April 21, 2004 Mr. G. R. Peterson, Vice President McGuire Nuclear Station Duke Energy Corporation 12700 Hagers Ferry Road Huntersville, NC 28078

SUBJECT:

MCGUIRE NUCLEAR STATION, UNITS 1 AND 2 - REQUEST FOR ADDITIONAL INFORMATION FOR THE PROPOSED AMENDMENTS CONCERNING SPENT FUEL ASSEMBLY STORAGE (TAC NOS. MC0945 AND MC0946)

Dear Mr. Peterson:

By letter dated September 29, 2003, you submitted a request for amendments to the Technical Specifications for McGuire Nuclear Station, Units 1 and 2, concerning spent fuel assembly storage. Enclosed is a request for additional information (RAI) related to the Boral neutron poison material that we need to continue our review. Mr. Norman Simms of your staff has indicated that the response to this RAI will be provided within 45 days of the date of this letter.

If you have any further questions on this matter, please call me at (301) 415-1388.

Sincerely,

/RA/

James J. Shea, Project Manager, Section 1 Project Directorate II Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket Nos. 50-369 and 50-370

Enclosure:

As stated

ML041170026 NRR-088 OFFICE PDII-1/PM PDII-1/LA PDII-1/SC NAME JShea CHawes JNakoski DATE 4/20/04 4/19/04 4/21/04

Enclosure REQUEST FOR ADDITIONAL INFORMATION RELATED TO SPENT FUEL ASSEMBLY STORAGE - SEPTEMBER 29, 2003, AMENDMENT REQUEST MCGUIRE NUCLEAR STATION, UNITS 1 AND 2 1.

The NRC staff notes that the defined Region 1 of the spent fuel pool was reracked without prior NRC approval utilizing a Boral neutron poison material. Therefore, the NRC staff requests a discussion of the procedures and tests used to ensure that the Boral panels in the racks have the minimum Boron-10 (B-10) loading assumed in the analyses.

2.

Recently, incidents of Boral blistering have been reported and the impact on the expected performance of this material is not yet known. Therefore, the NRC staff requests the licensee to implement a technical specification (TS) Boral coupon surveillance program to ensure consistent material performance assumed in its analyses. This program should monitor the physical and chemical properties of Boral over time and include the following:



description of the coupons used (e.g., from the same lot as the panels);



technique for measuring the initial B-10 content of the coupons;



frequency and its justification



tests to be performed on coupons (e.g., weight measurement, measurement of dimensions (length, width and thickness), and B-10 content).

In addition, please inform the NRC staff in writing if the coupons reveal a change in material performance from that assumed in the analyses.

McGuire Nuclear Station cc:

Ms. Lisa F. Vaughn Duke Energy Corporation Mail Code - PB06E 422 South Church Street P.O. Box 1244 Charlotte, North Carolina 28201-1244 County Manager of Mecklenburg County 720 East Fourth Street Charlotte, North Carolina 28202 Mr. C. Jeffrey Thomas Regulatory Compliance Manager Duke Energy Corporation McGuire Nuclear Site 12700 Hagers Ferry Road Huntersville, North Carolina 28078 Anne Cottingham, Esquire Winston and Strawn 1400 L Street, NW.

Washington, DC 20005 Senior Resident Inspector c/o U.S. Nuclear Regulatory Commission 12700 Hagers Ferry Road Huntersville, North Carolina 28078 Dr. John M. Barry Mecklenburg County Department of Environmental Protection 700 N. Tryon Street Charlotte, North Carolina 28202 Mr. Peter R. Harden, IV VP-Customer Relations and Sales Westinghouse Electric Company 6000 Fairview Road, 12th Floor Charlotte, North Carolina 28210 Ms. Karen E. Long Assistant Attorney General North Carolina Department of Justice P. O. Box 629 Raleigh, North Carolina 27602 Mr. R. L. Gill, Jr.

Manager - Nuclear Regulatory Issues and Industry Affairs Duke Energy Corporation 526 South Church Street Mail Stop EC05P Charlotte, North Carolina 28202 NCEM REP Program Manager 4713 Mail Service Center Raleigh, North Carolina 27699-4713 Mr. Richard M. Fry, Director Division of Radiation Protection North Carolina Department of Environment, Health and Natural Resources 3825 Barrett Drive Raleigh, North Carolina 27609-7721 Mr. T. Richard Puryear Owners Group (NCEMC)

Duke Energy Corporation 4800 Concord Road York, South Carolina 29745