TABLE 3.3.2-2 (Continued)

ISOLATION ACTUATION INSTRUMENTATION SETPOINTS TRIP FUNCTION

3.

REACTOR WATER CLEANUP SYSTEM ISOLATION

a.

RWCS A Flow - High

b.

RWCS Area Temperature - High

c.

RWCS Area Ventilation A Temperature - High

d.

SLCS Initiation

e.

Reactor Vessel Water Level

Low, Low, - Level 2
f.

Manual Initiation

4.

HIGH PRESSURE COOLANT INJECTION SYSTEM ISOLATION

a.

HPCI Steam Line A Pressure - High

b.

HPCI Steam Supply Pressure - Low

c.

HPCI Turbine Exhaust Diaphragm Pressure - High

d.

HPCI Equipment Room Temperature - High

e.

HPCI Equipment Room A Temperature - High

f.

HPCI Pipe Routing Area Temperature - High

g.

Manual Initiation

h.

HPCI Steam Line A Pressure - Timer LIMERICK - UNIT 1 TRIP SETPOINT

< 54.9 gpm

< 1550F or < 132 0F**

< 52°F or < 320F**

N.A.

> -38 inches

  • N.A.

< 974" H20

100 psig
  • 10 psig 225oF

< 1260F 175oF N.A.

3 T -< 12.5 seconds 3/4 3-19 ALLOWABLE VALUE

< 65.2 gpm S160°F or

  • 1370F**

S60°F or

  • 400F**

N.A.

> -45 inches N.A.

< 984" H20

> 90 psig

  • 20 psig

> 2180F, < 247oF

< 130.5°F

' 1650F, < 20OoF N.A.

2.5 <!9 < 13 seconds Amendment No. 34, 8-5, 4-06, 161

TABLE 3.3.2-2 (Continued)

ISOLATION ACTUATION INSTRUMENTATION SETPOINTS TRIP FUNCTION

3.

REACTOR WATER CLEANUP SYSTEM ISOLATION

a.

RWCS A Flow - High

b.

RWCS Area Temperature - High

c.

RWCS Area Ventilation A Temperature - High

d.

SLCS Initiation

e.

Reactor Vessel Water Level

Low, Low, - Level 2
f.

Manual Initiation

4.

HIGH PRESSURE COOLANT INJECTION SYSTEM ISOLATION

a.

HPCI Steam Line A Pressure - High

b.

HPCI Steam Supply Pressure - Low

c.

HPCI Turbine Exhaust Diaphragm Pressure - High

d.

HPCI Equipment Room Temperature - High

e.

HPCI Equipment Room A Temperature - High

f.

HPCI Pipe Routing Area Temperature - High

g.

Manual Initiation

h.

HPCI Steam Line A Pressure - Timer

s 54.9 gpm

< 155 0F or : 132°F**

< 520F or < 32°F**

N.A.

> -38 inches

  • N.A.

_< 974" H20

_> 100 psig

_< 10 psig 2250F

< 126 0F 1750F N.A.

3 _< T < 12.5 seconds LIMERICK - UNIT 2 TRIP ýElPUINI ALLOWABLE VALUE

_< 65.2 gpm

< 160°F or < 137*F**

< 60°F or < 40 0F**

N.A.

> -45 inches N.A.

< 984" H20

  • 90 psig
s 20 psig

> 218 0F, < 247 0F

_< 130.5 0F

> 165 0 F, < 200°F N.A.

2.5 _: T :s 13 seconds Amendment No. 46, ---,123 I

I 3/4 3-19