Diesel Fuel Oil, Lube Oil, and Starting Air 3.8.3 3.8 ELECTRICAL POWER SYSTEMS 3.8.3 Diesel Fuel Oil, Lube Oil, and Starting Air LCO 3.8.3 APPLICABILITY:
ACTIONS The stored diesel fuel oil, lube oil, and starting air subsystem shall be within limits for each required diesel generator (DG).
When associated DG is required to be OPERABLE.
NOTE Separate Condition entry is allowed for each DG.
COMPLET-ON CONDITION REQUIRED ACTION COMPLETION A. One or more DGs with fuel A.1 Restore fuel oil level to 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> level < 80,400 gal and within limits.
> 69,300 gal in storage tank.
B. One or more DGs with B.1 Restore lube oil 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> lube oil inventory < 750 gal inventory to within limits.
and > 686 gal.
C. One or more DGs with C.A Restore fuel oil total 7 days stored fuel oil total particulates within limit.
particulates not within limit.
D. One or more DGs with new D. I Restore stored fuel oil 30 days fuel oil properties not properties to within limits.
within limits.
(continued)
I CALLAWAY PLANT 3.8-19 Amendment No. 156