Attachment 3: List of Components in Fire Zones 98J and 99M
ML040640751
Person / Time
Site: Arkansas Nuclear 
Issue date: 02/20/2004
From:
Entergy Operations
To:
NRC Region 4
References
FOIA/PA-2003-0358
Download: ML040640751 (10)


Text

A1TACHMENT 3 LIST OF COMPONENTS IN FIRE ZONES 98J AND 99M Shortly after the inspection, Region IV requested a list and description of cables and components located in Fire Zones 98J and 99M. On August 28, 2001, the licensee provided this list. Because of its late arrival, Region IV did not consider all the components shown on the list in the Phase 2 SDP. It is provided with this TIA memo for use in performing the Phase 3 SDP. Please note that the list is not train specific and does not distiguish between power and control cables.

I COMPONENENTS ASSUMED TO FAIL IN 98J IEXUn rnQ2rnn nmp nF;_qrRiPTinN Al 04 CKTBKR Al SWGR feeder breaker to 4160/480V transformer Xl 4 A111 CKTBKR SU Transformer #2 feeder breaker to Al (non-safety related) Bus All1 RELAY SYNCH Check Relay for A 1I1 Breaker A202 CKTBKR A2 Bus feeder breaker to 4160/480V transformer X2 A212 CKTBKR Unit Aux Transformer feeder breaker to A2 (non-safety related) Bus A304 CKTBKR Reactor Building Spray Pump P-35A feeder breaker from A3 (red train) Bus A307 CKTBKR Primary Makeup Pump P-36B feeder breaker from A3 Bus A311 CKTBKR Emergency Feedwater Pump P-7B feeder breaker from A3 Bus A401 CKTBKR Vital A4 Bus feeder breaker to 4160/480V transformer X6 A402 CKTBKR Service Water Pump P-4C feeder breaker from A4 (green train) Bus A403 CKTBKR Service Water Pump P-4B feeder breaker from A4 Bus Breaker A403 to P-4B Motor Operator Disconnect (allows P-4B to be powered from A4 A601 Transfer Switch Bus)

A404 CKTBKR Reactor Building Spray Pump P-35B feeder breaker from A4 Bus A405 CKTBKR Decay Heat Pump P-34B feeder breaker from A4 Bus A406 CKTBKR Primary Makeup Pump P-36C feeder breaker from A4 Bus A407 CKTBKR Primary Makeup Pump P-36B feeder breaker from A4 Bus A408 CKTBKR Emergency Diesel Generator #2 Output Breaker A409 CKTBKR Bus A4 feeder breaker from Bus A2 815 SWGEAR Non-Vital 480VAC Motor Control Center B31 SWGEAR Non-Vital 480VAC Motor Control Center Non-Vital 480VAC Motor Control Center B31 feeder breaker from Non-Vital 480 VAC B321 CKTBKR Bus B3 B41 SWGEAR Non-Vital 480VAC Motor Control Center Non-Vital 480VAC Motor Control Center B41 feeder breaker from Non-Vital 480VAC B421 CKTBKR Bus B4 B4243 CKTBKR Feeder Breaker to Spare Instrument Air Compressor C2C B44 SWGEAR Non-Vital 480VAC Motor Control Center B5123 CKTBKR Emergency Diesel Generator #1 (red train) Room Exhaust Fan VEF-24B supply B5141 A CKTBKR 120VAC Inverter Yl 1 feeder breaker from Motor Control Center B51 (red train)

B5145B CKTBKR 120VAC Inverter Yl 3 feeder breaker from Motor Control Center B53 (red train)

B612 CKTBKR Vital 480VAC Bus B6 input supply breaker from Vital 4160VAC Bus A4 V_

B6123 CKTBKR Emergency Diesel Generator #2 (green train) Room Exhaust Fan VEF-24D supply B614 CKTBKR Motor Control Center B62 feeder breaker from Vital 480VAC Bus B6 (green train)

B623 CKTBKR Reactor Building Cooler VSF-= C supply B633 CKTBKR Reactor Building Cooler VSF-1 D supply B634 CKTBKR Motor Control Center B65 feeder breaker from Vital 480VAC Bus B6 B64 SWGEAR Vital 480VAC Motor Control Center (green train)

B65 SWGEAR Vital 480VAC Motor Control Center (green train)

B7 SWGEAR Non B71 SWGEAR Non B712 CKTBKR Motor Control Center B71 feeder breaker from Bus B7 B72 SWGEAR Non-Vital Motor Control Center B72 C187 TRANSMITTER Steam Generator E24B Low Rangle Level Transmitter LT-2617 Transmitter Bistable C2B GOMPRESSOR Spare Instrument Air Compressor C2B C3B COMPRESSOR Sprare Instrument Air Compressor C3B CV1 000 VALVE Pressurizer ERV (Electromatic Relief Valve) Isolation CV1009 VALVE Pressurizer Spray Block Valve CV1206 VALVE Reactor Coolant Pumps Seal Injection Block Valve from Makeup & Purification System CV1221 VALVE Reactor Coolant System Letdown Isolation CV1 227 VALVE High Pressure Injection to Reactor Coolant Loop "B" Isolation CV1 228 VALVE High Pressure Injection to Reactor Coolant Loop "B" Isolation CV1 234 VALVE Reactor Coolant System Makeup CV1 274 VALVE Reactor Coolant Pumps Seal Return Isolation back to Makeup Tank T4 CV1400 VALVE B Low Pressure Injection Isolation to RCS CV1 404 VALVE Decay Heat Pumps P-34A/B combined suction from Reactor Coolant System CV1 406 VALVE Outboard Reactor Building Sump Isolation to "B" Train HPI, LPI, RB Spray CV1 408 VALVE Borated Water Storage Tank (BWST) Outlet Valve CV1415 VALVE P34B/P35B (LPI & RB Spray Pump) Suction From RB Sump CV1416 VALVE Pressurizer Auxiliary Spray Containment Isolation From Decay Heat Sys.

CV2235 VALVE Control Rod Drives (CRD) Cooling Water Supply RB Isolation From ICW Sys CV2400 VALVE "B" Train RB Spray Header Isolation CV2613 VALVE P7A (Turbine Driven EFW Pump) Steam Admission Valve CV2617 VALVE "B" Steam Generator Supply Valve to P7A CV261 8 VALVE "B" Steam Generator Atmospheric Dump Valve (ADV)

CV2619 VALVE "B" Steam Generator ADV Block Valve CV2620 VALVE P7A to Steam Generator "B" Isolation CV2624 VALVE Main Feedwater Lo Load Block Valve (normally open) to NA" Steam Generator CV2625 VALVE Main Feedwater Block Valve to "A" Steam Generator CV2626 VALVE P-7B (Motor Driven) to "B" Steam Generator Isolation CV2627 VALVE P7A to "A" Steam Generator Isolation CV2630 VALVE Main Feedwater Reactor Building Isolation to NB" Steam Generator CV2645 VALVE P7A to "A" Steam Generator solenoid operated control valve CV2646 VALVE P78 to "A" Steam Generator solenoid operated control valve CV2647 VALVE P7A solenoid operated control isolation valve CV2648 VALVE P7B to NB" Steam Generator solenoid operated control CV2663 VALVE P7A steam admission valve CV2667 VALVE P7A steam bypass valve from "A' Steam Generator CV2668 VALVE "A' Steam Generator Atmospheric Dump Valve (ADV)

CV2670 VALVE P78 to NA" Steam Generator isolation (AC operated)

CV2674 VALVE Main Feedwater Lo Load Block Valve (normally open) to TB" Steam Generator CV2675 VALVE Main Feedwater Block Valve to "B" Steam Generator CV2680 VALVE Main Feedwater Reactor Building Isolation to "A" Steam Generator CV2802 VALVE P7A suction from Condensate Storage Tank CV2827 VALVE Main Feedwater Cross Connect Valve CV2870 VALVE P7A Test & Recirc Isolation CV3640 VALVE P-4B ("B" Service Water Pump) to Service Water Loop II crossover valve CV3642 VALVE P4B to Service Water Loop II crossover CV3806 VALVE

  1. 1 EDG Jacket Cooler (E-20A) service water supply isolation (loop 1)

CV3807 VALVE

  1. 2 EDG Jacket Cooler (E-20B) service water supply isolation (loop 11)

CV3811 VALVE Service Water Loop 1I supply to Intermediate Cooling Water (ICW) coolers CV3813 VALVE Service Water Loop II supply isolation to RB Cooling Coils (VCC-2C/2D)

CV3821 VALVE Service Water Loop II supply isolation to "B" Decay Heat Cooler (E35B)

CV3824 VALVE Combined Service Water return to Discharge Flume (lake)

CV3841 VALVE Service water air operated isolation to "B" Decay Heat Pump Seal/Bearing Cooler CV5611 VALVE Fire Water to Reactor Building Isolation CV7472 DAMPER Backdraft damper for RB Ventillation Supply Fan VSF-1 C CV7473 DAMPER Backdraft damper for RB Ventillation Supply Fan VSF-1 D D01 22A CKTBKR DC Breaker to 120VAC Inverter Y-1 1 (alternate source)

D02 SWGEAR Green Train 125 VDC Distribution Bus D0222A CKTBKR DC Suppply Breaker to 120VAC Inverter Y-24 (alternate source)

D03A/B CHARGE 125 VDC Battery Charger For D07 (Red Train)

D04ANB CHARGE 125 VDC Battery Charger For D06 (Green Train)

D06 BATTERY 125 VDC Green Station Battery to 125 VDC Bus D02 D1109 CKTBKR DC Control Power to Vital (Red) 480 VAC Load Center 85 D1114 CKTBKR DC Control Power to #1 EDG Control Cabinet C-107 (Controls engine protective trips)

DC Control Power to #1 EDG Field Flashing & voltage regulator remote control D1116 CKTBKR (control room)

D15 SWGEAR Non Vital 125 VDC Bus D21 PANEL 125 VDC Motor Control Center (normal supply D02)

D2104 CKTBKR DC Control Power to 4160 VAC Feeder Breaker A-409 (Bus A2 to A4 breaker)

D2109 CKTBKR DC Control Power to Vital (Green) 480 VAC Load Center B6 D2114 CKTBKR DC Control Power to #2EDG Control Cabinet C-1 08 (Controls engine protective trips)

DC Control Power to #2 EDG Field Flashing & Voltage regulator remote control D2116 CKTBKR (control room)

D25 SWGEAR 125 VDC Motor Control Center Electric to Pneumatic Converter (E/P) to Main Feedwater Lo Load Control Valve E/P2622 SIGCON CV-2622 (WA" S/G)

Electric to Pneumatic Converter (E/P) to Main Feedwater Startup Control Valve E1P2623 SIGCON CV-2623 ("A" S/G)

Electric to Pneumatic Converter (EIP) to Main Feedwater Lo Load Control Valve EIP2672 SIGCON CV-2672 ("B" SIG)

Electric to Pneumatic Converter (E/P) to Main Feedwater Startup Control Valve E/P 2673 SIGCON CV-2673 ("B" S/G)

H13 CKTBKR Startup Transformer #2 Feeder Breaker to 6900 VAC Bus H1 ENGINE/RELA K4B Y

  1. 2EDG (Running relays, Lockout relays, undervoltage relays are all affected)

LT2415 TRANSMITTER "A" Core Flood Tank (T2A) level transmitter (one of two)

LT2416 TRANSMITTER "A" Core Flood Tank (T2A) level transmitter (one of two)

LT2418 TRANSMITTER "B" Core Flood Tank (T2A) level transmitter (one of two)

LT2419 TRANSMITTER "B" Core Flood Tank (T2A) level transmitter (one of two)

LT2613 TRANSMITTER "B" Steam Generator Level Transmitter LT2617 TRANSMITTER "B" Steam Generator Level Transmitter LT2622 TRANSMITTER "A" Steam Generator Level Transmitter LT2624 TRANSMITTER "A' Steam Generator Level Transmitter LT2653 TRANSMITTER "A" Steam Generator Level Transmitter LT2668 TRANSMITTER 'A" Steam Generator Level Transmitter LT2671 TRANSMITTER "B" Steam Generator Level Transmitter LT2673 TRANSMITTER "B" Steam Generator Level Transmitter M55A RECOMBINER Red Channel Hydrogen Recombiner M55B RECOMBINER Green Channel Hydrogen Recombiner P34B PUMP "B" Decay Heat/Low Pressure Injection Pump P36B PUMP "B" Makeup/High Pressure Injection Pump P36C PUMP "C" Makeup/High Pressure Injection Pump P4B PUMP "B" Service Water Pump P4C PUMP "C" Service Water Pump P75 PUMP Auxiliary Feedwater Pump P7A PUMP Turbine Driven Emergency Feedwater Pump P7B PUMP Motor Driven Emergency Feedwater Pump PDIS2228 SWITCH "A" Intermediate Cooling Water Surge Tank (T-37A) level switch PDT2700 TRANSMITTER Delta Pressure Valve Controller for CV-2625 ("A" S/G Main Feedwater Block Valve)

PDT2701 TRANSMITTER Delta Pressure Valve Controller for CV-2675 ("B" S/G Main Feedwater Block Valve)

PS5432 SWITCH Autostart/Stop Pressure Switch for Backup Instrument Air Compressor C2B PS5436 SWITCH Autostart/Stop Pressure Switch for Service Air Compressor C3B "A" Reactor Coolant System Loop Pressure Transmitter (inputs to Engineered PT1 020 TRANSMITTER Safequards Actuation System Channnel 1)

"A" Reactor Coolant System Loop Pressure Transmitter (inputs to Reactor Protection PT1 021 TRANSMITTER System)

"A" Reactor Coolant System Loop Pressure Transmitter (inputs to Engineered PT1 022 TRANSMITTER Safeguards Actuation System Channnel 2)

'Bo Reactor Coolant System Loop Pressure Transmitter (inputs to Engineered PT1 040 TRANSMITTER Safeguards Actuation System Channel 3)

PT2415 TRANSMITTER "A" Core Flood Tank (T2A) pressure transmitter PT2416 TRANSMITTER "A" Core Flood Tank (T2A) pressure transmitter PT2418 TRANSMITTER "B" Core Flood Tank (T2B) pressure transmitter PT2419 TRANSMITTER "B" Core Flood Tank (T2B) pressure transmitter PT2617A TRANSMITTER "B" Steam Generator pressure transmitter for Main Steam Line Isolation (MSLI)

PT261 BB TRANSMITTER "A" Steam Generator pressure transmitter for Main Steam Line Isolation (MSLI)

PT2667B TRANSMITTER "B" Steam Generator pressure transmitter for Main Steam Line Isolation (MSLI)

PT2668A TRANSMITTER "A" Steam Generator pressure transmitter for Main Steam Line Isolation (MSLI)

RA1 PANEL 125 VDC Distribution Panel (fed from D01)

RA2 PANEL 125 VDC Distribution Panel (fed from D02)

RS2 PANEL Vital 120 VAC Distribution Panel (fed from inverters Y22 or Y25)

RS4 PANEL Vital 120 VAC Distribution Panel (fed from inverters Y24 or Y25)

"B" Intermediate Cooling Water Surge Tank (T37B) fill makeup solenoid valve (from SV2229 VALVE condensate makeup)

"B" Service Air Compressor After Air Cooler solenoid valve (supplies ICW thru cooler SV2250 VALVE on compressor start)

SV2252 VALVE "B" Backup Instrument Air Compressor cooling water inlet ( for cylinder jacket cooling)

"B" Backup Instrument Air Compressor After Air Cooler solenoid valve (supplies ICW SV2254 VALVE hru cooler on compressor start)

SV3841 VALVE Service Water to "B" Decay Heat Pump (P-34B) Seal/Bearing Cooler SV5237 VALVE Air Start Solenoid for #2EDG SV5239 VALVE Air Start Solenoid for #2EDG SV7401 VALVE Solenoid for CV-7401, Reactor Building Purge Outlet SV7402 VALVE Solenoid for CV-7402, Reactor Building Purge Outlet SV7412 DAMPER "C" Reactor Building Supply Fan (VSF-1C) bypass damper SV7413 DAMPER "D" Reactor Building Supply Fan (VSF-1 D) bypass damper SV7459 VALVE Reactor Building Hydrogen Analyzer (C179) inlet isolation SV7469 VALVE.

Reactor Building Hydrogen Analyzer (C179) outlet isolation Backup Instrument Air Compressor (C2B) After Air Cooler Discharge Temperature TS5403 SWITCH Switch TS5407 SWITCH Service Air Compressor (C3B) After Air Cooler Discharge Temperature Switch TS7903 SWITCH

  1. 2EDG Room Exhaust Fan (VEF-24C) Thermostat TS7904 SWITCH
  1. 2EDG Room Exhaust Fan (VEF-24D) Thermostat VEF-24C MOTOR Motor for VEF-24C (#2EDG Room Exhaust Fan)

VEF-24D MOTOR Motor for VEF-24C (#2EDG Room Exhaust Fan)

VSF1 C ACUNIT Reactor Building Ventillation Supply Fan VSF1 D ACUNIT Reactor Building Ventillation Supply Fan VUC1 C ACUNIT "B Decay Vault Room Cooler (Vault contains "B" Decay Heat & "BW Spray Pumps)

VUC1 D ACUNIT B Decay Vault Room Cooler (Vault contains "Bo Decay Heat & EBB Spray Pumps)

Y13 INVERT 120 VAC Inverter (supplies RS3)

Y22 INVERT 120 VAC Inverter (supplies RS2)

Y24 INVERT 120 VAC Inverter (supplies RS4)

COMPONENTS ASSUMED TO FAIL IN 99M TAr.

1cnmPr--nnF rIOMP nF9C-RiPTiOnt 4160 VAC Bus Al Feed to 4160-480 VAC Transformer (Feeds 480 VAC A104 CKTBKR Bus B14)

A304 CKTBKR Reactor Building Spray Pump (P-35A) Supply Breaker A307 CKTBKR Primary Makeup / High Pressure Injection Pump P-36B Supply Breaker A308 CKTBKR Emergency Diesel Generator #1 Output Breaker A311 CKTBKR Emergency Feedwater Pump P-7B (Motor Driven) Supply Breaker A4 SWGEAR Vital 4160 VAC Bus A4 4160 VAC Bus A4 Feed to 416-480 VAC Transformer X6 (Feeds 480 VAC A401 CKTBKR Bus B6)

A402 CKTBKR Service Water Pump P-4C Supply Breaker A403 CKTBKR Service Water Pump P-4B Supply Breaker from Bus A4 A404 CKTBKR Reactor Building Spray Pump P-35B Supply Breaker A405 CKTBKR Decay Heat Pump P-34B Supply Breaker A406 CKTBKR Primary Makeup /High Pressure Injection Pump P-36C Supply Breaker Primary Makeup /High Pressure Injection Pump P-36B Supply Breaker A407 CKTBKR from Bus A4 A408 CKTBKR Emergency Diesel Generator #2 Output Breaker A409 CKTBKR 4160 VAC Supply Breaker from Bus A2 to A4 Motor Operated Disconnect for Breaker A403 (Supply to Service Water A601 CKTBKR Pump P-4B)

B15 SWGEAR Non Vital 480 VAC Motor Control Center B31 SWGEAR Non Vital 480 VAC Motor Control Center B41 SWGEAR Non Vital 480 VAC Motor Control Center B43 SWGEAR Non Vital 480 VAC Motor Control Center B44 SWGEAR Non Vital 480 VAC Motor Control Center B55 SWGEAR Vital 480 VAC Motor Control Center from Load Center B5 B56 SWGEAR Vital 480 VAC Motor Control Center from Load Center B5 Temporary Power for Battery Charger D03B or D04B (outage related B5622B CKTBKR activity)

B5653 CKTBKR Feeder Breaker to CV-3643 (Service Water to Aux Cooling Water ISO VIv B57 SWGEAR Vital 480 VAC Motor Control Center from Load Center B5 B6 SWGEAR Vital 480 VAC Load Center B61 SWGEAR Vital 480 VAC Motor Control Center from Load Center B6 B612 CKTBKR Input Supply Breaker to 480 VAC Bus B6 From 4160 VAC Bus A4 B6123 CKTBKR Supply Breaker to #2EDG Room Exhaust Fan VEF-24D Supply Breaker to 480 VAC Motor Control Center B62 from 480 VAC Load B614.

CKTBKR Center B6 Normal AC input Supply Breaker to 120 VAC inverter Y-24 from 480 VAC B6145A CKTBKR Motor Control Center B61 B62 SWGEAR Vital 480 VAC Motor Control Center Supply breaker to 480 VAC Motor Control Center 861 from 480 VAC Load B621 CKTBKR Center B6 B622 CKTBKR 480 VAC Supply to Motor Control Center B56 from Load Center B6 B623 CKTBKR Supply Breaker to Reactor Building Ventillation Supply Fan VSF-1 C 8633 CKTBKR Supply Breaker to Reactor Building Ventillation Supply Fan VSF-1 D Supply Breaker to Motor Control Center B-65 From 480 VAC Load Center B634 CKTBKR B6 B64 SWGEAR Vital 480 VAC Motor Control Center B65 SWGEAR Vital 480 VAC Motor Control Center B7 SWGEAR Non Vital 480 VAC Motor Control Center B712 CKTBKR Input Supply Breaker to 480 VAC Bus B7 from 4160 VAC Bus Al B72 SWGEAR Non Vital 480 VAC Motor Control Center from Load Center B7 Senses LT-2617 ("B* Steam Generator Level) & and feeds that Input to C187 BISTBL C187 (Emergency Feedwater Initiation Control Cabinet)

CV1 009 VALVE Pressurizer Spray Block Valve Reactor Coolant Pump Seal Injection Block Valve (from Makeup &

CV1206 VALVE Purification System)

CV1404 VALVE Decay Heat Pumps P-34A/B Suction From RCS CV1416 VALVE Pressurizer Auxiliary Spray Containment Isolation Valve Control Rod Drive Mechanisms (CRDM) Cooling Supply Reactor Building CV2235 VALVE Isolation (from Intermediate Cooling Water)

CV2617 VALVE "B' Steam Generator Steam Supply to Emergency Feedwater Pump P-7A CV2618 VALVE "B" Steam Generator Atmospheric Dump Valve (ADV)

CV2625 VALVE Main Feedwater Block Valve to OA" Steam Generator Turbine Driven Emergency Feedwater Pump P-7A to "AO Steam Generator CV2627 VALVE Isolation (AC powered)

CV2630 VALVE Main Feedwater Isolation to "B" Steam Generator Motor Driven Emergency Feedwater Pump P-7B to FA" Steam Generator CV2646 VALVE Isolation (DC powered)

Turbine Driven Emergency Feedwater Pump P-7A Steam Admission vIv CV2663 VALVE Valve "A" Steam Generator Steam Supply Bypass to Turbine Driven Emergency CV2667 VALVE Feedwater Pump P-7A CV2668 VALVE "A" Steam Generator Atmospheric Dump Valve Main Feedwater Lo Load Block Valve to NBE Steam Generator (normally CV2674 VALVE open)

CV2680 VALVE Main Feedwater Isolation to NAn Steam Generator Turbine Driven Emergency Feedwater Pump P-7A suction from CV2802 VALVE Condensate Storage Tank (CST)

"B" Service Water Pump P-4B Discharge Cross Over Valve to Loop II CV3640 VALVE Service Water JB" Service Water Pump P-4B Discharge Cross Over Valve to Loop II CV3642 VALVE Service Water CV3643 VALVE Service Water to Auxiliary Cooling Water Isolation CV3821 VALVE Loop II Service Water Supply Isolation to "BN Decay Heat Cooler E-35B Loop 11 Service Water Supply Isolation to E-50B ("B" Decay Heat Pump CV3841 VALVE Bearing/Seal Cooler)

CV5611 VALVE Fire Water to Reactor Building Isolation CV7472 DAMPER Backdraft damper for RB Ventillation Supply Fan VSF-1 C CV7473 DAMPER Backdraft damper for RB Ventillation Supply Fan VSF-1 D D1109 CKTBKR DC Control Power to Vital (Red) 480 VAC Load Center B5 D15 SWGEAR Non Vital 125 VDC Bus DC Control Power to 4160 VAC Feeder Breaker A-409 (Bus A2 to A4 D2104 CKTBKR breaker)

D2109 CKTBKR DC Control Power to Vital (Green) 480 VAC Load Center B6

  1. 2EDG (Running relays, Lockout relays, undervoltage relays are all K4B ENGINE/RELAY affected)

LT2617 TRANSMITTER "B" Steam Generator Level Transmitter LT2668 TRANSMITTER "A" Steam Generator Level Transmitter M55A RECOMB Red Channel Hydrogen Recombiner P34B PUMP "B" Decay Heat Pump P36B PUMP "B" Makeup/High Pressure Injection Pump P36C PUMP "C" Makeup/High Pressure Injection Pump P4B PUMP "B" Service Water Pump P4C PUMP "C" Service Water Pump P7A PUMP Turbine Driven Emergency Feedwater Pump PT2617 "B" Steam Generator pressure transmitter for Main Steam Line Isolation A

TRANSMITTER (MSLI)

PT2668

'A' Steam Generator pressure transmitter for Main Steam Line Isolation A

TRANSMITTER (MSLI)

RS2 PANEL Vital 120 VAC Distribution Panel (fed from inverters Y22 or Y25)

RS4

  • PANEL Vital 120 VAC Distribution Panel (fed from inverters Y24 or Y25)

Lake Supply Isolation to "A" Service Water Bay ("NA Service Water Pump SG2 VALVE P4A is located in this bay)

"Cm Service Water Bay to "B" Service Water Bay Isolation (may be closed SG4 VALVE depending on service water pump configuration)

Solenoid Valve to supply air to CV-3805 ("B" Reactor Building Spray Pump SV3805 VALVE Bearing/Seal Cooler E-47B)

Solenoid Valve to supply air to CV-3805 ("B" Decay Heat Bearing/Seal SV3841 VALVE Cooler E-50B)

SV5237 VALVE Air Start Solenoid for #2EDG SV5239 VALVE Air Start Solenoid for #2EDG VSF1 C ACUNIT Reactor Building Ventillation Supply Fan VSF1 D ACUNIT Reactor Building Ventillation Supply Fan "B" Decay Vault Room Cooler (Vault contains "B" Decay Heat & "B" Spray VUC1 D ACUNIT Pumps)

VUC7B ACUNIT

"'B Makekup/HPI Room Cooler X6 TRANSFORMER 41601480 VAC Transformer from Bus A4 to B6 Y22 INVERT 120 VAC Inverter (supplies RS2)

Y24 INVERT 120 VAC Inverter (supplies RS4)