September 4, 2003 Mr. John L. Skolds, President and Chief Nuclear Officer Exelon Nuclear Exelon Generation Company, LLC 4300 Winfield Road Warrenville, IL 60555

SUBJECT:

CLINTON POWER STATION ANNOUNCEMENT OF BASELINE INSPECTION/REQUEST FOR INFORMATION

Dear Mr. Skolds:

On October 20, 2003, the NRC will begin the required biennial safety system design and performance capability inspection (SSDI) at your Clinton Power Station. This inspection will be performed in accordance with NRC baseline inspection procedure 71111.21. The systems selected for detailed review during the SSDI baseline inspection are the Shutdown Service Water and the 4 kV electrical systems.

Experience has shown that these baseline design inspections are extremely resource intensive for both the NRC inspectors and the utility staff. In order to minimize the impact that the inspection has on the plant and to ensure a productive inspection for both parties, we have enclosed requests for the documents needed to effectively plan and implement this inspection.

The documents requested for the SSDI inspection have been divided into two groups. The first group is primarily comprised of lists of information necessary to ensure that the inspection team can be adequately prepared for the inspection prior to arrival at the plant. This information should be available in the Regional Office no later than October 9, 2003. The inspection team will begin to review this information during the week of October 14, 2003, and will request specific items from the supplied lists which should be available for review when the team arrives onsite. The second group of documents requested are those items which the team would need during the on-site inspection.

In accordance with 10 CFR 2.790 of the NRCs "Rules of Practice," a copy of this letter and its enclosure will be available electronically for public inspection in the NRC Public Document Room or from the Publicly Available Records (PARS) component of NRCs document system (ADAMS). ADAMS is accessible from the NRC Web site at http://www.nrc.gov/reading-rm/adams.html (the Public Electronic Reading Room).

J. Skolds The lead inspector for this inspection is Hershell A. (Al) Walker. If there are questions about the material requested, or the inspection, please call Mr. Walker at (630) 829-9728.

Sincerely,

/RA/

Julio F. Lara, Chief Electrical Engineering Branch Division of Reactor Safety Docket No. 50-461 License No. NPF-62

Enclosure:

Initial Document Request cc w/encl:

Site Vice President - Clinton Power Station Clinton Power Station Plant Manager Regulatory Assurance Manager - Clinton Chief Operating Officer Senior Vice President - Nuclear Services Vice President - Operations Support Vice President - Licensing and Regulatory Affairs Manager Licensing - Clinton and LaSalle Senior Counsel, Nuclear, Mid-West Regional Operating Group Document Control Desk - Licensing

J. Skolds The lead inspector for this inspection is Hershell A. (Al) Walker. If there are questions about the material requested, or the inspection, please call Mr. Walker at (630) 829-9728.

Sincerely,

/RA/

Julio F. Lara, Chief Electrical Engineering Branch Division of Reactor Safety Docket No. 50-461 License No. NPF-62

Enclosure:

Initial Document Request cc w/encl:

Site Vice President - Clinton Power Station Clinton Power Station Plant Manager Regulatory Assurance Manager - Clinton Chief Operating Officer Senior Vice President - Nuclear Services Vice President - Operations Support Vice President - Licensing and Regulatory Affairs Manager Licensing - Clinton and LaSalle Senior Counsel, Nuclear, Mid-West Regional Operating Group Document Control Desk - Licensing ADAMS Distribution:

AJM DFT JBH1 RidsNrrDipmIipb GEG HBC PLL C. Ariano (hard copy)

DRPIII DRSIII PLB1 JRK1 DOCUMENT NAME: C:\\ORPCheckout\\FileNET\\ML032471673.wpd To receive a copy of this document, indicate in the box: "C" = Copy without attachment/enclosure "E" = Copy with attachment/enclosure "N" = No copy OFFICE RIII E RIII N RIII RIII NAME HWalker:tr JLara DATE 09/04/03 09/04/03 OFFICIAL RECORD COPY

INITIAL DOCUMENT REQUEST Enclosure 1

SAFETY SYSTEM DESIGN AND PERFORMANCE CAPABILITY INSPECTION (SSDI)

DOCUMENT REQUEST I.

Information Requested for In-Office Preparation Week The following information is requested by October 9, 2003, or sooner, to facilitate the selection of specific items that will be reviewed during the onsite inspection week. The team will select specific items from the information requested below and the lead inspector will identify the selected documents to your staff by the close of business October 15, 2003. We request that the specific items selected from the lists be available and ready for review on the first day of inspection, October 20, 2003. If you have questions regarding this information, please call the team leader as soon as possible. Information may be sent by hard copy or electronically (if desired) to haw@nrc.gov).

(1)

Current plant management and engineering organizational charts.

(2)

Name and phone numbers of technical contacts and a regulatory contact.

(3)

Listing and identification of system designators and other acronyms used at the plant.

The following requested items apply only to the selected systems, which have been identified as the Shutdown Service Water and the 4 kV electrical systems:

(1)

Identification of the design and system engineers for the selected systems.

(2)

One copy of the system(s) description, design basis document(s), related training manual(s) and system health report(s).

(2)

One copy of the normal and abnormal operating procedures.

(3)

Three half-size (18" x 24") copies of the piping and instrument drawings (P&IDs).

(4)

Two half-size (18" x 24") copies of the electrical schematics, single-line and key diagrams.

(7)

List of system calculations and calculation revisions. Specifically identify (by number) the latest calculation(s) that address each of the following areas. If a calculation cannot be identified for a particular area, please provide an explanation of why a calculation is not necessary.

Breaker and fuse coordination calculations; Diesel loading calculations; Instrument uncertainty calculations; Room temperature environmental qualification calculations for major equipment; Relay setting calculations;

INITIAL DOCUMENT REQUEST Enclosure 2

Setpoint calculations for all technical specification or emergency operation procedure equipment; Time delay calculations (for any component incorporating time delay features);

Undervoltage and degraded voltage calculations; Voltage drop calculations for all major electrical components (motors, MOVs);

Check valve leakage criteria calculations; Design basis (flow rates, levels, pressures, temperatures) confirmation calculations (including NSSS calculations);

Heat exchanger calculations; NPSH and total dynamic head calculations; Operability determination support calculations; Pressure transient/ water hammer evaluations; Pump minimum recirculation flow calculations; Relief valve sizing calculations; Tank over-pressurization calculations; and Tank sizing calculations.

(8)

List of major modifications or set-point changes made to the selected system(s) since pre-operational testing. Major changes are those that significantly affected the way the system operated, for example, replacement of major components, modification to electrical control logic, etc. Please include the number and title, the modification purpose (description), the date, the status (whether the calculation is active, canceled, superceded or under revision), the 10 CFR 50.59 evaluation or screening and a technical contact. Spell out abbreviations, or acronyms and give word titles for any numbers. Note if any of the modifications required prior NRC approval.

(9)

List of existing temporary modifications, if any.

(10)

List of the selected system(s) electrical equipment/components that have been removed from the licensees EQ Program, if any.

(11)

List of condition reports (corrective action documents) that are in one of the following categories. For each condition report, besides the number and title, clearly designate the status (open/closed), the importance ranking, the date initiated, the date closed (if applicable), the status of corrective actions, and a technical contact. (Note: it is not necessary to provide a separate list for each category)

Any condition report initiated more than two years prior to the inspection that is still open; Any condition report (open or closed) initiated in the last two years that required an apparent or root cause analysis (i.e., Category 1 or 2 condition reports);

INITIAL DOCUMENT REQUEST Enclosure 3

Any condition report (open or closed) initiated in the last two years that required an operability determination (include determination); and Any condition report (open or closed) initiated in the last two years that related to problems with the quality of engineering (not system specific).

(12)

The corrective maintenance history of major components for the last two years.

(13)

List of operability evaluations as far back as retrievable. Include both those currently relied upon and those that were previously relied upon for operability.

(14)

List of Engineering Related Operator Workarounds.

II.

Information Requested to be Available on First Day of Inspection (October 20, 2003)

The following information be available to the team when the team arrives onsite. Some documents, such as the Updated Final Safety Analysis Report (UFSAR) or the Technical Specification (TS), do not need to be solely available to the team (i.e., they can be located in a reference library or adjacent area) as long as the team has ready access to them. However, they should be located prior to the inspection team arriving on site so if the team requests the documents they will be readily available.

(1)

Copies of the calculations indicated by subject area in item I.(7), excluding data files. Please review the calculations and also provide copies of referenced material (such as drawings, engineering requests, vendor letters.)

(2)

Copies of all MAJOR design changes, modifications and set-point changes as indicated in item I.(8). For each modification, as a minimum provide the purpose, the 10 CFR 50.59 evaluation or screening, and the completed post-modification test.

(3)

Copies of any open temporary modifications.

(4)

Copies of all condition reports (corrective action documents) indicated in item I.(11), including any associated root/apparent cause analyses and operability determinations.

(5)

An Index of the surveillances for ALL Technical Specification equipment completed during the last two years.

(6)

List of all maintenance, surveillance, and annunciator response procedures related to the systems. Include name as well as number. For the surveillance procedures, provide a cross-reference which shows how each technical specification requirement is being met.

(7)

One copy of each major equipment drawing (valves, pumps, tanks, strainers),

including pump head curves (1/2 size, 18" x 24").

INITIAL DOCUMENT REQUEST Enclosure 4

(8)

Copies of isometric drawings for major flow paths (1/2 size).

(9)

Copies of elementary diagrams (1/2 size).

(10)

Index of wiring diagrams (1/2 size).

(11)

Copies of loop drawings (1/2 size).

(12)

Copies of P&IDs referred to on the system P&ID (1/2 size).

(13)

Copies of instrumentation and control logic drawings (1/2 size).

(14)

Maintenance history of major components for the last two years.

(15)

A copy of any self-assessments and associated corrective action documents generated in preparation for the inspection.

(16)

One copy of the current plant organization charts.

(17)

Reference materials (make available if needed):

Equipment qualification binders; General set of plant drawings; IPE/PRA report; Pre-operational tests, including documents showing resolution of deficiencies; Procurement documents for major components in each system (verify retrievable);

Relevant operating experience information (such as vendor letters or utility experience);

Standards used in system design (such as IEEE, ASME, TEMA);

System procedures; Technical Specifications; Technical Data Book; Updated Final Safety Analysis Report; and Vendor manuals.

(18)

Copies of selected operability evaluations and plans for restoring operability, if applicable. Include contact person for each item. The team will select specific documents to review approximately one week prior to the inspection.

(19)

Copies of selected work-around evaluations and plans for resolution. Include contact person for each item. The team will select specific documents to review approximately one week prior to the inspection.

INITIAL DOCUMENT REQUEST Enclosure 5

III.

Information Requested to be provided throughout the inspection (1)

Copies of any corrective action documents generated as a result of the teams questions or queries during this inspection.

(2)

Copies of the list of questions submitted by the team members and the status/resolution of the information requested (provide daily during the inspection to each team member).

NOTE: If you have questions regarding the requested information please contact Al Walker at NRC Region III, (630) 829-9728.