MONTICELLO NUCLEAR GENERATING PLANT ODCM-08.01 TITLE: REPORTING REQUIREMENTS Revision 1*
Page 1 of 7 OFFSITE DOSE CALCULATION MANUAL -TABLE OF CONTENTS SECTION PAGE 1.0 RECORD OF REVISION .......................-..................... 2 2.0 REPORTING REQUIREMENTS .. 3 2.1 Radioactive Effluent Release Report. 3 2.2 Radiological Environmental Operating Report. 4 2.3 Annual Summary of Meteorological Data. 6 2.4 Record Retention. 7 Prepared By:
Reviewed By:__ _ _ _ _ _ _ _ _
OC Final Review Meeting: L Date:
Approved By Plant Manager: Date:
- This is a major rewrite, therefor,no sidelines are required.
3087 (DOCUMENT CHANGE, HOLD, AND COMMENT FORM) incorporatedF\ > a 3:5 o Resp Supv: CHEM lAssoc Ref: CHEM-I I )ISR: N IFreq: vrsi ARMS: ODCM-08.01 Doc Type: .7030 Admin Initials: -Date I/pir
- 1 MONTICELLO NUCLEAR GENERATING PLANT I ODCM-08.01 TITLE: REPORTING REQUIREMENTS Revision 1*
Page 2 of 7 1.0 RECORD OF REVISION Revision No. Date Reason for Revision 2 October - 2000 Moved previous ODCM-08.01 contents to ODCM-APP-B, Rev 0. Changed this section name to "REPORTING REQUIREMENTS" and incorporated applicable sections of T.S. sections 6.6.A, 6.6.B, 6.7.A.4, 6.7.A.5, and 6.7.C into this document.
I/plr
MONTICELLO NUCLEAR GENERATING PLANT ODCM-08.01 TITLE: I REPORTING REQUIREMENTS Revision 1*
Page 3 of 7 2.0 REPORTING REQUIREMENTS 2.1 Radioactive Effluent Release Report In accordance with T.S. 6.7.A.4 the Radioactive Effluent Release Report covering the operation of the unit SHALL be submitted in accordance with 10CFR 50.G36A.
2.1.1 The Radioactive Effluent Release Report covering the operation of the unit during the previous calendar year SHALL be submitted prior to May 15 o each calendar year.
2.1.2 The Radioactive Effluent Release Report SHALL include a summary of the quantities of radioactive liquid and gaseous effluents and solid waste released as outlined in Appendix B of Regulatory Guide 1.21, Revision 1, June, 1974, with the data summarized on a quarterly basis.
In the event that some results are not available for inclusion with the report, the report SHALL be submitted noting and explaining the reasons for the missing results. The missing data SHALL be submitted as soon as possible in a supplementary report.
2.1.3 The Radioactive Effluent Release Report SHALL include an assessment of the radiation doses from radioactive effluents released from the unit during the previous calendar year. This report SHALL also include an assessment of the radiation doses from radioactive liquid and gaseous effluents to the individuals due to their activities inside the site boundary (ODCM-02.01 Figure 1 and ODCM-03.01 Figure 1) during the report period. All assumptions used in making these assessments (i.e., specific activity, exposure time and location)
SHALL be included in the reports. The assessment of radiation doses SHALL be performed in accordance with the ODCM or standard NRC computer codes.
2.1.4 The Radioactive Effluent Release Report SHALL also include an assessment of radiation doses to the most likely exposed member of the public from reactor releases and other nearby uranium fuel cycle sources (including doses from primary effluent pathways and direct radiation) for the previous 12 consecutive months to show compliance with 40CFR1 90, Environmental Radiation Protection Standards for Nuclear Power Operation.
2.1.5 The Radioactive Effluent Release Report SHALL include the following information for solid waste shipped off-site during the report period.
A. Container volume B. Total curie quantity (specify whether determined by measurements or estimate),
C. Principal radionuclides (specify whether determined by measurement or estimate),
I/plr
MONTICELLO NUCLEAR GENERATING PLANT ODCM-08.01 TITLE: REPORTING REQUIREMENTS Revision 1*
Page 4 of 7 D. Type of waste (e.g., spent resin, compacted dry waste),
E. Type of container (e.g., LSA, Type A, Type B, Large Quantity),
and F. Solidification agent (e.g., cement, urea formaldehyde).
2.1.6 The Radioactive Effluent Release Report SHALL include unplanned releases from the site of radioactive materials in gaseous and liquid effluents on a quarterly basis.
2.1.7 The Radioactive Effluent Release Report SHALL include a description of changes to the PCP.
2.1.8 The Radioactive Effluent Release Report SHALL contain a report of when milk or leafy green vegetable samples specified in ODCM-07.01 Table 1 cannot be obtained from the designated sample locations, and identify the new locations added to and deleted from the monitoring program.
2.1.9 The Radioactive Effluent Release Report SHALL identify Land Use Census identified locations which yield a calculated dose or dose commitment (via the same exposure pathway) 20 percent greater than at a location from which samples are currently being obtained in accordance with ODCM-07.01 Control 2.1.1.
2.2 Radiological Environmental Operating Report In accordance with T.S.6.7.C.1, the Radiological Environmental Operating Report covering the operation of the off-site monitoring program SHALL be submitted and SHALL include:
2.2.1 The Annual Radiological Environmental Operating Report covering the operation of the site during the previous calendar year SHALL be submitted by May 15 of each year. The report SHALL include summaries, interpretations, and analyses of trends of the results of the Radiological Environmental Monitoring Program for the reporting period.
The material provided SHALL be consistent with the objectives outlined in the Offsite Dose Ociculation Manual (ODCM), and in 10CFR50, Appendix I, Sections IV.B.2, IV.B.3, and IV.C.
I/plr
MONTICELLO NUCLEAR GENERATING PLANT ODCM-08.01 TITLE: REPORTING REQUIREMENTS Revision 1*
Page 5 of 7 2.2.2 The Annual Radiological Environmental Operating Report SHALL include the results of analyses of all radiological environmental samples and of all environmental radiation measurements taken during the period pursuant to the locations specified in the table and figures in the ODCM, as well as summarized and tabulated results of these analyses and measurements in the format of the table in the Radiological Assessment Branch Technical Position, Revision 1, November 1979. In the event that some individual results are not available for inclusion with the report, the report SHALL be submitted noting and explaining the reasons for the missing results. The missing data SHALL be submitted in a supplementary report as soon as possible.
2.2.3 The report SHALL also include the results of the land use census required by ODCM-07.01 Control 2.2.1. If harmful effects or evidence of irreversible damage are detected by the monitoring, the report SHALL provide an analysis of the problem and a planned course of action to alleviate the problem.
2.2.4 -The Radiological Environmental Operating Report SHALL include the following: a summary description of the Radiological Environmental Monitoring Program; a map of sampling locations keyed to a table giving distances and directions from the reactor; and the results of licensee participation in the Interlaboratory Comparison Program, required by ODCM-07.01 Control 2.4.1.A.
2.2.5 The Radiological Environmental Operating Report SHALL include reasons for all deviations from the REMP sampling program as specified in ODCM-07.01 Table 1 and plans for the prevention of a recurrence, if applicable.
2.2.6 If the level of radioactivity in an environmental sampling medium at a specified location exceeds the reporting levels of ODCM-07.01 Table 2 for the sample type specified in ODCM-07.01 Table I and is NOT the result of plant effluents, the condition SHALL be reported in the Radiological Environmental Operating Report.
2.2.7 A summary of the Interlaboratory Comparison Program SHALL be included in the Radiological Environmental Operating Report. If the required Interlaboratory Comparison Program analyses are NOT performed, corrective action SHALL be reported in the Radiological Environmental Operating Report.
2.2.8 The Radiological Environmental Operating Report SHALL NOT include the complete analysis data tables. These tables contain the results of each sample analysis and SHALL be maintained by the licensee.
I/plr
MONTICELLO NUCLEAR GENERATING PLANT ODCM-08.01 TITLE: REPORTING REQUIREMENTS Revision 1*
Page 6 of 7 2.3 Annual Summary of Meteorological Data The annual summary of meteorological data SHALL be submitted for the previous calendar year in the form of joint frequency tables of wind speed, wind direction, and atmospheric stability at the request of the Nuclear Regulatory Commission.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-08.01 TITLE: REPORTING REQUIREMENTS Revision 1*
Page 7 of 7 2.4 Record Retention 2.4.1 In accordance with T.S.6.6.A, the following records SHALL be retained for a minimum of five years:
A. Periodic checks, inspections, tests and calibrations of components and systems as related to the specifications and treatment systems defined in the ODCM.
B. Records of wind speed and direction.
C. Records of reviews performed for changes made to the Offsite Dose Calculation Manual.
2.4.2 In accordance with T.S.6.6.B, the following records SHALL be retained for the life of the plant:
A. Liquid and gaseous radioactive releases to the environs.
B. Off-site environmental surveys C. Radioactive shipments I/plr
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 I Page 1 of 74 OFFSITE DOSE CALCULATION MANUAL - TABLE OF CONTENTS SECTION PAGE 1.0 RECORD OF REVISION ......................... . 2 2.0
SUMMARY
OF DISPERSION CALCULATION PROCEDURES ............. 3 2.1 References ...................................................... 4 Table 1 Monticello Release Conditions. 5 Table 2 Distances to Controlling Unrestricted Area Boundary Locations. 6 Table 3 Monticello Reactor Vent Dispersion Parameters for Long Term Mixed Mode Releases >500 Hrs /Yr or >150 Hrs / Qtr. 7 Table 4 Monticello Reactor Vent Dispersion Parameters for Long Term Mixed Mode Releases >500 Hrs/Yr or >150 Hrs/Qtr. 8 Table 5 Monticello Reactor Vent Dispersion Parameters for Long Term Mixed Mode Releases >500 Hrs/Yr or >150 Hrs/Qtr .16 Table 6 Monticello Offgas Stack Dispersion Parameters for Long Term Elevated Releases >500 Hrs/Yr or >150 Hrs/Qtr .24 Table 7 Monticello Offgas Stack Dispersion Parameters for Long Term Elevated Releases >500 Hrs/Yr or >150 Hrs/Qtr .25 Table 8 Monticello Offgas Stack Dispersion Parameters for Long Term Elevated Releases >500 Hrs/Yr or >150 Hrs/Qtr .33 Table 9 Monticello Offgas Stack Dispersion Parameters for Short Term Elevated Releases <500 Hrs/Yr or <150 Hrs/Qtr .41 Table 10 Monticello Offgas Stack Dispersion Parameters for Short Term Elevated Releases <500 Hrs/Yr or <150 Hrs/Qtr .42 Table 11 Monticello Offgas Stack Dispersion Parameters for Short Term Elevated Releases <500 HrsYr or <150 Hrs/Qtr .50 Table 12 Monticello Reactor Building Vent Dispersion Parameters for Short Term Elevated Releases <500 Hrs/Yr or <150 Hrs/Qtr .58 Table 13 Reactor Building Vent Dispersion Parameters for Short Term Elevated Releases <500 Hrs/Yr or <150 Hrs/Qtr .59 Table 14 Reactor Building Vent Dispersion Parameters for Short Term Elevated Releases <500 Hrs/Yr or <150 Hrs/Qtr .67 Prepared By:
Reviewed By: , -
OC Final Review Meetih: .fi Date:
Approved By Plant Manager: 5<4 l- .Date: S/,
3087 (DOCUMENT CHANGE, HOLD, AND COMMENT FORM) incorporated- AOl Resp Supv: CHEM lAssoc Ref: CHEM-I _ IIR: N Freq: r ARMS: ODCM-APP-A Doc Type: 7030 IAdminlnitials: v4 IDatee I/pir
I l
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: - APPENDIX A Revision 0 Page 2 of 74 1.0 RECORD OF REVISION Revision No. Date Reason for Revision 0 October - 2000 Moved previous ODCM-06.01 tables into this Appendix to make the ODCM easier to use.
/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 3 of 74 2.0
SUMMARY
OF DISPERSION CALCULATION PROCEDURES Updepleted, undecayed dispersion parameters were computed using the computer program XOQDOQ (Sagendorf and Goll, 1977). Specifically, sector average X/Q and D/Q values were obtained for a sector width of 22.5 degrees. Credit was taken for momentum plume rise and effective plume height was adjusted for local terrain height for elevated releases. Building wake corrections were used to adjust calculations for ground-level releases. Standard open terrain recirculation correction factors were also applied as available as default values in XOQDOQ.
Dispersion calculations were based on mixed mode releases for the reactor vent and on elevated releases for the offgas stack. A summary of release conditions used as input to XOQDOQ is presented in Table 1 and controlling site boundary distances are defined in Table 2. Computed X/Q and D/Q values for unrestricted area boundary locations (relative to release points) and for standard distances (to five miles from the source in 0.1 mile increments) are presented in Tables 3 through 11.
For certain meteorological and release conditions, the enveloping interpolation routines in XOQDOQ used to compute short-term X/Q and D/Q values do not provide reasonable results. Because of this, results were reviewed for consistency and where possible, the distributions of calculated X/Q values were enveloped and interpolated by had.
In some cases, use of the NRC methodology is implemented in XOQDOQ for estimating short term dispersion values results in values which are lower than the annual values. For these cases, the annual average X/Q and D/Q values are used to conservatively represent short-term values. X/Q and D/Q values for on-site EPA locations were adjusted (multiplied by a factor of 0.238) to account for limited daily exposure of workers in accordance with NUREG-0473( 2).
On-site meteorological data for the period September 1, 1976 through August 31,1978 (as presented in Appendix B) were used as input to XOQDOQ. Data were collected and AT stability classes were defined in conformance with NRC Regulatory Guide 1.23(3). Dispersion calculations for the reactor vent were based on AT42.7-lOm and 10 meter wind data oint data recovery of 94 percent). Dispersion calculations for the offgas stack were based on AT,oo-1om and 100 meter wind data aoint data recovery of 95 percent).
I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 4 of 74 .
2.1 References
- 1. Sagendorf, J. F. and Goll, J. T., XOQDOQ Program for the Evaluation of Routine Effluent Releases at Nuclear Power Stations. NUREG 0324, U.S.
Nuclear Regulatory Commission, September 1977.
- 2. NUREG-0473
- 3. USNRC Regulatory Guide 1.23 I/pir
- 11 MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 D--- - of 7A I .I u Ul I t Table 1 Monticello Release Conditions Reactor Vent Off-Gas Stack Release Type Mixed mode (Long and Elevated (Long and short-short-term) term)
Release point height, m 42 100 Adjacent building height, m 42 42 Relative location to adjacent struc- Adjacent to 400' SE of tures Turbine Building Reactor Building Exit velocity, m/Sec 6.1 19.0 Internal stack diameter, m 2.41 0.36 Building cross-sectional area*,-m2 1480 N/A Purge frequency**, times per year 6 6 Purge duration', hours/release 24 24
- Applied to ground level releases.
Applied to short-term calculations only.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT I
ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 6 of 74 mms Table 2 Distances to Controlling Unrestricted Area Boundary Locations Miles Column 1 - Column 2*
As measured from Reactor Vent As Measured from Offgas Stack Sector Distance Sector Distance N 0.51 N 0.59 NNE 0.58 N 0.63 NE 0.65 NNE 0.65 ENE 0.83 ENE 0.78 E 0.59 E 0.50 ESE 0.59 E 0.50 SE 0.61 SSE 0.51 SSE 0.43 S 0.36 S 0.34 SSW 0.31 -
SSW 0.32 SW 0.33 SW 0.32 SW 0.33 WSW 0.35 WSW 0.38 w 0.48 W 0.56 WNW 0.68 NW 0.78 NW 0.43 NW 0.53 NNW 0.53 NNW 0.61 Locations specified in Column 2 are the same.geographic points as specified in Column 1 although the reference points are different.
I/pir
I MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 7 of 74 Table 3 Monticello Reactor Vent Dispersion Parameters for Long Term Mixed Mode Releases
>500 Hrs/Yr or >150 Hrs/Qtr Site Boundary Sector* x/Q (sec/m 3 ) D/Q (m-2 )
N 2.09E-06 2.89E-08 NNE 1.29E-06 1.82E-08 NE 7.76E-07 9.42E-09 ENE 6.11 E-07 5.62E-09 E 1.38E-06 1.45E-08 ESE 2.42E-06 3.15E-08 SE 2.53E-06 3.30E-08 SSE 4.08E-06 5.95E-08 S 2.30E-06 3.08E-08 SSW 1.80E-06 2.13E-08 SW 1.96E-06 2.54E-08 WSW 1 54E-06 1.72E-08 W 1.1OE-06 1.23E-08 WNW 1.22E-06 1.1 9E-08 NW 2.11 E-06 2.61 E-08 NNW 1.87E-06 2.55E-08 Period of record: 9-1-76 to 8-31-78
- Measured relevant to the Reactor Vent.
I/plr
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 8 of 74 Table 4 Monticello Reactor Vent Dispersion Parameters for Long Term Mixed Mode Releases
>500 Hrs/Yr or >150 Hrs/Qtr For Standard Distances (As Measured from the Reactor Vent) (/Q), sec/m3 Miles Sector* 0.1 0.2 0.3 0.4 0.5 0.6 0.7 N 2.94E-05 8.91 E-06 4.59E-06 2.98E-06 2.17E-06 1.74E-06 1.46E-06 NNE 1.98E-05 6.24E-06 3.25E-06 2.11 E-06 1.55E-06 1.25E-06 1.06E-06 NE 1.22E-05 3.84E-06 2.02E-06 1.33E-06 9.98E-07 8.21 E-07 7.09E-07 ENE 1.25E-05 3.91 E-06 2.05E-06 1.35E-06 1.01 E-06 8.46E-07 7.44E-07 E 1.97E-05 6.02E-06 3.20E-06 2.16E-06 1.64E-06 1.36E-06 1.19E-06 ESE 3.48E-05 1.05E-05 5.71 E-06 3.89E-06 2.94E-06 2.40E-06 2.04E-06 SE 3.91E-05 1.17E-05 6.34E-06 4.28E-06 3.20E-06 2.57E-06 2.15E-06 SSE 4.15E-05 1.26E-05 6.78E-06 4.52E-06 3.35E-06 2.70E-06 2.28E-06 S 1.60E-05 4.95E-06 2.69E-06 1.82E-06 1.39E-06 1.16E-06 1.02E-06 SSW 1.14E-05 3.54E-06 1.97E-06 1.39E-06 1.11E-06 9.79E-07 8.94E-07 SW 1.28E-05 3.85E-06 2.15E-06 1.51E-06 1.21E-06 1.06E-06 9.58E-07 WSW 1.08E-05 3.29E-06 1.85E-06 1.32E-06 1.06E-06 9.52E-07 8.89E-07 W 1.21 E-05 3.73E-06 2.01 E-06 1.37E-06 1.07E-06 9.24E-07 8.42E-07 WNW 1.96E-05 6.01 E-06 3.24E-06 2.17E-06 1.64E-06 1.37E-06 1.19E-06 NW 2.15E-05 6.49E-06 3.45E-06 2.32E-06 1.76E-06 1.45E-06 1.25E-06 NNW 2.71 E-05 8.24E-06 4.24E-06 2.74E-06 2.OOE-06 1.61 E-06 1.36E-06 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Reactor Vent.
1/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 9of74 Table 4 Monticello Reactor Vent Dispersion Parameters for Long Term Mixed Mode Releases
>500 Hrs/Yr or >150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Reactor Vent) (/Q), sec/m3 Miles Sector* 0.8 0.9 1.0 1.1 1.2 1.3 1.4 N 1.21 E-06 9.77E-07 8.18E-07 7.OOE-07 6.1 OE-07 5.39E-07 4.82E-07 NNE 8.85E-07 7.19E-07 6.07E-07 5.24E-07 4.59E-07 4.08E-07 3.66E-07 NE 6.02E-07 4.94E-07 4.19E-07 3.61 E-07 3.16E-07 2.80E-07 2.50E-07 ENE 6.46E-07 5.41E-07 4.69E-07 4.13E-07 3.69E-07 3.32E-07 3.02E-07 E 1.02E-06 8.42E-07 7.16E-07 6.20E-07 5.45E-07 4.85E-07 4.35E-07 ESE 1.69E-06 1.35E-06 1.11 E-06 9.35E-07 7.99E-07 6.92E-07 6.06E-07 SE 1.76E-06 1.39E-06 1.13E-06 9.46E-07 8.03E-07 6.93E-07 6.04E-07 SSE 1.89E-06 1.51 E-06 1.25E-06 1.06E-06 9.14E-07 7.98E-07 7.06E-07 S 8.69E-07 7.17E-07 6.09E-07 5.27E-07 4.63E-07 4.12E-07 3.71 E-07 SSW 7.94E-07 6.74E-07 5.85E-07 5.14E-07 4.57E-07 4.1 OE-07 3.70E-07 SW 8.43E-07 7.09E-07 6.09E-07 5.31 E-07 4.68E-07 4.16E-07 3.73E-07
-WSW 8.07E-07 6.97E-07 6.12E-07 5.44E-07 4.87E-07 4.39E-07 3.99E-07 W 7.50E-07 6.40E-07 5.59E-07 4.95E-07 4.42E-07 3.99E-07 3.63E-07 WNW 1.02E-06 8.42E-07 7.17E-07 6.22E-07 5.47E-07 4.87E-07 4.38E07 NW 1.05E-06 8.55E-07 7.15E-07 6.1OE-07 5.29E-07 4.64E-07 4.11E-07 NNW 1.13E-06 9.14E-07 7.68E-07 6.60E-07 5.76E-07 5.1 OE-07 4.57E-07 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Reactor Vent.
I/pir
I MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page
- 10 of 74 5 Table 4 Monticello Reactor Vent Dispersion Parameters for Long Term Mixed Mode Releases
>500 Hrs/Yr or >150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Reactor Vent) (X/Q), sec/m3 Miles Sector* 1.5 1.6 1.7 1.8 1.9 2.0 2.1 N 4.35E-07 3.91 E-07 3.54E-07 3.23E-07 2.96E-07 2.72E-07 2.52E-07 NNE 3.32E-07 3.OOE-07 2.72E-07 2.49E-07 2.28E-07 2.11 E-07 1.95E-07 NE 2.25E-07 2.07E-07 1.92E-07 1.78E-07 1.67E-07 1.57E-07 1.48E-07 ENE 2.77E-07 2.56E-07 2.37E-07 2.21 E-07 2.07E-07 1.94E-07 1.83E-07 E 3.94E-07 3.57E-07 3.25E-07 2.97E-07 2.73E-07 2.53E-07 2.34E-07 ESE 5.36E-07 -4.78E-07 4.29E-07 3.88E-07 3.53E-07 3.23E-07 2.97E-07 SE 5.33E-07 4.80E-07 4.35E-07 3.97E-07 3.65E-07 3.37E-07 3.12E-07 SSE 6.31 E-07 5.63E-07 5.05E-07 4.57E-07 4.16E-07 3.80E-07 3.49E-07 S 3.36E-07 3.03E-07 2.74E-07 2.49E-07 2.28E-07 2.1 OE-07 1.94E-07 SSW 3.37E-07 3.20E-07 3.05E-07 2.92E-07 2.81 E-07 2.71 E-07 2.62E-07 SW 3.37E-07 3.17E-07 2.99E-07 2.83E-07 2.70E-07 2.58E-07 2.47E-07 WSW 3.64E-07 3.44E-07 3.26E-07 3.1 OE-07 2.95E-07 2.82E-07 2.71 E-07 W 3.32E-07 3.16E-07 3.01 E-07 2.89E-07 2.78E-07 2.69E-07 2.61 E-07 WNW 3.97E-07 3.74E-07 3.54E-07 3.37E-07 3.23E-07 3.12E-07 3.02E-07 NW 3.68E-07 3.33E-07 3.03E-07 2.78E-07 2.57E-07 2.38E-07 2.21 E-07 NNW 4.13E-07 3.73E-07 3.39E-07 3.1 OE-07 2.85E-07 2.63E-07 2.44E-07 Period of Record: 9-1 -76 to 8-31 -78
- Measured relevant to the Reactor Vent.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0
- Page 11 of 74 Table 4 Monticello Reactor Vent Dispersion Parameters for Long Term Mixed Mode Releases
>500 Hrs/Yr or >150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Reactor Vent) (X/Q), sec/m3 Miles Sector* 2.2 2.3 2.4 2.5 2.6 2.7 2.8 N 2.34E-07 2.18E-07 2.04E-07 1.92E-07 1.83E-07 1.75E-07 1.68E-07 NNE 1.82E-07 1.70E-07 1.59E-07 1.50E-07 1.41 E-07 1.33E-07 1.26E-07 NE 1.40E-07 1.32E-07 1.26E-07 1.20E-07 1.13E-07 1.07E-07 1.02E-07 ENE 1.73E-07 1.64E-07 .1.56E-07 1.49E-07 1.41 E-07 1.34E-07 1.27E-07 E 2.18E-07 2.04E-07 1.91 E-07 1.80E-07 1.69E-07 1.60E-07 1.51 E-07 ESE 2.74E-07 2.53E-07 2.36E-07 2.20E-07 2.05E-07 1.93E-07 1.81 E-07 SE 2.91 E-07 2.73E-07 2.56E-07 2.41 E-07 2.26E-07 2.12E-07 1.99E-07 SSE 2.22E-07 2.99E-07 2.78E-07 2.59E-07 2.43E-07 2.29E-07 2.15E-07 S 1.80E-07 1.68E-07 1.57E-07 1.47E-07 1.42E-07 1.37E-07 1.33E-07 SSW 2.55E-07 2.48E-07 2.41 E-07 2.35E-07 2.20E-07 2.06E-07 1.94E-07 SW 2.38E-07 2.30E-07 2.22E-07 2.15E-07 2.04E-07 1.93E-07 1.83E-07 WSW 2.60E-07 2.51 E-07 2.42E-07 2.34E-07 2.18E-07 2.04E-07 1.92E-07 W 2.54E-07 2.48E-07 2.42E-07 2.37E-07 2.25E-07 2.14E-07 2.04E-07 WNW 2.93E-07 2.85E-07 2.79E-07 2.73E-07 2.64E-07 2.55E-07 2.47E-07 NW 2.07E-07 1.94E-07 1.82E-07 1.72E-07 1.66E-07 1.60E-07 1.55E-07 NNW 2.28E-07 2.13E 2.OOE-07 1.88E-07 1.78E-07 1.68E-07 1.60E-07 Period of Record: 9-1-76 to 8-31 -78
- Measured relevant to the Reactor Vent.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A I TITLE: APPENDIX A Revision 0 I Page 12 of 74 I Table 4 Monticello Reactor Vent Dispersion Parameters for Long Term Mixed Mode Releases
>500 Hrs/Yr or >150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Reactor Vent) (W/Q), sec/m3 Miles Sector* 2.9 3.0 3.1 3.2 3.3 3.4 3.5 N 1.62E-07 1.56E-07 1.51 E-07 1.46E-07 1.41 E-07 1.37E-07 1.33E-07 NNE 1.20E-07 1.14E-07 1.09E-07 1.04E-07 9.91 E-08 9.49E-08 9.1 OE-08 NE 9.64E-08 9.16E-08 8.73E-08 8.33E-07 7.96E-08 7.62E-08 7.30E-08 ENE 1.21 E-07 1.16E-07 1.11E-07 1.06E-07 1.02E-07 9.75E-08 9.37E-08 E 1.44E-07 1.36E-07 1.30E-07 1.24E-07 1.18E-07 1.13E-07 1.09E-07 ESE 1.71 E-07 1.61 E-07 1.53E-07 1.45E-07 1.38E-07 1.31 E-07 1.25E-07 SE 1.88E-07 1.77E-07 1.68E-07 1.59E-07 1.51 E-07 1.44E-07 1.37E-07 SSE 2.04E-07 1.93E-07 1.83E-07 1.74E-07 1.66E-07 1.58E-07 1.51 E-07 S 1.29E-07 1.26E-07 1.22E-07 1.19E-07 1.17E-07 1.14E-07 1.12E-07 SSW 1.83E-07 1.73E-07 1.63E-07 1.55E-07 1.47E-07 1.40E-07 1.33E-07 SW 1.75E-07 1.67E-07 1.59E-07 1.52E-07 1.46E-07 1.40E-07 1.34E-07 WSW 1.80E-07 1.70E-07 1.60E-07 1.52E-07 1.44E-07 1.37E-07 1.30E-07 W 1.95E-07 1.87E-07 1.79E-07 1.72E-07 1.65E-07 1.59E-07 1.53E-07 WNW 2.40E-07 2.33E-07 2.26E-07 2.19E-07 2.13E-07 2.07E-07 2.01 E-07 NW 1.50E-07 1.46E-07 1.42E-07 1.39E-07 1.36E-07 1.33E-07 1.31 E-07 NNW 1.52E-07 1.45E-07 1.38E-07 1.32E-07 1.26E-07 1.21 E-07 1.17E-07 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Reactor Vent..
I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 13 of 74 Table 4 Monticello Reactor Vent Dispersion Parameters for Long Term Mixed Mode Releases
>500 Hrs/Yr or >150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Reactor Vent) (/Q), sec/m3 Miles Sector* 3.6 3.7 3.8 3.9 4.0 4.1 4.2 N 1.28E-07 1.23E-07 1.18E-07 1.14E-07 1.1OE-07 1.06E-07 1.02E-07 NNE 8.74E-08 8.40E-08 8.09E-08 7.80E-08 7.52E-08 7.26E-08 7.02E-08 NE 7.01 E-08 6.74E-08 6.48E-08 6.24E-08 6.02E-08 5.81 E-08 5.61 E-08 ENE 9.02E-08 8.69E-08 8.38E-08 8.1OE-08 7.82E-08 7.57E-08 7.33E-08 E 1.04E-07 1.OOE-07 9.62E-08 9.26E-08 8.92E-08 8.61 E-08 8.31 E-08 ESE 1.19E-07 1.14E-07 1.09E-07 1.05E-07 1.01E-07 9.66E-07 9.29E-08 SE 1.31 E-07 1.25E-07 1.20E-07 1.15E-07 1.1OE-07 1.06E-07 1.02E-07 SSE 1.45E-07 1.40E-07 1.36E-07 1.31 E-07 1.27E-07 1.23E-07 1.19E-07 S 1.08E-07 1.05E-07 1.02E-07 9.95E-08 9.69E-08 9.44E-08 9.20E-08 SSW 1.29E-07 1.25E-07 1.21E-07 1.17E-07 1.13E-07 1.1OE-07 1.07E-07 SW 1.31E-07 1.27E-07 1.24E-07 1.20E-07 1.17E-07 1.14E-07 1.11E-07 WSW 1.27E-07 1.23E-07 1.20E-07 1.17E-07 1.14E-07 1.11E-07 1.09E-07 W 1.46E-07 1.39E-07 1.33E-07 1.28E-07 1.22E-07 1.17E-07 1.13E-07 WNW 1.91 E-07 1.82E-07 1.74E-07 1.66E-07 1.59E-07 1.52E-07 1.46E-07 NW 1.26E-07 1.23E-07 1.19E-07 1.16E-07 1.13E-07 i.1 OE-07 1.07E-07 NNW 1.12E-07 1.08E-07 1.04E-07 1.01E-07 9.73E-08 9.41E-08 9.11E-08 Period of Record: 9-1 -76 to 8-31-78
- Measured relevant to the Reactor Vent.
I/pir.
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 II Page 14 of 74 Table 4 Monticello Reactor Vent Dispersion Parameters for Long Term Mixed Mode Releases
>500 Hrs/Yr or >150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Reactor Vent) (X/Q), sec/m3 Miles Sector* 4.3 4.4 4.5 4.6 4.7 4.8 4.9 N 9.86E-08 9.54E-08 9.23E-08 8.95E-08 8.68E-08 8.42E-08 8.18E-08 NNE 6.79E-08 6.57E-08' 6.37E-08 6.18E-08 6.00E-08 5.83E-08 5.66E-08 NE 5.43E-08 5.25E-08 5.09E-08 4.93E-08 4.78E-08 4.65E-08 4.51 E-08 ENE 7.1OE-08 6.89E-08 6.68E-08 6.49E-08 6.31E-08 6.14E-08 5.97E-08 E 8.09E-08 7.77E-08 7.53E-08 7.29E-08 7.07E-08 6.87E-08 6.67E-08 ESE 8.05E-08 8.63E-08 8.33E-08 8.04E-08 7.78E-08 7.52E-08 7.28E-08 SE 9.84E-08 9.48E-08 9.15E-08 8.84E-08 8.55E-08 8.27E-08 8.01 E-08 SSE 1.16E-07 1.13E-07 1.10E-07 1.06E-07 1.03E-07 9.92E-08 9.61E-08 S 8.98E-08 8.77E-08 8.57E-08 8.28E-08 8.OOE-08 7.74E-08 7.50E-08 SSW 1.04E-07 1.01 E-07 9.84E-08 9.49E-08 9.16E-08 8.85E-08 8.55E-08 SW 1.08E-07 1.05E-07 1.02E-07 9.82E-08 9.46E-08 9.12E-08 8.79E-08 WSW 1.06E-07 1.03E-07 1.01 E-07 9.72E-08 9.36E-08 9.03E-08 8.72E-08 W 1.08E-07 1.04E-07 1.OOE-07 9.69E-08 9.36E-08 9.04E-08 8.74E-08 WNW 1.40E-07 1.35E-07 1.30E-07 1.25E-07 1.20E-07 1.1 6E-07 1.12E-07 NW 1.04E-07 1.02E-07 9.92E-08 9.58E-08 9.26E-08 8.95E-08 8.67E-08 NNW 8.83E-08 8.57E-08 8.32E-08 8.07E-08 7.82E-08 7.60E-08 7.38E-08 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Reactor Vent.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 15 of 74
-~~~~~~- -- -
Table 4 Monticello Reactor Vent Dispersion Parameters for Long Term Mixed Mode Releases
>500 Hrs/Yr or >150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Reactor Vent) (XQ), sec/m 3 Miles Sector* 5.0 N 7.94E-08 NNE 5.51 E-08 NE 4.39E-08 ENE 5.82E-08 E 6.48E-08 ESE 7.06E-08 SE 7.76E-08 SSE 9.31 E-08 S 7.26E-08 SSW 8.28E-08 SW 8.49E-08 WSW 8.42E-08 W 8.46E-08 WNW 1.08E-07 NW 8.40E-08 NNW 7.18E-08 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Reactor Vent.
I/pir
I1 MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 16 of 74 Table 5 Monticello Reactor Vent Dispersion Parameters for Long Term Mixed Mode Releases
>500 Hrs/Yr or >150 Hrs/Qtr For Standard Distances (As Measured from the Reactor Vent) (D/Q), /m2 Miles Sector* 0.1 0.2 0.3 0.4 0.5 0.6 0.7 N 2.75E-07 1.1 OE-07 6.31 E-08 4.18E-08 3.01 E-08 2.28E-08 1.80E-08 NNE 1.89E-07 7.89E-08 4.70E-08 3.17E-08 2.30E-08 1.74E-08 1.37E-08 NE 1.11E-07 4.68E-08 2.81E-08 1.91E-08 1.39E-08 1.06E-08 8.41E-09 ENE 1.03E-07 4.32E-08 2.61 E-08 1.78E-08 1.31 E-08 1.OOE-08 7.94E-09 E 1.58E-07 6.46E-08 3.08E-08 2.56E-08 1.87E-08 1.42E-08 1.13E-08 ESE 3.79E-07 1.49E-07 8.53E-08 5.66E-08 4.09E-08 3.11 E-08 2.46E-08 SE 4.31 E-07 1.67E-07 9.41 E-08 6.19E-08 4.43E-08 3.36E-08 2.65E-08 SSE 4.49E-07 1.77E-07 1.01 E-07 6.65E-08 4.78E-08 3.62E-08 2.86E-08 S 1.47E-07 6.03E-08 3.58E-08 2.43E-08 1.79E-08 1.38E-08 1.1 0E-08 SSW 9.22E-08 3.85E-08 2.33E-08 1.62E-08 1.21 E-08 9.50E-09 7.72E-09 SW 1.21E-07 4.80E-08 2.79E-08 1.90E-08 1.41E-08 1.10E-08 8.89E-09 WSW 8.33E-08 3.44E-08 2.07E-08 1.44E-08 1.09E-08 8.57E-09 7.01 E-09 W 9.09E-08 3.80E-08 2.29E-08 1.58E-08 1.18E-08 9.18E-09 7.41 E-09 WNW 1.51 E-07 6.14E-08 3.65E-08 2.49E-08 1.83E-08 1.41 E-08 1.13E-08 NW 1.86E-07 7.43E-08 4.30E-08 2.89E-08 2.11 E-08 1.62E-08 1.29E-08 NNW 2.45E-07 9.85E-08 5.73E-08 3.82E-08 2.76E 2.1 OE-08 1.66E-08 Period of Record: 9-1 -76 to 8-31-78
- Measured relevant to the Reactor Vent.
I/pir
I1 MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 17 of 74 Table 5 Monticello Reactor Vent Dispersion Parameters for Long Term Mixed Mode Releases
>500 Hrs/Yr or >150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Reactor Vent) (D/Q), /m2 Miles Sector* 0.8 0.9 1.0 1.1 1.2 1.3 1.4 N 1.38E-08 1.02E-08 7.88E-09 6.23E-09 5.03E-09 4.14E-09 3.55E-09 NNE 1.05E-08 7.83E-09 6.02E-09 4.76E-09 3.85E-09 3.17E-09 2.72E-09 NE 6.48E-09 4.84E-09 3.74E-09 2.96E-09 2.40E-09 1.98E-09 1.66E-09 ENE 6.14E-09 4.60E-09 3.56E-09 2.83E-09 2.30E-09 1.90E-09 1.60E-09 E 8.71 E-09 6.51 E-09 5.04E-09 4.OOE-09 3.24E-09 2.68E-09 2.24E-09 ESE 1.89E-08 1.41 E-09 1.09E-08 8.64E-09 7.OOE-09 5.77E-09 4.83E-09 SE 2.03E-08 1.51E-08 1.17E-08 9.22E-09 7.45E-09 6.14E-09 5.13E-09 SSE 2.19E-08 1.63E-08 1.26E-08 9.93E-09 8.03E-09 6.61 E-09 5.75E-09 S 8.57E-09 6.44E-09 5.01 E-09 3.99E-09 3.46E-09 2.85E-09 2.38E-09 SSW -6.08E-09 4.63E-09 3.63E-09 2.92E-09 2.39E-09 2.09E-09 1.76E-09 SW 6.99E-09 5.31 E-09 4.16E-09 3.34E-09 2.73E-09 2.41 E-09 2.02E-09 WSW 5.56E-09 4.86E-09 3.36E-09 2.71 E-09 2.23E-09 1.86E-09 1.63E-09 W 5.81 E-09 4.41 E-09 3.45E-09 2.77E-09 2.27E-09 1.89E-09 1.65E-09 WNW 8.82E-09 7.50E-09 5.17E-09 4.13E-09 3.76E-09 2.79E-09 2.48E-09 NW 9.99E-09 7.50E-09 5.82E-09 4.63E-09 3.76E-09 3.11 E-09 2.61 E-09 NNW 1.27E-08 9.47E-09 7.30E-09 5.78E-09 4.67E-09 3.85E-09 3.32E-09 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Reactor Vent.
I/plr
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 18 of 74 Table 5 Monticello Reactor Vent Dispersion Parameters for Long Term Mixed Mode Releases
>500 Hrs/Yr or >150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Reactor Vent) (DIQ), /M 2 Miles Sector* 1.5 1.6 - 1.7 1.8 1.9 2.0 2.1 N 3.OOE-09 2.57E-09 2.22E-09 1.93E-09 1.70E-09 1.51 E-09 1.34E-09 NNE 2.30E-09 1.97E-09 1.71 E-09 1.49E-09 1.31 E-09 1.1 6E-09 1.04E-09 NE 1.41 E-09 1.21 E-09 1.05E-09 9.18E-10 8.12E-10 7.20E-10 6.44E-10 ENE 1.36E-09 1.17E-09 1.01 E-09 8.84E-10 7.81 E-10 6.94E-10 6.20E-10 E 1.91 E-09 1.64E-09 1.42E-09 1.24E-09 1.09E-09 9.71 E-1 0 8.67E-1 0 ESE 4.09E-09 3.51 E-09 3.04E-09 2.65E-09 2.34E-09 2.07E-09 1.85E-09 SE 4.34E-09 3.72E-09 3.22E-09 2.81 E-09 2.48E-09 2.19E-09 1.96E-09 SSE 4.86E-09 4.16E-09 3.59E-09 3.13E-09 2.75E-09 2.43E-09 2.17E-09 S 2.03E-09 1.74E-09 1.50E-09 1.31 E-09 1.16E-09 1.02E-09 9.13E-10 SSW 1.50E-09 1.33E-09 1.15E-09 1.01 E-09 9.52E-1 0 8.43E-1 0 7.52E-1 0 SW 1.72E-09 1.52E-09 1.32E-09 1.15E-09 1.08E-09 9.53E-10 8.49E-10 WSW 1.39E-09 1.25E-09 1.09E-09 9.54E-10 9.16E-10 8.11E-10 7.23E-10 W 1.40E-09 1.24E-09 1.08E-09 9.44E-1 0 8.93E-1 0 7.91 E-1 0 7.05E-1 0 WNW 2.1OE-09 1.84E-09 1.59E-09 1.39E-09 1.28E-09 1.13E-09 1.01E-09 NW 2.22E-09 1.91 E-09 1.65E-09 1.45E-09 1.28E-09 1.13E-09 1.01 E-09 NNW 2.81 E-09 2.40E-09 2.08E-09 1.81 E-09 1.59E-09 1.42E-09 1.27E-09 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Reactor Vent.
I/plr
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 I IPage19of Table 5 Monticello Reactor Vent Dispersion Parameters for Long Term Mixed Mode Releases
>500 Hrs/Yr or >150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Reactor Vent) (D/Q), /m2 Miles Sector* 2.2 2.3 2.4 2.5 2.6 2.7 2.8 N 1.21E-09 1.09E-09 9.85E-10 8.97E-10 8.29E-10 7.64E-10 7.05E-10 NNE 9.29E-1 0 8.38E-1 0 7.60E-1 0 6.92E-1 0 6.33E-1 0 5.81 E-1 0 5.35E-1 0 NE 5.78E-1 0 5.23E-1 0 4.83E-1 0 4.40E-1 0 4.03E-1 0 3.70E-1 0 3.41 E-1 0 ENE 5.70E-10 5.14E-10 4.67E-10 4.25E-10 3.89E-10 3.57E-10 3.29E-10 E 7.79E-10 7.03E-10 6.38E-10 5.82E-10 5.32E-10 4.89E-10 4.51 E-10 ESE 1.66E-09 1.50E-09 1.36E-09 1.24E-09 1.13E-09 1.04E-09 9.56E-10 SE 1.81 E-09 1.63E-09 1.47E-09 1.35E-09 1.23E-09 1.13E-09 1.04E-09 SSE 1.94E-09 1.75E-09 1.59E-09 1.44E-09 1.32E-09 1.21 E-09 1.11 E-09 S 8.91 E-10 7.38E-10 6.69E-10 6.09E-10 5.59E-10 5.16E-10 4.76E-10 SSW 6.74E-1 0 6.08E-1 0 5.51 E-1 0 5.02E-1 0 4.60E-1 0 4.22E-1 0 3.90E-1 0 SW 7.61 E-10 6.86E-10 6.22E-10 5.66E-10 5.18E-10 4.75E-10 4.38E-10 WSW 6.49E-10 5.85E-10 5.30E-10 4.83E-10 4.42E-10 4.07E-10 3.75E-10 W 6.33E-10 5.71 E-10 5.18E-10 4.72E-10 4.32E-10 3.98E-10 3.67E-10 WNW 9.02E-10 8.14E-10 7.38E-10 6.72E-10 6.15E-10 5.66E-10 5.22E-10 NW 9.09E-10 8.48E-10 7.69E-10 7.OOE-10 6.48E-10 5.95E-10 5.52E-10 NNW 1.14E-09 1.03E-09 9.29E-10 8.46E-10 7.77E-10 7.14E-10 6.59E-10 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Reactor Vent.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 20 of 74 Table 5 Monticello Reactor Vent Dispersion Parameters for Long Term Mixed Mode Releases
>500 Hrs/Yr or >150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Reactor Vent) (D/Q), /m2 Miles Sector* 2.9 3.0 3.1 3.2 3.3 3.4 3.5 N 6.52E-1 0 6.09E-1 0 5.67E-1 0 5.30E-1 0 5.OOE-1 0 4.71 E-1 0 4.46E-1 0 NNE 4.95E-1 0 4.59E-1 0 4.26E-1 0 3.97E-1 0 3.71 E-1 0 3.48E-1 0 3.27E-1 0 NE 3.15E-10 2.92E-10 2.72E-10 2.53E-10 2.37E-10 2.22E-10 2.08E-10 ENE 3.04E-10 2.82E-10 2.62E-10 2.44E-10 2.28E-10 2.14E-10 2.01 E-10 E 4.16E-10 3.86E-10 3.59E-10 3.34E-10 3.12E-10 2.93E-10 2.75E-10 ESE 8.83E-10 8.18E-10 7.60E-10 7.08E-10 6.61 E-10 6.19E-10 5.80E-10 SE 9.59E-1 0 8.88E-1 0 8.25E-1 0 7.68E-10 7.17E-1 0 6.71 E-1 0 6.30E-1 0 SSE 1.03E-09 9.56E-1 0 8.89E-1 0 8.28E-1 0 7.73E-1 0 7.24E-1 0 6.79E-1 0 S 4.42E-10 4.12E-10 3.93E-10 3.68E-10 3.44E-10 3.24E-10 3.05E-10 SSW 3.61 E-10 3.35E-10 3.13E-10 2.92E-10 2.74E-10 2.58E-10 2.43E-10 SW 4.05E-10 3.76E-10 3.50E-10 3.27E-10 3.06E-10 2.87E-10 2.71 E-10 WSW 3.47E-10 3.23E-10 3.01 E-10 2.81 E-10 2.64E-10 2.48E-10 2.34E-10 W 3.40E-10 3.16E-10 2.95E-10 2.76E-10 2.60E-10 2.44E-10 2.31 E-10 WNW 4.83E-10 4.49E-10 4.19E-10 3.91 E-10 3.68E-10 3.90E-10 3.98E-10 NW 5.13E-10 4.78E-10 4.54E-10 4.25E-10 3.99E-10 3.75E-10 3.53E-10 NNW 6.1 OE-1 0 5.66E-1 0 5.27E-1 0 4.92E-1 0 4.61 E-1 0 4.33E-1 0 4.08E-1 0 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Reactor Vent.
I/plr
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 1.
. Page 21 of 74 Table 5 Monticello Reactor Vent Dispersion Parameters for Long Term Mixed Mode Releases
>500 Hrs/Yr or >150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Reactor Vent) (D/Q), /m2 Miles Sector* 3.6 3.7 3.8 3.9 4.0 4.1 4.2 N 4.22E-10 4.OOE-10 3.80E-10 3.62E-10 3.45E-10 3.30E-10 3.16E-10 NNE 3.08E-10 2.90E-10 2.74E-10 2.59E-10 2.46E-10 2.34E-10 2.22E-10 NE 1.96E-1 0 1.87E-1 0 1.75E-1 0 1.65E-1 0 1.57E-1 0 1.49E-1 0 1.41 E-1 0 ENE 1.89E-10 1.78E-10 1.68E-10 1.59E-10 1.51 E-10 1.43E-10 1.36E-10 E 2.58E-10 2.43E-10 2.29E-10 2.17E-10 2.05E-10 1.95E-10 1.85E-10 ESE 5.45E-10 5.13E-10 4.84E-10 4.57E-10 4.33E-10 4.1 OE-10 3.89E-10 SE 5.93E-10 5.58E-10 5.27E-10 4.98E-10 4.72E-10 4.48E-10 4.26E-10 SSE 6.46E-10 6.09E-10 5.76E-10 5.55E-10 5.27E-10 5.02E-10 4.79E-10 S 2.88E-10 2.73E-10 2.59E-10 2.46E-10 2.35E-10 2.24E-10 2.14E-10 SSW 2.30E-10 2.18E-10 2.07E-10 1.97E-10 1.88E-10 1.80E-10 1.72E-10 SW 2.55E-10 2.42E-10 2.29E-10 2.18E-10 2.28E-10 2.33E-10 2.22E-10 WSW 2.21 E-10 2.1 OE-10 1.99E-10 1.90E-10 1.81 E-10 1.73E-10 1.66E-10 W 2.19E-10 2.08E-10 1.98E-10 1.88E-10 .1.80E-10 1.72E-10 1.65E-10 WNW- 3.75E-1 0 3.55E-1 0 3.36E-1 0 3.19E-10 3.04E-1 0 2.89E-1 0 2.76E-1 0 NW 3.34E-10 3.17E-10 3.01 E-10 2.86E-10 2.73E-10 2.61 E-10 2.50E-10 NNW 3.85E-10 3.64E-10 3.45E-10 3.28E-10 3.12E-10 3.04E-10 2.90E-10 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Reactor Vent.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT I ODCM-APP-A TITLE: APPENDIX A - Revision 0 Page 22 of 74 Table 5 Monticello Reactor Vent Dispersion Parameters for Long Term Mixed Mode Releases
>500 Hrs/Yr or >150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Reactor Vent) (D/Q), t/M2 Miles Sector* 4.3 4.4 4.5 4.6 4.7 4.8 4.9 N 3.03E-10 2.91 E-10 2.80E-10 2.70E-10 2.61 E-10 2.52E-10 2.44E-10 NNE 2.12E-10 2.02E-10 1.93E-10 1.84E-10 1.76E-10 1.69E-10 1.62E-10 NE 1.35E-10 1.28E-10 1.23E-10 1.17E-10 1.12E-10 1.07E-10 1.03E-10 ENE 1.29E-10 1.23E-10 1.18E-10 1.12E-10 1.08E-10 1.03E-10 9.88E-11 E 1.76E-10 1.67E-10 1.59E-10 1.52E-10 1.45E-10 1.39E-10 1.33E-10 ESE 3.70E-10 3.52E-10 3.35E-10 3.20E-10 3.05E-10 2.92E-10 2.79E-10 SE 4.05E-10 3.87E-10 3.69E-10 3.53E-10 3.38E-10 3.24E-10 3.11E-10 SSE 4.61 E-10 4.41 E-10 4.26E-10 4.09E-10 3.94E-10 3.80E-10 3.66E-10 S 2.05E-1 0 1.97E-1 0 1.90E-1 0 1.83E-1 0 1.76E-1 0 1.70E-1 0 1.65E-1 0 SSW 1.65E-1 0 1.59E-1 0 1.53E-1 0 1.48E-1 0 1.43E-1 0 1.38E-1 0 1.34E-1 0 SW 2.42E-10 2.42E-10 2.41 E-10 2.30E-10 2.20E-10 2.1 OE-10 2.01 E-10 WSW 1.59E-1 0 1.53E-10 1.58E-10 1.52E-1 0 1.47E-1 0 1.42E-1 0 1.37E-1 0 W 1.59E-1 0 1.53E-1 0 1.48E-1 0 1.43E-1 0 1.38E-1 0 1.34E-1 0 1.30E-1 0 WNW 2.64E-10 2.53E-10 2.42E-10 2.33E-10 2.24E-10 2.16E-10 2.08E-10 NW 2.39E-10 2.30E-10 2.22E-10 2.14E-10 2.07E-10 2.00E-10 1.93E-10 NNW 2.78E-10 2.67E-10 2.57E-10 2.47E-10 2.38E-10 2.30E-10 2.22E-10 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Reactor Vent.
I/plr
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 23 of 74 Table 5 Monticello Reactor Vent Dispersion Parameters for Long Term-Mixed Mode Releases
>500 Hrs/Yr or >150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Reactor Vent) (D/Q), /2 Miles Sector* 5.0 N 2.36E-10 NNE 1.56E-10 NE 9.90E-11 ENE 9.49E-11 E 1.27E-1 0 ESE 2.68E-10 SE 2.99E-10 SSE 3.54E-10 S 1.60E-1 0 SSW 1.30E-1 0 SW 1.93E-1 0 WSW 1.33E-1 0 W 1.27E-1 0 WNW 2.01 E-1 0 NW 1.87E-1 0 NNW 2.15E-10 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Reactor Vent.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 24 of 74 Table 6 Monticello Offgas Stack Dispersion Parameters for Long Term Elevated Releases
>500 Hrs/Yr or >150 Hrs/Qtr Site Boundary Sector* X/Q (Sec/M 3) D/Q (m-2)
N 7.04E-08 4.51 E-09 NNE 7.06E-08 4.30E-09 NE 1.OOE-07 6.18E-09 ENE 6.20E-08 2.34E-09 E 4.46E-08 2.77E-09 ESE 5.28E-08 3.93E-09 SE 5.50E-08 4.98E-09 SSE 3.99E-08 4.20E-09 S 1.83E-08. 2.63E-09 SSW 1.17E-08 1.46E-09 SW 1.17E-08 1.46E-09 WSW 1.34E-08 1.34E-09 W 3.42E-08 1.67E-09 WNW 7.22E-08 2.43E-09 NW 5.67E-08 2.82E-09 NNW 1.08E-07 5.80E-09 Period of record: 9-1-76 to 8-31 -78.
- Measured relevant to the Reactor Vent.
I/plr
- 1 MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 25 of 74 M"
Table 7 Monticello Offgas Stack Dispersion Parameters for Long Term Elevated Releases
>500 Hrs/Yr or >150 Hrs/Qtr For Standard Distances (As Measured from the Offgas Stack) (/Q), sec/m3 Miles Sector* 0.1 0.2 0.3 0.4 0.5 0.6 0.7 N 2.39E-11 4.33E-08 6.96E-08 7.18E-08 7.08E-08 7.05E-08 7.15E-08 NNE 3.93E-11 6.93E-08 1.04E-07 1.03E-07 1.02E-07 1.01 E-07 9.96E-08 NE 1.15E-11 2.27E-08 4.42E-08 5.50E-08 6.09E-08 6.34E-08 6.46E-08 ENE 1.OOE-11 1.96E-08 3.74E-08 4.75E-08 5.48E-08 5.94E-08 6.22E-08 E 3.09E-12 7.35E-09 2.33E-08 3.64E-08 4.44E-08 4.93E-08 5.30E-08 ESE 2.80E-12 7.63E-09 2.67E-08 4.30E-08 5.31 E-08 5.99E-08 6.61 E-08 SE 5.57E-1 2 1.31 E-08 3.90E-08 5.97E-08 7.41 E-08 8.66E-08 9.91 E-08.
SSE 6.56E-12 1.40E-08 3.27E-08 4.50E-08 5.37E-08 6.41 E-08 7.81 E-08 S 4.93E-12 1.23E-08 3.06E-08 4.42E-08 5.35E-08 6.15E-08 6.95E-08 SSW 1.62E-12 4.83E-09 1.73E-08 2.93E-08 3.77E-08 4.45E-08 5.11E-08 SW 5.96E-13 2.06E-09 9.62E-09 1.69E-08 2.21 E-08 2.73E-08 3.37E-08 WSW 3.07E-13 1.30E-09 7.80E-09 1.43E-08 1.87E-08 2.33E-08 2.94E-08 W 1.87E-12 6.43E-09 1.74E-08 2.59E-08 3.15E-08 3.63E-08 4.14E-08 WNW 1.56E-1 2 5.49E-09 2.06E-08 3.41 E-08 4.21 E-08 4.76E-08 5.27E-08 NW 5.29E-12 1.20E-08 3.15E-08 4.53E-08 5.46E-08 6.24E-08 6.92E-08 NNW 3.03E-11 5.55E-08 9.01E-08 9.73E-08 1.02E-07 1.07E-07 1.11E-07 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
I/plr
I MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 26 of 74 Table 7 Monticello Offgas Stack Dispersion Parameters for Long Term Elevated Releases
>500 Hrs/Yr or >150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (/Q), sec/m3 Miles Sector* 0.8 0.9 1.0 1.1 1.2 1.3 1.4 N 7.07E-08 6.72E-08 6.55E-08 6.42E-08 6.30E-08 -6.18E-08 6.05E-08 NNE 9.48E-08 8.63E-08 8.08E-08 7.65E-08 7.29E-08 7.29E-08
- X MONTICELLO NUCLEAR GENERATING PLANT TITLE: APPENDIX A ODCM-APP-A Revision 0 Page 27 of 74 zzz4 Table 7 Monticello Offgas Stack Dispersion Parameters for Long Term Elevated Releases
- >500 Hrs/Yr or >150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (X/Q), sec/m 3 Miles Sector* 1.5 1.6 1.7 1.8 1.9 2.0 2.1 N 5.91 E-08 5.66E-08 5.43E-08 5.20E-08 4.99E-08 4.78E-08 4.59E-08 NNE 6.40E-08 6.06E-08 5.74E-08 5.45E-08 5.17E-08 4.92E-08 4.69E-08 NE 4.33E-08 4.23E-08 4.14E-08 4.06E-08 3.96E-08 3.88E-08 3.79E-08 ENE 4.28E-08 4.1 OE-08 3.93E-08 3.77E-08 3.62E-08 3.47E-08 3.34E-08 E 4.12E-08 3.94E-08 3.76E-08 3.60E-08 3.44E-08 3.29E-08 3.15E-08 ESE 5.80E-08 5.59E-08 -5.39E-08 5.18E-08 4.98E-08 4.78E-08 4.60E-08 SE 8.97E-08 8.77E-08 8.55E-08 8.32E-08 8.07E-08 7.83E-08 7.59E-08 SSE 1.04E-08 9.98E-08 9.58E-08 9.19E-08 8.80E-08 8.42E-08 8.06E-08 S 6.85E-08 6.54E-08 6.23E-08 5.93E-08 5.65E-08 5.39E-08 5.14E-08 SSW 4.99E-08 5.03E-08 5.04E-08 5.04E-08 5.02E-08 4.99E-08 4.95E-08 SW 4.37E-08 4.46E 4.51 E-08 4.54E-08 4.55E-08 4.54E-08 4.52E-08 WSW 4.57E-08 4.71 E-08 4.81 E-08 4.88E-08 4.92E-08 4.94E-08 4.95E-08 W 4.71 E-08 4.79E-08 4.85E-08 4.89E-08 4.90E-08 4.90E-08 4.89E-08 WNW 5.05E-08 5.1OE-08 5.12E-08 5.13E-08 5.12E-08 5.11E-08 5.08E-08 NW 5.81 E-08 5.64E-08 5.47E-08 5.30E-08 5.13E-08 4.97E-08 4.82E-08 NNW 7.29E-08 6.89E-08 6.52E-08 6.18E-08 5.87E-08 5.58E-08 5.31 E-08 Period of Record: 9-1-76 to 8-31-7
- Measured relevant to the Offgas Stack.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 28 of 74 Table 7 Monticello Offgas Stack Dispersion Parameters for Long Term Elevated Releases
>500 Hrs/Yr or >150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (X/Q), sec/M 3 Miles Sector* 2.2 2.3 2.4 2.5 2.6 2.7 2.8 N 4.41 E-08 4.23E-08 4.07E-08 3.92E-08 3.82E-08 3.73E-08 3.64E-08 NNE 4.48E-08 4.28E-08 4.09E-08 3.92E-08 3.76E-08 3.61 E-08 3.47E-08 NE 3.71 E-08 3.63E-08 3.53E-08 3.47E-08 3.35E-08 3.24E-08 3.13E-08 ENE 3.21 E-08 3.09E-08 2.98E-08 -2.87E-08 2.76E-08 2.65E-08 2.55E-08 E 3.02E-08 2.90E-08 2.78E-08 2.67E-08 2.57E-08 2.47E-08 2.38E-08 ESE 4.42E-08 4.25E-08 4.09E-08 3.94E-08 3.79E-08 3.66E-08 3.53E-08 SE 7.35E-08 7.12E-08 6.89E-08 6.68E-08 6.38E-08 6.11 E-08 5.85E-08 SSE 7.72E-08 7.39E-08 7.08E-08 6.79E-08 6.53E-08 6.28E-08 6.05E-08 S 4.91 E-08 4.69E-08 4.48E-08 4.29E-08 4.20E-08 4.11 E-08 4.03E-08 SSW 4.90E-08 4.85E-08 4.79E-08 4.73E-08 4.51 E-08 4.30E-08 4.11 E-08 SW 4.49E-08 4.46E-08 4.42E-08 4.38E-08 4.23E-08 4.09E-08 3.96E-08 WSW 4.93E-08 4.91 E-08 4.88E-08 4.84E-08 4.63E-08 4.42E-08 4.24E-08 W 4.86E-08 4.83E-08 4.79E-08 4.75E-08 4.59E-08 4.44E-08 4.30E-08 WNW 5.05E-08 5.01 E-08 4.97E-08 4.93E-08 4.84E-08 4.75E-08 4.66E-08 NW 4.67E-08 4.52E-08 4.38E-08 4.25E-08 4.19E-08 4.14E-08 4.08E-08 NNW 5.06E-08 4.83E-08 4.62E-08 4.42E-08. 4.24E-08 4.07E-08 3.91 E-08 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
I/plr
MONTICELLO NUCLEAR GENERATING PLANT TITLE: APPENDIX A ODCM-APP-A Revision 0 Page 29 of 74
-I I Table 7 Monticello Offgas Stack Dispersion Parameters for Long Term Elevated Releases
>500 Hrs/Yr or >150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (X/Q), sec/m3 Miles Sector* 2.9 3.0 3.1 3.2 3.3 3.4 3.5 N 3.55E-08 3.47E-08 3.39E-08 3.31E-08 3.24E-08 3.17E-08 3.10E-08 NNE 3.34E-08 3.22E-08 3.11 E-08 3.OOE-08 2.90E-08 2.80E-08 2.71 E-08 NE 3.03E-08 2.93E-08 2.84E-08 2.76E-08 .2.67E-08 2.60E-08 2.52E-08 ENE 2.46E-08 2.37E-08 2.29E-08 2.21 E-08 2.14E-08 2.07E-08 2.OOE-08 E 2.30E-08 2.22E-08 2.14E-08 2.07E-08 2.OOE-08 1.94E-08 1.88E-08 ESE 3.41E-08 3.29E-08 3.18E-08 3.08E-08 2.98E-08 2.89E-08 2.80E-08 SE 5.62E-08 5.39E-08 5.18E-08 4.98E-08 4.80E-08 4.62E-08 4.46E-08 SSE 5.83E-08 5.62E-08 5.42E-08 5.23E-08 5.05E-08 4.89E-08 4.73E-08 S 3.94E-08 3.86E-08 3.78E-08 3.70E-08 3.63E-08 3.55E-08 3.49E-08 SSW 3.93E-08 3.77E-08 3.61 E-08 3.47E-08 3.34E-08 3.21 E-08 3.09E-08 SW 3.84E-08 3.72E-08 3.61 E-08 3.51 E-08 3.41 E-08 3.32E-08 3.23E-08 WSW 4.06E-08 3.90E-08 3.74E-08 3.60E-08 3.47E-08 3.34E-08 3.22E-08 W 4.17E-08 4.04E-08 3.93E-08 3.81 E-08 3.70E-08 3.60E-08 3.50E-08 WNW 4.58E-08 4.50E-08 4.42E-08 4.34E-08 4.27E-08 4.20E-08 4.14E-08 NW 4.02E-08 3.96E-08 3.90E-08 3.85E-08 3.79E-08 3.74E-08 3.68E-08 NNW 3.76E-08 3.62E-08 3.49E-08 3.36E-08 3.25E-08 3.14E-08 3.03E-08 Period of Record: 9-1-76 to 8-31 -78
- Measured relevant to the Offgas Stack.
I/pir e
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 30 of 74 Table 7 Monticello Offgas Stack Dispersion Parameters for Long Term Elevated Releases
>500 Hrs/Yr or >150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (X/Q), sec/m3 Miles Sector* 3.6 3.7 3.8 3.9 4.0 4.1 4.2 N 3.00E-08 2.91 E-08 2.82E-08 2.74E-08 2.66E-08 2.59E-08 2.51 E-08 NNE 2.63E-08 2.54E-08 2.47E-08 2.40E-08 2.33E-08 2.26E-08 2.20E-08 NE 2.45E-08 2.39E-08 2.32E-08 2.26E-08 2.20E-08 2.15E-08 2.09E-08 ENE 1.94E-08 1.88E-08 1.83E-08 1.77E-08 1.73E-08 1.68E-08 1.63E-08 E 1.82E-08 1.77E-08 1.71 E-08 1.66E-08 1.62E-08 1.57E-08 1.53E-08 ESE 2.72E-08 2.64E-08 2.56E-08 2.49E-08 2.42E-08 2.35E-08 2.29E-08 SE 4.30E-08 4.16E-08 4.02E-08 3.89E-08 3.77E-08 3.65E-08 3.54E-08 SSE 4.60E-08 4.49E-08 4.37E-08 4.27E-08 4.16E-08 4.06E-08 3.97E-08 S 3.39E-08 3.30E-08 3.22E-08 3.14E-08 3.06E-08 2.99E-08 2.92E-08 SSW 3.01 E-08 2.93E-08 2.86E-08 2.79E-08 2.72E-08 2.65E-08 2.59E-08 SW 3.17E-08 3.12E-08 3.07E-08 3.02E-08 2.98E-08 2.93E-08 2.89E-08 WSW 3.17E-08 3.12E-08 3.07E-08 3.03E-08 2.98E-08 2.94E-08 2.89E-08 W 3.38E-08 3.26E-08 3.15E-08 3.05E-08 2.95E-08 2.86E-08 2.7iE-08 WNW 3.99E-08 3.84E-08 3.71 E-08 3.58E-08 3.46E-08 3.35E-08 3.24E-08 NW 3.60E-08 3.51 E-08 3.43E-08 3.35E-08 3.28E-08 3.20E-08 3.13E-08 NNW 2.94E-08 2.84E-08 2.76E-08 2.67E-08 2.60E-08 2.52E-08 2.45E-08 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 lIPage 31 of 74 Table 7 Monticello Offgas Stack Dispersion Parameters for Long Term Elevated Releases
>500 Hrs/Yr or >150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (X/Q), sec/m 3 Miles Sector* 4.3 4.4 4.5 4.6 4.7 4.8 4.9 N 2.45E-08 2.38E-08 2.32E-08 2.26E-08 2.20E-08 2.15E-08 2.10E-08 NNE 2.14E-08 2.08E-08 2.03E-08 1.98E-08 1.93E-08 1.88E-08 1.84E-08 NE 2.04E-08 1.99E-08 1.95E-08 1.90E-08 1.86E-08 1.82E-08 1.78E-08 ENE 1.59E-08 1.55E-08 1.51 E-08 1.47E-08 1.44E-08 1.40E-08 1.37E-08 E 1.49E-08 1.45E-08 1.42E-08 1.38E-08 1.35E-08 1.31 E-08 1.28E-08 ESE 2.23E-08 2.18E-08 2.12E-08 2.07E-08 2.02E-08 1.97E-08 1.93E-08 SE 3.43E-08 3.33E-08 3.24E-08 3.15E-08 3.06E-08 2.98E-08 2.90E-08 SSE 3.88E-08 3.79E-08 3.71 E-08 3.60E-08 3.50E-08 3.41 E-08 3.32E-08 S 2.85E-08 2.79E-08 2.73E-08 2.65E-08 2.57E-08 2.50E-08 2.43E-08 SSW 2.53E-08 2.48E-08 2.42E-08 2.35E-08 2.28E-08 2.22E-08 2.16E-08 SW 2.85E-08 2.81 E-08 2.77E-08 2.69E-08 2.61 E-08 2.53E-08 2.46E-08 WSW 2.85E-08 2.81 E-08 2.77E-08 2.69E-08 2.61 E-08 2.53E-08 2.46E-08 W 2.68E-08 2.60E-08 2.53E-08 2.46E-08 2.39E-08 2.33E-08 2.26E-08 WNW 3.14E-08 3.05E-08 2.95E-08 2.87E-08 2.79E-08 2.71 E-08 2.64E-08 NW 3.07E-08 3.OOE-08 2.94E-08 2.86E-08 2.78E-08 2.70E-08 2.63E-08 NNW 2.38E-08 2.32E-08 2.26E-08 2.20E-08 2.14E-08 2.08E-08 2.03E-08 Period of Record: 9-1-76 to 8-31-78 Measured relevant to the Offgas Stack.
I/pir.
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0
'Page 32 of 74 l Table 7 Monticello Offgas Stack Dispersion Parameters for Long Term Elevated Releases
>500 Hrs/Yr or >150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (X/Q), sec/m3 Miles 5.0 Sector*
N 2.05E-08 NNE 1.79E-08 NE 1.74E-08 ENE 1.34E-08 E 1.25E-08 ESE 1.88E-08 SE 2.82E-08 SSE 3.23E-08 S 2.36E-08 SSW 2.1 OE-08 SW 2.39E-08 WSW 2.39E-08 w 2.21 E-08 WNW 2.57E-08 NW 2.57E-08 NNW 1.98E-08 Period of Record: 9-1 -76 to 8-31-78
- Measured relevant to the Offgas Stack.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 33 of 74 Table 8 Monticello Offgas Stack Dispersion Parameters for Long Term Elevated Releases
>500 Hrs/Yr or >150 Hrs/Qtr For Standard Distances (As Measured from the Offgas Stack) (D/Q), m-2 Miles Sector* 0.1 0.2 0.3 0.4 0.5 0.6 0.7 N 1.44E-09 4.89E-09 6.31 E-09 5.66E-09 5.00E-09 4.44E-09 4.00E-09 NNE 2.25E-09 7.63E-09 9.79E-09 8.72E-09 7.59E-09 6.61 E-09 5.82E-09 NE 1.06E-09 3.60E-09 4.65E-09 4.17E-09 3.68E-09 3.27E-09 2.94E-09 ENE 9.73E-10 3.30E-09 4.25E-09 3.81 E-09 3.34E-09 2.95E-09 2.64E-09 E 7.84E-10 2.67E-09 3.45E-09 3.11 E-09 2.77E-09 2.49E-09 2.27E-09 ESE 1.06E-09 3.61 E-09 4.70E-09 4.31 E-09 3.92E-09 3.63E-09 3.42E-09 SE 1.42E-09 4.87E-09 6.41 E-09 6.OOE-09 5.64E-09 5.40E-09 5.30E-09 SSE 1.19E-09 4.11 E-09 5.46E-09 5.20E-09 5.OOE-09 4.92E-09 4.96E-09 S 9.90E-1 0 3.38E-09 4.42E-09 4.08E-09 3.75E-09 3.50E-09 3.34E-09 SSW 5.92E-10 2.02E-09 2.65E-09 2.45E-09 2.25E-09 2.11E-09 2.03E-09 SW 3.23E-10 1.11E-09 1.48E-09 1.41E-09 1.35E-09 1.33E-09 1.34E-09 WSW 2.97E-1 0 1.03E-09 1.38E-09 1.33E-09 1.31 E-09 1.32E-09 1.36E-09 W 4.41 E-1 0 1.51 E-09 1.98E-09 1.85E-09 1.72E 1.64E-09 1.59E-09 WNW 6.23E-10 2.13E-09 1.78E-09 2.56E-09 2.35E-09 2.20E-09 2.1OE-09 NW 7.59E-10 2.59E-09 3.39E-09 3.13E-09 2.87E-09 2.69E-09 2.57E-09 NNW 1.94E-09 6.59E-09 8.48E-09 7.59E-09 6.66E-09 5.88E-09 5.25E-09 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
I/plr
. . ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ws I1 MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 34 of 74 Table 8 Monticello Offgas Stack. Dispersion Parameters for Long Term Elevated Releases
>500 Hrs/Yr or >150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (D/Q), m-2 Miles Sector* 0.8 0.9 1.0 1.1 1.2 1.3 1.4 N 3.47E-09 2.90E-09 2.39E-09 1.98E-09 1.67E-09 1.42E-09 1.23E-09 NNE 4.93E-09 4.OOE-09 3.24E-09 2.65E-09 2.20E-09 1.85E-09 1.58E-09 NE 2.56E-09 2.13E-09 1.76E-09 1.46E-09 1.23E-09 1.05E-09 9.02E-10 ENE 2.27E-09 1.88E-09 1.54E-09 1.27E-09 1.06E-09 9.03E-1 0 7.75E-1 0 E 2.01 E-09 1.70E-09 1.41 E-09 1.18E-09 1.OOE-09 8.59E-10 7.45E-10 ESE 3.12E-09 2.74E-09 2.32E-09 1.97E-09 1.69E-09 1.47E-09 1.29E-09 SE 5.02E-09 4.56E-09 3.94E-09 3.38E-09 2.94E-09 2.58E-09 2.29E-09 SSE 4.81 E-09 4.46E-09 3.89E-09 3.37E-09 2.95E-09 2.61 E-09 2.32E-09 S 3.09E-09 2.74E-09 2.34E-09 1.99E-09 1.72E-09 1.50E-09 1.32E-09 SSW 1.88E-09 1.67E-09 1.43E-09 1.22E-09 1.05E-09 9.18E-10 8.09E-10 SW 1.30E-09 1.21E-09 1.05E-09 9.14E-10 8.OOE-10 7.06E-10 6.29E-10 WSW 1.35E-09 1.27E-09 1.12E-09 9.76E-10 8.59E-10 7.62E-10 6.81 E-10 W 1.49E-09 1.35E-09 1.16E-09 9.93E-10 8.61 E-10 7.54E-10 6.66E-10 WNW 1.93E-09 1.71 E-09 1.46E-09 1.24E-09 1.07E-09 9.35E-1 0 8.22E-1 0 NW 2.37E-09 2.1 OE-09 1.80E-09 1.53E-09 1.32E-09 1.15E-09 1.01 E-09 NNW 4.52E-09 3.73E-09 3.06E-09 2.53E-09 2.12E-09 1.80E-09 1.54E-09 Period of Record: 9-1 -76 to 8-31-78
- Measured relevant to the Offgas Stack.
I/plr
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 35 of 74 Table 8 Monticello Offgas Stack Dispersion Parameters for Long Term Elevated Releases
>500 Hrs/Yr or >150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (D/Q), m-2 Miles Sector* 1.5 1.6 1.7 1.8 1.9 2.0 2.1 N 1.07E-09 9.36E-10 8.27E-10 7.36E-10 6.92E-1 0 6.30E-1 0 5.75E-10 NNE 1.36E-09 1.18E-09 1.03E-09 9.08E-1 0 8.58E-1 0 7.77E-1 0 7.07E-1 0 NE 7.84E-1 0 6.88E-1 0 6.08E-1 0 5.41 E-1 0 5.09E-1 0 4.63E-1 0 4.23E-1 0 ENE 6.72E-10 5.88E-10 5.18E-10 4.59E-10 4.32E-10 3.93E-10 3.58E-10 E 6.51 E-10 5.75E-10 5.1 OE-10 4.56E-10 4.28E-10 3.90E-10 3.57E-10 ESE 1.14E-09 1.01E-09 9.06E-10 8.16E-10 7.64E-10 6.99E-10 6.43E-10 SE 2.04E-09 1.83E-09 1.65E-09 1.50E-09 1.40E-09 1.28E-09 1.18E-09 SSE 2.08E-09 1.87E-09 1.70E-09 1.54E-09 1.44E-09 1.32E-09 1.22E-09 S 1.17E-09 1.04E-09 9.35E-1 0 8.44E-1 0 7.89E-1 0 7.23E-1 0 6.66E-1 0 SSW 7.1 7E-1 0 6.41 E-1 0 5.76E-1 0 5.20E-1 0 4.86E-1 0 4.46E-1 0 4.1 OE-1 0 SW 5.63E-10 5.08E-10 4.60E-10 4.18E-10 3.90E-10 3.59E-10 3.31 E-10 WSW 6.12E-10 5.53E-10 5.02E-10 4.58E-10 4.26E-10 3.93E-10 3.63E-1 0 W 5.93E-10 5.32E-10 4.79E-10 4.34E-10 4.05E-10 3.72E-10 3.42E-10 WNW 7.28E-10 6.50E-10 5.84E-10 5.27E-10 4.92E-10 4.51E-10 4.15E-10 NW 8.97E-10 8.01E-10 7.20E-10 6.50E-10 6.07E-10 5.57E-10 5.12E-10 NNW 1.34E-09 1.17E-09 1.03E-09 9.12E-10 8.59E-10 7.81E-10 7.12E-10 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 36 of 74 Table 8 Monticello Offgas Stack Dispersion Parameters for Long Term Elevated Releases
>500 Hrs/Yr or >150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (D/Q), m-2 Miles Sector* 2.2 2.3 2.4 2.5 2.6 2.7 2.8 N 5.28E-10 4.86E-10 4.49E-10 4.17E-10 3.87E-10 3.61 E-10 3.37E-10 NNE 6.46E-10 5.93E-10 5.46E-10 5.05E-10 4.68E-10 4.35E-10 4.06E-10 NE 3.88E-10 3.58E-10 3.30E-10 3.06E-10 2.85E-10 2.65E-10 2.48E-10 ENE 3.28E-10 3.02E-10 2.79E-10 2.58E-10 2.40E-10 2.24E-10 2.09E-10 E 3.28E-10 3.03E-10 2.80E-10 2.60E-10 2.42E-10 2.26E-10 2.11E-10 ESE 5.93E-10 5.48E-10 5.09E-10 4.73E-10 4.41 E-10 4.12E-1 0 3.86E-10 SE 1.09E-09 1.01 E-09 9.43E-10 8.78E-1 0 8.21 E-1 0 7.68E-1 0 7.20E-1 0 SSE 1.13E-09 1.05E-09 9.78E-10 9.12E-10 8.52E-10 7.98E-10 7.48E-10 S 6.14E-10 5.69E-10 5.28E-10 4.92E-10 4.59E-10 4.29E-10 4.02E-10 SSW 3.79E-10 3.76E-10 3.90E-10 3.92E-10 3.62E-10 3.34E-10 3.1 OE-10 SW 3.07E-10 2.98E-10 3.09E-10 3.18E-10 2.93E-10 2.71 E-10 2.51 E-10 WSW 3.36E-10 3.41 E-10 3.44E-10 3.58E-10 3.30E-10 3.05E-10 2.83E-10 W 3.17E-10 3.11 E-10 3.09E-10 3.19E-10 2.94E-10 2.72E-10 2.53E-10 WNW 3.83E-10 3.86E-10 3.86E-10 3.89E-10 3.59E-10 3.45E-10 3.20E-10 NW 4.73E-10 4.38E-10 4.07E-10 3.78E-10 3.53E-10 3.30E-10 3.09E-10 NNW 6.53E-10 6.01E-10 5.55E-10 5.14E-10 4.77E-10 4.44E-10 4.15E-10 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 37 of 74 Table 8 Monticello Offgas Stack Dispersion Parameters for Long Term Elevated Releases
>500 Hrs/Yr or >150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (D/Q), m-2 Miles Sector* 2.9 3.0 3.1 3.2 3.3 3.4 3.5 N 3.16E-10 2.96E-10 2.78E-10 2.62E-10 2.47E-10 2.33E-10 2.20E-10 NNE 3.79E-10 3.55E-10 3.33E-10 3.13E-10 2.95E-10 2.78E-10 2.63E-10 NE 2.32E-10 2.18E-10 2.04E-10 1.92E-10 1.81 E-10 1.71 E-10 1.62E-10 ENE 1.95E-10 1.83E-10 1.72E-10 1.62E-10 1.52E-10 1.44E-10 1.36E-10 E 1.98E-10 1.86E-10 1.75E-10 1.64E-10 1.55E 1.46E-10 1.39E-10 ESE 3.62E-10 3.40E-10 3.20E-10 3.02E-10 2.85E-10 2.69E-10 2.55E-10 SE 6.76E-10 6.35E-10 5.98E-10 5.64E-10 5.33E-10 5.04E-10 4.77E-10 SSE 7.03E-10 6.62E-10 6.23E-10 5.88E-10 5.56E-10 5.26E-10 4.98E-10 S 3.77E-10 3.54E-10 3.33E-10 3.14E-10 2.97E-10 2.81E-10 2.66E-10 SSW 2.88E-1 0 2.68E-1 0 2.50E-1 0 2.34E-1 0 2.20E-1 0 2.06E-1 0 1.94E-1 0 SW 2.44E-10 2.27E-10 2.12E-10 1.98E-10 1.86E-10 1.75E-10 1.64E-10 WSW 2.63E-10 2.45E-10 2.29E-10 2.14E-10 2.01 E-10 1.89E-10 1.78E-10 W 2.47E-10 2.30E-10 2.15E-10 2.01 E-10 1.88E-10 1.77E-10 1.66E-10 WNW 2.97E-10 2.76E-10 2.58E-10 2.41 E-10 2.26E-10 2.12E-10 2.0OE-10 NW 2.90E-10 2.73E-10 2.57E-10 2.42E-10 2.26E-10 2.16E-10 2.04E-10 NNW 3.88E-1 0 3.64E-1 0 3.41 E-1 0 3.21 E-1 0 3.03E-1 0 2.86E-1 0 2.70E-1 0 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 38 of 74 Table 8 Monticello Offgas Stack Dispersion Parameters for Long Term Elevated Releases
>500 Hrs/Yr or >150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (D/Q), m-2 Miles Sector* 3.6 3.7 3.8 3.9 4.0 4.1 4.2 N 2.09E-1 0 1.98E-1 0 1.88E-1 0 1.78E-1 0 1.70E-10 1.62E-10 1.54E-10 NNE 2.49E-10 2.36E-10 2.24E-10 2.13E-10 2.02E-10 1.93E-10 1.84E-10 NE 1.53E-10 1.45E-10 1.38E-10 1.31 E-10 1.25E-10 1.19E-10 1.13E-10 ENE 1.29E-10 1.22E-10 1.16E-10 1.1OE-10 1.05E-10 9.98E-11 9.51 E-11 E 1.31 E-10 1.24E-10 1.18E-10 1.12E-10 1.07E-10 1.02E-10 9.71 E-11 ESE 2.42E-1 0 2.29E-1 0 2.18E-1 0 2.07E-1 0 1.97E-1 0 1.88E-1 0 1.79E-1 0 SE 4.53E-10 4.30E-10 4.08E-10 3.88E-10 3.69E-10 3.52E-10 3.36E-10 SSE 4.72E-10 4.48E-10 4.26E-10 4.05E-10 3.85E-10 3.67E-10 3.50E-10 S 2.52E-10 2.46E-10 2.34E-10 2.32E-10 2.34E-10 2.23E-10 2.12E-10 SSW 1.83E-10 1.73E-10 1.64E-10 1.59E-10 1.51E-10 1.43E-10 1.36E-10 SW 1.55E-10 1.46E-10 1.38E-10 1.31 E-10 1.24E-10 1.18E-10 1.12E-10 WSW 1.68E-1 0 1.62E-1 0 1.54E-1 0 1.46E-1 0 1.38E-1 0 1.31 E-1 0 1.25E-1 0 W 1.57E-10 1.48E-10 1.40E-10 1.33E-10 1.26E-10 1.20E-10 1.14E-10 WNW 1.88E-1 0 1.78E-1 0 1.68E-1 0 1.59E-1 0 1.51 E-1 0 1.44E-1 0 1.37E-1 0 NW 1.94E-1 0 1.86E-1 0 1.77E-1 0 1.73E-1 0 1.76E-1 0 1.67E-1 0 1.59E-1 0 NNW 2.56E-10 2.43E-10 2.30E-10 2.19E-10 2.08E-10 1.98E-10 1.89E-10 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
I/plr
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 39 of 74 Table 8 Monticello Offgas Stack Dispersion Parameters for Long Term Elevated Releases
>500 Hrs/Yr or >150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (D/Q), m-2 Miles Sector* 4.3 4.4 4.5 4.6 4.7 4.8 4.9 N 1.47E-10 1.41 E-10 1.34E-10 1.29E-10 1.23E-10 1.18E-10 i.13E-10 NNE 1.75E-10 1.67E-10 1.60E-10 1.53E-10 1.47E-10 1.41 E-10 1.35E-10 NE 1.08E-10 1.03E-10 9.88E-11 9.45E-11 9.05E-11 8.68E-11 8.32E-11 ENE 9.08E-11 8.67E-11 8.29E-11 7.94E-11 7.60E-11 7.28E-11 6.99E-11 E 9.26E-11 8.85E-11 8.46E-11 8.1 OE-11 7.75E-11 7.43E-11 7.13E-11 ESE 1.71 E-10 1.63E-10 1.56E-10 1.49E-10 1.43E-10 1.37E-10 1.31 E-10 SE 3.20E-10 3.06E-10 2.92E-10 2.80E-10 2.68E-10 2.57E-10 2.46E-10 SSE 3.34E-10 3.19E-10 3.05E-10 2.92E-10 2.80E-10 2.68E-10 2.57E-10 S 2.08E-1 0 1.98E-1 0 1.89E-1 0 1.81 E-10 1.73E-10 1.66E-1 0 1.59E-1 0 SSW 1.30E-10 1.24E-10 1.18E-10 1.13E-10 1.08E-10 1.03E-10 9.90E-11 SW 1.08E-10 1.03E-10 9.82E-11 9.39E-11 8.98E-11 8.59E-11 8.24E-11 WSW 1.19E-10 1.13E-10 1.08E-10 1.03E-10 9.88E-11 9.46E-11 9.06E-11 W 1.08E-10 1.03E-10 9.87E-11 9.43E-11 9.02E-11 8.64E-11 8.28E-11 WNW 1.30E-10 1.24E-10 1.18E-10 1.13E-10 1.08E-10 1.04E-10 9.94E-11 NW 1.58E-10 1.51 E-10 1.44E-10 1.38E-10 1.32E-10 1.26E-10 1.21 E-10 NNW 1.80E-10 1.72E-10 1.65E-10 1.58E-10 1.51 E-10 1.45E-10 1.39E-10 Period of Record: 9-1 -76 to 8-31 -78
- Measured relevant to the Offgas Stack.
I/plr
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 40 of 74 Table 8 Monticello Offgas Stack Dispersion Parameters for Long Term Elevated Releases
>500 Hrs/Yr or >150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (D/Q), m-2 Miles Sector* 5.0 N 1.09E-10 NNE 1.30E-10 NE 7.99E11 ENE 6.71 E-11 E 6.84E-11 ESE 1.26E-1 0 SE 2.36E-1 0 SSE 2.46E-10 S 1.52E-1 0 SSW 9.49E-11 SW 7.90E-11 WSW 8.69E-11 W 7.94E-11 WNW 9.53E-11 NW 1.16E-10 NNW 1.33E-10 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 41 of 74 Table 9 Monticello Offgas Stack Dispersion Parameters for Short Term Elevated Releases
<500 Hrs/Yr or <150 Hrs/Qtr Site Boundary Sector* X/Q (sec/m 3 ) D/q (m-2)
N 1.55E-07 9.93E-09 NNE 1.41 E-07 8.59E-09 NE 1.88E-07 1.16E-08 ENE 1.60E-07 6.04E-09 E 1.47E-07 9.15E-09 ESE SE SSE S
SSW SW WSW W 5.95E-08 2.91 E-09 WNW 1.39E-07 4.68E-09 NW NNW 2.33E-07 1.25E-08 Period of record: 9-1 -76 to 8-31 -78
- Measured relevant to the Offgas Stack.
See appropriate offgas stack long term elevated release values.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 42 of 74 Table 10 Monticello Offgas Stack Dispersion Parameters for Short Term Elevated Releases
<500 Hrs/Yr or <150 Hrs/Qtr For Standard Distances (As Measured from the Offgas Stack) (/q), sec/m3 Miles Sector* 0.1 0.2 0.3 0.4 0.5 0.6 0.7 N 1.67E-07 1.85E-07 1.50E-07 1.18E-07 NNE 2.82E-07 2.50E-07 2.12E-07 1.69E-07 NE 7.93E-08 1.29E-07 1.21 E-07 1.08E-07 ENE ** 1.63E-07 1.87E-07 1.77E-07 1.46E-07 E 8.63E-08 1.47E-07 1.29E-07 1.07E-07 ESE ** 6.17E-08 1.02E-07 SE 1.17E-07 SSE 1.04E-07 S ** ** 7.75E-08 1.13E-07 SSW 7.15E-08 1.03E-07 SW 4.73E-08 8.22E-08 WSW 3.82E-08 6.85E-08 W 4.06E-08 7.49E-08 8.73E-08 WNW 4.56E-08 8.41 E-08 9.88E-08 NW 7.36E-08 1.08E-07 NNW 2.73E-07 2.57E-07 2.37E-07 1.94E-07 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
- Values less than the value for 0.4 miles.
See appropriate offgas stack long term elevated release values.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 43 of 74 Table 10 Monticello Offgas Stack Dispersion Parameters for Short Term Elevated Releases
<500 Hrs/Yr or <150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (/q), sec/m 3 Miles Sector* 0.8 0.9 1.0 1.1 1.2 1.3 1.4 N 1.52E-07 1.77E-07 1.94E-07 1.82E-07 1.96E-07 1.87E-07 2.07E-07 NNE 1.83E-07 2.05E-07 2.18E-07 2.30E-07 2.15E-07 1.99E-07 2.13E-07 NE 1.30E-07 1.60E-07 1.67E-07 1.75E-07 1.76E-07 1.61 E-07 1.55E-07 ENE 1.62E-07 1.80E-07 1.75E-07 1.84E-07 1.96E-07 1.94E-07 1.91 E-07 E 1.38E-07 1.62E-07 1.65E-07 1.75E-07 1.72E-07 1.59E-07 1.77E-07 ESE 1.36E-07 1.62E-07 1.71 E-07 1.57E-07 1.62E-07 1.64E-07. 1.70E-07 SE 1.56E-07 1.84E-07 1.98E-07 1.93E-07 2.02E-07 2.06E-07 2.46E-07 SSE 1.42E-07 1.78E-07 1.97E-07 2.50E-07 2.26E-07 2.35E-07 2.77E-07 S 1.55E-07 1.86E-07 2.07E-07 1.92E-07 2.08E-07 2.01 E-07 2.71 E-07 SSW 1.43E-07 1.64E-07 1.81 E-07 1.86E-07 1.83E-07 1.79E-07 2.01 E-07 SW 1.17E-07 1.45E-07 1.63E-07 1.77E-07 1.70E-07 1.74E-07 2.58E-07 WSW 9.91 E-07 1.25E-07 1.31 E-07 1.43E-07 1.62E-07 1.59E-07 2.45E-07 W 1.25E-07 1.56E-07 1.76E-07 1.86E-07 2.OOE-07 2.04E-07 2.77E-07 WNW 1.39E-07 1.71 E-07 1.89E-07 1.96E-07 2.04E-07 2.12E-07 2.79E-07 NNW 2.OOE-07 2.24E-07 2.43E-07 2.48E-07 2.36E-07 2.14E-07 3.06E-07 Period of Record: 9-1 -76 to 8-31-78
- Measured relevant to the Offgas Stack.
- Values less than the value for 0.4 miles.
- See appropriate offgas stack long term elevated release values.
I/plr
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 44 of 74 Table 10 Monticello Offgas Stack Dispersion Parameters for Short Term Elevated Releases
<500 Hrs/Yr or <150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (/q), sec/m 3 Miles Sector* 1.5 1.6 1.7 1.8 1.9 2.0 2.1 N 2.56E-07 1.89E-07 2.1 OE-07 2.05E-07 1.94E-07 1.88E-07 1.79E-07 NNE 2.59E-07 1.97E-07 2.23E-07 2.13E-07 1.97E-07 1.87E-07 1.77E-07 NE 1.71 E-07 1.63E-07 1.55E-07 1.86E-07 1.77E-07 1.74E-07 1.66E-07 ENE 1.82E-07 1.67E-07 2.13E-07 1.89E-07 1.74E-07 1.69E-07 1.64E-07 E 1.73E-07 1.61 E-07 1.51 E-07 1.88E-07 1.75E-07 1.66E-07 1.59E-07 ESE 1.84E-07 1.77E-07 1.70E-07 1.55E-07 1.52E-07 1.50E-07 SE 2.06E-07 2.05E-07 1.90E-07 2.OOE-07 2.01 E-07 1.89E-07 1.77E-07 SSE 2.25E-07 2.1 OE-07 2.01 E-07 2.21 E-07 1.77E-07 1.78E-07 1.78E-07 S 2.1 OE-07 2.38E-07 2.35E-07 2.18E-07 2.04E-07 2.97E-07 SSW 1.90E-07 1.84E-07 2.46E-07 2.34E-07 2.24E-07 2.20E-07 2.17E-07 SW 1.80E-07 1.74E-07 1.69E-07 1.87E-07 2.01 E-07 1.99E-07 1.91 E-07 WSW 1.78E-07 1.76E-07 1.72E-07 1.89E-07 2.OOE-07 1.99E-07 1.94E-07 W 2.14E-07 2.22E-07 2.50E-07 2.50E-07 2.32E-07 2.31 E-07 2.23E-07 WNW 1.96E-07 1.87E-07 1.81E-07 1.97E-07 2.11E-07 2.09E-07 2.01E-07 NW 2.OOE-07 1.90E-07 2.59E-07 2.40E-07 2.28E-07 2.1 OE-07 2.01 E-07 NNW 2.28E-07 2.01 E-07 1.96E-07 1.92E-07 1.87E-07 1.81 E-07 1.74E-07 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
- Values less than the value for 0.4 miles.
See appropriate offgas stack long term elevated release values.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 45 of 74 Table 10 Monticello Offgas Stack Dispersion Parameters for Short Term Elevated Releases
<500 Hrs/Yr or <150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (/q), sec/m3 Miles Sector* 2.2 2.3 2.4 2.5 2.6 2.7 2.8 N 1.70E-07 1.66E-07 1.58E-07 1.54E-07 1.51 E-07 1.47E-07 1.37E-07 NNE 1.70E-07 1.62E-07 1.57E-07 1.51 E-07 1.46E-07 1.44E-07 1.38E-07 NE 1.60E-07 1.53E-07 1.53E-07 1.47E-07 1.40E-07 1.36E-07 1.30E-07 ENE 1.57E-07 1.50E-07 1.47E-07 1.44E-07 1.36E-07 1.33E-07 1.28E-07 E 1.49E-07 1.44E-07 1.36E-07 1.33E-07 1.27E-07 1.23E-07 1.1 7E-07 ESE 1.48E-07 1.46E-07 1.43E-07 1.38E-07 1.33E-07 1.28E-07 1.23E-07 SE 1.95E-07 1.68E-07 1.64E-07 1.61 E-07 1.55E-07 1.66E-07 1.60E-07 SSE 1.69E-07 1.58E-07 1.58E-07 1.50E-07 1.42E-07 1.35E-07 1.60E-07 S 1.65E-07 1.58E-07 1.51 E-07 1.46E-07 1.41 E-07 1.40E-07 1.65E-07 SSW 2.1OE-07 2.11E-07 2.12E-07 1.89E-07 1.82E-07 1.76E-07 1.71E-07 SW 1.81E-07 1.90E-07 1.93E-07 1.93E-07 2.32E-07 2.23E-07 2.11E-07 WSW 1.82E-07 1.86E-07 1.79E-07 1.72E07 1.90E-07 1.84E-07 2.12E-07 W 2.15E-07 2.18E-07 2.20E-07 2.19E-07 2.1 OE-07 2.08E-07 2.05E-07 WNW 1.89E-07 1.89E-07 1.90E-07 1.93E-07 2.26E-07 2.18E-07 2.11E-07 NW 1.91 E-07 1.86E-07 1.80E-07 1.76E-07 1.72E-07 1.69E-07 1.64E-07 NNW 1.72E-07 1.68E-07 1.68E-07 1.59E-07 1.54E-07 1.45E-07 1.36E-07 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
- Values less than the value for 0.4 miles.
See appropriate offgas stack long term elevated release values.
I/pir
. MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 46 of 74 Table 10 Monticello Offgas Stack Dispersion Parameters for Short Term Elevated Releases
<500 Hrs/Yr or <150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (xlq), sec/M 3 Miles Sector* 2.9 3.0 3.1 3.2 3.3 3.4 3.5 N 1.35E-07 1.34E-07 1.32E-07 1.30E-07 1.28E-07 1.25E-07 1.23E-07 NNE 1.30E-07 1.26E-07 1.22E-07 1.19E-07 1.15E-07 1.12E-07 1.09E-07.
NE 1.22E-07 1.20E-07 1.16E-07 1.14E-07 1.11E-07 1.09E-07 1.06E-07 ENE 1.21 E-07 1.81 E-07 1.15E-07 1.13E-07 1.1 OE-07 1.07E-07 1.04E-07 E 1.13E-07 1.1OE-07 1.05E-07 1.03E-07 1.01 E-07 1.01 E-07 9.17E-08 ESE 1.19E-07 1.14E-07 1.08E-07 1.06E-07 1.03E-07 9.93E-08 9.89E-08 SE 1.31 E-07 1.33E-07 1.35E-07 1.32E-07 1.26E-07 1.20E-07 1.1 5E-07 SSE 1.30E-07 1.32E-07 1.34E-07 1.35E-07 1.31 E-07 1.26E-07 1.22E-07 S 1.63E-07 1.54E-07 1.46E-07 1.42E-07 1.34E-07 1.33E-07 1.32E-07 SSW 1.66E-07 1.57E-07 1.51 E-07 1.46E-07 1.39E-07 1.34E-07 1.31 E-07 SW 1.97E-07 1.82E-07 1.79E-07 1.71 E-07 1.64E-07 1.59E-07 1.54E-07 WSW 2.02E-07 1.95E-07 1.85E-07 1.77E-07 1.69E-07 1.62E-07 1.54E-07 W 2.01 E-07 1.92E-07 1.90E-07 1.84E-07 1.82E-07 1.78E-07 1.71 E-07 WNW 2.02E-07 1.96E-07 1.92E-07 1.90E-07 1.85E-07 1.78E-07 1.75E-07 NW 1.70E-07 1.50E-07 1.48E-07 1.47E-07 1.39E-07 1.37E-07 1.38E-07 NNW 1.31 E-07 1.30E-07 1.27E-07 1.22E-07 1.19E-07 1.16E-07 1.13E-07 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
- Values less than the value for 0.4 miles.
See appropriate offgas stack long term elevated release values.
I/plr
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 I Page 47 of 74 Table 10 Monticello Offgas Stack Dispersion Parameters for Short Term Elevated Releases
<500 Hrs/Yr or <150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (X/q), sec/m3 Miles Sector* 3.6 3.7 3.8 3.9 4.0 4.1 4.2 N 1.18E-07 1.15E-07 1.14E-07 1.11E-07 1.08E-07 1.06E-07 1.05E-07 NNE 1.07E-07 1.05E-07 1.01 E-07 9.83E-08 9.61 E-08 9.38E-08 9.04E-08 NE 1.03E-07 1.01 E-07 9.84E-08 9.65E-08 9.20E-08 9.00E-08 8.81 E-08 ENE 1.03E-07 1.01 E-07 9.56E-08 9.34E-08 9.07E-08 8.79E-08 8.58E-08 E 9.OOE-08 8.74E-08 8.37E-08 8.17E-08 7.94E-08 7.80E-08 7.64E-08 ESE 9.67E-08 9.46E-08 8.97E-08 8.91 E-08 8.79E-08 8.64E-08 8.45E-08 SE 1.1OE-07 1.06E-07 1.06E-07 1.02E-07 9.89E-08 1.03E-07 9.99E-08 SSE 1.18E-07 1.15E-07 1.11E-07 1.08E-07 1.12E-07 1.1OE-07 1.08E-07 S 1.27E-07 1.23E-07 1.21 E-07 1.17E-07 1.13E-07 1.1OE-07 1.1OE-07 SSW 1.27E-07 1.24E-07 1.21 E-07 1.17E-07 1.15E-07 1.13E-07 1.08E-07 SW 1.52E-07 1.46E-07 1.43E-07 1.43E-07 1.41 E-07 1.40E-07 1.38E-07 WSW 1.49E-07 1.43E-07 1.44E-07 1.43E-07 1.34E-07 1.33E-07 1.34E-07 W 1.66E-07 1.61 E-07 1.56E-07 1.49E-07 1.42E-07 1.39E-07 1.35E-07 WNW 1.73E-07 1.67E-07 1.63E-07 1.58E-07 1.54E-07 1.49E-07 1.45E-07 NW 1.34E-07 1.27E-07 1.25E-07 1.24E-07 1.21 E-07 1.19E-07 1.17E-07 NNW 1.1 OE-07 1.07E-07 1.02E-07 1.OOE-07 9.75E-08 9.52E-08 9.37E-08 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
- Values less than the value for 0.4 miles..
See appropriate offgas stack long term elevated release values.
I/plr
P . s~~~~~~~~~~~~~~~~~~
I1 MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 48 of 74 Table 10 Monticello Offgas Stack Dispersion Parameters for Short Term Elevated Releases
<500 Hrs/Yr or <150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (X/q), sec/m3 Miles Sector* 4.3 4.4 4.5 4.6 4.7 4.8 4.9 N 1.01 E-07 9.83E-08 9.37E-08 9.14E-08 8.97E-08 8.80E-08 8.61 E-08 NNE 8.88E-08 8.71 E-08 8.63E-08 8.42E-08 8.14E-08 8.OOE-08 7.84E-08 NE 8.69E-08 8.53E-08 8.40E-08 8.25E-08 8.19E-08 8.02E-08 7.81 E-08 ENE 8.42E-08 8.26E-08 8.09E-08 7.87E-08 7.69E-08 7.55E-08 7.38E-08 E 7.33E-08 7.27E-08 7.02E-08 6.85E-08 6.71 E-08 6.56E-08 6.40E-08 ESE 8.27E-08 8.1 OE-08 7.40E-08 7.77E-08 7.61 E-08 7.46E-08 7.32E-08 SE 9.71 E-08 9.47E-08 9.24E-08 9.01 E-08 8.78E-08 8.56E-08 8.18E-08 SSE 1.07E-07 1.02E-07 1.02E-07 9.90E-08 9.66E-08 9.41 E-08 1.19E-07 S 1.06E-07 1.04E-07 1.02E-07 9.72E-08 9.63E-08 9.35E-08 9.03E-08 SSW 1.05E-07 1.03E-07 1.01 E-07 9.78E-08 9.46E-08 9.20E-08 9.OOE-08 SW 1.38E-07 1.37E-07 1.34E-07 1.30E-07 1.26E-07 1.24E-07 1.22E-07 WSW 1.31 E-07 1.28E-07 1.28E-07 1.22E-07 1.20E-07 1.1 9E-07 1.18E-07 W 1.33E-07 1.28E-07 1.25E-07 1.24E-07 1.20E-07 1.17E-07 1.15E-07 WNW 1.43E-07 1.38E-07 1.35E-07 1.33E-07 1.33E-07 1.27E-07 1.25E-07 NW 1.14E-07 1.12E-07 1.11E-07 1.07E-07 1.04E-07 1.01E-07 9.74E-08 NNW 9.12E-08 8.89E-08 8.64E-08 8.31 E-08 8.26E-08 8.08E-08 7.72E-08 Period of Record: 9-1-76 to 8-31 -78
- Measured relevant to the Offgas Stack.
- Values less than the value for 0.4 miles.
- See appropriate offgas stack long term elevated release values.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 49 of 74 Table 10 Monticello Offgas Stack Dispersion Parameters for Short Term Elevated Releases
<500 Hrs/Yr or <150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (/q), sec/m 3 Miles Sector* 5.0 N 8.28E-08 NNE 7.56E-08 NE 7.58E-08 ENE 7.11E-08 E 6.33E-08 ESE 7.16E-08 SE 8.1 OE-08 SSE 1.11 E-07 S 8.84E-08 SSW 8.80E-08 SW 1.19E-07 WSW 1.13E-07 W 1.13E-07 WNW 1.21 E-07 NW 9.51 E-08 NNW 7.53E-08 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
- Values less than the value for 0.4 miles.
See appropriate offgas stack long term elevated release values.
I/plr
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 50 of 74 Table 11 Monticello Offgas Stack Dispersion Parameters for Short Term Elevated Releases
<500 HrsYr or <150 Hrs/Qtr For Standard Distances (As Measured from the Offgas Stack) (D/q), m-2 Miles Sector* 0.1 0.2 0.3 0.4 0.5 0.6 0.7 N *** 1.32E-08 1.31 E-08 9.45E-09 6.60E-09 NNE 2.39E-08 1.86E-08 1.39E-09 9.88E-09 NE 6.01 E-09 7.80E-09 6.24E-09 4.92E-09 ENE 1.31 E-08 1.14E-08 8.79E-09 6.20E-09 E 7.37E-09 9.17E-09 6.52E-09 4.58E-09 ESE ** 3.74E-09 5.28E-09 SE ** 6.26E-09 SSE 6.60E-09 S ** ** **
- ***** 3.34E-09 WSW 2.16E-09 3.17E-09 W ** 2.22E-09 3.38E-09 3.35E-09 WNW 2.55E-09 3.89E-09 3.94E-09 NW ** 3.17E-09 4.01 E-09 NNW 2.13E-08 1.68E-08 1.30E-08 .9.18E-09 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
.I I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 51 of 74 Table 11 Monticello Offgas Stack Dispersion Parameters for Short Term Elevated Releases
<500 HrsYr or <150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (D/q), m-2 Miles Sector* 0.8 0.9 1.0 1.1 1.2 1.3 1.4 N 7.46E-09 7.64E-09 7.08E-09 5.61 E-09 5.20E-09 4.30E-09 4.21 E-09 NNE 9.52E-09 9.50E-09 8.74E-09 7.97E-09 6.49E-09 5.28E-09 5.05E-09 NE 5.32E-09 5.92E-09 5.43E-09 4.98E-09 4.43E-09 3.60E-09 3.11 E-09 ENE 6.OOE-09 5.94E-09 5.01 E-09 4.56E-09 4.25E-09 3.75E-09 3.31 E-09 E 5.18E-09 5.40E-09 4.74E-09 4.36E-09 3.76E-09 3.08E-09 3.09E-09 ESE 6.16E-09 6.58E-09 5.98E-09 4.72E-09 4.30E-09 3.89E-09 3.66E-09 SE 7.39E-09 7.99E-09 7.50E-09 6.40E-09 5.96E-09 5.50E-09 6.04E-09 SSE 7.58E-09 8.26E-09 7.59E-09 6.02E-09 6.29E-09 5.79E-09 6.12E-09 S 6.46E-09 6.88E-09 6.53E-09 5.17E-09 4.89E-09 4.19E-09 5.08E-09 SSW 4.90E-09 4.99E-09 4.71 E-09 4.17E-09 3.58E-09 3.12E-09 3.17E-09 SW 5.67E-09 4.25E-09 3.97E-09 3.65E-09 3.03E-09 2.74E-09 3.65E-09 WSW 3.83E-09 4.16E-09 3.58E-09 3.23E-09 3.12E-09 2.66E-09 3.64E-09 W 4.14E-09 4.59E-09 4.35E-09 3.87E-09 3.59E-09 3.20E-09 3.87E-09 WNW 4.86E-09 5.37E-09 5.09E-09 4.51 E-09 4.1 OE-09 3.77E-09 4.44E-09 NW 4.75E-09 5.16E-09 5.03E-09 4.25E-09 3.55E-09 3.43E-09 3.86E-09 NNW 8.37E-09 8.39E-09 7.94E-09 7.09E-09 5.96E-09 4.82E-09 6.18E-09 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
I/plr
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 I Page 52 of 74 Table 11 Monticello Offgas Stack Dispersion Parameters for Short Term Elevated Releases
<500 HrsYr or <150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (D/q), m-2 Miles Sector* 1.5 1.6 1.7 1.8 1.9 2.0 2.1 N 4.63E-09 3.13E-09 3.20E-09 2.90E-09 2.69E-09 2.48E-09 2.24E-09 NNE 5.50E-09 3.78E-09 4.02E-09 3.56E-09 3.27E-09 2.95E-09 2.66E-09 NE 3.1 OE-09 2.65E-09 2.28E-09 2.48E-09 2.27E-09 2.08E-09 1.85E-09 ENE 2.86E-09 2.40E-09 2.81 E-09 2.31 E-09 2.08E-09 1.91 E-09 1.76E-09 E 2.73E-09 2.35E-09 2.05E-09 2.39E-09 2.18E-09 1.96E-09 1.81 E-09 ESE 3.62E-09 3.20E-09 2.86E-09 - 2.38E-09 2.22E-09 2.1 OE-09 SE 4.68E-09 4.28E-09 3.67E-09 3.61 E-09 3.49E-09 3.09E-09 2.75E-09 SSE 4.50E-09 3.93E-09 3.57E-09 3.70E-09 2.90E-09 2.79E-09 2.69E-09 S 3.59E-09 3.58E-09 3.34E-09 3.04E-09 2.74E-09 2.55E-09 SSW 2.73E-09 2.34E-09 2.81 E-09 2.42E-09 2.17E-09 1.97E-09 1.80E-09 SW 2.32E-09 1.98E-09 1.72E-09 1.72E-09 1.72E-09 1.57E-09 1.40E-09 WSW 2.38E-09 2.07E-09 1.80E-09 1.77E-09 1.73E-09 1.58E-09 1.42E-09 W 2.70E-09 2.47E-09 2.47E-09 2.22E-09 1.92E-09 1.75E-09 1.57E-09 WNW 2.83E-09 2.38E-09 2.06E-09 2.02E-09 2.03E-09 1.84E-09 1.64E-09 NW 3.09E-09 2.70E-09 3.41 E-09 2.94E-09 2.70E-09 2.35E-09 2.13E-09 NNW 4.19E-09 3.41 E-09 3.09E-09 2.84E-09 2.74E-09 2.54E-09 2.33E-09 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
See appropriate long term values.
I/plr
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 53 of 74 Table 11 Monticello Offgas Stack Dispersion Parameters for Short,Term Elevated Releases
<500 HrsYr or <150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (D/q), m-2 Miles Sector* 2.2 2.3 2.4 2.5 2.6 2.7 2.8 N 2.04E-09 1.90E-09 1.75E-09 1.64E-09 1.53E-09 1.42E-09 1.27E-09 NNE 2.45E-09 2.25E-09 2.1 OE-09 1.95E-09 1.82E-09 1.73E-09 1.61 E-09 NE 1.67E-09 1.51E-09 1.42E-09 1.30E-09 1.19E-09 1.11E-09 1.03E-09 ENE 1.61 E-09 1.47E-09 1.38E-09 1.29E-09 1.18E-09 1.12E-09 1.04E-09 E '1.62E-09 1.51E-09 1.37E-09 1.30E-09 1.20E-09 1.12E-09 1.04E-09 ESE 1.99E-09 1.88E-09 1.78E-09 1.66E-09 1.55E-09 1.44E-09 1.34E-09 SE 2.89E-09 2.38E-09 2.24E-09 2.12E-09 1.97E-09 2.09E-09 1.97E-09 SSE 2.47E-09, 2.24E-09 2.18E-09 2.01 E-09 1.85E-09 1.72E-09 1.98E-09 S 2.06E-09 1.92E-09 1.80E-09 1.67E-09 1.54E-09 1.46E-09 1.64E-09 SSW 1.62E-09 1.64E-09 1.73E-09 1.57E-09 1.46E-09 1.37E-09 1.29E-09 SW 1.24E-09 1.27E-09 1.35E-09 1.40E-09 1.60E-09 1.48E-09 1.34E-09 WSW 1.24E-09 1.29E-09 1.26E-09 1.27E-09 1.35E-09 1.27E-09 1.42E-09 W 1.40E-09 1.40E-09 1.42E-09 1.47E-09 1.35E-09 1.27E-09 1.20E-09 WNW 1.43E-09 1.46E-09 1.48E-09 1.52E-09 1.68E-09 1.58E-09 1.44E-09 NW 1.93E-09 1.80E-09 1.67E-09 1.57E-09 1.45E-09 1.35E-09 1.25E-09 NNW 2.22E-09 2.09E-09 2.02E-09 1.85E-09 1.74E-09 1.58E-09 1.44E-09 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
I/pir
I1 MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 54 of 74 Table 11 Monticello Offgas Stack Dispersion Parameters for Short Term Elevated Releases
<500 HrsYr or <150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (D/q), m 2 Miles Sector* 2.9 3.0 3.1 3.2 3.3 3.4 3.5 N 1.20E-09 1.15E-09 1.08E-09 1.03E-09 9.77E-10 9.22E-10 8.74E-10 NNE 1.47E-09 1.39E-09 1.31 E-09 1.25E-09 1.17E-09 1.11E-09 1.06E-09 NE 9.37E-10 8.90E-10 8.37E-10 7.98E-10 7.54E-10 7.19E-10 6.82E10 ENE 9.64E-10 9.11 E-10 8.65E-10 8.28E-10 7.85E-10 7.41 E-10 7.09E-10 E 9.72E-10 9.18E-10 8.55E-10 8.15E-10 7.80E-10 7.63E-10 6.77E-10 ESE 1.26E-09 1.18E-09 1.09E-09 1.04E-09 9.85E-10 9.24E-10 9.01 E-10 SE 1.58E-09 1.57E-09 1.56E-09 1.49E-09 1.40E-09 1.31 E-09 1.23E-09 SSE 1.57E-09 1.55E-09 1.54E-09 1.52E-09 1.44E-09 1.36E-09 1.28E-09 S 1.56E-09 1.41 E-09 1.29E-09 1.21 E-09 1.1 0E-09 1.05E-09 1.01 E-09 SSW 1.22E-09 1.12E-09 1.04E-09 9.83E-10 9.12E-10 8.63E-10 8.24E-10 SW 1.25E-09 1.11E-09 1.05E-09 9.69E-10 8.96E-10 8.36E-10 7.83E-10 WSW 1.31E-09 1.22E-09 1.13E-09 1.05E-09 9.80E-10 9.14E-10 8.49E-10 W 1.19E-09 1.09E-09 1.04E-09 9.69E-10 9.26E-10 8.75E-10 8.11E-10 WNW 1.31 E-09 1.21 E-09 1.12E-09 1.06E-09 9.78E-10 9.OOE-10 8.43E-10 NW 1.23E-09 1.03E09 9.72E-1 0 9.26E-1 0 8.37E-1 0 7.94E-1 0 7.63E-1 0 NNW 1.35E-09 1.30E-09 1.25E-09 1.17E-09 1.11E-09 1.06E-09 1.44E-09 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page-55 of 74 Table 11 Monticello Offgas Stack Dispersion Parameters for Short Term Elevated Releases
<500 HrsYr or <150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (D/q), m-2 Miles Sector* 3.6 3.7 3.8 3.9 4.0 4.1 4.2 N 8.20E-10 7.85E-10 7.57E-10 7.26E-10 6.90E-10 6.64E-10 6.42E-10 NNE 1.01 E-09 9.76E-10 9.14E-10 8.72E-10 8.35E-10 7.98E-10 7.55E-10 NE 6.45E-10 6.15E-10 5.85E-10 5.60E-10 5.22E-10 4.99E-10 4.77E-10 ENE 6.83E-10 6.52E-10 6.06E-10 5.79E-10 5.51 E-10 5.22E-10 5.00E-10 E 6.49E-10 6.16E-10 5.77E-10 5.51 E-10 5.25E-10 5.05E-10 4.85E-10 ESE 8.60E-10 8.21 E-10 7.64E-10 7.41 E-10 7.16E-10 6.91 E-10 6.61 E-10 SE. 1.16E-09 1.1OE-09 1.08E-09 1.02E-09 9.68E-10 9.93E-10 9.48E-10 SSE 1.21 E-09 1.15E-09 1.08E-09 1.02E-09 1.04E-09 9.94E-10 9.52E-10 S 9.44E-10 9.15E-10 8.76E-10 8.65E-10 8.63E-10 8.23E-10 7.95E-10 SSW 7.76E-10 7.35E-10 6.96E-10 6.69E-10 6.35E-10 6.08E-10 5.70E-10 SW 7.42E-10 6.82E-10 6.45E-10 6.21 E-10 5.90E-10 5.64E-10 5.37E-10 WSW 7.90E-1 0 7.45E-1 0 7.21 E-1 0 6.88E-1 0 6.21 E-1 0 5.94E-1 0 5.78E-1 0 W 7.69E-10 7.29E-10 6.93E-10 6.50E-10 6.08E-10 5.83E-10 5.56E-1 0 WNW 8.16E-10 7.73E-10 7.41 E-10 7.05E-10 6.72E-10 6.38E-10 6.11 E-10 NW 7.24E-10 6.75E-10 6.45E-10 6.43E-10 6.48E-10 6.19E-10 5.95E-10 NNW 9.60E-10 9.1 OE-10 8.53E-10 8.18E-10 7.82E-10 7.49E-10 7.22E-10 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
I/plr
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 56 of 74 Table 11 Monticello Offgas Stack Dispersion Parameters for Short Term Elevated Releases
<500 HrsYr or <150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (D/q), m-2 Miles Sector* 4.3 4.4 4.5 4.6 4.7 4.8 4.9 N 6.07E-1 0 5.80E-1 0 5.43E-1 0 5.20E-1 0 5.01 E-1 0 4.83E-1 0 4.65E-1 0 NNE 7.27E-10 7.OOE-10 6.81E-10 6.52E-10 6.20E-10 5.98E-10 5.76E-10 NE 4.61 E-10 4.42E-10 4.27E-10 4.1 OE-10 3.99E-10 3.83E-10 3.66E-10 ENE 4.81 E-1 0 4.63E-1 0 4.45E-1 0 4.24E-1 0 4.07E-1 0 3.92E-1 0 3.76E-1 0 E 4.55E-10 4.43E-10 4.19E-10 4.02E-10 3.86E-10 3.71 E-10 3.55E-10 ESE 6.34E-10 6.06E-10 5.45E-10 5.59E-10 5.39E-10 5.19E-10 4.97E-10 SE 9.05E-1 0 8.70E-1 0 8.33E-1 0 8.01 E-1 0 7.69E-1 0 7.38E-1 0 6.94E-1 0 SSE 9.43E-10 8.59E-10 8.39E-10 8.03E-10 7.73E-10 7.40E-10 9.18E-10 S 7.75E-1 0 7.42E-1 0 7.1 OE-1 0 6.65E-1 0 6.49E-1 0 6.21 E-1 0 5.91 E-1 0 SSW 5.39E-10 5.15E-10 4.91 E-10 4.69E-10 4.47E-10 4.28E-10 4.13E-10 SW 5.23E-10 5.02E-10 4.74E-10 4.53E-10 4.35E-10 4.22E-10 4.08E-10 WSW 5.46E-10 5.16E-10 4.98E-10 4.69E-10 4.55E-10 4.45E-10 -4.34E-10 W 5.35E-10 5.09E-10 4.89E-10 4.77E-10 4.53E-10 4.36E-10 4.20E-10 WNW 5.91 E-10 5.61 E-10 5.41 E-10 5.24E-10 5.16E-10 4.87E-10 4.69E-10 NW 5.88E-10 5.66E-10 5.44E-10 5.17E-10 4.96E-10 4.72E-10 4.48E-10 NNW 6.90E-1 0 6.60E-1 0 6.30E-1 0 5.96E-1 0 5.83E-1 0 5.61 E-1 0 5.28E-1 0 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
- I/plr
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 57 of 74 Table 11 Monticello Offgas Stack Dispersion Parameters for Short Term Elevated Releases
<500 HrsYr or <150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (D/q), m-2 Miles' 5.0 Sector*
N 4.39E-1 0 NNE 5.46E-10 NE 3.48E-10 ENE 3.56E-1 0 E 3.45E-10 ESE 4.80E-1 0 SE 6.78E-10 SSE 8.45E-10 S 5.70E-10 SSW 3.98E-10 SW 3.92E-1 0 WSW 4.12E-10 W 4.05E-10 WNW 4.48E-1 0 NW 4.31 E-10 NNW 5.06E-10 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 I Page 58 of 74 Table 12 Monticello Reactor Building Vent Dispersion Parameters for Short Term Elevated Releases <500 Hrs/Yr or <150 Hrs/Qtr Distance X/q (sec/m) 3 D -2 Sector* Miles Meters No Decay Undepleted N 0.51 821. 5.18E-06 7.19E-08 NNE 0.58 933. 3.51 E-06 5.02E-08 NE 0.65 1046. 2.33E-06 2.93E-08 ENE 0.83 1336. 1.82E-06 1.69E-08 E 0.59 950. 3.67E-06 3.90E-08 ESE 0.59 950. 4.95E-06 6.51 E-08 SE 0.61 982. 4.96E-06 6.49E-08 SSE 0.43 692. 8.06E-06 1.18E-07 S 0.34 547. 6.92E-06 9.30E-08 SSW 0.32 515. 5.92E-06 7.04E-08 SW 0.32 515. 6.31 E-06 8.24E-08 WSW 0.35 563. 4.91 E-06 5.50E-08 W 0.48 772.. 3.38E-06 3.82E-08 WNW 0.68 1094. 2.94E-06 2.88E-08 NW 0.43 692. 5.70E-06 7.09E-08 NNW 0.53 853. 4.44E-06 6.09E-08 Period of Record: 9-1 -76 to 8-31 -78
- Measured relevant to the Reactor Vent.
I/pir
I MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 59 of 74 Table 13 Reactor Building Vent Dispersion Parameters for Short Term Elevated Releases
<500 Hrs/Yr or <150 Hrs/Qtr For Standard Distances (As Measured from the Offgas Stack) (fq), sec/M 3 Miles Sector* 0.1 0.2 0.3 0.4 0.5 0.6 0.7 N 7.30E-05 2.19E-05 1.10E-05 7.14E-06 5.28E-06 4.19E-06 3.46E-06 NNE 5.81 E-05 1.77E-05 8.96E-06 5.84E-06 4.23E-06 3.34E-06 2.79E-06 NE 4.26E-05 1.29E-05 6.69E-06 4.33E-06 3.19E-06 2.54E-06 2.16E-06 ENE 4.27E-05 1.29E-05 6.65E-06 4.32E-06 3.15E-06 2.53E-06 2.16E-06 E 5.76E-05 1.73E-05 9.22E-06 6.20E-06 4.51 E-06 3.63E-06 3.04E-06 ESE 7.80E-05 2.30E-05 1.24E-05 8.28E-06 6.16E-06 4.84E-06 4.01 E-06 SE 8.52E-05 2.48E-05 1.31 E-05 8.85E-06 6.46E-06 5.08E-06 4.18E-06 SSE 8.87E-05 2.60E-05 1.36E-05 8.91 E-06 6.53E-06 5.15E-06 4.22E-06 S 4.89E-05 1.47E-05 7.95E-06 5.35E-06 3.95E-06 3.17E-06 2.63E-06 SSW 4.04E-05 1.19E-05 6.58E-06 4.38E-06 3.34E-06 2.80E-06 2.46E-06 SW 4.37E-05 1.34E-05 7.26E-06 4.76E-06 3.62E-06 2.97E-06 2.62E-06 WSW 3.65E-05 1.09E-05 6.13E-06 4.11E-06 3.17E-06 2.70E-06 2.43E-06 W 4.07E-05 1.23E-05 6.47E-06 4.32E-06 3.19E-06 2.67E-06 2.35E-06 WNW 5.53E-05 1.65E-05 8.74E-06 5.74E-06 4.22E-06 3.37E-06 2.85E-06 NW 6.25E-05 1.85E-05 9.62E-06 6.32E-06 4.65E-06 3.76E-06 3.15E-06 NNW 7.11E-05 2.11E-05 1.04E-05 6.70E-06 4.78E-06 3.76E-06 3.15E-06 Period of Record: 9-1 -76 to 8-31 -78
- Measured relevant to the Reactor Vent.
I/pIr
I1 MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 60 of 74 Table 13 Reactor Building Vent Dispersion Parameters for Short Term Elevated Releases
<500 Hrs/Yr or <150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (/q), sec/m 3 Miles Sector* 0.8 0.9 1.0 1.1 1.2 1.3, 1.4 N 2.84E-06 2.43E-06 2.05E-06 1.79E-06 1.61 E-06 1.46E-06 1.31 E-06 NNE 2.33E-06 2.02E-06 1.71 E-06 1.51 E-06 1.37E-06 1.24E-06 1.12E-06 NE 1.83E-06 1.58E-06 1.37E-06 1.21 E-06 1.11E-06 9.99E-06 9.23E-06 ENE 1.87E-06 1.64E-06 1.46E-06 1.31 E-06 1.20E-06 1.11E-06 1.04E-06 E 2.51E-06 2.18E-06 1.87E-06 1.64E-06 1.50E-06 1.38E-06 1.26E-06 ESE 3.34E-06 2.77E-06 2.38E-06 2.07E-06 1.80E-06 1.59E-06 1.44E-06 SE 3.42E-06 2.82E-06 2.39E-06 2.07E-06 1.78E-06 1.57E-06 1.40E-06 SSE 3.47E-06 2.89E-06 2.43E-06 2.12E-06 1.86E-06 1.64E-06 1.47E-06 S 2.27E-06 1.96E-06 1.70E-06 1.51 E-06 1.38E-06 1.27E-06 1.1 5E-06 SSW 2.18E-06 1.93E-06 1.74E-06 1.52E-06 1.48E-06 1.33E-06 1.21 E-06 SW 2.26E-06 1.99E-06 1.81 E-06 1.58E-06 1.44E 1.32E-06 1.21 E-06 WSW 2.18E-06 1.94E-06 1.82E-06 1.63E-06 1.48E-06 1.39E-06 1.29E-06 W 2.07E-06 1.87E-06 1.67E-06 1.52E-06 -1.41 E-06 1.29E-06 .1.19E-06 WNW 2.47E-06 2.15E-06 1.86E-06 1.68E-06 1.52E-06 1.37E-06 1.26E-06 NW 2.60E-06 2.22E-06 1.89E-06 1.64E-06 1.49E-06 1.34E-06 1.22E-06 NNW 2.64E-06 2.25E-06 1.90E-06 1.68E-06 1.50E-06 1.37E-06 1.25E-06 Period of Record: 9-1-76 to 8-31 -78
- Measured relevant to the Reactor Vent.
I I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A *Revision 0 F
Page 61 of 74 Table 13 Reactor Building Vent Dispersion Parameters for Short Term Elevated Releases
<500 Hrs/Yr or <150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (/q), sec/M 3 Miles Sector* 1.5 1.6 1.7 1.8. 1.9 2.0 2.1 N 1.28E-06 1.15E-06 1.05E-06 9.60E-07 9.OOE-07 8.28E-07 7.67E-07 NNE 1.11 E-06 9.94E-07 9.14E-07 8.44E-07 7.91 E-07 7.31 E-07 6.94E-07 NE 8.63E-07 7.69E-07 7.26E-07 7.09E-07 6.71 E-07 6.31 E-07 6.08E-07 ENE 9.50E-07 9.08E-07 8.65E-07 8.22E-07 7.80E-07 7.31 E-07 7.OOE-07 E 1.15E-06 1.06E-06 1.02E-06 9.40E-07 8.72E-07 8.20E-07 7.72E-07 ESE 1.31 E-06 1.1 6E-06 1.07E-06 1.03E-06 9.41 E-07 8.73E-07 8.08E-07 SE 1.26E-06 1.15E-06 1.06E-06 1.01E-06 9.48E-07 8.74E-07 8.19E-07 SSE 1.33E-06 1.1 7E-06 1.09E-06 1.05E-06 9.69E-07 9.01 E-07 8.34E-07 S 1.13E-06 1.OOE-06 9.21 E-07 8.55E-07 7.94E-07 7.33E-07 6.96E-07 SSW 1.19E-06 1.12E-06 1.08E-06 1.04E-06 1.02E-06 1.02E-06 9.95E-07 SW 1.18E-06 1.09E-06 1.06E-06 1.01 E-06 9.62E-07 9.53E-07 9.34E-07 WSW 1.27E-06 1.21 E-06 1.16E-06 1.09E-06 1.05E-06 1.04E-06 1.02E-06 W 1.19E-06 1.12E-06 1.06E-06 1.02E-06 1.01E-06 9.95E 9.91E-07 WNW 1.25E-06 1.16E-06 1.11E-06 1.06E-06 1.02E-06 1.01 E-06 9.90E-07 NW 1.09E-06 9.91E-07 9.57E-07 8.87E-07 8.18E-07 7.65E-07 7.25E-07 NNW 1.24E-06 1.12E-06 1.03E-06 9.46E-07 8.85E-07 8.17E-07 7.74E-07 Period of Record: 9-1 -76 to 8-31 -78
- Measured relevant to the Reactor Vent.
I/p r
I1 MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 62 of 74 Table 13 Reactor Building Vent Dispersion Parameters for Short Term Elevated Releases
<500 Hrs/Yr or <150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (x/q), sec/m3 Miles Sector* 2.2 2.3 2.4 2.5 2.6 2.7 2.8 N 7.21 E-07 6.79E-07 6.38E-07 6.1 OE-07 5.92E-07 5.77E-07 5.62E-07 NNE 6.47E-07 6.14E-07 5.79E-07 5.45E-07 5.26E-07 4.99E-07 4.80E-07 NE 5.81 E-07 5.55E-07 5.23E-07 5.11 E-07 4.86E-07 4.63E-07 4.47E-07 ENE 6.68E-07 6.41 E-07 6.1 OE-07 5.90E-07 5.62E-07 5.41 E-07 5.22E-07 E 7.25E-07 6.92E-07 6.51 E-07 6.19E-07 5.74E-07 5.53E-07 5.35E-07 ESE 7.53E-07 7.07E-07 6.62E-07 6.25E-07 5.91 E-07 5.56E-07 5.28E-07 SE 7.76E-07 7.36E-07 7.02E-07 6.75E-07 6.37E-07 6.04E-07 5.74E-07 SSE 7.74E-07 7.28E-07 6.87E-07 6.46E-07 6.1 OE-07. 5.77E-07 5.51 E-07 S 6.44E-07 6.08E-07 5.80E-07 5.54E-07 5.40E-07 5.25E-07 5.14E-07 SSW 9.71 E-07 9.89E-07 9.88E-07 9.58E-07 9.03E-07 8.47E-07 8.1 OE-07 SW 9.09E-07 9.03E-07 8.97E-07 8.65E-07 8.24E-07 7.90E-07 7.65E-07 WSW 9.86E-07 9.81 E-07 9.76E-07 9.48E-07 8.87E-07 8.35E-07 7.92E-07 W 9.66E-07 9.80E-07 9.78E-07 9.56E-07 9.12E-07 8.87E-07 8.66E-07 WNW 9.90E-07 9.88E-07 9.97E-07 9.75E-07 9.54E-07 9.43E-07 9.29E-07 NW 6.91 E-07 6.47E-07 6.07E-07 5.89E-07 5.72E-07 5.60E-07 5.51 E-07 NNW 7.27E-07 6.76E-07 6.47E-07 6.28E-07 5.95E-07 5.74E-07 5.52E-07 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Reactor Vent.
1/pir
MONTICELLO NUCLEAR GENERATING PLANT I
ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 63 of 74 Table 13 Reactor Building Vent Dispersion Parameters for Short Term Elevated Releases
<500 Hrs/Yr or <150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (/q), sec/m3 Miles Sector* 2.9 3.0 3.1 3.2 3.3 3.4 3.5 N 5.48E-07 5.29E-07 5.16E-07 5.02E-07 4.91 E-07 4.99E-07 4.82E-07 NNE 4.65E-07 4.49E-07 4.30E-07 4.15E-07 3.98E-07 3.83E-07 3.71 E-07 NE 4.31 E-07 4.13E-07 3.96E-07 3.82E-07 3.66E-07 3.51 E-07 3.39E-07 ENE 5.06E-07 4.87E-07 4.64E-07 4.52E-07 4.36E-07 4.25E-07 4.14E-07 E 5.13E-07 5.OOE-07 4.80E-07 4.62E-07 4.45E-07 4.27E-07 4.09E-07 ESE 5.01 E-07 4.74E-07 4.57E-07 4.36E-07 4.15E-07 3.99E-07 3.83E-07 SE 5.51 E-07 5.28E-07 5.05E-07 4.78E-07 4.55E-07 4.35E-07 4.16E-07 SSE 5.27E-07 5.06E-07 4.85E-07 4.59E-07 4.44E-07 4.26E-07 4.1 OE-07 S 5.03E-07 4.91 E-07 5.05E-07 4.93E-07 4.96E-07 4.76E-07 4.67E-07 SSW 7.70E-07 7.34E-07 7.03E-07 6.76E-07 6.48E-07 6.25E-07 5.97E-07 SW 7.38E-07 7.09E-07 6.87E-07 6.61 E-07 6.43E-07 6.16E-07 5.94E-07 WSW 7.52E-07 7.13E-07 6.84E-07 6.52E-07 6.24E-07 6.02E-07 5.73E-07 W 8.43E-07 8.16E-07 7.91 E-07 7.64E-07 7.44E-07 7.09E-07 6.90E-07 WNW 9.07E-07 8.94E-07 8.62E-07 8.44E-07 8.18E-07 8.OOE-07 7.84E-07 NW 5.34E-07 5.22E-07 5.28E-07 5.15E-07 5.16E-07 5.04E-07 4.97E-07 NNW 5.28E-07 5.08E-07 4.93E-07 4.74E-07 4.55E-07 4.35E-07 4.20E-07 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Reactor Vent.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 64 of 74 Table 13 Reactor Building Vent Dispersion Parameters for Short Term Elevated Releases
<500 Hrs/Yr or <150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (/q), sec/m3 Miles Sector* 3.6 3.7 3.8 3.9 4.0 4.1 4.2 N 4.65E-07 4.49E-07 4.32E-07 4.19E-07 4.06E-07 3.95E-07 3.83E-07 NNE 3.58E-07 3.47E-07 3.37E-07 3.25E-07 3.16E-07 3.18E-07 3.08E-07 NE 3.29E-07 3.18E-07 3.1 OE-07 3.01 E-07 2.93E-07 2.90E-07 2.77E-07 ENE 4.02E-07 3.90E-07 3.80E-07 3.72E-07 3.60E-07 3.55E-07 3.46E-07 E 3.97E-07 3.83E-07 3.72E-07 3.74E-07 3.66E-07 3.55E-07 3.44E-07 ESE 3.71 E-07 3.57E-07 3.42E-07 3.37E-07 3.28E-07 3.17E-07 3.06E-07 SE 4.01 E-07 3.86E-07 3.70E-07 3.61 E-07 3.48E-07 3.44E-07 3.42E-07 SSE 3.92E-07 3.78E-07 3.68E-07 3.66E-07 3.52E-07 3.41 E-07 3.29E-07 S 4.49E-07 4.43E-07 4.36E-07 4.29E-07 4.22E-07 4.16E-07 4.12E-07 SSW 5.79E-07 5.58E-07 5.49E-07 5.38E-07 5.25E-07 5.14E-07 5.02E-07 SW 5.80E-07 5.64E-07 5.48E-07 5.28E-07 5.15E-07 5.04E-07 4.94E-07 WSW 5.61 E-07 5.59E-07 5.50E-07 5.35E-07 5.23E-07 5.13E-07 4.90E-07 W 6.66E-07 6.40E-07 6.16E-07 5.94E-07 5.73E-07 5.54E-07 5.36E-07 WNW 7.52E-07 7.22E-07 6.90E-07 6.65E-07 6.37E-07 6.19E-07 5.97E-07 NW 4.79E-07 4.71 E-07 4.66E-07 4.57E-07 4.49E-07 4.41E-07 4.38E-07 NNW 4.07E-07 3.95E-07 3.86E-07 3.72E-07 3.68E-07 3.57E-07 3.51 E-07 Period of Record: 9-1 -76 to 8-31-78
- Measured relevant to the Reactor Vent.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 65 of 74 omms Table 13 Reactor Building Vent Dispersion Parameters for Short Term Elevated Releases
<500 Hrs/Yr or <150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (q), sec/m 3 Miles Sector* 4.3 4.4 4.5 4.6 4.7 4.8 4.9 N 3.65E-07 3.55E-07 3.41 E-07 3.33E-07 3.25E-07 3.20E-07 3.12E-07 NNE 3.08E-07 3.OOE-07 2.85E-07 2.79E-07 2.72E-07 2.66E-07 2.59E-07 NE 2.79E-07 2.69E-07 2.53E-07 2.53E-07 2.48E-07 2.41 E-07 2.36E-07 ENE 3.36E-07 3.29E-07 3.12E-07 3.07E-07 3.OOE-07 2.98E-07 2.91 E-07 E 3.37E-07 3.28E-07 3.19E-07 3.11E-07 3.02E-07 2.95E-07 2.85E-07 ESE 2.98E-07 2.89E-07 2.80E-07 2.71 E-07 2.63E-07 2.56E-07 2.48E-07 SE 3.32E-07 3.20E-07 3.1OE-07 3.01 E-07 2.92E-07 2.83E-07 2.75E-07 SSE 3.21 E-07 3.11 E-07 3.02E-07 2.92E-07 2.84E-07 2.75E-07 2.68E-07 S 4.03E-07 3.94E-07 3.87E-07 3.76E-07 3.65E-07 3.53E-07 3.43E-07 SSW 4.92E-07 4.81 E-07 4.71 E-07 4.57E-07 4.39E-07 4.26E-07 4.11 E-07 SW 4.84E-07 4.79E-07 4.69E-07 4.54E-07 4.39E-07 4.25E-07 4.12E-07 WSW 4.89E-07 4.77E-07 4.66E-07 4.50E-07 4.35E-07 4.24E-07 4.11 E-07 W 5.19E-07 5.03E-07 4.87E-07 4.73E-07 4.56E-07 4.43E-07 4.25E-07 WNW 5.78E-07 5.59E-07 5.41 E-07 5.25E-07 5.09E-07 4.92E-07 4.78E-07 NW 4.29E-07 4.20E-07 4.11E-07 4.OOE-07 3.88E-07 3.77E-07 3.66E-07 NNW 3.45E-07 3.32E-07 3.22E-07 3.15E-07 3.07E-07 2.98E-07 2.91 E-07 Period of Record: 9-1 -76 to 8-31 -78
- Measured relevant to the Reactor Vent.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 66 of 74 Table 13 Reactor Building Vent Dispersion Parameters for Short Term Elevated Releases
<500 Hrs/Yr or <150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (xlq), sec/m3 NAiImc Sector* 5.0 N 3.03E-07 NNE 2.52E-07 NE 2.30E-07 ENE 2.84E-07 E 2.82E-07 ESE 2.41 E-07 SE 2.67E-07 SSE 2.62E-07 S 4.67E-07 SSW 4.OOE-07 SW 3.99E-07 WSW 3.99E-07 W 4.12E-07 WNW 4.66E-07 NW 3.52E-07 NNW 2.78E-07 Period of Record: 9-1 -76 to 8-31 -78
- Measured relevant to the Reactor Vent.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 I Page 67 of 74 Table 14 Reactor Building Vent Dispersion Parameters for Short Term Elevated Releases
<500 Hrs/Yr or <150 Hrs/Qtr For Standard Distances (As Measured from the Offgas Stack) (D/q), m 2 Miles Sector* 0.1 0.2 0.3 0.4 0.5 0.6 0.7 N 6.91 E-07 2.69E-07 1.52E-07 1.01 E-07 7.36E-08 5.53E-08 4.28E-08 NNE 5.55E-07 2.24E-07 1.30E-07 8.81 E-08 6.33E-08 4.71 E-08 3.65E-08 NE- 3.90E-07 1.58E-07 9.37E-08 6.24E-08 4.48E-08 3.32E-08 2.59E-08 ENE 3.50E-07 1.43E-07 8.49E-08 5.71 E-08 4.08E-08 3.02E-08 2.33E-08 E 4.63E-07 1.86E-07 1.1 OE-07 7.39E-08 5.16E-08 3.82E-08 2.91 E-08 ESE 8.49E-07 3.27E-07 1.86E-07 1.21 E-07 8.62E-08 6.33E-08 4.88E-08 SE 9.41 E-07 3.56E-07 1.96E-07 1.29E-07 9.01 E-08 6.69E-08 5.19E-08 SSE 9.60E-07 3.67E-07 2.02E-07 1.32E-07 9.36E-08 6.99E-08 5.40E-08 S 4.50E-07 1.79E-07 1.06E-07 7.18E-08 5.11 E-08 3.80E-08 2.88E-08 SSW 3.27E-07 1.30E-07 7.81 E-08 5.13E-08 3.67E-08 2.75E-08 2.15E-08 SW 4.13E-07 1.67E-07 9.51 E-08 6.02E-08 4.24E-08 3.12E-08 2.46E-08 WSW 2.82E-07 1.14E-07 6.90E-08 4.53E-08 3.27E-08 2.46E-08 1.94E-08 W 3.06E-07 1.25E-07 7.41 E-08 5.02E-08 3.55E-08 2.68E-08 2.1 OE-08 WNW 4.25E-07 1.69E-07 9.89E-08 6.61 E-08 4.73E-08 3.52E-08 2.73E-08 NW 5.40E-07 2.12E-07 1.21 E-07 7.91 E-08 5.61 E-08 4.23E-08 3.28E-08 NNW 6.42E-07 2.53E-07 1.42E-07 9.39E-08 6.65E-08 4.95E-08 3.87E-08 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
I/pir
I MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 68 of 74 Table 14 Reactor Building Vent Dispersion Parameters for Short Term Elevated Releases
<500 HrsfYr or <150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (D/q), m 2 Miles Sector* 0.8 0.9 1.0 1.1 1.2 1.3 1.4 N 3.25E-08 2.57E-08 1.99E-08 1.61 E-08 1.34E-08 1.13E-08 9.77E-09 NNE 2.79E-08 2.22E-08 1.71 E-08 1.39E-08 1.1 6E-08 9.77E-09 8.45E-09 NE 1.99E-08 1.56E-08 1.23E-08 1.OOE-08 8.52E-09 7.15E-09 6.20E-09 ENE 1.80E-08 1.41E-08 1.12E-08 9.11E-09 7.57E-09 6.45E-09 5.55E09 E 2.17E-08 1.70E-08 1.33E-08 1.07E-08 9.01 E-09 7.69E-09 6.56E-09 ESE 3.78E-08 2.92E-08 2.35E-08. 1.93E-08 1.59E-08 1.34E-08 1.16E-08 SE 3.99E-08 3.1 OE-08 2.48E-08 2.04E-08 1.67E-08 1.40E-08 1.20E-08 SSE 4.16E-08 3.26E-08 2.57E-08 2.12E-08 1.76E-08 1.48E-08 1.27E-08 S 2.26E-08 1.78E-08 1.41 E-08 1.16E-08 9.75E-09 8.85E-09 7.48E-09 SSW 1.69E-08 1.34E-08 1.1 OE-08 9.02E-09 7.60E-09 6.52E-09 5.84E-09 SW 1.89E-08 1.51 E-08 1.25E-08 1.01 E-08 8.52E-09 7.27E-09 6.61 E-09 WSW 1.52E-08 1.20E-08 1.01 E-08 8.20E-09 6.85E-09 5.94E-09 5.35E-09 W 1.62E-08 1.31 E-08 1.04E-08 8.64E-09 7.29E-09 6.19E-09 5.49E-09 WNW 2.16E-08 1.72E-08 1.36E-08 1.12E-08 9.47E-09 7.95E-09 7.1BE-09 NW 2.49E-08 1.97E-08 1.55E-08 1.26E-08 1.07E-08 -9.05E-09 7.82E-09 NNW 3.OOE-08 2.36E-08 1.82E-08 1.49E-08 1.22E-08 1.05E-08 9.21 E-09 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
I/plr
=me I
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 69 of 74 0 Table 14 Reactor Building Vent Dispersion Parameters for Short Term Elevated Releases
<500 Hrs/Yr or <150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (D/q), m-2 Miles Sector* 1.5 1.6 1.7 1.8 1.9 2.0 2.1 N 8.90E-09 7.61E-09 6.62E-09 5.81E-09 5.23E-09 4.63E-09 4.13E-09 NNE 7.75E-09 6.61 E-09 5.79E-09 5.1 OE-09 4.56E-09 4.07E-09 3.71 E-09 NE 5.46E-09 4.54E-09 4.02E-09 3.69E-09 3.30E-09 2.93E-09 2.48E-09 ENE 4.71 E-09 4.1 9E-09 3.73E-09 3.33E-09 2.98E-09 2.64E-09 2.40E-09 E 5.63E-09 4.93E-09 4.49E-09 3.96E-09 3.53E-09 3.18E-09 2.88E-09 ESE 1.01 E-08 8.60E-09 7.60E-09 7.07E-09 6.28E-09 5.64E-09 5.07E-09 SE 1.03E-08 9.OOE-09 7.94E-09 7.17E-09 6.48E-09 5.74E-09 5.17E-09 SSE 1.10E-08 9.30E-09 8.32E-09 7.72E-09 6.89E-09 6.20E-09 5.56E-09 S 6.89E-09 5.81 E-09 5.11 E-09 4.54E-09 4.06E-09 3.61 E-09 3.30E-09 SSW 5.34E-09 4.70E-09 4.14E-09 3.63E-09 3.26E-09 3.21 E-09 2.88E-09 SW 6.60E-09 5.31 E-09 4.72E-09 4.14E-09 3.66E-09 3.56E-09 3.24E-09 WSW 4.91 E-09 4.44E-09 3.92E-09 3.40E-09 3.03E-09 3.03E-09 2.76E-09 W 5.07E-09 4.44E-09 3.82E-09 3.36E-09 3.07E-09 2.96E-09 2.71 E-09 WNW 6.67E-09 5.78E-09 5.06E-09 4.43E-09 3.92E-09 3.71 E-09 3.34E-09 NW 6.67E-09' 5.73E-09 5.26E-09 4.65E-09 4.11 E-09 3.68E-09 3.35E-09 NNW 8.53E-09 7.30E-09 6.36E-09 5.58E-09 5.OOE-09 4.42E-09 4.03E-09 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT - ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 70of74 Table 14 Reactor Building Vent Dispersion Parameters for Short Term Elevated Releases
<500 Hrs/Yr or <150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (D/q), m-2 Miles Sector* 2.2 2.3 2.4 2.5 2.6 2.7 2.8 N 3.75E-09 3.42E-09 3.11 E-09 2.88E-09 2.68E-09 2.53E-09 2.38E-09 NNE 3.34E-09 3.06E-09 2.79E-09 2.55E-09 2.38E-09 2.20E-09 2.06E-09 NE 2.43E-09 2.21 E-09 2.02E-09 1.89E-09 1.74E-09 1.61 E-09 1.51 E-09 ENE 2.18E-09 2.03E-09 1.85E-09 1.70E-09 1.57E-09 1.46E-09 1.36E-09 E 2.61 E-09 2.41 E-09 2.20E-09 2.02E-09 1.82E-09 1.71 E-09 1.61 E-09 ESE 4.60E-09 4.21 E-09 3.84E-09 3.54E-09 3.28E-09 3.01 E-09 2.80E-09 SE 4.71 E-09 4.43E-09 4.07E-09 3.79E-09 3.49E-09 3.24E-09 3.02E-09 SSE 5.01 E-09 4.58E-09 4.21 E-09 3.86E-09 3.55E-09 3.28E-09 3.06E-09 S 2.95E-09 2.70E-09 2.50E-09 2.32E-09 2.15E-09 2.OOE-09 1.86E-09 SSW 2.60E-09 2.45E-09 2.28E-09 2.06E-09 1.90E-09 1.75E-09 1.64E-09 SW 2.93E-09 2.72E-09 2.53E-09 2.29E-09 2.11 E-09 1.96E-09 1.84E-09 WSW 2.48E-09 2.31 E-09 2.16E-09 1.98E-09 1.81 E-09 1.68E-09 1.56E-09 W 2.44E-09 2.29E-09 2.12E-09 1.93E-09 1.77E-09 1.66E-09 1.57E-09 WNW 3.09E-09 2.85E-09 2.67E-09 2.43E-09 2.25E-09 2.11 E-09 1.98E-09 NW 3.06E-09 2.76E-09 2.58E-09 2.41 E-09 2.25E-09 2.1 OE-09 1.98E-09 NNW 3.64E-09 3.26E-09 3.04E-09 2.85E-09 2.62E-09 2.45E-09 2.29E-09 Period of Record: 9-1 -76 to 8-31 -78
- Measured relevant to the Offgas Stack.
I/pir-
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0
. Page 71 of 74 Table 14 Reactor Building Vent Dispersion Parameters for Short Term Elevated Releases
<500 Hrs/Yr or <150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (D/q), m- 2 Miles Sector* 2.9 3.0 3.1 3.2 3.3 3.4 3.5 N 2.23E-09 2.09E-09 1.96E-09 1.84E-09 1.74E-09 1.73E-09 1.63E-09 NNE 1.94E-09 1.82E-09 1.71 E-09 1.61 E-09 1.51 E-09 1.42E-09 i .35E-09 NE 1.42E-09 1.33E-09 1.25E-09 1.17E-09 1.1OE-09 1.03E-09 9.77E-10 ENE 1.28E-09 1.20E-09 1.11E-09 1.05E-09 9.92E-10 9.42E-10 8.97E-10 E 1.50E-09 1.43E-09 1.34E-09 1.26E-09 1.19E-09 1.11E-09 1.04E-10 ESE 2.60E-09 2.42E-09 2.29E-09 2.15E-09 2.OOE-09 1.90E-09 1.79E-09 SE 2.84E-09 2.67E-09 2.50E-09 2.32E-09 2.18E-09 2.05E-09 1.93E-09 SSE 2.86E-09 2.69E-09 2.53E-09 2.34E-09 2.23E-09 2.1 OE-09 1.98E-09 S 1.74E-09 1.63E-09 1.64E-09 1.54E-09 1.48E-09 1.36E-09 1.29E-09 SSW 1.53E-09 1.44E-09 1.36E-09 1.29E-09 1.22E-09 1.16E-09 1.10E-09 SW 1.73E-09 1.61 E-09 1.52E-09 1.43E-09 1.36E-09 1.27E-09 1.21 E-09 WSW 1.46E-09 1.37E-09 1.29E-09 1.22E-09 1.15E-09 1.10E-09 1.04E-09 W 1.48E-09 1.40E-09 1.32E-09 1.24E-09 1.18E-09 1.1OE-09 1.05E-09 WNW 1.84E-09 1.74E-09 1.61 E-09 1.52E-09 1.42E-09 1.52E-09 1.56E-09 NW 1.83E-09 1.72E-09 1.67E-09 1.59E-09 1.53E-09 1.42E-09 1.36E-09 NNW 2.13E-09 2.01 E-09 1.90E-09 1.79E-09 1.67E-09 1.57E-09 1.49E-09 Period of Record: 9-1 -76 to 8-31 -78
- Measured relevant to the Offgas Stack.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 72 of 74 Table 14 Reactor Building Vent Dispersion Parameters for Short Term Elevated Releases
<500 Hrs/Yr or <150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (D/q), m-2 Miles Sector* 3.6 3.7 3.8 3.9 4.0 4.1 4.2 N 1.55E-09 1.47E-09 1.40E-09 1.34E-09 1.29E-09 1.24E-09 1.20E-09 NNE 1.27E-09 1.21 E-09 1.16E-09 1.09E-09 1.04E-09 1.03E-09 9.85E-10 NE 9.27E-10 8.82E-10 8.44E-10 8.04E-10 7.68E-10 7.48E-10 7.05E-10 ENE 8.50E-10 8.08E-10 7.71 E-10 7.38E-10 7.01 E-10 6.78E-10 6.48E-10 E 9.92E-1 0 9.39E-1 0 8.94E-1 0 8.83E-1 0 8.48E-1 0 8.09E-1 0 7.71 E-1 0 ESE 1.71 E-09 1.61 E-09 1.53E-09 1.48E-09 1.42E-09 1.35E-09 1.29E-09 SE 1.83E-09 1.73E-09 1.64E-09 1.57E-09 1.50E-09 1.46E-09 1.44E-09 SSE 1.86E-09 1.76E-09 1.69E-09 1.65E-09 1.56E-09 1.49E-09 1.42E-09 S 1.20E-09 1.16E-09 1.11E-09 1.07E-09 1.03E-09 9.96E-10 9.67E-10 SSW 1.04E-09 9.85E-10 9.51 E-10 9.16E-10 8.78E-10 8.46E-10 8.15E-10 SW 1.14E-09 1.08E-09 1.02E-09 9.62E-10 1.01 E-09 9.88E-10 9.93E-10 WSW 9.89E-10 9.58E-10 9.19E-10 8.74E-10 8.35E-10 8.03E-10 7.53E-10 W 1.01 E-09 9.61 E-10 9.21 E-10 8.85E-10 8.52E-10 8.21 E-10 7.93E-10 WNW 1.49E-09 1.42E-09 1.34E-09 1.29E-09 1.23E-09 1.18E-09 1.14E-09 NW 1.28E-09 1.23E-09 1.19E-09 1.14E-09 1.10E-09 1.06E-09 1.03E-09 NNW 1.41 E-09 1.34E-09 1.29E-09 1.22E-09 1.19E-09 1.14E-09 1.1OE-09 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
I/pir
EMM MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 Page 73 of 74 I mmg Table 14 Reactor Building Vent Dispersion Parameters for Short Term Elevated Releases
<500 Hrs/Yr or <150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (D/q), m 2 Miles Sector* 4.3 4.4 4.5 4.6 4.7 4.8 4.9 N 1.13E-09 1.09E-09 1.05E-09 1.02E-09 9.85E-10 9.67E-10 9.40E-10 NNE 9.68E-10 9.29E-10 8.71 E-10 8.40E-10 8.07E-10 7.79E-10 7.49E-10 NE 6.98E-10 6.63E-10 6.16E-10 6.06E-10 5.87E-10 5.62E-10 5.45E-10 ENE 6.19E-10 5.96E-10 5.55E-10 5.37E-10 5.17E-10 5.06E-10 4.86E-10 E 7.43E-10 7.1 OE-10 6.81 E-10 6.53E-10 6.25E-10 6.01 E-10 5.72E-10 ESE 1.24E-09 1.18E-09 1.13E-09 1.08E-09 1.04E-09 9.99E-10 9.57E-10 SE 1.38E-09 .1.31 E-09 1.26E-09 1.21 E-09 1.16E-09 1.12E-09 1.07E-09 SSE 1.36E-09 1.30E-09 1.25E-09 1.18E-09 1.14E-09 1.09E-09 1.05E-09 S 9.28E-10 8.94E-10 8.64E-10 8.38E-10 8.12E-10 7.83E-10 7.60E-10 SSW 7.88E-10 7.61 E-10 7.38E-10 7.17E-10 6.89E-10 6.70E-10 6.49E-10 SW 1.09E-09 1.06E-09 1.11E-09 1.07E-09 1.02E-09 9.83E-10 9.46E-10 WSW 7.39E-10 7.09E-10 7.33E-10 7.08E-10 6.86E-10 6.70E-10 6.50E-10 W 7.67E-1 0 7.44E-1 0 7.22E-1 0 7.02E-1 0 6.79E-1 0 6.61 E-1 0 6.36E-1 0 WNW 1.10E-09 1.06E-09 1.02E-09 9.86E-10 9.55E-10 9.22E-10 8.94E-10 NW 9.96E-10 9.60E-10 9.27E-10 9.OOE-10 8.73E-10 8.48E-10 8.24E-10 NNW 1.07E-09 1.02E-09 1.01E-09 9.77E-10 9.43E-10 9.13E-10 8.84E-10 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
I/plr
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-A TITLE: APPENDIX A Revision 0 i Page 74 of 74 Table 14 Reactor Building Vent Dispersion Parameters for Short Term Elevated Releases
- <500 Hrs/Yr or <150 Hrs/Qtr (cont'd)
For Standard Distances (As Measured from the Offgas Stack) (D/q), m-2 Miles Sector* 5.0 N 9.09E-10 NNE 7.21 E-10 NE 5.24E-10 ENE 4.68E-1 0 E 5.58E-10 ESE 9.19E-10 SE 1.04E-09 SSE 1.01 E-09 S 1.29E-09 SSW 6.32E-1 0 SW 9.1OE-10 WSW 6.32E-1 0 W 6.21 E-1 0 WNW 8.70E-10 NW 7.93E-10 NNW 8.42E-10 Period of Record: 9-1-76 to 8-31-78
- Measured relevant to the Offgas Stack.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-B TITLE: APPENDIX B Revision 1 -
. , Page 1 of 21 OFFSITE DOSE CALCULATION MANUAL - TABLE OF CONTENTS SECTION PAGE 1.0 RECORD OF REVISION ................... - -4 Table 1 Monticello Nuclear Generating Plant Site Meteorology - Stability Class A, Elevation 10 Meters ......... ....................................... 5 Table 2 Monticello NJuclear Generating Plant Site Meteorology - Stability Class B, Elevation 10 Meters ............... 6 Table 3 Monticello Nuclear Generating Plant Site' Meteorology - Stability Class C, Elevation 10 Meters ................................................ 7 Table 4 Monticello Nuclear Generating Plant Site Meteorology - Stability Class D, Elevation 10 Meters ........... ; 8 Table 5 Monticello Nuclear Generating Plant Site Meteorology - Stability Class E, Elevation 10 Meters ............... 9 Table 6 Monticello Nuclear Generating Plant Site Meteorology - Stability Class F, Elevation 10 Meters ............ 10 Table 7 Monticello Nuclear Generating Plant Site Meteorology - Stability Class G, Elevation 10 Meters ............ - - .11 Table 8 Monticello Nuclear Generating Plant Site Meteorology - All Classes Combined Elevation 10 Meters .12 Table 9 Monticello Nuclear Generating Plant Site Meteorology - Stability Class A, Elevation 100 Meters .............. 14 Table 10 Monticello Nuclear Generating Plant Site Meteorology.- Stability Class B, Elevation 100 Meters . . 15 Table 11 Monticello Nuclear Generating Plant Site'Meteorology - Stability Class C, Elevation 100 Meters.16 Table 12 Monticello Nuclear Generating Plant Site Meteorology - Stability Class D, Elevation 100 Meters .................. 17 Prepared By:
Reviewed By: , _ _ _
OCFinal R Meeting .
eview : Date:
Approved By Plant Manager: AL L .~
p 4 I' Date:
3087(DOCUMENTCHANGE, HOLD,ANDCOMMENTFORM)incorporated: -
Resp Supv: CHEM lAssoc Ref: CHEM-1 . SR: N Freq: .2 ARMS: ODCM-APP-B DocType: 7030 Admin Initials: IDate: ,: JVI I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-B TITLE: APPENDIX B Revision 1 Page 2 of 21 SECTION PAGE Table 13 Monticello Nuclear Generating Plant Site Meteorology - Stability Class E, Elevation 100 Meters .............. - 18 Table 14 Monticello Nuclear Generating Plant Site Meteorology - Stability Class F, Elevation 100 Meters .19 Table 15 Monticello Nuclear Generating Plant Site Meteorology - Stability Class G, Elevation 100 Meters .20 Table 16 Monticello Nuclear Generating Plant Site Meteorology.- All Classes Combined Elevation 100 Meters .21 I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-B TITLE APPENDIX B Revision 1 I Page 3 of 21 1.0 RECORD OF REVISION Revision No. Date Reason for Revision 0 October - 2000 Moved previous ODCM-07.01 and ODCM-08.01 tables of meterological data to this document.
1 November - 2001 Typo, replaced missing M in Monticello on Page 1 of Table of Content. I I/plr
I MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-B TITLE: APPENDIX B . Revision 1
_ Page 4 of 21 A,
Table 1 Monticello Nuclear Generating Plant Site Meteorology Stability Class Table 1 Monticello Nuclear Generating Plant Site Meteorology - Stability Class A, Elevation 10 Meters Frequency Distribution Tables, Hours at each.Wind Speed and Direction Period of record: 9-1-76 through 8-31 -78 Wind Speed (mph) at 10 Meter Level Direction 1 to 3 4 to 7 8 to 12 13 to 18 19 to 24 Above 24 Total N 4 18 63 30 7 0 122 NNE 2 20 30 14 2 0 68 NE 1 13 21 26 2 2 65 NNE 1 14 16 4 0 0 35 E 0 28 40 12 0 0 80 ESE 3 33 50 5 6 0 97 SE 2 26 50 35 12 3 128 SSE 8 46 96 122 11 0 283 S 9 36 68 117 42 3 275 SSW 5 63 94 58 20 4 244 SW 4 35 64 32 5 3 143 WSW 3 25 74 26 0 0 128 W 0 O 29 47 18 1. 0 95 WNW 4 34 73 79 14 0 204 NW 3 29 -58 61 3 0 154 NNW 6 29 109 67 13 0 224 VAR 0 0 0 0 0 0 0 Total Hours This Class: 2350 Hours of Calm This Class: 5 Percent of All Data This Class: 14.27 I/plr
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-B TITLE: APPENDIX B Revision 1 Page 5 of 21 Table 2 Monticello Nuclear Generating Plant Site Meteorology - Stability Class B, Elevation 10 Meters Frequency Distribution Tables, Hours at each Wind Speed and Direction Period of record: 9-1 -76 through 8-31 -78 Wind Speed (mph) at 10 Meter Level Direction 1 to 3 4 to 7 8 to 12 13 to 18 19 to 24 Above 24 Total N 2 14 19 4 0 1 40 NNE 4 10 8 5 0 0 27 NE 0 6 3 2 0 0 11 ENE 1 11 7 . 2 0 0 21 E 0 13 4 0 0 0 17 ESE 1 15 10 3 3 0 32 SE 0 9 9 9 0 0 27 SSE 2 12 9 9 0 0 32 S 2 13 21 7 1 0 44 SSW 1 22 19 4 0 0 46 SW 0 11 10 3 0 0 24 WSW 1 12 11 3 0 0 27 W 0 12 19 8 2 1 42 WNW 0 . 11 20 21 5 1 58 NW 1 8 22 13 3 0 47 NNW 1 8 40 26 4 . 1 80 VAR 0 0 0 0 0 0 0 Total Hours This Class: 575 Hours of Calm This Class: 0 Percent of All Data This Class: 3.49 I/plr
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-B TITLE: APPENDIX B Revision 1 Page 6 of 21 Table 3 Monticello Nuclear Generating Plant Site Meteorology - Stability Class C,
-Table 3 Monticello Nuclear Generating Plant Site Meteorology - Stability Class C, Elevation 10 Meters Frequency Distribution Tables, Hours at each Wind Speed and Direction Period of record: 9-1-76 through 8-31-78 Wind Speed (mph) at 10 Meter Level Direction 1 to 3 4 to 7 8to 12 13to 18 19to24 Above 24 Total N 0 12 16 8 0 0 36 NNE 3 13 13 .4 1 0 34 NE 2 10 11 5 2 0 30-ENE 1 19 4 2 0 0 26 E 0 8 10 2 0 '0 20 ESE 2 14 12 .5 2 0 35 SE 0 12 16 .9 0 0 37 SSE 0 10 21 8 0 0 39 S 6 12 28 18 3 0 67 SSW 3 16 12 3 2 1 37 SW 3 11 14 3 1 0 32 WSW 2 5 11 2 0 0 20 W 4 22 19 5 .1 0 51 WNW 4 23 38 - 19 3 0 87 NW 3 17 18 30 4 0 72 NNW 2 22 40 27 5 1 97 VAR 0 0 0 0 0 0 0 Total Hours This Class: 720 Hours of Calm This Class: 0 Percent of All Data This Class: 4.37 I/pir
I MONTICELLO NUCLEAR GENERATING PLANT TITLE:
Table 4. Monticello APPENDIX B Nuclear Generating Plant Site Meteorology ODCM-APP-B Revision 1 Page 7 of 21
- Stability Class D,
-1 Table 4 Monticello Nuclear Generating Plant Site Meteorology - Stability Class D, Elevation 10 Meters Frequency Distribution Tables, Hours at each Wind Speed and Direction Period of record: 9-1-76 through 8-31 -78 Wind Speed (mph) at 10 Meter Level Direction 1 to 3 4to7 8to12 13to18 19 to 24 Above 24 Total N 9 107 135 39 1 0 291 NNE 32 132 87 18 1 0 270 NE 37 129 116 50 3 0 335 ENE 43 153 66 30 1 0 293
-E 29 125 64 27 0 0 245 ESE 28 107 148 60 4 0 347 SE 16 103 153 36 2 0 310 SSE 13 - 97 103 35 2 0 250 S 19 84 96 33 1 0 233 SSW 16 73 70 19 6 1 185 SW 19 58 52 10 4 0 143 WSW 14 69 63 14 2 1 163 W 16 79 98 33 3 5 234 WNW 13 112 262 159 25 2- 573 NW 17 82 255 232 61 3 650 NNW 19 104 247 246 49 1 666 VAR 0 0 0 0 0 0 0 Total Hours This Class: 5198 Hours of Calm This Class: 10 Percent of All Data This Class: 31.56 I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-B -
TITLE: APPENDIX B Table5 Generting Plnt SiteMeteoroogy onticeloNucler Revision 1 Page 8 of 21
- SabilityClass E III Tabl e 5 Monticello Nuclear Generating Plant Site Meteorology - Stability Class E, Elevation 10 Meters Frequency Distribution Tables, Hours at each Wind Speed and Direction Period of record: 9-1 -76 through 8-31 -78 Wind Speed (mph) at 10 Meter Level
- Direction I to3 4to7 8to12 13to18 19to24 Above 24 Total N 20 98 57 6 0 0 181 NNE 43 81 35 2 0 0 161 NE 35 94 41 6. 2 0 178 ENE 50 122 29 10 0 0 211 E 36 109 40 2 0 0 187 ESE 26 117 46 6 0 0 195 SE 19 111 136 18 2 0 286 SSE 20 95 116 33 1 I0 265 S 22 84 144 43 1 0 294 SSW 22 72 99 25 9 0 227 SW 23 84 57 10 2 *0 176 WSW 37 -86 44 4 0 0 171 w 30 156 123 12 4 0 325 WNW 24 195 233 41 2 ~0 495 NW 20 133 247 84 0 0 484 NNW 25 145 217 38 1 0 426 VAR 0 0 0 0 0 0 0 I~~~~~~~~~~~~~~~~~~~~~~~~
Total Hours This Class: 4269 Hours of Calm This Class: 7 Percent of All Data This Class: 25.92 I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-B TITLE: APPENDIX B Revision 1
. Page 9 of 21 Table 6 Monticello Nuclear Generating Plant Site Meteorology - Stability Class F, Elevation 10 Meters Frequency Distribution Tables, Hours at each Wind Speed and Direction Period of record: 9-1-76 through 8-31-78 Wind Speed (mph) at 10 Meter Level Direction 1 to 3 4 to 7 8 to 12 13 to 18 19 to 24 Above 24 Total N 30 62 3 0 0 0 95 NNE 37 54 0 0 0 0 91 NE 29 29 0 0 0 .0 58 ENE 32 28 0 0 0 0 60 E 32 59 5 0 0 0 96 ESE 25 97 11 0- 0 0 133 SE' 22 83 19 0 :0 0 124 SSE 16 122 12 0 0 0 150 S 24 93 31 3 0 0 151 SSW 27 67 14 0 0 0 108 SW 27 52 7 0 0 0 86 WSW 52 68 8 0 0 0 128 W 51 91 14 0 0 0 156 WNW 28 68 9 0 0 0 105 NW 36 67 12 0 0 0 115 NNW 30 119 29 0 0 0 178 VAR 0 0 0 0 0 0 0 Total Hours This Class: - 1847 Hours of Calm This Class: 13 Percent of All Data This Class: -11.21 I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-B TITLE: APPENDIX B Revision 1 Page 10 of 21 Table7 Monticello Nuclear Generating Plant Site Meteorology Stability Class G, Table 7 Monticello Nuclear Generating Plant Site Meteorology - Stability Class G, Elevation 10 Meters Frequency Distribution Tables, Hours at each Wind Speed and Direction Period of record: 9-1-76 through 8-31-78 Wind Speed (mph) at 10 Meter Level Direction 1 to 3 4 to 7 8 to 12 13 to 18 19 to 24 Above 24 Total N 45 31 0 0 0 0 76 NNE 40 16 0 O 0 0 0 56 NE 33 12 0 0 0 0 45 ENE 31 5 0 0 0 0 36 E 46 18 0 0 0 0 64 ESE 47 54 2 0 0 0 103 SE 52 34 1 '1 0 0 88 SSE - 67 111 3 6 0 0 187 S 64 109 23 2 0 0 198 SSW 61 65 . 10 2 0 0 138 SW 43 32 1 0 0 0- 76 WSW 77 37 0 0 O 0 114 W 53 31 0 0 0 0 84 WNW 37 13 2 0 0 0 52 NW 49 15 3 4. 0 0 71 NNW 47 48 2 0 0 0 97 VAR 0 0 0 0 0 0 Total Hours This Class: 1512 Hours of Calm This Class: 27 Percent of All Data This Class: 9.18 I/plr
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-B TITLE: APPENDIX B Revision 1 Page 11 of 21 II Table 8 Monticello Nuclear Generating Plant Site Meteorology - All Classes Combined Elevation 10 Meters Frequency Distribution Tables, Hours at each Wind Speed and Direction Period of record: 9-1-76 through 8-31-78 Wind Speed (mph) at 10 Meter Level Direction 1 to 3 4 to 7 8 to 12 13 to 18 19 to 24 Above 24 Total N 110 342 293 87 8 1 841 NNE 161 326 173 43 4 0 707 NE 137 293 192 89 9 2 722 ENE 159 352 122 48 1 0 682 E 143 360 163 43 0 0 709 ESE 132 437 279 79 15 0 942 SE 111 378 384 108 16 3 1000 SSE 126 493 360 213 14 0 1206 S 146 431 411 223 48 3 1262 SSW 135 378 318 111 37 6 985 SW 119 283 205 58 12 3 680 WSW 186 302 211 49 2 1 751 W 154 420 320 76 11 6 987 WNW 110 456 637 319 49 3 1574 NW 129 351 615 424 71. 3 1593 NNW 130 475 684 404 72 3 1768 VAR 0 0 0 0 0 0 0 I/plr
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-B TITLE: APPENDIX B Revision 1 l . Page 12 of 21 Table 8 Monticello Nuclear Generating Plant Site Meteorology - All Classes Combined-Elevation 10 Meters (cont'd)
Frequency Distribution Tables, Hours at each Wind Speed and Direction Period of record: 9-1-76 through 8-31-78 Data Recovery for the Period Total Hours: 17520 Hours of Calm: 62 Hours of Bad Data: 1049 Percent Data Recovery: 94.01 Percent Acceptable Observations in each Stability Class Class A 14.27 Class B 3.49 Class C 4.37 Class D 31.56 Class E 25.92 Class F 11.21 Class G 9.18 Average Wind Speed for each Wind Category 1 to 3 MPH 2.5 4 to 7 MPH 5.5 8 to 12 MPH 9.7 13 to 18 MPH 14.7 19 to 24 MPH 20.6 Above 24 MPH 27.2 I/pir
- 1 MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-B TITLE: APPENDIX B Revision 1 Page 13 of 21.
Table 9 Monticello Nuclear Generating Plant Site Meteorology - Stability Class A, Elevation 100 Meters Frequency Distribution Tables, Hours at each Wind Speed and Direction Period of record: 9-1-76 through 8-31-78 Wind Speed (mph) at 100 Meter Level Direction 1 to 3 4 to 7 8 to 12 13 to 18 19 to 24 Above 24 Total N 0- 1 2 10 1 0 14 NNE 0 1 1 1 0 0 3 NE 0 0 1 0 0 0 1 ENE 0 0 0 0 1 0 1 E 0 1 4 0 0 .0 5 ESE 0 0 4 0 0 0 4 SE 0 0 4 8 0 6 18 SSE 0 1 5 42 36 15 99 S 0 1 3 28 35 12 79 SSW 0 1 10 37 53 39 140 SW 0 0 4 19 6 5 36 WSW 0 0 3 16 10 1 30-W 0 0 0 7 2 0 9 WNW 0 0 2 4 1 2 9 NW 0 0 3 6 6 .3 18 NNW 0 - 0 1 14 4 0 19.
VAR 0 0 0 0 0 0 0 Total Hours This Class: 489 Hours of Calni This Class: 4 Percent of All Data This Class: 2.95 I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-B TITLE: APPENDIX B Revision 1 Page 14 of 21 Stability Class B, Table 10 Monticello Nuclear Generating Plant Site Meteorology -
Table 10 Monticello Nuclear Generating Plant Site Meteorology - Stability Class B, Elevation 100 Meters Frequency Distribution Tables, Hours at each Wind Speed and Direction Period of record: 9-1-76 through 8-31 -78 Wind Speed (mph) at 100 Meter Level Direction 1 to 3 4to7 8to 12 13 to 18 19 to 24 Above 24 Total N 0 3 13 18 3 0 37 NNE 0 6 3 9 2 2 22 NE 0 1 7 6 0 0 14 ENE 0 2 3 7 2 0 14 E 0 2 15 1 0
- 0 18 ESE 0 5 17 3 0 2 27 SE 1 7 15 9 2 2 36 SSE 1 9 28 12 8 2 60 S 0 5 23 18 3 0 49 SSW 0 8' 23 17 5 2 60 SW 0 7 18 8 5 1 39 WSW 0 7 8 14 2 1 32 W 0 4 8 18 5 0 35 WNW 0 4 12 17 7 6 46 NW 1 5 14 23 12 5 60 NNW 0 1 8 25 11 2 47 VAR 0 0 0 0 ,0 0 0, Total Hours This Class: 602 Hours of Calm This Class: 6 Percent of All Data This Class: 3.64 I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-B TITLE: APPENDIX B Revision 1 Page 15 of 21 Tablel11 Monticello Nuclear Generating Plant Site Meteorology -Stability Class C, Elevation 100 Meters Frequency Distribution Tables, Hours at each Wind Speed and Direction Period of record: 9-1-76 through 8-31-78 Wind Speed (mph) at 100 Meter Level Direction 1 to 3 4 to 7 - 8 to 12 13 to 18 19 to 24 Above 24 Total N 3 9 26 25 13 2 78 NNE 2 12 14 14 8 2 52 NE 1 7 9 8 2 0 27 ENE 0 5 12 6 1 0 24 E 0 13 19 1 2 0 35 ESE 0 13 25 11 1 1 51 SE 2 17 12 8 4 0 43 SSE 0 26 38 19 10 2 95 S 0 15 23 13 7 4 62 SSW 0 28 33 23 11 2 97 SW 0 20 24 17 4 0 65 WSW 3 17 27 14 3 1 65 w 3 10 20 14 -8 3 58 WNW 3 10 16 27 18 9 83 NW 2 8 22 38 26 10 106 NNW 2 3 16 42 19 8 90 VAR 0 0 0 0 0 0 0 Total Hours This Class: 1041 Hours of Calm This Class: 10 Percent of All Data This Class: 4.29 I/plr
i' MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-B TITLE: APPENDIX B Revision 1 Page 16 of 21 Table 12 Monticello Nuclear Generating Plant Site Meteorology - Stability Class D, Elevation 100 Meters Frequency Distribution Tables, Hours at each Wind Speed and Direction Period of record: 9-1-76 through 8-31-78 Wind Speed (mph) at 100 Meter Level Direction 1 to 3 4 to 7 8 to 12 13 to 18 19 to 24 Above 24 Total N 11 51 95 181 130 82 NNE 11 41 106 120 50 12 340 NE 15 53 105 93 25 8 299 ENE 14 41 131 83 59 12 340 E 18 61 '103 62 38 6 288 ESE 17 55 101 85 47 31 336
'SE 13 57 108 152 68 23 421 SSE 9 63 119 148 71 17 427 SSE S 16 61 95 122 61 8 363 SSW 14 61 85 120 46 34 360 SW 14 54 80 74 32 11 265 WSW 13 52 69 44 21 11 210 w ' 8 45 89 59 29 17 247 WNW 14 51 141 165 77 62 510 NW 7 50 170 366 312 143 1048 NNW -12 52 176 312 350 229 1131 VAR 0 0 0 0 0 0 0 Total Hours This Class: 7264 Hours of Calm This Class: 129 Percent of All Data This Class: 43.87
/pir
I MONTICELLO NUCLEAR GENERATING PLANT _ODCM-APP-B TITLE: APPENDIX B Revision 1 Page 17.of 21 Class E, Table 13 Monticello Nuclear Generating Plant Site Meteorology Stability Table 13 Monticello Nuclear Generating Plant Site Meteorology - Stability Class E, Elevation 100 Meters Frequency Distribution Tables, Hours at each Wind Speed and Direction Period of record: 9-1-76 through 8-31 -78 Wind Speed (mph) at 100 Meter Level Direction 1 to 3 4 to 7 8 to 12 13 to 18 19 to 24 Above 24 Total' N 4 17 59 99 82 11 272 NNE 7 18 37 68 32 3 - 165 NE 4 16 47 58 20 2 147 ENE 4 33 68 93 27 9 234 E 4 27 64 75 15 2 187 ESE 5 20 46 74 37 11 193 SE 10 23 63 97 58 3 254 SSE 5 22 58 94 105 16 300 S 5 13 57 140 .97 20 332 SSW 2 25 49 115 125 22 338 SW 7 24 67 102 84. 18 302 WSW 3 19 42 73 37 8 182 W 5 20 47 55 35 .2 164 WNW 4 18 -63 136 93 13 327 NW 6 15 71 172 141 12 417 NNW 3 27 86 244 198 17 575 VAR 0 0 0 -0 ' ' 0 0 0 Total Hours This Class: 4433 Hours of Calm This Class: 44 Percent of All Data This Class: 26.77 I/plr
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-B TITLE: APPENDIX B Revision 1 Page 18 of 21 Table 14 Monticello Nuclear Generating Plant Site Meteorology Stability Class F, Table 14 Monticello Nuclear Generating Plant Site Meteorology - Stability Class F, Elevation 100 Meters Frequency Distribution Tables, Hours at each Wind Speed and Direction Period of record: 9-1-76 through 8-31-78 Wind Speed (mph) at 100 Meter Level Direction 1 to 3 4 to 7 8 to 12 13 to 18 19 to 24 Above 24 Total' N 3 12 28 45 28 0 116 NNE 2 4 15 39 16 1 77 NE 4 7 23 49 17 1 101 ENE 1 7 19 40 6 3 76 E 4 10 26 15 3 0 58 ESE 8 16 28 31 14 2 99 SE 2 7 28 46 19 5 107 SSE 2 8 25 62 40 1 138 S 1 12 30 60 36 1 140 SSW 1 11 28 58 57 4 159 SW 3 14 19 75 33 2 146 WSW 5 6 22 28 29 0 90 W 1 14 22 27 16 0 80 WNW 4 10 44 49 27 1 135 NW 4 12 37 87 29 0 169 NNW 4 14 38 51 21 1 129 VAR 0 0 0 0 0 0 0 Total Hours This Class: 1826 Hours of Calm This Class: 6 Percent of All Data This Class: 11.03 I/plr
- 1 MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-B TITLE: APPENDIX B Revision 1 Page 19 of 21 Table 15 Monticello Nuclear Generating Plant Site Meteorology Stability Class G, Table 15 Monticello Nuclear Generating Plant Site Meteorology - Stability Class G, Elevation 100 Meters Frequency Distribution Tables, Hours at each Wind Speed and Direction Period of record: 9-1 -76 through 8-31 -78 Wind Speed (mph) at 100 Meter Level Direction 1 to 3 4 to 7 8 to 12 13 to 18 19 to 24 Above 24 Total N 6 8 16 9 0 0 39 NNE 3 : 1 12 15 8 1 0 39 NE -4 6 11 16 4 0 41 ENE 6 11 15 11 3. 1 47 E 8 7 11 11 1 0 38 ESE 1 12 9 16 2 0 40 SE 5 9 10 5 9 1 39 SSE 6 6 12 .8 11 1 44 S 2 6 13 30 12. 1 64 SSW 1 14 26 55 21 0 117 SW 1 9 21 26 25 3 85 WSW 5 16 29 16 14 0 80 W 3 14 8 16 18 2 61 WNW 5 15 23 21 9 0 73 NW 2 7 14 17 1 0 41 NNW 8 13 21 7 5 0 54 VAR 0 0 0 0 0 0 0 Total Hours This Class: 904
- Hours of Calm This Class: 2 Percent of All Data This Class: 5.46 I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-B TITLE: APPENDIX B Revision 1 Page 20 of 21 Table 16 Monticello Nuclear Generating Plant Site Meteorology - All Classes Combined Elevation 100 Meters Frequency Distribution Tables, Hours at each Wind Speed and Direction Period of record: 9-1-76 through 8-31-78 Wind Speed (mph) at 100 Meter Level Direction 1 to 3 4 to 7 8 to 12 13 to 18 19 to 24 Above 24 Total N 27 101 239 387 257 95 1106 NNE 25 94 191 259 109 20 698 NE 28 90 203 230 68 11 630 ENE 25 99 248 240 99 25 736 E 34 121 242 165 59 8 629 ESE 31 121- 230 220 101 47 750 SE 33 120 240 325 160 40 918 SSE 23 135 285 385 281 54 1163 S 24 113 244 411 251 46 1089 SSW 18 148 259 425 318 103 1271 SW 25 128 233 321 191 40 938 WSW 29 117 200 205 116 22 689
-W 20 107 194 196 113 24 654 WNW 30 108 301 419 232 - 93 1183 NW 22 97 331 709 527 173 1859 NNW 29 110 346 695 608 257 2045 VAR 0 0 0 '0 0 0 0 I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-B TITLE: APPENDIX B Revision 1 Page 21 of 21 Table 16 Monticello Nuclear Generating Plant Site Meteorology - All Classes Combined Elevation 100 Meters (cont'd)
Frequency Distribution Tables, Hours at each Wind Speed and Direction Period of record: 9-1-76 through 8-31-78 Data Recovery for the Period Total Hours: 17520 Hours of Calm: 201 Hours of Bad Data: 961 Percent Data Recovery: 94.51 Percent Acceptable Observations in each Stability Class Class A 2.95 Class B 3.64 Class C 6.29 Class D 43.87 Class E 26.77 Class F 11.03 Class G 5.46 Average Wind Speed for each Wind Category 1 to3MPH 2.5 4 to 7 MPH 5.8 8 to 12 MPH 10.1 13 to 18 MPH 15.4 19to24 MPH 20.9 Above 24 MPH 28.1 I/plr
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-C TITLE: APPENDIX C Revision 0 Page 1 of 5 OFFSITE DOSE.CALCULATION MANUAL - TABLE OF CONTENTS SECTION PAGE 1.0 RECORD OF REVISION ............................................... 2 Table 1 Parameters for Cow and Goat Milk Pathways .......................... 3 Table 2 Parameters for the Cow Meat Pathway ............................... 4 Table 3 Parameters for the Vegetable Pathway ................................. 5 Prepared By:
Reviewed By: ,_ _
OC Final Review Meetin: Date:
Approved By Plant Manager: 7 z- Date: /<! .
3087 (DOCUMENT CHANGE, HOLD, AND COMMENT FORM) incornorated IJ I Resp Supv: CHEM lAssoc Ref: CHEM-I l 110R: N lFreq: yrs ARMS: ODCM-APP-C Doc Type: 7030 lAdmin Initials: \ I IDate I/pir
MONTICELLO NUCLEAR GENERATING PLANT I ODCM-APP-C I - -
I TITLE: APPENDIX C I Revision 0 I0 I Page 2 of 5 I 1.0 RECORD OF REVISION Revision No. Date Reason for Revision 0 October - 2000 Moved previous ODCM-1 0.01 tables of parameters to this document.
I/pir
MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-C TITLE: APPENDIX C Revision 0
. -- -- Page 3 of 5 Table 1 Parameters for Cow and Goat Milk Pathways Reference in Parameter Value - Reg. Guide 1.109 Rev. 1 QF (kg/day) 50 (cow) Table E-3 6 (goat) Table E-3 tf (seconds) 1.73 X 05 (2 days) Table E-15 r 1.0 (radioiodines) Table E-15 0.2 (particulates) Table E-15 (DFLj)a (mrem/pCi) Each radionuclide Table E-11 to E-14 Fm (pCi/day per pCi/liter) Each stable element Table E-1 (cow)
Table E-2 (goat) tb (seconds) 4.73 X 108 (15 yr) Table E-15 Y,(kg/m2 ) 2.0 Table E-15 Yp (kg/M2 ) .75 Table E-15 th (seconds) 7.78 X 106 (90 days) Table E-1 5 Uap (liters/yr) 330 infant Table E-5 330 child Table E-5 400 teen Table E-5 310 adult Table E-5 tep (seconds) 2.59 X 106 (pasture) Table E-15 tes (seconds) 5.18 X 106 (stored feed) Table E-15 Biv (pCi/kg (wet weight) Each stable element Table E-1 per pCi/kg (dry soil))
P (kg dry soil/M2 ) 240 Table E-1 5 I/plr
m
- 1 MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-C TITLE: APPENDIX C Revision 0 Page 4 of 5 Table 2 Parameters for the Cow Meat Pathway Reference in Parameter Value Reg. Guide 1.109 Rev. 1 1.0 (radiolodines) r 1.0 (radioiodines) Table E-15 0.2 (particulates) Table E-15 Ff (pCi/kg per pCi/day) Each stable elemient Table E-1 Uap (kg/yr) 0 infant Table E-5 41 child Table E-5 65 teen Table E-5
-110 adult Table E-5 (DFLi)a (mrem/pCi) Each radionuclide Table E-11 to E-14 Yp (kg/M2 ) 0.7 Table E-15 Ys(kg/m 2 ) 2.0 Table E-1 5 tb (seconds) 4.73 X 1 8 (15 yr) Table E-1 5 ts (seconds) 1.73 X 106 (20 days) Table E-15 th (seconds) 7.78 X 106 (90 days) Table E-15 tep (seconds) 2.59 X 106 (pasture) Table E-15 tes (seconds) 5.18 X 106 (stored feed) Table E-1 5 QF (kg/day) 50 Table E-3 Biv (pCi/kg (wet weight) Each stable element Table E-1 per pCi/kg (dry soil))
P (kg dry soil/m2 ) 240 Table E-15 I/pir
II MONTICELLO NUCLEAR GENERATING PLANT ODCM-APP-C TITLE: APPENDIX C Revision 0 Page 5 of 5 EMEMENOMMMMMS Table 3 Parameters for the Vegetable Pathway Reference in Parameter Value Reg. Guide 1.109 Rev. 1 r (dimensionless) 1.0 (radioiodines) Table E-1 0.2 (particulates) Table E-1 (DFLi)a (mrem/Ci) Each radionuclide Tables E-11 to E-14 ULa (kg/yr) 0 Infant Table E-5 26 Child Table E-5 42 Teen Table E-5 64 Adult Table E-5 USa (kg/yr) 0 Infant Table E-5 520 Child Table E-5 630 Teen Table E-5 520 Adult Table E-5 tL (seconds) 8.6 X 104 (1 day) Table E-15 th (seconds) 5.18 X 106 (60 days) Table E-15 Yv (kg/m2) 2.0 Table E-15 te (seconds) 5.18 X 106 (60 days) Table E-1 5 tb (seconds) 4.73 X 108 (15 yr) Table E-1 5 P (kg/(dry soil)/m2) 240 Table E-15 Biv (pCi/kg(wet weight) Each stable element Table E-1 per pCi/kg (dry soil))
I/pir