From:
Peter Tam To:
David Helker; Pareez Golub Date:
10/21/03 1:58PM
Subject:
Oyster Creek - Draft RAI for Discussion (TAC MB8481)
Pareez:
This is regarding AmerGens application for amendment dated 4/21/03, as supplemented on 9/11/03, regarding DC power source requirements based on TSTF-360. Our review is ongoing and we believe more information is needed to completed our review. Accordingly, we are providing the following draft questions for discussion in a phone call:
(1)
Provide the basis, including results of analysis demonstrating the need and justification for, the proposed 7-day allowed outage time for an inoperable battery charger.
(2)
Describe and justify the extent to which risk has (or has not) been considered as part of the basis and analysis justifying the proposed 7-day allowed outage time for an inoperable battery charger.
(3)
Identify and justify compensatory measures that will be implemented during the proposed 7-day allowed outage time for an inoperable battery charger.
This e-mail aims solely to prepare you and others for a telephone discussion. This e-mail does not formally request for information, nor does it convey a formal NRC staff position.
Peter S. Tam, Senior Project Manager Project Directorate I-1 Division of Licensing Project Management Office of Nuclear Reactor Regulation e-mail: pst@nrc.gov Tel.: 301-415-1451 CC:
John Knox; Matthew McConnell; Ngoc Le; Saba Saba Mail Envelope Properties (3F9573CD.F48 : 10 : 20510)
Subject:
Oyster Creek - Draft RAI for Discussion (TAC MB8481)
Creation Date:
10/21/03 1:58PM From:
Peter Tam Created By:
PST@nrc.gov Recipients Action Date & Time owf2_po.OWFN_DO Delivered 10/21/03 01:58PM SNS1 CC (Saba Saba)
Opened 10/21/03 02:35PM
owf4_po.OWFN_DO Delivered 10/21/03 01:58PM NBL CC (Ngoc Le) exeloncorp.com Transferred 10/21/03 01:58PM david.helker (David Helker) pareez.golub (Pareez Golub) nrc.gov owf2_po.OWFN_DO Delivered 10/21/03 01:58PM JLK CC (John Knox)
Opened 10/21/03 01:59PM nrc.gov owf4_po.OWFN_DO Delivered 10/21/03 01:58PM MXM4 CC (Matthew McConnell)
Opened 10/21/03 02:01PM Post Office Delivered Route owf2_po.OWFN_DO 10/21/03 01:58PM owf4_po.OWFN_DO 10/21/03 01:58PM exeloncorp.com owf2_po.OWFN_DO 10/21/03 01:58PM nrc.gov owf4_po.OWFN_DO 10/21/03 01:58PM nrc.gov Files Size Date & Time MESSAGE 2444 10/21/03 01:58PM Options Auto Delete:
No Expiration Date:
None Notify Recipients:
Yes Priority:
Standard Reply Requested:
No Return Notification:
None Concealed
Subject:
No Security:
Standard To Be Delivered:
Immediate Status Tracking:
Delivered & Opened