Issuance of Technical Specification Page Permanently Revised Stram Generator Voltage-Based Repair Criteria Probability of Detection Method
ML043200442
Person / Time
Site: Diablo Canyon  
Issue date: 10/28/2004
From:
NRC/NRR/DLPM
To:
SHUKLA G , NRR/DLPM/PD4, 415-8420
Shared Package
ML043140456 List:
References
TAC MC2313, TAC MC2314
Download: ML043200442 (1)


Text

Reporting Requirements 5.6 5.6 Reporting Requirements (continued) 5.6.10 Steam Generator (SG) Tube Inspection Report

5)

Performance evaluation of the operational assessment methodology for predicting flaw distributions as a function of flaw size.

6)

Evaluation results of number and size of previously reported versus new PWSCC indications found in the inspection, and the potential need to account for new indications in the operational assessment burst evaluation.

7)

Identification of mixed mode (axial PWSCC and circumferential) indications found in the inspection and an evaluation of the mixed mode indications for potential impact on the axial indication burst pressures or leakage.

8)

Any corrective actions found necessary in the event that condition monitoring requirements are not met.

i.

For implementation of the probability of prior cycle detection (POPCD) method, for the voltage-based repair criteria at tube support plate intersections, if the end-of-cycle conditional main steamline break burst probability, the projected main steamline break leak rate, or the number of indications are underpredicted by the previous cycle operational assessment, the following shall be reported to the Commission pursuant to 10 CFR 50.4 within 90 days following return to service of the steam generators:

1)

The assessment of the probable causes for the underpredictions, proposed corrective actions, and any recommended changes to probability of detection or growth methodology indicated by potential methods assessments.

2)

An assessment of the potential need to revise the alternate repair criteria analysis methods if: the burst probability is underpredicted by more than 0.001 (i.e., 10% of the reporting threshold) or an order of magnitude; or the leak rate is underpredicted by more than 0.5 gpm or an order of magnitude.

3)

An assessment of the potential need to increase the number of predicted low voltage indications at the beginning of cycle if the total number of as-found indications in any SG are underestimated by greater than 15% or by greater than 150 indications.

DIABLO CANYON - UNITS 1 & 2 5.0-30a Unit 1 - Amendment No. 435,454,4-2,177 Unit 2 - Amendment No. 435,454,452,179