January 21, 2004 Mr. Thomas Coutu Site Vice President Kewaunee Nuclear Power Plant Nuclear Management Company, LLC N490 State Highway 42 Kewaunee, WI 54216
SUBJECT:
KEWAUNEE NUCLEAR POWER PLANT - REQUEST FOR ADDITIONAL INFORMATION FOR PROPOSED AMENDMENT REQUEST TO REVISE TECHNICAL SPECIFICATION 3.3.E, SERVICE WATER SYSTEM (TAC NO. MB9944)
Dear Mr. Coutu:
By letter dated July 7, 2003, the Nuclear Management Company, LLC (NMC or the licensee) submitted a request for a proposed amendment to revise the Kewaunee Nuclear Power Plant Technical Specifications 3.3.E, Service Water System, regarding the turbine building service water header isolation logic.
The Nuclear Regulatory Commission (NRC) staff has reviewed the information NMC provided with the July 7, 2003, submittal. Based on the review, the NRC staff has determined that additional information is required in order to complete the evaluation. The additional information being requested is enclosed.
A draft of the request for additional information was e-mailed to Mr. G. Riste (NMC) on December 18, 2003.
A phone call was held between G. Riste (NMC) and myself on January 13, 2004, to discuss the e-mail sent on December 18, 2003, to ensure that there was no misunderstanding.
Also, the phone call on January 13, 2004, established that February 28, 2004, would be a mutually agreeable response date.
Please contact me at (301) 415-1446 if future circumstances should require a change in this response date.
Sincerely,
/RA/
John G. Lamb, Project Manager, Section 1 Project Directorate III Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket No. 50-305
Enclosure:
Request for Additional Information cc w/encl: See next page
ML040150183 OFFICE PDIII-1/PM PDIII-1/LA PDIII-1/SC NAME JLamb THarris LRaghavan DATE 01/16/04 01/16/04 01/20/04
ENCLOSURE REQUEST FOR ADDITIONAL INFORMATION (RAI)
REGARDING PROPOSED AMENDMENT REQUEST TO TECHNICAL SPECIFICATION TS 3.3.E, SERVICE WATER SYSTEM KEWAUNEE NUCLEAR POWER PLANT DOCKET NO. 50-305 1.
The July 7, 2003, license amendment request (LAR) states that a Section 3 will be added to Technical Specifications (TS) 3.3.e, Service Water System to include an automatic isolation function to isolate the turbine building non-safety-related service water from the service water header during a design-basis accident. The isolation logic is based on Safety Injection signal coincident with a service water low-pressure signal.
Since the isolation function is required to mitigate a design-basis accident, the design of isolation logic should meet the protection system design criteria as required by regulation 10 CFR 50.55a(h) (IEEE std. 279/603). Provide detailed design information to demonstrate that the service water automatic isolation function meets the IEEE std. 279 or IEEE std. 603 requirements.
2.
Table TS 4.1-1, Minimum Frequencies for Checks, Calibrations and Test of Instrument Channels indicates that the instruments for service water isolation logic will be calibrated each refueling cycle and will be tested each refueling cycle. Justify these calibration and test frequencies.
3.
The LAR states that turbine building service water header isolation logic is only required to function for the service water train aligned to the turbine building header during a design-basis accident; therefore, the operability of the service water train not aligned to the turbine building header is independent of the operability of the isolation logic.
Discuss the operability determination criteria for the isolation logic and for the service water train.
Kewaunee Nuclear Power Plant cc:
John Paul Cowan Executive Vice President &
Chief Nuclear Officer Nuclear Management Company, LLC 700 First Street Hudson, MI 54016 James McCarthy Plant Manager Kewaunee Nuclear Power Plant N490 Highway 42 Kewaunee, WI 54216-9511 Gerry Riste Manager, Regulatory Affairs Kewaunee Nuclear Power Plant N490 Highway 42 Kewaunee, WI 54216-9511 David Molzahn Nuclear Asset Manager Wisconsin Public Service Corporation 600 N. Adams Street Green Bay, WI 54307-9002 Thomas Webb Nuclear Asset Manager Wisconsin Public Service Corporation 600 N. Adams Street Green Bay, WI 54307-9002 Resident Inspectors Office U. S. Nuclear Regulatory Commission N490 Hwy 42 Kewaunee, WI 54216-9510 Regional Administrator Region III U. S. Nuclear Regulatory Commission 801 Warrenville Road Lisle, IL 60532-4351 Jonathan Rogoff Vice President, Counsel & Secretary Nuclear Management Company, LLC 700 First Street Hudson, WI 54016 Larry L. Weyers Chairman, President and CEO Wisconsin Public Service Corporation 600 North Adams Street Greey Bay, WI 54307-9002 David Zellner Chairman - Town of Carlton N2164 County B Kewaunee, WI 54216 Mr. Jeffery Kitsembel Electric Division Public Service Commission of Wisconsin PO Box 7854 Madison, WI 53707-7854