ML042960473

From kanterella
Jump to navigation Jump to search
E-mail from D. Straka Regarding Westwing Oil Sample Results
ML042960473
Person / Time
Site: Palo Verde  
Issue date: 07/06/2004
From: Straka D
Arizona Public Service Co
To: Gody A
Office of Nuclear Reactor Regulation, Division of Reactor Safety IV
References
FOIA/PA-2004-0307
Download: ML042960473 (3)


Text

From:

<DSTRAKA@a comr n>

2 To:

<atg@nrc.gov>PWfUVt CA OY Date:

7/6/04 4:14PM l

Subject:

FW: WESTWING OIL SAMPLE RESULTS Tony:

Per your request. Transformer testing results.

Regards, Don Straka Senior Consultant Regulatory Affairs dstraka~apsc.com phone: 623.393.5041 pager: 602.509.6240 mobile: 602.509.6240

> --Original Message-

> From:

Kesler, Steven L(Z55768)

> Sent:

Tuesday, July 06, 2004 2:10 PM

> To: Straka, Donald J(Z99942)

> Cc: Kesler, Steven L(Z55768); Leake, Harvey C(Z60326); Arndt,

> Gregory M(Z02742); Paramithas, Panos (V72983); Mueller, Paul L(Z69499)

Subject:

FW: WESTWING OIL SAMPLE RESULTS

> Importance: High

> Attached is the result of the oil samples taken of the 500/230 kV

> transformer bank on 6/16/04.

> Steve Kesler

> --Original Message---

> From:

Arndt, Gregory M(Z02742)

> Sent:

Tuesday, July 06, 2004 2:02 PM

> To:

Kesler, Steven L(Z55768)

Subject:

FW: WESTWING OIL SAMPLE RESULTS

> Importance: High

> FYI

> --Original Message--

> From:

Amdt, Gregory M(Z02742)

> Sent:

Wednesday, June 16, 2004 3:30 PM

> To: Lamontagne, Donald R(Z99964); Riccitelli, Michael J(Z78555);

> Lucas, John R(K61483)

> Cc: Atwell, Paul N(K03560); Bischoff, Stephen J(H11690); Kesler,

> Steven L(Z55768); Leake, Harvey C(Z60326)

Subject:

FW: WESTWING OIL SAMPLE RESULTS

> Importance: High

> The oil sample results shown below are acceptable for continued

> operation of all 500/230kV transformer banks at Westwing. We will

> resample the high moisture content on T732, this has nothing to do

> with the fault currents seen at Westwing.

  • -- Original Message--

> From:

Rice, Steven A(Z78582)

> Sent:

Wednesday, June 16,2004 3:19 PM

> To: Amdt, Gregory M(Z02742)

Subject:

WESTWING OIL SAMPLE RESULTS

> WESTWING T1 BANK

> HYDROGEN

> NITROGEN

>CO

> OXYGEN

> METHANE

>C02

>ACETYLENE

> ETHYLENE

>ETHANE

>TDCG T732 7.13 66947.91 69.14 6694.43 16.59 1381.43 0.00 1.67 12.52 107.06 T733 7.19 83130.54 47.05 4772.88 9.45 896.39 0.40 7.97 2.55 74.61 T734 5.06 62767.43 10.59 3324.03 3.77 672.52 0.00 2.32 21.05 42.79

> MOISTURE 16.8

> INT.TENSION 33.0

> TOTAL ACID#

0.018

> DIELEC. STR.

34.70

> PWR. FACTOR 0.060

> WESTWING T4 BANK 1.9 44.0 0.020 37.34 0.030 2.6 37.6 0.052 43.30 0.064

> HYDROGEN

> NITROGEN

>CO

> OXYGEN

> METHANE

>C02

> ACETYLENE

> ETHYLENE

> ETHANE

> TDCG T788 13.13 63668.36 4.53 1454.51 23.29 1488.80 1.16 75.66 15.45 133.22 T789 9.75 65040.04 12.09 3114.88 3.68 1605.61 0.16 1.78 7.8 35.27 T790 4.67 65300.07 4.63 1222.15 3.61 923.63 0.45 2.30 11.13 26.79

> MOISTURE

> INT.TENSION

> TOTAL ACID #

> DIELEC. STR.

> PWR. FACTOR 4.0 47.0 0.040 41.05 0.058 4.3 44.1 0.036 40.37 0.066 5.4 41.8 0.023 40.37 0.054

> WESTWING T10 BANK

> HYDROGEN

> NITROGEN

>CO

> OXYGEN

> METHANE

>C02

>ACETYLENE

> ETHYLENE

>ETHANE

>TDCG Tl 044 22.30 40752.21 163.83 3216.22 138.57 1500.84 0.00 2.70 198.87 526.27 TI 045 11.11 29546.34 101.07 853.63 115.29 1029.92 0.00 2.03 169.03 398.53 TI 046 21.38 49295.77 119.88 4326.12 137.80 1561.19 0.00 2.36 214.63 496.04

> MOISTURE

> INT.TENSION

> TOTAL ACID #

> DIELEC. STR.

3.95 41.6 0.037 51.61 2.0 44.8 0.030 49.26 0.063

<2.0 41.9 0.033 52.19 0.052

> PWR. FACTOR 0.070 CC:

<SKESLER@apsc.com>, <DMAULDIN@apsc.com>,

<MWINSOR@apsc.com>, <HLEAKE~apsc.com>