June 8, 2004 Mr. G. R. Peterson Site Vice President Catawba Nuclear Station Duke Energy Corporation 4800 Concord Road York, South Carolina 29745-9635

SUBJECT:

CATAWBA NUCLEAR STATION, UNIT 2 RE: STEAM GENERATOR TUBE INSPECTION REPORT FOR THE END OF CYCLE 12 REFUELING OUTAGE (TAC NO. MC0957)

Dear Mr. Peterson:

By letters dated April 7, 2003, June 18, 2003, February 10, 2004 and April 7, 2004, Duke Energy Corporation, the licensee for Catawba Nuclear Station, Unit 2, submitted information summarizing the steam generator tube inspections performed during the 2003 End of Cycle 12 refueling outage.

Upon review of this information, the Nuclear Regulatory Commission (NRC) staff concluded that the licensee provided the information required by the Technical Specifications and that no additional follow-up was required. The NRC staffs evaluation is enclosed.

Sincerely,

/RA/

Sean E. Peters, Project Manager, Section 1 Project Directorate II Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket No. 50-414

Enclosure:

As stated cc w/encl: See next page

June 8, 2004 Mr. G. R. Peterson Site Vice President Catawba Nuclear Station Duke Energy Corporation 4800 Concord Road York, South Carolina 29745-9635

SUBJECT:

CATAWBA NUCLEAR STATION, UNIT 2 RE: STEAM GENERATOR TUBE INSPECTION REPORT FOR THE END OF CYCLE 12 REFUELING OUTAGE (TAC NO. MC0957)

Dear Mr. Peterson:

By letters dated April 7, 2003, June 18, 2003, February 10, 2004 and April 7, 2004, Duke Energy Corporation, the licensee for Catawba Nuclear Station, Unit 2, submitted information summarizing the steam generator tube inspections performed during the 2003 End of Cycle 12 refueling outage.

Upon review of this information, the Nuclear Regulatory Commission (NRC) staff concluded that the licensee provided the information required by the Technical Specifications and that no additional follow-up was required. The NRC staffs evaluation is enclosed.

Sincerely,

/RA/

Sean E. Peters, Project Manager, Section 1 Project Directorate II Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket No. 50-414

Enclosure:

As stated cc w/encl: See next page DISTRIBUTION:

PDII-1 R/F SPeters PUBLIC SCoffin RidsRgn2MailCenter DClarke JTerrell KKarcagi ACRS GHill(4)

Llund JNakoski OGC Accession NumberML041660478

  • No Significant Changes Made to Summary OFFICE PDII-1/PM PDII-1/LA (A)

EMCB/SC*

PDII-1/SC (A)

NAME SPeters DClarke LLund SCoffin DATE 6/1/04 6/1/04 04/25/04 6/7/04 OFFICIAL RECORD COPY

Enclosure

SUMMARY

OF REVIEW BY THE OFFICE OF NUCLEAR REACTOR REGULATION RELATED TO THE STEAM GENERATOR TUBE INSPECTION REPORT FOR THE END OF CYCLE 12 REFUELING OUTAGE DUKE ENERGY CORPORATION, ET AL.

CATAWBA NUCLEAR STATION, UNIT 2 DOCKET NO. 50-414 By letters dated April 7 and June 18, 2003, Duke Energy Corporation, the licensee for Catawba Nuclear Station (Catawba), Unit 2, submitted reports summarizing the steam generator (SG) tube inspections performed during the end of cycle 12 refueling outage. The licensee submitted these reports in accordance with Technical Specifications (TSs) 5.6.8.a and 5.6.8.b.

The Nuclear Regulatory Commission (NRC) staff required additional information in order to complete the review and, therefore, sent requests for this information by letters dated January 5 and March 31, 2004. The licensee responded to these requests in letters dated February 10 and April 7, 2004. A summary of the NRCs evaluation of the EOC 12 refueling outage is provided below.

Catawba, Unit 2 has four Westinghouse Model D5 SGs, which were placed in service in 1986.

The tubing is made from thermally treated Alloy 600. The SGs feature full-depth hydraulically expanded joints in the tubesheet and type 405 stainless steel support plates with quatrefoil holes. Each SG contains 4570 tubes.

In the submittals referenced above, the licensee provided the scope, extent, method, and results of the steam generator tube inspections. In addition, the licensee described corrective actions (i.e., tube plugging or repair) taken in response to the inspection findings. Based on a review of the information provided, the NRC staff concludes that the licensee provided the information required by the TSs. In addition, the NRC staff concludes that there are no technical issues that warrant follow-up action at this time since the inspections appear to be consistent with industry practice, and the results of the inspection appear to be consistent with industry operating experience at similarly designed and operated units.

Catawba Nuclear Station cc:

Lee Keller, Manager Regulatory Compliance Duke Energy Corporation 4800 Concord Road York, South Carolina 29745 Ms. Lisa F. Vaughn Duke Energy Corporation Mail Code - PB05E 422 South Church Street P.O. Box 1244 Charlotte, North Carolina 28201-1244 Anne Cottingham, Esquire Winston and Strawn 1400 L Street, NW Washington, DC 20005 North Carolina Municipal Power Agency Number 1 1427 Meadowwood Boulevard P. O. Box 29513 Raleigh, North Carolina 27626 County Manager of York County York County Courthouse York, South Carolina 29745 Piedmont Municipal Power Agency 121 Village Drive Greer, South Carolina 29651 Ms. Karen E. Long Assistant Attorney General North Carolina Department of Justice P. O. Box 629 Raleigh, North Carolina 27602 NCEM REP Program Manager 4713 Mail Service Center Raleigh, North Carolina 27699-4713 North Carolina Electric Membership Corp.

P. O. Box 27306 Raleigh, North Carolina 27611 Senior Resident Inspector U. S. Nuclear Regulatory Commission 4830 Concord Road York, South Carolina 29745 Henry Porter, Assistant Director Division of Waste Management Bureau of Land and Waste Management Dept. of Health and Environmental Control 2600 Bull Street Columbia, South Carolina 29201-1708 Mr. R. L. Gill, Jr., Manager Nuclear Regulatory Issues and Industry Affairs Duke Energy Corporation 526 South Church Street Mail Stop EC05P Charlotte, North Carolina 28202 Saluda River Electric P. O. Box 929 Laurens, South Carolina 29360 Mr. Peter R. Harden, IV, Vice President Customer Relations and Sales Westinghouse Electric Company 6000 Fairview Road 12th Floor Charlotte, North Carolina 28210 Mary Olson Director of the Southeast Office Nuclear Information and Resource Service 729 Haywood Road, 1-A P. O. Box 7586 Asheville, North Carolina 28802

Catawba Nuclear Station cc:

Mr. T. Richard Puryear Owners Group (NCEMC)

Duke Energy Corporation 4800 Concord Road York, South Carolina 29745 Richard M. Fry, Director Division of Radiation Protection N. C. Dept. of Environment, Health, and Natural Resources 3825 Barrett Drive Raleigh, North Carolina 27609-7721