February 26, 2004 LICENSEE: Southern Nuclear Operating Company FACILITY: Joseph M. Farley Nuclear Plant, Units 1 and 2

SUBJECT:

SUMMARY

OF TELEPHONE CONFERENCES ON FEBRUARY 13, 17, AND 18, 2004, BETWEEN THE U.S. NUCLEAR REGULATORY COMMISSION AND THE SOUTHERN NUCLEAR OPERATING COMPANY CONCERNING DRAFT REQUESTS FOR ADDITIONAL INFORMATION ON JOSEPH M. FARLEY NUCLEAR PLANT, UNITS 1 AND 2, LICENSE RENEWAL APPLICATION (TAC NOS. MC0774 AND MC0775)

The U.S. Nuclear Regulatory Commission staff and representatives of Southern Nuclear Operating Company (SNC or the applicant) held telephone conferences on February 13, 17, and 18, 2004, to discuss the draft requests for additional information (D-RAIs) concerning the Joseph M. Farley Nuclear Plant (FNP) license renewal application.

The conference calls were useful in clarifying the intent of the staffs questions. On the basis of the discussion, the applicant was able to understand the staff's questions. No staff decisions were made during the telephone conferences. In some cases, the applicant agreed to provide information for clarification. provides a list of the telephone conference participants. Enclosure 2 contains a listing of the D-RAIs discussed with the applicant, including a brief description on the status of the items. The applicant has had an opportunity to review and comment on this summary.

/RA/ Samson Lee for Tilda Y. Liu, Project Manager License Renewal Section A License Renewal and Environmental Impacts Program Division of Regulatory Improvement Programs Office of Nuclear Reactor Regulation Docket Nos: 50-348 and 50-364

Enclosures:

As stated cc w/enclosures: See next page

February 26, 2004 LICENSEE: Southern Nuclear Operating Company FACILITY: Joseph M. Farley Nuclear Plant, Units 1 and 2

SUBJECT:

SUMMARY

OF TELEPHONE CONFERENCES ON FEBRUARY 13, 17, AND 18, 2004, BETWEEN THE U.S. NUCLEAR REGULATORY COMMISSION AND THE SOUTHERN NUCLEAR OPERATING COMPANY CONCERNING DRAFT REQUESTS FOR ADDITIONAL INFORMATION ON JOSEPH M. FARLEY NUCLEAR PLANT, UNITS 1 AND 2, LICENSE RENEWAL APPLICATION (TAC NOS. MC0774 AND MC0775)

The U.S. Nuclear Regulatory Commission staff and representatives of Southern Nuclear Operating Company (SNC or the applicant) held telephone conferences on February 13, 17, and 18, 2004, to discuss the draft requests for additional information (D-RAIs) concerning the Joseph M. Farley Nuclear Plant (FNP) license renewal application.

The conference calls were useful in clarifying the intent of the staffs questions. On the basis of the discussion, the applicant was able to understand the staff's questions. No staff decisions were made during the telephone conferences. In some cases, the applicant agreed to provide information for clarification. provides a list of the telephone conference participants. Enclosure 2 contains a listing of the D-RAIs discussed with the applicant, including a brief description on the status of the items. The applicant has had an opportunity to review and comment on this summary.

/RA/ Samson Lee for Tilda Y. Liu, Project Manager License Renewal Section A License Renewal and Environmental Impacts Program Division of Regulatory Improvement Programs Office of Nuclear Reactor Regulation Docket Nos: 50-348 and 50-364

Enclosures:

As stated cc w/enclosures: See next page DISTRIBUTION:

See next page Accession No: ML040580696 Document Name:C:\ORPCheckout\FileNET\ML040580696.wpd OFFICE LA:RLEP PM:RLEP SC:RLEP NAME M. Jenkins T. Liu SSL for S. Lee DATE 2/25/04 2/26/04 2/26/04 OFFICIAL RECORD COPY

DISTRIBUTION: Note to Licensee: So. Nuclear Operating Company, Re: JMFarley, Dated: February 26, 2004 Accession No: ML040580696 HARD COPY RLEP RF T. Liu (PM)

J. Medoff K. Chang G. Morris D. Nguyen D. Jeng E-MAIL:

PUBLIC J. Craig D. Matthews F. Gillespie C. Grimes RidsNrrDe E. Imbro G. Bagchi K. Manoly W. Bateman J. Calvo R. Jenkins P. Shemanski J. Fair S. Black B. Boger D. Thatcher R. Pettis G. Galletti C. Li J. Moore R. Weisman M. Mayfield A. Murphy S. Smith (srs3)

S. Duraiswamy Y. L. (Renee) Li RLEP Staff C. Julian (R-II)

C. Patterson (R-II)

R. Fanner (R-II)

S. Peters D. Cummings/M. Lemoncelli (OGC)

OPA B. Jain L. Whitney J. Honcharik M. Lintz

LIST OF PARTICIPANTS FOR TELEPHONE CONFERENCES ON DRAFT REQUESTS FOR ADDITIONAL INFORMATION February 13, 2004 Participants Affiliation Tilda Liu NRC Jim Medoff NRC Ken Chang NRC Mark Lintz NRC Sean Peters NRC John Honcharik NRC Jan E. Fridrichsen SNC Mike Macfarlane SNC Chuck Pierce SNC Rick Mullins SNC Doug Daughhetee SNC Jon Hornbuckle SNC February 17, 2004 Participants Affiliation Tilda Liu NRC George Morris NRC Duc Nguyen NRC Jim Leivo ISL Jan Fridrichsen SNC Mike Macfarlane SNC Chuck Pierce SNC Jeff Mulvehill SNC Mark Crisler SNC Partha Ghosal SNC Cary Martin SNC February 18, 2004 Participants Affiliation Tilda Liu NRC David Jeng NRC Richard Morante BNL Jan Fridrichsen SNC Mike Macfarlane SNC Jeff Mulvehill SNC Mark Crisler SNC Partha Ghosal SNC Cary Martin SNC Bill Evans SNC Enclosure 1

REVIEW OF LICENSE RENEWAL APPLICATION (LRA) FOR FARLEY UNITS 1 AND 2 February 13, 2004 The NRC staff and representatives of SNC held a telephone conference on February 13, 2004, to discuss the applicants proposed aging management programs (AMPs) at FNP, Units 1 and

2. The subject AMPs were Reactor Vessel Surveillance Program and Reactor Vessel Internals Program. A summary of the issues discussed and the applicants proposed actions are presented below.

B.3.4, Reactor Vessel Surveillance Program The staff and the applicant discussed the reactor vessel capsule withdrawal schedule. The applicant stated that it planned to submit the withdrawal schedule under 10 CFR Part 50, Appendix H, requirements. The staff indicated that the schedule needed to be submitted under 10 CFR Part 54. The staff and the applicant agreed that the statuary regulatory requirement would need to be clarified with the Office of General Counsel (OGC). This issue will be discussed again between the staff and the applicant at a future conference call.

B.5.1, Reactor Vessel Internals Program The staff discussed an alternate option for defining the component locations and examinations that will be performed as part of implementation of the applicant's Reactor Vessel (RV) Internals Program. During this phone call, the staff informed the applicant that this alternative viable option would use a commitment for industry participation (including implementation of industry recommendations) and submittal of an inspection plan for the RV internals as the basis for defining the component locations and inspections that will be implemented as part of the AMP.

The applicant indicated that it would discuss the applicability of this option to the Farley LRA with its management. This issue will be discussed again between the staff and the applicant at a future conference call.

Enclosure 2

REVIEW OF LICENSE RENEWAL APPLICATION (LRA) FOR FARLEY UNITS 1 AND 2 DRAFT REQUESTS FOR ADDITIONAL INFORMATION (D-RAIs)

February 17, 2004 Section 3.6: Aging Management of Electrical Components Draft-RAI 3.6.2-1 Table 3.6.2-1, Electrical Components - Summary of Aging Management Review, discusses the intended functions and aging effects and aging management programs associated with the oil-static cables. Under the Pressure Boundary function, the AMPs referenced are Buried Piping and Tank Inspection Program [B.5.4] and External Surfaces Monitoring Program [B.5.3]. These programs list the Oil-Static Cable Pressurization System. Under the Provide Electrical Connections function, it states that there is no aging effect and no AMP is required. The table does not address the effect of aging on the oil impregnated paper insulation system and the terminations at each end of the cable.

a. LR boundary drawing D-372816L does not appear to include the oil-static cable.

Confirm that the boundary of the oil-static cable pressurization system includes the oil-static cable. If not, describe the AMP that covers the oil-static cable.

b. Describe how the aging effects on the oil-static cable insulation system is to be monitored. Provide operating experience with this cable system at FNP.

Response: The applicant indicated that the question is clear. This D-RAI will be sent as a RAI.

Specifically, the applicant stated the following:

a. The applicant stated that the oil-static cable itself is shown on the one-line diagrams referenced in Section 3.6, Aging Management of Electrical Components, of the application. The aging management for the pipe surrounding the oil-static cable is covered by the Buried Pipe Aging Management Program.
b. The applicant stated that it will research the Southern Company electrical system to identify operating experiences on oil-static cable insulation system to support its conclusion.

Section 4.4: Environmental Qualification of Electrical Equipment Draft-RAI 4.4-1 The FNP LRA, Table 4.4, List of EQ Packages, lists the Electrical Penetration Assemblies in a number of different packages (09B, 09C, 09E, 18 and 42). SNC stated during the Aging Management Program Audit conducted from November 3 to 7, 2003, and confirmed in its letter dated December 5, 2003, NL-03-2418, Enclosure 1, Electrical Question E2, that the 4160 kV power penetrations were not safety related and their electrical connection functions were covered under the Non-EQ Cables and Connections Program. The response did not identify any other non-EQ penetrations in low voltage power control or instrumentation applications.

The response also did not address the pressure/fission product boundary functions of the electrical penetrations.

a. Confirm that all electrical penetration assemblies (other than the 4160 kV power penetrations described in your letter) are included in the different packages listed in Table 4.4 of the LRA.
b. Identify where the pressure/ fission product boundary functions of the EQ and Non-EQ electrical penetrations assemblies are evaluated and how those functions will be maintained.
c. Confirm that the electrical penetrations assemblies associated with the personnel air locks, if any, are either included in one of the penetration items listed in Table 4.4 of the LRA or provide an evaluation that addresses the license renewal requirements.

Response: The applicant stated that it plans to revise Table 2.4.1 in the LRA to include mechanical portion of the electrical penetration assemblies, so that it would also help clarify this D-RAI. The applicant indicated that the question is clear. This D-RAI will be sent as a RAI.

REVIEW OF LICENSE RENEWAL APPLICATION (LRA) FOR FARLEY UNITS 1 AND 2 DRAFT REQUESTS FOR ADDITIONAL INFORMATION (D-RAIs)

February 18, 2004 Section 2.4.1: Containment Structures Draft-RAI 2.4-7 LRA Section 2.4.1 Containment Structure contains the following discussion related to electrical penetrations through containment:

2.4.1.3 Penetrations In general, a containment penetration consists of a sleeve embedded in the concrete wall or floor and welded to the containment liner plate. Loads on the penetration are transferred to the containment structure. The process pipe or cable feed-through assembly passes through the sleeve and is seal welded to the sleeve via an appropriate adapter. Additional detail is provided below.

Electrical Penetrations Electrical penetrations consist of a sleeve that passes through the containment boundary. The sleeve is welded to the containment liner plate. A cable feed-through assembly is inserted in the sleeve and welded to the sleeve inside containment for Conax and GE type penetrations. The feed-through assembly is screwed to the clip angle for a Westinghouse type penetration.

LRA Table 2.2-1f Systems and Structures within the Scope of License Renewal - Electrical Components specifically lists (Electrical) Containment Penetrations. However, LRA Table 2.5.1 Electrical Component Types Subject to Aging Management Review and their Intended Functions does not specifically identify the cable feed-through assembly.

LRA Table 2.4.1 Containment Structure Component Types Subject to Aging Management Review and their Intended Functions does not identify any component group that would obviously include the cable feed-through assembly.

From the information in the LRA, the staff cannot determine whether the applicant is treating the cable feed-through assembly as a component of the containment structure or as an electrical component. The staff requests the applicant to clarify its treatment of the cable feed-through assembly, and also to identify where the AMR is located in the LRA.

Response: The applicant stated that it plans to modify Tables 2.4.1 and 3.5.2 in the LRA to include electrical assemblies. The applicant indicated that the question is clear.

This D-RAI will be sent as a RAI.

Joseph M. Farley Nuclear Plant cc:

Mr. Don E. Grissette Mr. Charles R. Pierce General Manager - Plant Farley Manager - License Renewal Southern Nuclear Operating Company Southern Nuclear Operating Company Post Office Box 470 40 Inverness Center Parkway Ashford, AL 36312 Post Office Box 1295 Birmingham, AL 35201 Mr. B. D. McKinney Licensing Manager Mr. Fred Emerson Southern Nuclear Operating Company Nuclear Energy Institute 40 Inverness Center Parkway 1776 I Street, NW, Suite 400 Post Office Box 1295 Washington, DC 20006-3708 Birmingham, AL 35201-1295 Resident Inspector Mr. Stanford M. Blanton, esq. U.S. Nuclear Regulatory Commission Balch and Bingham Law Firm 7388 N. State Highway 95 Post Office Box 306 Columbia, AL 36319 1710 Sixth Avenue North Birmingham, AL 35201 Mr. L. M. Stinson, Jr.

Vice President - Farley Project Mr. J. B. Beasley, Jr. Southern Nuclear Operating Company Executive Vice President 40 Inverness Center Parkway Southern Nuclear Operating Company Post Office Box 1295 40 Inverness Center Parkway Birmingham, AL 35201 Post Office Box 1295 Birmingham, AL 35201 Dr. D. E. Williamson State Health Officer Alabama Department of Public Health The RSA Tower 201 Monroe Street, Suite 1500 Montgomery, AL 36130-1701 Chairman Houston County Commission Post Office Box 6406 Dothan, AL 36302 Mr. William D. Oldfield SAER Supervisor Southern Nuclear Operating Company Post Office Box 470 Ashford, AL 36312