ML033010575

From kanterella
Jump to navigation Jump to search
Corrections to IR 05000400-02-008 for Shearon Harris Nuclear Power Plant
ML033010575
Person / Time
Site: Harris Duke Energy icon.png
Issue date: 09/05/2003
From:
NRC/RGN-II/DRS/EB
To: Scarola J
Carolina Power & Light Co
References
FOIA/PA-2003-0358 IR-02-008
Download: ML033010575 (20)


See also: IR 05000400/2002008

Text

iR

EC4

UNITED STATES

NUCLEAR REGULATORY COMMISSION

0 {

o

REGION II

SAM NUNN ATLANTA FEDERAL CENTER

61 FORSYTH STREET SW SUITE 23T85

ATLANTA, GEORGIA 30303-31

Carolina Power & Light Company

ATTN: Mr. James Scarola

Vice President - Harris Plant

Shearon Harris Nuclear Power Plant

P. 0. Box 165, Mail Code: Zone 1

New Hill, NC 27562-0165

lk4

SUBJECT:

SHEARON HARRIS NUCLEAR POWER PLANT - NRC SUPPLEMENTAL

INSPECTION REPORT 50-400/02-08

J

.

>I

Dear Mr. Scarola:

9

a9

This supplemental inspection was an examination of your proble h identification, root cause

evaluation, extent of condition determination, and corrective actions associated with a White

finding identified in the mitigating systems cornerstone. The White finding involved a violation

of your fire protection program resulting from a Thermo-Lag fire barrier assembly (wall) which

had an indeterminate fire resistance rating.

I

_'4"'ased on the results of the

ee-s_-L-r

For administrative purposes, a Severity Level IlIl violation associated with the Thermo-Lag fire

barrier assembly between the B train switchgear room/auxiliary control panel room and the A

train cable spreading room which was previously dispositioned in NRC's letter dated April 16,

2002, is identified in the enclosed report.

I

No findings of significance were identified during the inspection.

4.

P

O0/

I-

611

6 3i

3/,, 2a /

A-L

1  A-* AA



72A-4

/2 /

7i

kt'4

  1. L

rj

4

d;i/

jcl

/

1



t24%/

4

96Z.

e*-

/



~/,,/j

6

~

5

l64Ux

C d


v

.

if

)e4(

-1

.

ZleL,

Po

Ale-z,

I

I

I

I'

I

i

A"6

By~~~~~~~~

4

7, rl`f

A.-



yxw/

xol"f-

le-

/11

p

9~ 27y

/7-I

/v C1/C

57$6 )

.

W,,-ez

,

N

-10,

Ejj ~

~

~ ~ /-7;

~opl,-

-

-

rF

,,

,,

,

,aw

plk-e,

,o,--~

.

/

r "' -

"-

/Zft-fl

714't-

46

,S

Age

64Z

a41!x

it

CP&L

2

In accordance with 10 CFR 2.790 of the NRC's Rules of Practice," a copy of this letter and its

enclosure will be available electronically for public inspection in the NRC Public Document

Room or from the Publically Available Records (PARS) component of NRC's document system

(ADAMS). ADAMS is accessible from the NRC Web site at http://www.nrc.aov/readina-

rm/adams.html (the Public Electronic Reading Room).

Sincerely,

Charles R. Ogle, Chief

Engineering Branch 1

Division of Reactor Safety

Docket No.: 50-400

License No.: NPF-63

Enclosure: NRC Inspection Report No. 50-400/02-08

w/Attachment

cc w/encl:

Terry C.'Morton, Manager

Performance Evaluation and

Regulatory Affairs

CPB 9

Carolina Power & Light Company

Electronic Mail Distribution

Robert J. Duncan II

Director of Site Operations

Carolina Power & Light Company

Shearon Harris Nuclear Power Plant

Electronic Mail Distribution

Benjamin C. Waldrep

Plant General Manager-Harris Plant

Carolina Power & Light Company

Shearon Harris Nuclear Power Plant

Electronic Mail Distribution

James W. Holt, Manager

Support Services

Carolina Power & Light Company

Shearon Harris Nuclear Power Plant

Electronic Mail Distribution

(cc w/encl cont'd - See page 3)

CP&L

3

(cc w/encl cont'd)

John R. Caves, Supervisor

Licensing/Regulatory Programs

Carolina Power & Light Company

Shearon Harris Nuclear Power Plant

Electronic Mail Distribution

William D. Johnson

Vice President & Corporate Secretary

Carolina Power & Light Company

Electronic Mail Distribution

John H. O'Neill, Jr.

Shaw, Pittman, Potts & Trowbridge

2300 N. Street, NW

Washington, DC 20037-1128

Beverly Hall, Acting Director

Division of Radiation Protection

N. C. Department of Environmental

Commerce & Natural Resources

Electronic Mail Distribution

Peggy Force

Assistant Attorney General

State of North Carolina

Electronic Mail Distribution

.

.1

.. .

Public Service Commission

State of South Carolina

P. 0. Box 11 649

Columbia, SC 29211

Chairman of the North Carolina

Utilities Commission

P. 0. Box 29510

Raleigh, NC 27626-0510

Robert P. Gruber

Executive Director

Public Staff NCUC

4326 Mail Service Center

Raleigh, NC 27699-4326

(cc w/encl cont'd - See page 4)

CP&L

4

(cc w/encl cont'd)

Linda Coleman, Chairman

Board of County Commissioners

of Wake County

P. O. Box 550

Raleigh, NC 27602

Gary Phillips, Chairman

Board of County Commissioners

of Chatham County

Electronic Mail Distribution

U. S. NUCLEAR REGULATORY COMMISSION

REGION I I

O,

t

.

Docket No:

License No:

Report No:

Licensee:

Facility:

Location:

Dates:

Inspectors:

Approved By:

50-400

_

NPF-63

50-400/2002-08

Carolina Power & Light (CP&L)

Shearon Harris Nuclear Power Plant, Unit 1

5413 Shearon Harris Road

New Hill, NC 27562

V"-

nnng

-

_

c

CAL 4I.

A

R?02-

'

J. Lenahan, Senior Reactor Inspector

Charles R. Ogle, Chief

Engineering Branch 1

Division of Reactor Safety

SUMMARY OF FINDINGS

IR 05000400-02-08; Carolina Power and Light Company; on65e21~2; Shearon Harris

Nuclear Plant, Unit 1; Supplemental inspection of Thermo-Lag fire barrier with indeterminate

fire resistance rating.

This inspection was conducted by regional inspectors. A White finding, which was previously

dispositioned in an NRC letter dated April 16, 2002, is identified in this report for administrative

purposes. The significance of most findings is indicated by their color (Green, White, Yellow,

Red) using IMC 0609 Significance Determination Process" (SDP). Findings for which the SDP

does not apply are indicated by "Green" or be assigned a severity level after management

review. The NRC's program for overseeing the safe operation of commercial nuclear power

reactors is described in NUREG-1 649, "Reactor Oversight Process," Revision 3, dated Julyt

2000.

Cornerstone: Mitigating Systems

( 0 A,77

The

uclear Requ

NRC3_performed t

supplemental inspection to

assess the licensee's

assoc ate with the Therm

Lag fire barrier s8parating Train-A

and Train B safoty related eables in the Auxiliary Control P

Inel

(ACP) room. The Thermo-Lag

barrier provided a fire resistance o n h

a

1 m

,

e

1

t

the minimum three-

hour fire resistance rating required by 10 CFR 50, Appendix

This performance

issue was previously documented in NRC Inspection Report

5000/99-13 and later

tt J,

characterized as having low to moderate risk significance

ite) in an NRC letter dated

r' ,/vJ

April 16, 2002.

(3'

During this supplemental inspection, performed in accorda e with Inspection Procedure

(

95001, the inspectors determined that the licensee's pro em identification, root cause and

extent of condition evaluation were adequate. The lice see's corrective actions to resolve the

issues were ongoingtdapoarod to be adeguato.

owever, the inspectors identified that the

licensee intended to use local manual operator actions

lieu of protect ig Train A a,1J T.v11 B

cablcs in the new AGP room fire

eoa

as roquired Ly 10 CFR 50, Appendix R.The licensee

entered this issue into its corrective action program and resolution is pending.

As a result of this z

Tncem,

the white pen4Fnce issue associated with the Thermo-Lag fire

barrier willnot be closed at this time. The issue will remain open pending further NRC review of

the licensee's corrective actions associated with the use of loal ma operator actions in the

Ponnrt Dntgair

01

INSPECTION SCOPE

The U.S. Nuclear Regulatory C

mrnic2

ormed this supplemental inspection

to assess the licensee's evaluation assoc

d with

Thermo-Lag fire barriers

n

Train A ad Train Bafetv R

elatd

cables in the Auxiliary Control Panel (ACP) room. The

JheroLgbrirddl

resistance -of ne hur an ;~1mjLS*,

rather 0-

.0 it;-

mminimum three-hour fire resistance rating required

50,Appendix R regaut22.

This performance issue was previously documented in NRC Inspection Report number

50-400/99-13 and later characterized as having low to moderate risk significance (White)

in an NRC letter dated April 16, 2002.

The inspectors assessed problem identification, the licensee's root cause and extent of

condition evaluation, and the licensee's corrective actions to solve the White finding in

their fire protection program. The inspectors reviewed desinge documents,

including design inputs, assumptions, and design evaluati

nsee self assessmer)

and changes to operating procedures, fire protection proceswes, and the safe shutd;Rn-

analysis. The inspector also examined in process plant modifications being performed on

fire barriers.

02

EVALUATION OF INSPECTION REQUIREME

02.01 Problem Identification

a.

Determination of who identified the issue and un er what conditins-

During he 4

ire

protection inspectio ,

/

ucted fro

ember

1 -5, 1999, and documented in NRC Inspe

onport No. 0-400/99-13,

unresolved

items (URls) were identified by NRC inspe ors. One of th URls concerned the

adequacy of a Thermo-Lag wall whi

designated as

three-hour fire barrier

between the Train B switchgear ro m

d rain A safety elated cables routed in the

Auxiliary Control Pane

ron. Te

otential problm of using Thermo-Lag as a fire

barrier material was

entified to indu

y the NRC in 992 in Generic Letter (GL) 92-08

and NRC Bulletin 9201D Inr s s oNRC Bulletin 9 -01 and GL 92-08, the licensee

conducted testing o a mo k-up of

Thermo-Lag wa . This testing showed the barrier

failed fire endurance le-acceptance criteria at 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> 8 minutes. The licensee then

performed an engineering evaluation which concluded the as-constructed Thermo-Lag

wa

_izci1M94retrelBFbrif

The licensee\\

initiated Problem Evaluation Report (PER) 99-006863 to document and disposition the

URI identified'/

b. Determination o h

n

the issue existed, and prior opportunities for identification

Hog

The degraded fires

installe during original plant construction. Prior2-08k

Y'

,

\\

opprtuntiesfar dentficaion

erersponse to NRC Bulletin 92-01 and GL 92-081t

t{

\\

gcensee actions to addres

esulted in the acceptance of an inadequate

Thermo-Lag fire barrier in 1997 (ESR 95-00620, Thermo-lag Fire Protection Issues

Resolution," Revision 1). There v

vcre b

Itl uppui luatics to find this prb~obe.The final

\\

ptv

fi<

r;ea

S

Cut

S

go

>Agokwiz

noie mddiat;E~.t998 triennial fire

otection Nuclear Assessment Section audit

iaspacte"

Sa O

f Ther-ghr

and included thereurdiepnrl

er}"'

performee y

s of the fire protection program

after 1 997, also head Ihu ieuppurtuliyt}fn the poeblem.

v

Determination of the plant-specific risk consequences (as applicable) and compliance

concerns associated with the issue

The degraded fire barrier was evaluated for a postulated fire in the B switchgear room than

_! -1Mki:Cagxfid

eaM*Q-d

cause the Thermo-Lag fire barrier wall in the ACP area of the

B switchgear room fire area to fail. Failure of this wall exposed Train A..cables, located

within the enclosed barrier area, to the postulatesfre. The Train A cables behind the

Thermo-Lag wall affected the Train

eayl

Gdwater function and the A steam

generator pressure operated relief vWe funcioPs. The NRC assessment concluded that

this event was in the increased regulatory response (White) band. The results of the

NRC's final significance determination for the degraded fire barrier were documented in

an NRC letter to CP&L dated April 16, 2002, Subject: Final Significance Determination For

a White Finding and Notice of Violation (Shearon Harris Nuclear Power Plant - NRC

Inspection Report 50-400/00-09).

02.02 Root Cause and Extent of Condition Evaluation

a.

Evaluation of methods used to identify root causes and contributing causes.

The licensee initiated a Significant Adverse Condition Report, Action Request number

53063, to evaluate and correct the problem associated with the Thermo-Lag wall. The

evaluation was performed using the systematic methods specified in the licensee's

corrective action program specified in CP&L procedure CAP-NGGC-0200. The licensee

concluded that the root cause of the White finding was. *

-inannrmwriate

'use of an

analysis to accept changes to the NRC approved fire

causes were inadequate testing of installed fire barriers..

evaluations, and failure to address design requirement:

b.

Level of detail of the root cause evaluation

The inspectors determined that the root cause evaluat

support the identified root and contributing causes. Ti

identify why the inadequate fire testing of the installed

or why there was too much reliance on GL 86-10 engi

cause), or why there was a failure to adequately addres

_..-:,..

(contributing cause). How

r

-

PI

i

r"'it

.__t

... pg.

_

addiio' ln:t

"

"

  • -

...

Ind

I-

A_,

,_v.^t

,,

q o o ,- J .___ _

AA4a"A%4*.

3

c.

Consideration of prior occurrences of the problem and knowledge of prior operating

experience

The licensee's investigation identified 218 matches from the INPO database including

GLs, NRC Bulletins and Information Notices, and LERs related to similar Thermo-Lag

issues at various nuclear power plants. The root cause evaluation found that the method

of resolution at HNP was unique from the others identified.

d.

Consideration of potential common causes and extent of condition of the problem

In late 2000, the NRC identified additional Thermo-Lag fire barriers in the cable

spreading rooms which did not meet the requirements for three-hour fire barriers.

Because fire suppression systems (sprinklers) existed in most of these areas, the

licensee was able to downgrade the barriers to a'one-hour fire rating and comply with

i

10 CFR 50, Appendix R requirements. However, soMe areas did not have sufficient

spatial coverage by these sprinklers. The licensee also did not have sufficient test

data/documentation to adequately demonstrate that some as-built Thermo-Lag barrier

configurations in the cable spreading room provided a one-hour barrier. As a result, the

licensee has initiated a program to evaluate existing sprinkler coverage, install new

sprinklers as required, and test the existing barrier configurations to show they will meet

the one-hour requirement. These corrective actions are scheduled to be completed by

December 2002. The licensee performed a detailed self-assessment to examine the

overall fire protection program and compare it to applicable regulatory requirements,

(Appendix R, UFSAR, SERs, etc.) 'The evaluation portion of the assessment has been

completed. Numerous findings were identified. Examples of findings include: illegible

UFSAR drawings, typographical errors in the UFSAR, unclear statements In the UFSAR

and SERs, factual errors in the UFSAR (e.g., location of hose stations), and lack of test

documentation to demonstrate the mullians door frames and transoms over fire doors

meet 10 CFR 50, Appendix R requirements. Ti

.4 indingsar being ro'iowod to

detrmi a-howt

ripo UaAugust, 2002.

02.03 Corrective Actions

a.

Appropriateness of corrective action

The inspector determined that

licensee's corrective actions were dequate to res

the issue. Corrective action included modifying the ACP fire are

-for the-Thormeag-barior._

Th

_

_wouldb

d 1

by upgradin

n existing concrete wall

toa-free-hour fire barrier. Jign procedures were revis

to emphasize the

requirement

a dequate q lification testing be perfor ed prior to changing the

approved fire protection program. However, the insp

ors identified that the licensee

intended to use local manual operator actions'ie of protecting Train A and Train B

cables in the new ACP room fire area

10 CFR 50, Appendix R. The

licensee entered this issue into its corrective action program as NCR 20020823, Fire

Protection Manual Action Discrepancies."

~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~'

5war <7=

11~~~~~~~~~~#?

4

As a resulef ie eeRewe, the White pe4oranoe issue associated with the Thermo-Lag

fire barrier will not be closed at this time. The issue will remain open pending further

NRC review of the licensee's corrective actions asoeiated wth II ie us of local mai Iuat

oporator Oatien9 in the netw A

rom fire area t aehove safe shutdown in-

the

ovilf x

b.

Pq`AtftW'o =etive actions °-

The inspector concluded that the licensee's corrective actions were properly prioritized to

address the risk. The changes to the ACP fire area were being worked concurrent with

completion of the engineering change. The inspectors revi we

emr

Change

(EC) 48802 to upgrade an existing concrete wall betweenW

g

m B and the

ACP room to a three-hour rated fire barrier. This work inc uded sealing the existing

penetrations in the wall. The above actionsZ sforted the ACP room into a new fire

area. The licensee has revised its fire

f?136, Safe Shutdown Following a Fire)

to address the newly created area

cludes the use of local manual operator

actions to achieve safe shutdown

ire scenarios in the new ACP room fire area.

As

dic..so abd "'xH

c.

Establishment of schedule for implementing and completing the corrective actions

The inspector verified that the Iiensee's corrective action program identified assigned

individuals, completion dates,

d reference numbers to the licensee's corrective action

tracking program to ensure t t corrective actions would be completed in accordance

with:their priority. Procedur changes to ensure that review criteria exist to ensure that

fire barrier modifications daSnot invalidate test results in the future was complete.

Although the EC for the

CP room had not been issued, the field work had been

-

perfoormed at risk and w s essentially completed prior to completion of the.EC Revews

of other fire barri

in progress, and initial walk dowrs were complete. Resolution

oter fire protection is

s

k*dtsce

ing prioritized based on risk.

b W

d.

Establishment of quantitative or qualitative measures of success for determining the

effectiveness of the corrective actions to prevent recurrence

The effectiveness of these measures will be determined through direct observation of the

completed modifications and changes to the fire protection program. The licensee has

scheduled an effectiveness review for July 2003.

The inspectors performed plant walk downs and conducted document reviews in

determining that the extent of condition for the Thermo-Lag wall issue included all

Thermo-Lag usage in the plant. Thermo-Lag usage in the plant included various

transoms and mullions on the 216', 236', 261', and 305' elevations of the reactor auxiliary

building and control building; and Thermo-Lag wall and tunnel assemblies in the A and B

cable spreading rooms, the B switchgear room and the ACP area. The problem with the

Thermo-Lag issue was related to the use of engineering evaluations for determining the

applicability of fire test results to qualify plant features as rated fire barriers. In the case

of the Thermo-Lag, a failed three-hour qualification fire test was used to accept Thermo-

Lag features by engineering evaluation as adequate for the hazard. The use of failed

tests for fire rating determination appears specific to the resolution of this Thermo-Lag

5

issue. In other cases, hardware modifications were made to reconcile the configurations

to the test configurations that passed rating tests. Upgrading the concrete wall between

the B switchgear room and the ACP room to a three-hour barrier decreases the risk of

damaging the A train cables in the ACP room as a result of a fire in the B switchgear

room.

03

OTHER ACTIVITIES

03.01 Other

(Closed) AV 50-400/00-09-01: ailure to Maintain the Fire Area Separation Barrier

Between The B Train Switchgear Room/Auxiliary Control Panel Room and the A Train

Cable Spreading Room as a 3-hour Rated Barrier

This apparent violation was identified to the licensee in a letter dated December 18,

2001, Subject: NRC Inspection Report 50-400/00-09; Preliminary White Finding. The Scl"

apparent violation concerned the Thermo-Lag fire barrier assembly whiclFeB train

switchgear room and the A train cable spreading room. The results of testing performed

by the licensee in 1994 and 1995 showed that the fire barrier did not have the required

three-hour fire resistance rating. After reviewing the test results, the licensee changed

the fire protection program by revising the rating of the fire barrier from three hours to

.

that suitable for the hazard. This issue had been initially identified by NRC as unresolved

item 50-400/99-13-01. In a letter dated April 16, 2002, Subject: Final Significance

Determination For a White Finding and Notice of Violation (Shearon Harris Nuclear

Power Plant - NRC Inspection Report 50-400/00-09), the licensee was informed that

NRC had determined that this issue was a violation of License Condition 2F of the Harris

Operating License. A Notice of Violation, Severity Level IlIl, was included as an

Enclosure to the April 16, 2002 letter. For tracking purposes, this Severity Level ill

violation is identified as Violation (VIO) 50-400/02-08-01: Failure to Implement and

Maintain NRC Approved Fire Protection Program Safe Shutdown System Separation

Requirements. Apparent Violation 50-400/00-09-01 is closed.

'

(Closed) AV 50-40000-09-026Falure to Obtain NRC Approval Prior to Implementing a

Change to the Approved Fire Protection Program

This apparent violation was also identified to the licensee in a letter dated December 18,

2001, Subject: NRC Inspection Report 50-400/00-09; Preliminary White Finding. This

apparent violation concerned the fact that the licensee made changes to the approved

fire protection program by accepting the degraded fire barrier, through an engineering

evaluation, without prior Commission approval. This issue had been initially identified by

NRC as unresolved item 50-400/99-13-02. In a letter dated April 16,2002, Subject: Final

Significance Determination For a White Finding and Notice of Violation (Shearon Harris

Nuclear Power Plant - NRC Inspection Report 50-400/00-09), the licensee was informed

that NRC had determined that it was appropriate to cite this issue as part of Violation

(VIO) 50-400/02-08-01: Failure to Implement and Maintain NRC Approved Fire Protection

Program Safe Shutdown System Separation Requirements. Apparent Violation

50-400/00-09-02 is closed.

0z

6

MANAGEMENT MEETINGS

Exit Meeting Summary

The inspector presented interim results of the inspection to Mr. J. Scarola and other

members of his staff at the conclusion of the inspection on May 31, 2002.

exit 4l

,

-metig was held

ee

with Mr.

es on September 6, 2002, to I

44

present the final results of the inspection. The license acknowledged the findings

presented. Proprietary information is not included in tije nspection report.

7

SUPPLEMENTAL INFORMATION

PARTIAL LIST OF PERSONS CONTACTED

Licensee

D. Alexander, Manager, Nuclear Assessment Section

J. Caves, Supervisor, Licensing

M. Fletcher, Fire Protection System Engineer

C. Georgeson, Electrical Engineer

J. Holt, Site Support Services Manager

A. Khanpour, Superintendent of Design, Harris Engineering Support Services (HESS)

D. McAfee, Fire Protection Program Manager

E. McCartney, Superintendent Of Technical Services, HESS

J. Scarola, Harris Plant Vice President

M. Wallace, Senior Analyst, Licensing

NRC

J. Brady, Senior Resident Inspector

ITEMS OPENED, CLOSED AND DISCUSSED

Opened

50-400/02-08-01

Vlo

Failure to Implement and Maintain NRC

Approved Fire Protection Program Safe

Shutdown System Separation Requirements

(Section 03.01)

Closed

50-400/00-09-01

AV

Failure to Maintain the Fire Area Separation

Barrier Between The B Train Switchgear

Room/Auxiliary Control Panel Room and the

A Train Cable Spreading Room as a 3-hour

Rated Barrier (Section 03.01)

Failure to Obtain NRC Approval Prior to

Implementing a Change to the Approved

Fire Protection Program(Section 03.01)

50-400/00-09-02

AV

LIST OF BASELINE INSPECTIONS PERFORMED

The following procedure was used to perform the inspection during the report period.

Documented findings are contained in the body of the report.

IP 95001

Supplemental Inspection For One Or Two White inputs In A Strategic

Performance Area.

ATTACHMENT

LIST OF DOCUMENTS REVIEWED

CP&L Procedure CAP-NGGC-200, Corrective Action Program, Rev. 4

Engineering Service Request 99-0180, Evaluation of Low Density Silicone Elastomer (LDSE)

Seals, Rev. 0, 6/16/99

Engineering Change 48802, Make ACP Room Separate Fire Area, Revision 0, 7/17/02

Design Basis Document

Calculation E-5525, Safe Shutdown Analysis in Case of Fire, Rev. 5, 517/02, and pending

changes resulting from EC 48802

Calculation E-5524, Safe Shutdown Analysis Changes to the Cable Function Report and

Essential Cable Analysis, Rev. 5, 6/2/02

Abnormal Operating Procedure AOP-036, Safe Shutdown Following A Fire, Rev. 19, and

pending revisions resulting from EC 48802

Drawing Numbers SK-48802-C-1 000, ACP Door Transom Detail, Sheets 1 and 2

Drawing Number SK-48802-C-1 000, ACP Wall Penetrations, Sheet 1

Work Orders 233062 01 and 233062 02, Make ACP Room Separate Fire Area

ATTACHMENT

Carolina Power & Light Company

ATTN: Mr. James Scarola

Vice President - Harris Plant

Shearon Harris Nuclear Power Plant

P. 0. Box 165, Mail Code: Zone 1

New Hill, NC 27562-0165

SUBJECT:

SHEARON HARRIS NUCLEAR POWER PLANT - NRC SUPPLEMENTAL

INSPECTION REPORT 50-400/02-08

Dear Mr. Scarola:

On May 31, 2002, the Nuclear Regulatory Commission (NRC) completed a supplemental

inspection at your Shearon Harris Nuclear Power Plant. The enclosed report documents the

inspection findings which were discussed on May 31, 2002, with you and other members of

your staff.

This supplemental inspection was an examination of your problem identification, root.cause

evaluation, extent of condition determination, and corrective actions associated with a White

finding identified in the mitigating systems cornerstone. The White finding irvolved a violation

of your fire protection program resulting from a Thermo-Lag fire barrier assembly (wall) which

had an indeterminate fire resistance rating.

Based on the results of the inspection, the NRC determined that your corrective actions (both

planned and already completed) are appropriate to resolve the deficiency in your fire protection

program concerning the Thermo-Lag fire barriers which did not comply with 10 CFR 50,

Appendix R requirements. However, the White finding will remain open pending further NRC

review of your corrective actions associated with the use of local manual operator actions in the

new ACP room fire area to achieve safe-shutdown in the event of a fire.

For administrative purposes, a Severity Level IlIl violation associated with the Thermo-Lag fire

barrier assembly between the B train switchgear room/auxiliary control panel room and the A

train cable spreading room which was previously dispositioned in NRC's letter dated April 16,

2002, is identified in the enclosed report.

No findings of significance were identified during the inspection.

CP&L

2

In accordance with 10 CFR 2.790 of the NRC's "Rules of Practice,' a copy of this letter and its

enclosure will be available electronically for public inspection in the NRC Public Document

Room or from the Publically Available Records (PARS) component of NRC's document system

(ADAMS). ADAMS is accessible from the NRC Web site at httP://www.nrc.aov/readinp-

rm/adams.html (the Public Electronic Reading Room).

Sincerely,

Charles R. Ogle, Chief

..Engineering Branch 1

Division of Reactor Safety

Docket No.: 50-400

License No.: NPF-63

Enclosure: NRC Inspection Report No. 50-400/02-08

w/Attachment

cc w/encl:

Terry C. Morton, Manager

Performance Evaluation and

Regulatory Affairs

CPB 9

Carolina Power & Light Company

Electronic Mail Distribution

Robert J. Duncan II

Director of Site Operations

Carolina Power & Light Company

Shearon Harris Nuclear Power Plant

Electronic Mail Distribution

Benjamin C. Waldrep

Plant General Manager--Harris Plant

Carolina Power & Light Company

Shearon Harris Nuclear Power Plant

Electronic Mail Distribution

James W. Holt, Manager

Support Services

Carolina Power & Light Company

Shearon Harris Nuclear Power Plant

Electronic Mail Distribution

(cc w/encl cont'd - See page 3)

CP&L

3

(cc w/encl cont'd)

John R. Caves, Supervisor

Licensing/Regulatory Programs

Carolina Power & Light Company

Shearon Harris Nuclear Power Plant

Electronic Mail Distribution

William D. Johnson

Vice President & Corporate Secretary

Carolina Power & Light Company

Electronic Mail Distribution

John H. O'Neill, Jr.

Shaw, Pittman, Potts & Trowbridge

2300 N. Street, NW

Washington, DC 20037-1128

Beverly Hall, Acting Director

Division of Radiation Protection

N. C. Department of Environmental

Commerce & Natural Resources

Electronic Mail Distribution

Peggy Force

Assistant Attorney General

State of North Carolina

Electronic Mail Distribution

Public Service Commission

State of South Carolina

P. 0. Box 11649

Columbia, SC 29211

Chairman of the North Carolina

Utilities Commission

P. O. Box 29510

Raleigh, NC 27626-0510

Robert P. Gruber

Executive Director

Public Staff NCUC

4326 Mail Service Center

Raleigh, NC 27699-4326

(cc w/encl cont'd - See page 4)