area as defined in Title 10 of the Code of Federal Regulations (10 CFR) Part 20. The NRC staff has determined that the amendment involves no significant increase in the amounts, and no significant change in the types, of any effluents that may be released offsite, and that there is no significant increase in individual or cumulative occupational radiation exposure. The Commission has previously issued a proposed finding that the amendment involves no significant hazards consideration, and there has been no public comment on such finding (69 FR 7521). Accordingly, the amendment meets the eligibility criteria for categorical exclusion set forth in 10 CFR 51.22(c)(9). Pursuant to 10 CFR 51.22(b), no environmental impact statement or environmental assessment need be prepared in connection with the issuance of the amendment.
6.0 CONCLUSION
The Commission has concluded, based on the considerations discussed above, that: (1) there is reasonable assurance that the health and safety of the public will not be endangered by operation in the proposed manner, (2) such activities will be conducted in compliance with the Commission's regulations, and (3) the issuance of the amendment will not be inimical to the common defense and security or to the health and safety of the public.
7.0 REFERENCES
1.
Letter from Michael A. Balduzzi (Entergy) to NRC, License Amendment Request to Amend Technical Specifications (TS) Table 3.2.C-1, dated August 19, 2003.
2.
Letter from NRC to George W. Davis (Boston Edison), Issuance of Amendment No. 138 to Facility Operating License No. DPR Pilgrim Nuclear Power Station, dated July 1, 1991.
3.
Letter from William J. Riggs (Entergy) to NRC, Core Operating Limits Report 15A, dated May 13, 2003.
4.
Letter from Michael A. Balduzzi (Entergy) to NRC, Response to NRC Request for Additional Information on License Amendment Request to Amend Technical Specifications (TS) Table 3.2.C-1, dated March 12, 2004.
Principal Contributor: T. Ford Date: February 2, 2005