ML022380309

From kanterella
Jump to navigation Jump to search
Emergency Plan Implementing Procedures Manual Volume B, Revision 2002-07
ML022380309
Person / Time
Site: Oconee  Duke Energy icon.png
Issue date: 08/21/2002
From: Mccollum W
Duke Energy Corp
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
Download: ML022380309 (77)


Text

P Duke Duke Energy

Energv Oconee Nuclear Station 7800 Rochester Highway Seneca, SC 29672 (864) 885-3107 OFFICE W. R McCoru, Jn (864) 885-3564 FAX Vice President August 21, 2002 U.

S. Nuclear Regulatory Commission Document Control Desk Washington, D. C.

20555

Subject:

Oconee Nuclear Station Docket Nos.

50-269, -270,

-287 Emergency Plan Implementing Procedures Manual Volume B, Revision 2002-07 Please find attached for your use and review copies of the revision to the Oconee Nuclear Station Emergency Plan:

Volume B Revision 2002-07 August 2002 This revision is being submitted in accordance with 10 CFR 50-54(q) and does not decrease the effectiveness of the Emergency Plan or the Emergency Plan Implementing Procedures.

Any questions or concerns pertaining to this revision please call Rodney Brown, Emergency Planning Manager at 864-885-3301.

By copy of this letter, two copies of this revision are being provided to the

NRC, Region II, Atlanta, Georgia.

Very truly yours, W. R. McCollum, VP, Oconee Nuclear Site xc:

(w/2 copies of attachments)

Mr. Luis Reyes, Regional Administrator, Region II U.

S. Nuclear Regulatory Commission 61 Forsyth St., SW, Suite 24T23 Atlanta, Georgia 30303 w/copy of attachments Mr.

Steven Baggett Rockville, Maryland (w/o Attachments, Oconee Nuclear Station)

NRC Resident Inspector M. D. Thorne, Manager, Emergency Planning AoL5

August 21, 2002 OCONEE NUCLEAR SITE

SUBJECT:

Emergency Plan Implementing Procedures Volume B, Revision 2002-07 Please make the following changes to the Emergency Plan, Volume B by following these instructions.

REMOVE Cover Sheet Rev. 2002-06 Table of Contents page 1 Table of Contents page 2 CP/1&2/A/2002/005 -

(12/13/01)

CP/3/A/2002/005 -

(12/13/01)

Chemistry Manual 5.1 -

(04/16/02)

Chemistry Manual 5.2 -

(04/11/02)

ADD Cover Sheet Rev. 2002-07 Table of Contents page 1 Table of Contents page 2 CP/1&2/A/2002/005 -

(07/24/02)

CP/3/A/2002/005 -

(07/24/02)

Chemistry Manual 5.1 -

(07/29/02)

Chemistry Manual 5.2 -

(07/29/02)

DUKE POWER EMERGENCY PLAN IMPLEMENTING PROCEDURES VOLUME B APPROVED:

eVwX.

oserVMnae W. IV. Foster, Manager Safety Assurance August 21. 2002 Date Approved August 21, 2002 Effective Date VOLUME B REVISION 2002-07 AUGUST 2002

Chemistry Lab LM-O-P003C Chemistry Lab LM-O-P919 CP/l/A/2002/004C CP/1 &2/A/2002/005 CP/2/A/2002/004C CP/3/A/2002/004C CP/3/A/2002/005 HPIOIB/10091009 HP10B/10091012 HPIO/B/1009/015 HP/OJB/1009/016 HP/I/A/1009/017 HP/2/A/1009/017 HP/3/A/1009/017 RP/O/B/10000O 11 RP/0/B/1000/025 RP/O/B/1000/027 VOLUME B TABLE OF CONTENTS Determination Of Boron By Manual Colorimetric Titration Boron Analysis by Mettler DL 58 Boron Titration Operating Procedure For The Post Accident Liquid Sampling System (PALSS)

Post Accident Caustic Injection Into The Low Pressure Injection System Operating Procedure For The Post Accident Liquid Sampling System (PALSS)

Operation Procedure For The Post-Accident Liquid Sampling System (PALSS)

Post Accident Caustic Injection Into The Low Pressure Injection System Procedure For Determining The Inplant Airborne Radioiodine Concentration During Accident Conditions Distribution Of Potassium Iodide Tablets In The Event Of A Radioiodine Release Procedure For Sampling And Quantifying High Level Gaseous Radioiodine And Particulate Radioactivity Procedure For Emergency Decontamination Of Personnel And Vehicles On-Site And From Off-Site Remote Assembly Area Operating Procedure For Post-Accident Containment Air Sampling System Operating Procedure For Post-Accident Containment Air Sampling System Operating Procedure For Post-Accident Containment Air Sampling System Planned Emergency Exposure Operational Support Center Manager Procedure Re-Entry Recovery Procedure 11/18/96 07/18/02 01/08/02 07/24/02 01/08/02 01/08/02 07/24/02 12/03/97 01/09/01 07/23/01 12/29/97 09/13/00 09/13/00 09/13/00 02/01/94 03/20/02 05/30/00 Revision 2002-07 August 2002 1

Chemistry Manual 5.1 Chemistry Manual 5.2 Maintenance Directive 9.1 Maintenance Directive 9.2 OMP 1-7 Radiation Protection Manual 11.1 Radiation Protection Manual 11.4 Safety Services Procedure 2.1 Revision 2002-07 August, 2002 2

VOLUME B TABLE OF CONTENTS Emergency Response Guidelines Post Accident Procedure Use Guidelines Emergency Preparedness Plan Activation Emergency Plan For Members Of The Work Control Group Operations Emergency Response Organization Radiation Protection Emergency Response Radiation Protection Site Assembly Safety Services Emergency Response Procedure 2.1 07/29/02 07/29/02 02/25/02 12/19/00 08/31/00 09/01/98 06/05/00 03/14/00

(r04 01)

Duke Power Company (1) ID No CP/1 &2/A/2002/005 PROCEDURE PROCESS RECORD Revsio. No.

17

'-PREZPARATION INFORMATION ONLY Continuous Use (2)

Station Oconee Nuclear Station (3)

Procedure Title Post Accident Caustic Injection into the Low Pressure Iniection System (4)

Prepared By 147-

/,

/,7/,r'q--iV' Date-2-

2/0-2 (5)

Requires NSD 228 Applicability Determination?

El Yes (New procedure or revision with major changes) 6"No (Revision with minor changes)

El No (To inco rate previously approved changes)

(6)

Reviewed By ____(QR)

Date Cross-Disciplinary Review By (QR) NA.,ý Date Reactivity Mgmt. Review By (QR) NA fj_

Date Mgmt. Involvement Review By (Ops. Supt.) NA if-4-- Date (7)

Additional Reviews QA Review By Date Reviewect By Date Reviewed By Date

.8)

Temporazy Approval (if necessary)

By (OSMIQR)

Date By (QR)

Date (9)

Approved By 2Date c

tI PERFORMANCE (compare w I control copy every 14 calendar days while work is being performed.)

(10)

Compared with Control C py Date Compared with Control Copy Date Compared with Control Copy_

Date (11)

Date(s) Performed Work Order Number (WOft)

COMPLETION (12)

Procedure Completion Verification El Yes El NA Check lists and/or blanks initialed, signed, dated, or filled in NA, as appropriate" El Yes El NA Required enclosures attached?

El Yes El NA Data sheets attached, completed, dated, and signed?

El Yes El NA Charts. graphs, etc attached, dated, identified, and matked" El Yes El NA Procedure IcquCmemCnts MtC?

'cri [Ied By

_......_"1).at "13) lPIoccdue (Complettoll [)l(m,(I l)

K I-, ~llI '

ta*.di~dp',*

/(****.

cP/1 &2/A/2oo0005 Page 2 of 7 Post Accident Caustic Injection into the Low Pressure Injection System NOTE:

1. This entire procedure supports an AP or EOP action. The procedure will require AP/EOP validation per NSD 705.
2. A control copy of this procedure shall be routed to the Emergency Preparedness Team within 3 working days after any approved changes.
1. Purpose 1.1 This procedure is to provide instruction for determining the amount and method of caustic addition into the LPI System during a LOCA.

1.2 Principle Caustic is injected into the LPI System during a LOCA to neutralize the borated water used in the Reactor Building Emergency Spray System to pH 7.0 - 8.0.

The neutralization will inhibit the generation* of hydrogen gas and promote a higher partition factor for iodine.

2. Limits and Precautions 0I 2.1 The following safety equipment shall be worn when connecting/disconnecting caustic tote bins:

2.1.1 Chemical goggles 2.1.2 Face shield 2.1.3 Corrosive resistant suit, neoprene or chemrel 2.1.4 Corrosive resistant boots, neoprene or PVC 2.1.5 Corrosive resistant gloves, neoprene or PVC 0I 2.2 Chemical hazards shall be known prior to use. For additional information refer to the MSDS sheets.

0I 2.3 Under accident conditions, valve alignments shall NOT be made and injection shall NOT begin without prior authorization from the Operations Emergency Coordinator OR the Technical Support Center (TSC)/Operational Support Center (OSC)!

cP/1&2/A/2002/005 Page 3 of 7 NOTE:

An initial caustic add of 15 inches will neutralize an RCS inventory of 80,000 gallons with a boron concentration of 1800 ppm. This is a conservative initial add to allow immediate response to a large break LOCA.

LI 2.4 An initial caustic add of 15 inches can be made without performing CSM 5.2, Enclosure 6.3 (Caustic Addition Calculations).

0l 2.5 In the event of a caustic spill, call 4911.

0I 2.6 ITS 5.4.1.a and SLC 16.13.7 require that pH be measured AND that the addition of caustic to Reactor Coolant commence within 30 minutes AFTER switchover to Recirculation Mode of Core Cooling to adjust the pH to a range of 7.0 to 8.0 WiTHIN 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

During recirculation mode, long-term core cooling is provided by injection of water from the Reactor Building Emergency Sump to the core by the Low Pressure Injection (LPI) pumps (1 LP-19 & 20 or 2 LP-19 & 20 are open). Switchover to recirculation mode is accomplished with minimal level in the BWST.

LI 2.7 Safety and caustic addition equipment is stored in the brown storage container located in the Auxiliary Building, Unit 1 & 2 Chemical Addition Area.

LI 2.8 Keys to the brown storage container are stored with the caustic addition procedures in the OSC Chemistry Emergency Procedure Files and in the filing cabinet located in the Primary Chemistry lab office. All personnel in Primary Chemistry and Radwaste have also been issued individual keys.

LI 2.9 Power to the caustic addition pump is provided through 1XL located near the LPI hatch area.

For power supply diagram, see Enclosure 5.6.

3. Procedure 3.1 Upon notification from Operations Emergency Coordinator OR TSC / OSC take the following actions to align the caustic addition system to the appropriate unit:

NOTE:

The following steps may be performed simultaneously to conserve time.

LI Verify eyewash station and safety shower operable.

El Mark the current liquid level directly on the translucent tote bin container.

LI Measure down from the liquid level mark 15 inches and mark this level directly on the tote bin.

cP/1&2/A/2002/005 Page 4 of 7 El IF necessary, move the tote bin into position.

"El Remove dust cover from swagelock fitting on tote bin.

"El Remove dust cover from swagelock fitting at CA-36 (Caustic Pump Suction Tell Tale) (Bottom of 1&2 Caustic Mix Tank downstream of CA-35, Elev 783).

El 3.1.1 For Unit 1 only, make valve alignments per Enclosure 5.1 to allow caustic injection into the Low Pressure Injection (LPI) pump suction on Unit 1.

El 3.1.2 For Unit 2 only, make valve alignments per Enclosure 5.2 to allow caustic injection into the Low Pressure Injection (LPI) pump suction on Unit 2.

NOTE:

Protective clothing shall be wom prior to Step 3.1.3.

El 3.1.3 Connect stainless steel flex hose to the Swagelock quick-connect fitting upstream of CA-36 (Caustic Pump Suction Tell Tale) (Bottom of 1&2 Caustic Mix Tank downstream of CA-35, Elev. 783).

El 3.1.4 Connect stainless steel flex hose to the Swagelock fitting on tote-bin.

El 3.1.5 Vent the caustic tote bin by removing the tote bin fill cap.

El 3.1.6 Open the caustic tote bin outlet valve.

El 3.1.7 Notify Operations OR the OSC (if activated) that valve alignments for caustic injection are complete and ready to be initiated.

Person contacted Date/Time I

NOTE:

Use low dose waiting area as possible during addition.

El 3.1.8 WHEN notified by Operations, start the caustic addition pump at maximum flow setting. The caustic pump switch is located on the Chemical Addition Control Panel. The maximum pump capacity is approximately 2 gallons per minute.

El 3.1.9 Notify Operations OR the OSC (if activated) that caustic injection has begun.

Person contacted Date/Time

cP/l&2/A/2002/005 Page 5 of 7 NOTE:

The caustic pump has an average pump rate of 1.2 gallons per minute. To pump the initial setting of 15 inches will require 1.5 hours5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br />.

El 3.1.10 Calculate the total amount of caustic (in gallons) to be added for the neutralization of the borated water added to the system by using CSM 5.2 (Enclosure 6.3).

El 3.1.11 Convert gallons from Step 3.1.10 to inches (in the 350 gallon tote bin) by dividing the number of gallons to be added by 8.1. Record the values below:

Gallons to be added Inches to be added from the tote bin El 3.1.12 Mark the calculated liquid level directly on the tote bin by measuring down from the original "current liquid level" mark made in Step 3.1.

El 3.1.13 WHEN the caustic tote bin level reaches the desired level (as marked in Step 3.1)

OR WHEN the caustic tote bin is empty, STOP caustic addition pump using the switch located on the Chemical Addition Control Panel.

El 3.1.14 Close tote bin outlet valve.

El 3.1.15 Close CA-36 (Caustic Pump Suction Tell Tale) (Bottom of 1&2 Caustic Mix Tank downstream of CA-35, Elev 783).

El 3.1.16 Record time and volume added on Enclosure 5.5.

El 3.1.17 IF necessary, replace the caustic tote bin as follows:

"El 3.1.17.1 Replace tote bin fill cap.

"El 3.1.17.2 Disconnect empty tote bin from swagelock fitting on stainless flex hose.

"El 3.1.17.3 IF necessary, move tote bins and remove dust cover from swagelock fitting on new tote bin.

El 3.1.17.4 Connect stainless flex hose to the new tote bin.

El 3.1.17.5 IF pumping is to continue, mark the tote bin per Section 3.1 for the amount to be added from the new tote bin and go to Step 3.1.5.

El 3.1.18 Notify OSC that caustic addition to the LPI is complete and no further additions are in progress at this time.

Person contacted Date/Time El 3.1.19 After caustic addition is complete, allow LPI recirculation time of at least 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />.

cP/1&2/A/2002/005 Page 6 of 7 El 3.1.20 WHEN authorized by the TSC/OSC, collect sample (per appropriate procedure) to determine the resultant pH of the reactor coolant.

El 3.1.21 IF pH is < 7.0,

"* Calculate (refer to CSM 5.2, Enclosure 6.3) the amount of caustic (in gallons) to be added to complete the neutralization of the borated water-added to the system.

"* Convert this number to inches (in the 350 gallon tote bin) by dividing the number of gallons to be added by 8.1 gallons/inch.

"* Record the values below:

Gallons to be added:

Inches to be added from tote bin:

El 3.1.22 IF pH is > 7.0, go to Step 3.1.26.

El 3.1.23 Mark the current liquid level directly on the translucent tote bin container.

E0 3.1.24 Measure down from this mark the number of inches calculated in Step 3.1.21 above. Mark this level directly on the tote bin.

El 3.1.25 Repeat Steps 3.1.1 through 3.1.22 until all necessary caustic (as determined by TSC/OSC) has been added.

El 3.1.26 After all necessary caustic has been added and upon authorization from the TSC/OSC, return the system to normal as follows:

0l 3.1.26.1 Replace tote bin fill cap.

0l 3.1.26.2 Disconnect empty tote bin from swagelock fitting on stainless flex hose.

El 3.1.26.3 For Unit 1 only, make alignments per Enclosure 5.3 to return valves to normal position.

El 3.1.26.4 For Unit 2 only, make alignments per Enclosure 5.4 to return valves to normal position.

CP/1&2/A/2002/005 Page 7 of 7

4. References 4.1 Dwg. No. OFD-1 1OA-1.8 Chemical Addition System (Primary Side Chemical Addition) 4.2 Dwg. No. OFD-102A-1.1 and OFD-102A-2.1 Low Pressure Injection System, Borated Water Supply and LPI Pump Suction.

4.3 CSM 5.2 4.4 ITS 5.4.1.a 4.5 SLC 16.13.7

5. Enclosures 5.1 Valve Alignment for Caustic Injection on Unit 1 5.2 Valve Alignment for Caustic Injection on Unit 2 5.3 Normal Valve Alignment for Caustic Injection System on Unit 1 5.4 Normal Valve Alignment for Caustic Injection System on Unit 2 5.5 Caustic Mixing and Injection Record 5.6 Unit 1&2 Caustic Pump Power Supplies

.1 Valve Alignment for Caustic Injection on Unit 1 cP/ &2/A/2002/oo5 Page 1 of 1 NOTE:

This enclosure is AP[EOP related.

Date DV Init Position Valve No.

Valve Name Location Closed 2CA-98 Caustic to Unit #2 LPI Unit 1&2 LPI Hatch Area, AB Block (Chm)

Rm. 119, Elev 771, Col. T-74 Closed ICA-58 Caustic to Ul LPI Suct Tell Unit l&2 LPI Hatch Area, AB, Tale (Chm)

Elev 771, Col. T-72 Open 1CA-39 Caustic to Unit #1 LPI Unit 1&2 LPI Hatch Area, AB Block (Chm)

Rm 118, Elev 771, Col. T-72 Open 1CA-62 Caustic to Unit #1 LPI Unit 1&2 LPI Hatch Area, AB Block (Ops)

Rm. 119, Elev 771, Col. T-72 Open 1LP-51 LPI Sample Recirc Isolation Unit 1&2 LPI Hatch Area, AB (Ops)

Rm. 061, Elev 771, Col. T-71 Open CA-103 Caustic Recirc Line and Downstream of 1&2 Caustic Press Gauge Block Pump and CA-37, Elev 783, Col. Q-67 Closed CA-96 Caustic Recirc Block Recirc Line tapping off between CA-103 & CA-1 12 returning to Caustic Mix Tank, Elev 783 Closed CA-35 Caustic Pump Suction Next valve after CA-34 Tank and upstream of Caustic Pump, Elev 783 Closed CA-37 Caustic Header to Waste AB Hallway, Elev 783, near Col.

Evap. Feed Tank Block P-74, 6 ft. overhead Open CA-112 Caustic Pump Press Gauge First valve downstream of Isol PG-27 (Pressure Gauge) behind Caustic Mix Tank on West Wall, Elev 783 Open CA-36 Caustic Pump Suction Tell Bottom of l&2 Caustic Mix Tale Tank downstream of CA-35, Elev 783

.2 Valve Alignment for Caustic Injection System on Unit 2 cP/1&2/A/2002/005 Page 1 of 1 NOTE:

This enclosure is AP/EOP related.

Date DV Init Position Valve No.

Valve Name Location Closed 1CA-39 Caustic to Unit #1 LPI Block Unit 1&2 LPI Hatch Area, AB (Chmi)

Rm 118, Elev 771, Col. T-72 Closed 2CA-58 Caustic to #2 LPI Pump Suct Unit 1&2 LPI Hatch Area, AB Tell Tale (Chin)

Rm 119, Elev 771, Col. T-74 Open 2CA-98 Caustic to Unit #2 LPI Block Unit 1&2 LPI Hatch Area, AB (Chm)

Rim 119, Elev 771, Col. T-74 Open 2CA-63 Caustic to Unit #2 LPI Block Unit 1 &2 LPI Hatch Area, AB (Ops)

Rrn 119, Elev 771, Col. T-74 Open 2LP-51 LPI Sample Recirc Isolation Unit 1&2 LPI Hatch Area, AB (Ops)

Rm. 063, Elev 771, Col. T-71 Open CA-103 Caustic Recirc Line and Press Downstream of 1&2 Caustic Gauge Block Pump and CA-37, Elev 783, Col. Q-67 Closed CA-96 Caustic Recirc Block Recirc Line tapping off between CA-103 & CA-112 returning to Caustic Mix Tank, Elev 783 Closed CA-35 Caustic Pump Suction Next valve after CA-34 Tank and upstream of Caustic Pump, Elev 783 Closed CA-37 Caustic Header to Waste Evap.

AB Hallway, Elev 783, near Col.

Feed Tank Block P-74, 6 ft. overhead Open CA-112 Caustic Pump Press Gauge Isol First valve downstream of PG-27 (Pressure Gauge) behind Caustic Mix Tank on West Wall, Elev 783 Open CA-36 Caustic Pump Suction Tell Tale Bottom of 1&2 Caustic Mix Tank downstream of CA-35, Elev 783

.3 Normal Valve Alignment for Caustic Injection System on Unit 1 cP/l&2/A/2oo2uoo5 Page 1 of 1 I NOTE:

This enclosure is AP/EOP related.

Date DV Init Position Valve No.

Valve Name Location Closed 2CA-98 Caustic to Unit #2 LPI Block Unit 1&2 LPI Hatch Area, AB (Chm)

Rm. 119, Elev 771, Col. T-74 Closed 2CA-63 Caustic to Unit #2 LPI Block Unit 1&2 LPI Hatch Area, AB (Ops)

Rm. 119, Elev 771, Col. T-74 Closed ICA-58 Caustic to Ul LPI Suct Tell Unit 1&2 LPI Hatch Area, AB, Tale (Chm)

Elev 771, Col. T-72 Closed 1CA-39 Caustic to Unit #1 LPI Block Unit 1&2 LPI Hatch Area, AB (Chm)

Rm 118, Elev 771, Col. T-72 Closed 1CA-62 Caustic to Unit #1 LPI Block Unit 1&2 LPI Hatch Area, AB (Ops)

Rm. 119, Elev 771, Col. T-72 Closed 1LP-51 LPI Sample Recirc Isolation Unit 1 &2 LPI Hatch Area, AB (Ops)

Rm. 061, Elev 771, Col. T-71 Open CA-103 Caustic Recirc Line and Downstream of 1&2 Caustic Press Gauge Block Pump and CA-37, Elev 783, Col. Q-67 Open CA-97 Caustic Recirc Block Downstream of CA-96 and upstream of DW-120 on Caustic Mix Tank Recirc Line, Elev 783 Open CA-96 Caustic Recirc Block Recirc Line tapping off between CA-103 & CA-112 returning to Caustic Mix Tank, Elev 783 Closed LWD-267 Caustic Tank Outlet Drain Base of Caustic Mix Tank West Side, Elev 783 Closed CA-34 Caustic Mix Tank Outlet First valve from bottom of Caustic Mix Tank and upstream of Caustic Pump, Elev 783 Col. Q-68 Closed CA-35 Caustic Pump Suction Next valve after CA-34 Tank and upstream of Caustic Pump, Elev 783 Closed CA-37 Caustic Header to Waste AB Hallway, Elev 783, near Col.

Evap. Feed Tank Block P-74, 6 ft. overhead Open CA-1 12 Caustic Pump Press Gauge First valve downstream of Isol PG-27 (Pressure Gauge) behind Caustic Mix Tank on West Wall, Elev 783 Closed CA-36 Caustic Pump Suction Tell Bottom of 1&2 Caustic Mix Tank I _

Tale downstream of CA-35, Elev 783

.4 Normal Valve Alignment fori Caustic Injection System on Unit 2 CP/1&2/A/2002/005 Page 1 of 1 NOTE:

This enclosure is AP/EOP related.

I Date DV Init Position Valve No.

Valve Name Location Closed 1CA-39 Caustic to Unit #1 LPI Block Unit 1&2 LPI Hatch Area, AB (Chm)

Rm 118, Elev 771, Col. T-72 Closed ICA-62 Caustic to Unit #1 LPI Block Unit 1&2 LPI Hatch Area, AB (Ops)

Rm. 119, Elev 771, Col. T-72 Closed 2CA-58 Caustic to #2 LPI Pump Suct Unit 1&2 LPI Hatch Area, AB Tell Tale (Chmn)

Rm 119, Elev 771, Col. T-74 Closed 2CA-98 Caustic to Unit #2 LPI Block Unit 1&2 LPI Hatch Area, AB (Chm)

Rm. 119, Elev 771, Col. T-74 Closed 2CA-63 Caustic to Unit #2 LPI Block Unit 1&2 LPI Hatch Area, AB (Ops)

Rm. 119, Elev 771, Col. T-74 Closed 2LP-51 LPI Sample Recirc Isolation Unit 1 &2 LPI Hatch Area, AB (Ops)

Rm. 063, Elev 771, Col. T-71 Open CA-103 Caustic Recirc Line and Press Downstream of 1&2 Caustic Gauge Block Pump and CA-37, Elev 783, Col. Q-67 Open CA-97 Caustic Recirc Block Downstream of CA-96 and upstream of DW-120 on Caustic Mix Tank Recirc Line, Elev 783 Open CA-96 Caustic Recirc Block Recirc Line tapping off between CA-103 & CA-112 returning to Caustic Mix Tank, Elev 783 Closed LWD-267 Caustic Tank Outlet Drain Base of Caustic Mix Tank West Side, Elev 783 Closed CA-34 Caustic Mix Tank Outlet First valve from bottom of Caustic Mix Tank and upstream of Caustic Pump, Elev 783 Col. Q-68 Closed CA-35 Caustic Pump Suction Next valve after CA-34 Tank and upstream of Caustic Pump, Elev 783 Closed CA-37 Caustic Header to Waste Evap.

AB Hallway, Elev 783, near Feed Tank Block Col. P-74, 6 ft. overhead Open CA-112 Caustic Pump Press Gauge Isol First valve downstream of PG-27 (Pressure Gauge) behind Caustic Mic Tank on West Wall, Elev 783 Closed CA-36 Caustic Pump Suction Tell Tale Bottom of l&2 Caustic Mix Tank downstream of CA-35, Elev 783

.5 Caustic Mixing and Injection Record NOTE:

enclosure is I

related.

Date/Time of Injection cP/1&2/A/2002/oo5 Page 1 of I Gal NaOH

.6 Unit I & 2 Caustic Pump Powei Supplies 1TE2 cP/1& 2 /A/2002/005 Page 1 of 1 TE (4160) 4A 1X5 4AT (600 VOLT) 1XL 6D 1X6 3A 208 VOLT 1XL 5A Unit I & 2 CAUSTIC PUMP NOTE:

1. This enclosure is AP/EOP related.
2. Operations alternates the power logic as outlined. Verification will be required to establish which alignment is in use at the time of question.

1 TD2 TD (4160) 4A 5C I 2A 6D 1X6

.5 Caustic Mixing and Injection Record cP/1&2/A/2002/005 Page 1 of 1 NOTE:

This enclosure is AP/EOP related.

I Date/Time of Injection Gal NaOH

.6 Unit 1 & 2 Caustic Pump Power Supplies 1TE2 cP/1 &2/A/2002/005 Page 1 of I TE (4160) 4A 1X5 4AT (600 VOLT) IXL 6D 1X6 3A 208 VOLT 1XL 5A Unit 1 &2 CAUSTIC PUMP NOTE:

1. This enclosure is AP/EOP related.
2. Operations alternates the power logic as outlined. Verification will be required to establish which alignment is in use at the time of question.

1 TD2 TD (4160) 4A 5C I 2A

(R04, I)

Duke Power Company PROCEDURE PROCESS RECORD K-k-EPARATI (2)

Station (3)

Procedur INFORMATION ONLY

[ON Oconee Nuclear Station e Title Post Accident Caustic Injection into the Low Pressure Iniection System (4)

Prepared By

ýO/k

?&

077' Date 72 / 62 (5)

Requires NSD 228 Applicability Determination?

El Yes (New procedure or revision with major changes)

E*'

No (Revision with minor changes)

El No (To incorporate previously a proved changes)

(6)

Reviewed By __

(QR)

Date Cross-Disciplinary Review By _(QR)

NAA,1 Date Reactivity Mgmt. Review By _(QR)

NA.OA-Date Mgmt. Involvement Review By (Ops. Supt.) NAjZ&.,_ Date (7)

Additional Reviews QA Review By Date Reviewed By Date Reviewed By Date

)

Temporary Approval (if necessary)

By (OSM/QR)

Date By (QR)

Date (9)

Approved By.

Date PERFORMANCE (Compare w" h ontrol copy every 14 calendar days while work is being performed.)

(10) Compared with Control Copy Date Compared with Control Copy Date Compared with Control Copy_

Date (11)

Date(s) Performed Work Order Number (WO#)

COMPLETION (12)

Procedure Completion Verification El Yes El NA Check lists and/or blanks initialed, signed, dated, or filled in NA, as appropriate?

El Yes El NA Required enclosures attached?

El Yes El NA Data sheets attached, completed, dated, and signed?

El Yes El NA Charts, graphs, etc. attached, dated, identified, and marked?

El Yes El NA Procedure requirements met?

Verified By Date K_)

Procedure Completion Approved Date (14) Remarks (Attach additional pages, if necessary)

(1) ID No CP/3/A/2002/005 Revision No 15 Continuous Use

CP/3/A/2002/005 Page 2 of 7 Post Accident Caustic Injection into the Low Pressure Injection System NOTE:

1. This entire procedure supports an AP or EOP action. The procedure will require AP/EOP validation per NSD 705.
2. A control copy of this procedure shall be routed to the Emergency Preparedness Team within 3 working days after any approved changes.
1. Purpose 1.1 This procedure is to provide instruction for caustic addition into the LPI System during a Loss of Coolant Accident. (LOCA) 1.2 Principle Caustic is injected into the LPI System during a LOCA to neutralize the borated water used in the Reactor Building Emergency Spray System to pH 7.0 - 8.0.

The neutralization will inhibit the generation of hydrogen gas and promote a higher partition factor for iodine.

2. Limits and Precautions 0l 2.1 The following safety equipment shall be worn when connecting/disconnecting caustic tote bins:

2.1.1 Chemical goggles 2.1.2 Face shield 2.1.3 Corrosive resistant suit, neoprene or chemrel 2.1.4 Corrosive resistant boots, neoprene or PVC 2.1.5 Corrosive resistant gloves, neoprene or PVC El 2.2 Chemical hazards shall be known prior to use. For additional information, refer to the MSDS sheets.

El 2.3 Under accident conditions, valve alignments shall NOT be made and injection shall NOT begin without prior authorization from the Operations Emergency Coordinator OR the Technical Support Center (TSC) / Operational Support Center (OSC)!

CP/3/A/2002/005 Page 3 of 7 NOTE:

An initial caustic add of 15 inches will neutralize an RCS inventory of 80,000 gallons with a boron concentration of 1800 ppm. This is a conservative initial add to allow immediate response to a large break LOCA.

0l 2.4 An initial caustic add of 15 inches can be made without performing CSM 5.2,.3 (Caustic Addition Calculations).

0l 2.5 In the event of caustic spill, call 4911.

0l 2.6 ITS 5.4.1.a and SLC 16.13.7 require that pH be measured AND that the addition of caustic to Reactor Coolant commence within 30 minutes AFTER switchover to recirculation mode of core cooling to adjust pH to a range of 7.0 to 8.0 WITHIN 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.

During recirculation mode, long-term core cooling is provided by injection of water from the Reactor Building Emergency Sump to the core by the Low Pressure Injection (LPI) pumps (3 LP-19 and 3 LP-20 are open). Switchover to recirculation mode is accomplished with minimal level in the BWST.

El 2.7 Safety and caustic addition equipment is stored in the brown storage container located in the Auxiliary Building, Unit 1 & 2 Chemical Addition Area. The following equipment should be retrieved for Caustic Addition:

Chemical Goggles Tape Measure Face Shield Marking Pen (to mark level on Tote Bin)

Corrosive resistant suit Bung Wrench Corrosive resistant gloves Leather Gloves El 2.8 Keys to the brown storage container are stored with the caustic addition procedure in the OSC Chemistry Emergency Procedure Files and in the filing cabinet located in the Primary Chemistry lab office. All personnel in Primary Chemistry and Radwaste have also been issued individual keys.

0l 2.9 Power to the caustic addition pump is provided through 3XL located near the LPI Hatch Area. For power supply diagram, see Enclosure 5.4.

CP/3/A/2002/005 Page 4 of 7

3. Procedure 3.1 Upon notification from Operations Emergency Coordinator OR TSC / OSC, take the following actions to align the caustic addition system to the appropriate unit:

NOTE:

The following steps may be performed simultaneously to conserve time.

"El Verify eyewash and safety shower operable.

"E] Mark the current liquid level directly on the translucent tote bin container.

"El Measure down from the liquid level mark 15 inches and mark this level directly on the tote bin.

El IF necessary, move the tote bin into position.

"El Remove dust cover from Swagelock fitting on tote bin.

"El Remove dust cover from Swagelock fitting at 3CA-36 (Caustic Pump Suction Tell Tale) (AB Elev 771 at base of Unit 3 NaOH pump).

El 3.1.1 Make valve alignments per Enclosure 5.1 to allow caustic injection into the Low Pressure Injection (LPI) pump suction on Unit 3.

NOTE:

Protective clothing shall be worn prior to Step 3.1.2.

o 3.1.2 Connect stainless steel flex hose to the Swagelock quick-connect fitting upstream of 3CA-36 (Caustic Pump Suction Tell Tale). (AB 771 at base of Unit 3 NaOH pump) o 3.1.3 Connect stainless steel flex hose to the Swagelock fitting on the tote bin.

El 3.1.4 Vent the caustic tote bin by removing the tote bin fill cap.

El 3.1.5 Open the caustic tote bin outlet valve.

0l 3.1.6 Notify Operations OR the OSC (if activated) that valve alignments for caustic injection are complete and ready to be initiated.

Person contacted Date/Time 0l 3.1.7 WHEN notified by Operations, start the caustic addition pump at maximum flow setting. The caustic pump switch is located on the Chemical Addition Control Panel. The maximum pump capacity is approximately 2 gallons per minute.

CP/31A/2002/005 Page 5 of 7 NOTE:

Use low dose waiting area as possible during addition LI 3.1.8 Notify Operations OR the OSC (if activated) that caustic injection has begun.

Person contacted Date/Time I

NOTE:

The caustic pump has an average pump rate of 1.2 gallons per minute. To pump the initial setting of 15 inches will require 1.5 hours5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br />.

LI 3.1.9 Calculate the total amount of caustic (in gallons) to be added for the neutralization of the borated water added to the system by using CSM 5.2 (Enclosure 6.3).

LI 3.1.10 Convert gallons from Step 3.1.9 to inches (in the 350 gallon tote bin) by dividing the number of gallons to be added by 8.1. Record the values below:

Gallons to be added Inches to be added from the tote bin LI 3.1.11 Mark the calculated liquid level directly on the tote bin by measuring down from the original "current liquid level" mark made in Step 3.1.

LI 3.1.12 WHEN the caustic tote bin level reaches the desired level (as marked in Step 3.1) OR WIEN the caustic tote bin is empty, stop caustic addition pump using the switch located on the Chemical Addition Control Panel.

LI 3.1.13 Close tote bin outlet valve.

LI 3.1.14 Close 3CA-36 (Caustic Pump Suction Tell Tale) (AB Elev. 771 at base of _

Unit 3 NaOH pump).

LI 3.1.15 Record time and volume added on Enclosure 5.3.

CP/3/A/2002/005 Page 6 of 7 Li 3.1.16 IF necessary, replace the caustic tote bin as follows:

"El 3.1.16.1 Replace tote bin fill cap.

"Li 3.1.16.2 Disconnect empty tote bin from Swagelock fitting on stainless flex hose.

Li 3.1.16.3 IF necessary, move tote bins and remove dust cover from Swagelock fitting on new tote bin.

Li 3.1.16.4 Connect stainless flex hose to the new tote bin.

0i 3.1.16.5 IF pumping is to continue, mark the tote bin per Section 3.1 for the amount to be added from the new tote bin and go to Step 3.1.4.

0i 3.1.17 Notify OSC caustic addition to U-3 LPI is complete and no further additions are in progress.

Person contacted Date/Time Fl 3.1.18 After caustic addition is complete, allow LPI recirculation time of 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br />.

0l 3.1.19 WHEN authorized by the TSC/OSC, collect sample (per appropriate I

procedure) to determine the resultant pH of the reactor coolant.

Li 3.1.20 IFpHis <7.0:

" Calculate (refer to CSM 5.2, Enclosure 6.3) the amount of caustic (in gallons) to be added to complete the neutralization of the borated water added to the system.

"* Convert this number to inches (in the 350 gallon tote bin) by dividing the number of gallons to be added by 8.1 gallons/inch.

"* Record the values below:

Gallons to be added:

Inches to be added from tote bin:

Li 3.1.21 IF pH is > 7.0, go to Step 3.1.25.

Li 3.1.22 Mark the current liquid level directly on the translucent tote bin container.

Li 3.1.23 Measure down from this mark the number of inches calculated in Step 3.1.20 above. Mark this level directly on the tote bin.

CP/3/A12002/005 Page 7 of 7 5 3.1.24 Repeat Steps 3.1.1 through 3.1.21 until all necessary caustic (as determined by TSC/OSC) has been added.

Li 3.1.25 After all necessary caustic has been added and upon authorization from the TSC/OSC, return the system to normal as follows:

"LI 3.1.25.1 Replace tote bin fill cap.

"[] 3.1.25.2 Disconnect empty tote bin from Swagelock fitting on stainless flex hose.

"0 3.1.25.3 Make alignments per Enclosure 5.2 to return valves to normal position.

4. References 4.1 Dwg. No. OFD-1 1OA-3.8 Chemical Addition System (Primary Side Chemical Addition) 4.2 Dwg. No. OFD-102A-3.1, Low Pressure Injection System, Borated Water Supply and LPI Pump Suction.

4.3 CSM 5.2 4.4 ITS 5.4.1.a 4.5 SLC 16.13.7

5. Enclosures 5.1 Valve Alignment for Caustic Injection on Unit 3 5.2 Normal Valve Alignment for Caustic Injection System on Unit 3 5.3 Caustic Mixing and Injection Record 5.4 Unit 3 Caustic Pump Power Supplies

.1 Valve Alignment for Caustic Injection on Unit 3 CP/3/A/2002/005 Page 1 of 1 NOTE:

This enclosure is AP/EOP related.

Date DV Init Position Valve No.

Valve Name Location Open 3CA-103 Caustic Recirc Line & Press AB Rm. 150, at Caustic Gauge Block Mix Tank north side downstream of PG27 &

upstream of 3CA-103 Closed 3CA-96 Caustic Recirc Block AB Elev 771 at Unit 3 NaOH Pump Discharge Closed 3CA-35 Caustic Pump Suction AB Elev 771 at base of Unit 3 NaOH pump Open 3CA-36 Caustic Pump Suction Tell AB Elev 771 at base of Tale Unit 3 NaOH pump Open 3CA-112 Caustic Pump Pressure AB Elev 771 adjacent to Gauge Isolation but west of Unit 3 NaOH mix tank Closed 3CA-58 Caustic to #3 LIP Pump AB Elev 783 Col. Q-91, Suction Tell Tale near CC Cooler Room Open 3CA-39 Caustic to Unit #3 LP Block AB Hall, Elev 783 (Chm)

Col. Q-91, near CC Cooler Room Open 3CA-62 Caustic to Unit #3 LPI AB Elev 783 Col. Q-91, Block (OPS) near CC Cooler Room Open 3LP-51 LPI Sample Recirc.

AB Elev 783 Col. R-90 Isolation Valve (Ops) near CC Cooler Room

.2 Normal Valve Alignment for Caustic Injection System on Unit 3 CP/3/A/2002/005 Page 1 of I NOTE:

This enclosure is AP/EOP related.

Date DV Init Position Valve No.

Valve Name Location Open 3CA-103 Caustic Recirc Line &

AB Rm. 150, at Caustic Mix Press Gauge Block Tank north side downstream of PG27 & upstream of 3CA-103 Open 3CA-97 Caustic Recirc Block AB Elev 771 overhead at Unit 3 NaOH mix tank Open 3CA-96 Caustic Recirc Block AB Elev 771 at Unit 3 NaOH Pump Discharge Closed 3LWD-267 Caustic Tank Outlet Drain AB Elev 771 at tank drain pipe of Unit 3 NaOH pump Closed 3CA-34 Caustic Mix Tank Outlet AB Elev 771 at base of Unit 3 NaOH pump Closed 3CA-35 Caustic Pump Suction AB Elev 771 at base of Unit 3 NaOH pump Closed 3CA-36 Caustic Pump Suction AB Elev 771 at base of Unit 3 Tell Tale NaOH pump Open 3CA-112 Caustic Pump Pressure AB Elev 771 adjacent to but Gauge Isolation west of Unit 3 NaOH mix tank Closed 3CA-58 Caustic to #3 LPI Pump AB Elev 783 Col. Q-91, near Suct Tell Tale CC Cooler Room Closed 3CA-39 Caustic to Unit #3 LPI AB Hall, Elev 783 Block (Chm)

Col. Q-91, near CC Cooler Room Closed 3CA-62 Caustic to Unit #3 LPI AB Elev 783 Col. Q-91, near Block (OPS)

CC Cooler Room Closed 3LP-51 LPI Sample Recirc.

AB Elev 783 Col. R-90 near Isolation Valve (Ops)

CC Cooler Room

.3 Caustic Mixing and Injection Record NOTE:

This enclosure is AP/EOP related.

Date/Time of Injection CP/3/A12002/005 Page 1 of 1 Gal. NaOH

.4 Unit 3 Caustic Pump Power Supplies CP/3/A/2002/005 Page 1 of 1 3 TD3 3TD (4160) 3TC3 3TC (4160) 4A 4A 5C 1X5 4AT

.1.

.4 2A (600 VOLT)

WyT 6B 3X4 3A 208 VOLT 3XL 5

Unit 3 CAUSTIC PUMP NOTE:

1. This enclosure is APIEOP related.
2. Operations alternates the power logic as outlined. Verification will be required to establish which alignment is in use at the time of question.

INFORMATION ONLY CHEMISTRY MANUAL 5.1 EMERGENCY RESPONSE GUIDELINES REVISION NUMBER Original 1

2 3

4 5

6 7

8 9

10 11 12 13 14 15 16 17 18 19 20 21 Prepared by:

>? 62 Date: __________

10CFR50.

required: Yes

/

No Approval: >,",_

Date:

Control Copies delivered to Emergency Planning:

Date:

DUKE POWER COMPANY OCONEE CHEMISTRY MANUAL ISSUE DATE 10/25/83 09/27/95 11/30/95 01/24/96 03/14/96 09/16/96 10/31/96 11/26/96 01/02/97 09/22/97 11/20/97 03/12/98 06/15/98 08/24/98 02/04/99 05/27/99 09/29/99 03/27/00 12/05/00 02/22/01 04/11/02 04/16/02

CSM 5.1 Page 2 of 7 Emergency Response Guidelines NOTE:

Seven Control Copies and one Information Only copy of this CSM shall be routed to the Emergency Preparedness Team within three (3) working days following any approved changes/modifications.

1. Purpose 1.1 To identify members of the Chemistry Emergency Response Organization and their responsibilities.

1.2 Provide preplanned responses to emergency situations that may arise.

2. Chemistry Emergency Response Organization 2.1 The positions identified in Enclosure 6.1 may be filled by personnel identified in.2.

2.2 Chemistry Manager, Chemistry Team Leader or qualified Scientists may serve as Chemistry Manager in the OSC as identified in Enclosure 6.2. During backshift, holidays and weekends the Radwaste or Primary shift/coverage person will be the Chemistry Single Point of Contact until relieved.

2.3 A list of alternates for other positions is identified in Enclosure 6.2. These personnel may be designated by the Chemistry Manager as essential or non-essential as the emergency condition or event dictates.

2.4 The responsibilities of the Chemistry Emergency Response Organization are contained in Enclosure 6.3.

2.5 Once the OSC is activated for emergency response, all activities of field teams prior to, during, and thereafter become the responsibility of the OSC to coordinate and control.

Upon the activation of the OSC all chemistry activities currently in progress should be turned over to the OSC for coordination. The turnover should at a minimum include:

"* Emergency Job(s) in the field

"* Communication capability with the field team

"* Emergency equipment out of service/job description

"* Status of plant including power availability If approval to continue is given, an OSC task sheet should be submitted to document the activity(s).

CSM 5.1 Page 3 of 7 2.6 The SPOC Supervisor is responsible for assigning tasks and managing all resources during the first 75 minutes of a back shift drill and/or emergency. If Chemistry management is not available, the SPOC Supervisor (Interim OSC Manager) will direct the Chemistry resources. If Chemistry management arrives in the OSC during the 75 minutes, then Chemistry management will manage Chemistry resources.

2.7 When calling in personnel who are off site, determine Fitness for Duty per Enclosure 6.4.

2.8 The Chemistry Emergency Response Organization work schedule should be established as the emergency condition or event dictates.

2.9 The Chemistry Emergency Response Organization should use Enclosure 6.5 and 6.6 to assist in planning sampling, analysis, and chemical addition activities during an emergency situation.

2.10 If G.O. Chemistry support is needed, contact one of the following per the Chemistry Emergency phone list in the OSC file:

R. W. Eaker M. K. Johnson D. P. Rochester P. W. Downing 2.11 Expectations for Communication in the OSC:

2.11.1 Use the 4 communication techniques which help reduce errors:

  • Communications will be directed.

Use repeat backs (I send, you repeat, I confirm).

  • Radio / telephone communications should include name and location.
  • Use the phonetic alphabet for train designations.

2.11.2 Teams dispatched from the OSC will take a radio or have access to a radio.

Chemistry staff in the OSC will have access to a radio.

2.11.3 Radio communications will be verified. If radio communication CANNOT be made, the dispatched team will call Chemistry Staff in the OSC at 3858 or 3495 to determine how communications will be handled.

2.11.4 Prior to the team leaving the OSC, specify when communications will be required (e.g., when the team reaches the task area, every 30 minutes, when results are obtained, etc.).

CSM 5.1 Page 4 of 7 2.11.5 Tasks are to be completed as directed from the OSC. Should conditions change, notify Chemistry Staff in the OSC immediately. Do NOT go off on another task without direction from the OSC.

3. Chemistry Response to Site Assembly During Normal Working Hours (Monday through Thursday excluding holidays) 3.1 Inside the Protected Area:

"* Personnel shall assemble at their respective Chemistry office.

"* Upon arriving at assembly location,

"* Card in (swipe security badge)

"* Report accountability to Team Leader or designee

"* Remain in the assembly location until given further instructions by the Emergency Coordinator.

"* Personnel who assemble at an alternate Chemistry office shall:

"* Card in (swipe security badge)

"* Report accountability to their Team Leader or designee

"* Remain in the assembly location until given further instructions by the Emergency Coordinator.

"* Personnel working in the RCA/RCZ who are wearing protective clothing shall:

"* Proceed to the change room

"* Frisk appropriately

"* Card in (swipe security badge)

"* Contact their Team Leader or designee to report their location

"* Wait for further instructions

"* Personnel who CANNOT reach their card reader / assembly location within 30 minutes of the Site Assembly alarm shall:

  • Immediately call their Team Leader or designee

"* Proceed to their card reader / assembly location as soon as possible

CSM 5.1 Page 5 of 7 Personnel engaged in critical work activities: (e.g., resin bed regeneration, valve /

equipment operation related to the event, critical path work, work of a sensitive nature associated with the Security Plan, Fire Plan, or Nuclear Safety)

"* must contact their Team Leader or designee to provide their names, work location, nature of work, estimated time to completion, and any other relevant information.

"* Team Leaders shall relay pertinent information through the Chemistry Manager to the OSC Coordinator/Manager, who then assumes responsibility for the industrial and radiological safety of the workers.

"* For drills, such arrangements may be made in advance by location management and Emergency Planning.

  • Team Leaders or designee will report location and numbers to the Administrative Specialist at ext. 3856.

3.2 Outside the Protected Area

  • Environmental Chemistry personnel shall:

"* Assemble in the Environmental Chemistry office area.

"* Report their accountability to their Team Leader or designee.

"* Team Leader or designee will provide location and numbers to the Administrative Specialist at ext. 3856.

"* Personnel shall not enter the Protected Area unless they are responding to the OSC and shall keep their Team Leader or designee informed of their location until the Emergency Coordinator terminates the Site Assembly.

3.3 The Administrative Specialist will report accountability to the Security Shift Supervisor at ext. 5050 no later than 20 minutes after the initiation of Site Assembly. She will leave a message stating her name, department name, number and names of missing personnel.

3.4 When personnel accountability has been completed as part of the Site Assembly, one of the following will occur:

3.4.1 If the Assembly was a test of response time and accountability procedures or if the requirement for an assembly no longer exists, permission to return to normal duties will be given by the Operations Shift Manager/Emergency Coordinator.

CSM 5.1 Page 6 of 7 3.4.2 Plant conditions may require activation of the Site Emergency Response Organization. The notification to establish the Technical Support Center (TSC) and Operational Support Center (OSC) should be made over the PA system. The Chemistry Manager/Alternate should then implement the Organization outlined in Enclosure 6.1.

3.4.3 Other instructions may be given by the Operations Shift Manager / Emergency Coordinator.

4. Chemistry Response to Site Assembly During Backshifts, Weekends, and Holidays 4.1 All Chemistry personnel should assemble at their normal office area or any other Chemistry Assembly point, card in (swipe their badge), and report their location to the Radwaste Control Room at ext. 3230 or Primary at 2323. The Radwaste or Primary shift/coverage person should account for all Chemistry personnel on site. The accountability should be reported by calling ext. 5050 with name, location, and number of people accounted for including names of any personnel presently not accounted for.

All jobs in progress should be safely secured before reporting.

4.2 When personnel accountability has been completed as part of a Site Assembly one of the following may occur:

4.2.1 If the Assembly was a test of response time and accountability procedures or if the requirement for an assembly no longer exists, permission to return to normal duties should be given by the Operations Shift Manager/Emergency Coordinator.

4.2.2 Plant conditions may require activation of the Site Emergency Response Organization. The notification to establish the TSC/OSC shall come from the Operations Shift Manager/Emergency Coordinator. The Radwaste/Primary shift/coverage person will establish the Chemistry Organization and act as Chemistry Single Point of Contact until relieved by Chemistry Manager or designee.

4.2.3 Other instructions may be given by the Operations Shift Manager/ Emergency Coordinator.

CSM 5.1 Page 7 of 7

5. Chemistry Response to Site Evacuation Announcement NOTE:

A Site Assembly alarm will always precede a Site Evacuation Announcement.

5.1 Based on plant conditions or radiological conditions, the Emergency Coordinator makes a determination that Site Evacuation / Relocation is warranted.

5.2 TSC requests OSC personnel to prepare for Site Evacuation / Relocation.

5.3 Chemistry management will identify essential / non-essential personnel and provide information to Group Evacuation Coordinator at ext. 3856.

5.4 TSC Offsite Communicator makes PA announcement to initiate Site Evacuation I Relocation.

5.5 Group Evacuation Coordinator accesses Evacuation / Relocation instructions through the DAE (Duke Application Environment) and coordinates evacuation / relocation of assigned personnel by notifying Team Leaders or designee.

5.6 Personnel being relocated to Oconee Training Center or Oconee Complex should notify the Group Evacuation Coordinator at ext. 3856 of their location and a number where they can be reached. The Group Evacuation Coordinator will then notify TSC/OSC/EOF Managers.

6. Enclosures 6.1 Chemistry Emergency Response Organization 6.2 Designation of Essential Chemistry Personnel 6.3 Responsibilities of Emergency Response Organization 6.4 Fitness For Duty Questions for Call Outs (if needed) 6.5 Post Accident Sampling and Analysis Checklist 6.6 Post Accident Chemical Addition Checklist

.1 CSM 5.1 Chemistry Emergency Response Organization Page 1 of 1 (Minimum Staffing)

NOTE:

OSC - Operational Support Center - the area in the back of the Unit 3 Control Room.

  • - 75 minute response time oSC Chemistry Manager * (one)

(phone: ext. 3495)

OSC Chemistry Area Manager (one)

(phone: ext. 3858)

OSC Chemistry Staff Support (one)

OSC Chemistry Specialist (five)

.2 CSM 5.1 Designation of Essential Chemistry Personnel Page 1 of 2

1. Operational Support Center (OSC)

NOTE:

For Initial Response, one Chemistry Manager OR Area Manager is all that is required to respond. For extended drills and all emergencies, two persons are required.

1.1 Chemistry Manager / Area Manager (one) - OSC phone 3495 Bryon Norris Dean Cantrell Rick Wright Amanda Breland Dale White Andy Perry NOTE:

Two Staff persons will be called out per the Community Alert Network System.

1.2 Chemistry Staff Support (one) - OSC phone 3858 Dedrick Wald Steve Davenport Ellen Morris Keith Beddingfield Garen Denard Davis Harrelson Mark Sanders Ann Clark Travis Rollins

.2 CSM 5.1 Designation of Essential Chemistry Personnel Page 2 of 2 NOTE:

Only five technicians are required although as many as seven may respond (includes two shift persons (minimum staffing requirements) plus five persons to be called by the Community Alert Network System).

Included in the minimum staffing is the requirement that the qualifications of the two shift persons in combination will allow RCS sampling, PALS operation, and Caustic addition.

1.3 Chemistry Technicians / Specialists (five)

Secondary Environmental Primary Radwaste Lance Young Mike McCoy Sheri Lackey Roy Hanks Saverne Williams Rick Morris Dennis Earle Sharon Strickland Ida Huff Jac Cashin Gina Roach Greg Aldrich Lawrence Nesbitt Ronnie Tucker Charlie Hendricks On Tran Skip Fletcher PNri Smith Dana Gaillard Ron Sager Lynette Wright Gary Barker Vivian Howell Wayne Evans E. T. Moss Stephen Johannes Jake Lamey Harold Bruce

- Luke Calvert

.3 CSM 5.1 Responsibilities of Page 1 of 4 Emergency Response Organization

1. Responsibilities of the Chemistry Manager 1.1 Set up the Chemistry Emergency Response Organization for OSC and Chemistry Office.

Designate non-essential personnel.

NOTE:

Appropriate procedures are located in OSC in the identified file cabinet.

1.2 Keep the OSC Coordinator informed of current status of Chemistry areas of responsibility.

1.3 Inform OSC Coordinator of any Chemistry Emergency Response Activities initiated prior to the activation of OSC.

1.4 Maintain assessment of the emergency and recovery efforts and identify trends and conditions that have the potential to cause changes in the chemical parameters of the emergency situation.

1.5 Participate in the development of recovpry programs in Chemistry areas of responsibility.

1.6 Use Enclosures 6.5 and 6.6 as needed to plan sampling, analysis and/or chemical addition activities.

1.7 IF liquid radioactive releases are in progress, classify the release for ihe OSC/TSC.

SReleases < 10 EC are within normal limits.

  • Releases > 10 EC are above normal limits.
2. Responsibilities of the Radwaste/Primary Shift/Coverage Person on Holidays, Weekends, Backshift 2.1 Serve as Single Point of Contact for Chemistry until relieved.

2.2 Account and report for all Chemistry personnel on-site during a Site Assembly. The accountability should be reported to Security at ext. 5050 within 20 minutes and should include name, location, and number of people accounted for including names of any personnel presently not accounted for.

2.3 Upon implementation of the Site Emergency Response, report to the Operational Support Center (OSC) and provide immediate support to the Operations Shift Manager.

.3 CSM 5.1 Responsibilities of Page 2 of 4 Emergency Response Organization NOTE:

Appropriate procedures are located in the OSC in the file cabinet labeled Chemistry procedures.

2.4 Inform OSC Coordinator of any Chemistry Emergency Response Activities prior to the activation of OSC.

2.5 IF radioactive releases are in progress, classify the release for the OSC/TSC.

  • Releases < 10 EC are within normal limits.
  • Releases > 10 EC are above normal limits.

2.6 No persons will need to be called out. One (1) Chemistry Manager/Alternate will always be on duty and will respond when their emergency response paget is automatically actuated. Five (5) technicians/specialists and two (2) area Staff support persons and one (1) Team Leader will be called out by the automated "Community Alert Network System".

2.7 in the event the Community Alert Network System fails or is out-of-service, Call Outs for the five technicians/specialists may be requested. Persons have the responsibility to respond to a call out (Management Procedure "Overtime, Call-Outs and 16-H-our Provision").

  • Fitness for duty must be determined by asking the questions listed in Enclosure 6.4.
  • Two Staff persons from the Duty list should be paged a second time through the Switchboard Operator to please report to the OSC.
3. Responsibilities of the Chemistry Staff Support 3.1 Keep Chemistry personnel informed of current status of the emergency situation and recovery effort.

3.2 Implement control measures to operate the laboratory during emergency conditions.

3.3 Use Enclosures 6.5 and 6.6 as needed to plan sampling, analysis, and/or chemical addition activities.

3.4 Conduct pre-job briefings to:

3.4.1 Ensure employees are sufficiently familiar with the task to efficiently perform it under the anticipated conditions.

.3 CSM 5.1 Responsibilities of Page 3 of 4 Emergency Response Organization 3.4.2 Ensure materials, parts, tools, and equipment necessary to perform the task are proper for the job, are readily available, have electric or pneumatic power sources available, and are familiar to workers.

3.4.3 Ensure workers assigned to the task have sufficient remaining exposure to contribute significantly to its completion and necessary requests for dose extensions are submitted in a timely manner and with proper justification.

3.4.4 Coordinate work activities with those of other work groups to achieve maximum efficiency in the task as a whole and to minimize the potential for unnecessary exposure due to poor communications or lack of proper planning/scheduling.

4. Responsibilities of Chemistry Technicians 4.1 Follow applicable emergency procedures unless directed to do otherwise by the Chemistry Manager.

4.2 Comply with requirements and special instructions of the applicable Radiation Work Permit (RWP), warning sign or barrier concerning radiation/contamination control unless directed to do otherwise by, Radiation Protection or Chemistry Manager.

4.3 Know location of radiation sources and their dose rates at the task location or accesses.,

Utilize Low Exposure Waiting Areas where applicable. This information is to be provided by Radiation Protection personnel.

4.4 Ensure you are sufficiently familiar with the task to efficiently perform it under the anticipated conditions. Pre-job briefings should be conducted to ensure your complete understanding of the job. (Repeat any instructions given.)

4.5 Ensure you have sufficient remaining exposure to contribute significantly to the completion of the assigned task.

.3 Responsibilities of Emergency Response Organization

5. Training for Emergency Response Organization NOTE:

Emergency Response Training Module (OC-1818) was rep Worker Training).

CSM 5.1 Page 4 of 4 laced with UALIIB (Radiation 5.1 Chemistry Manager / Team Leader

"* Initial Chemistry Emergency Response Training (OC3704)

"* Participate in at least one drill / two years (HS0537)

"° Initial Training - OSC Facility Specific (OC7099)

"* Chemistry Specific Emergency Plan / Response Yearly Update (OCC043) 5.2 Staff o Initial Chemistry Emergency Response Training (OC3704)

  • Participate in at least one drill / two years (HS0537)
  • Initial Training - OSC Facility Specific (0C7099) o Chemistry Specific Emergency Plan / Response Yearly Update (OCC043) 5.3 Technicians o Initial Chemistry Emergency Response Training (OC 3704)
  • Initial Training - OSC Facility Specific (OC 7099)

.4 CSM 5.1 Fitness for Duty Questions for Call Outs Page 1 of 1

1. Employees who acknowledge consumption of alcohol within 5 hours5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br /> must be evaluated by supervision upon reporting to work. Evaluation may be by observation or breathalyzer.
2.

IF the answer to the first question is no, the other questions should NOT be asked.

3. These questions apply to anyone being called out to work in the Protected Area of the plant, regardless of position or whether his/her name appears on a "duty list". Documentation of the phone call is NOT required by the Fitness for Duty "rule". However, if the call out results in a questionable situation, you may want this information documented.

The following questions MUST be asked to determine Fitness for Duty:

1.

Have you consumed alcohol in the last 5 hours5.787037e-5 days <br />0.00139 hours <br />8.267196e-6 weeks <br />1.9025e-6 months <br />?

2.

What did you have?

3.

Uow much did you have?

4.

Can you perform your job unimpaired?

5.

Can you drive?

.5 CSM 5.1 Post Accident Sampling Page 1 of 4 and Analysis Checklist SNOTE:

Do NOT uethis Enclosure for documentation.

Date:

Time:

Unit:

Sample requested by TSC.

Sample from:

Normal PALSS Appendix R RCS - Pri. Sample Hood RCS "J-Leg" RCS "J-Leg" RCS - Wst. Sample Hood HPI Letdown LPI - Wst. Sample Hood LPI Pump Disch.

Determine analysis / analyses to be performed and list below:

Initiate OSC Task Work Sheet.

.5 Post Accident Sampling and Analysis Checklist Procedures I Lab Methods to be used:

CP/OJB/2001/008 CP/I/A/2002/001 CP12/A/20021001 CP/3/A/2002/001 CPIl/A/2002/004 C CP/2/A/2002/004 C CP131A/2002/004 C CPIIIAI2002/004 E CP/21A/2002/004 E CP/3/A/2002/004 E CP/1&2/A.'2002/005 "CP/3/A/2002i005 CP/O/B/20051021 CP/1/B/3002/002 CP/2/B/3002/002 CP/3/B/3002/002 CP/O/B/5200/012 CPIOBI/5200/045 LMIO/PO03C LM/OJP004 LM/O/P919 CSM 3.8 CSM 3.10 CSM 5.1 CSM 5.2 Chemical Safety Equipment and Spill Control Response Unit One Primary Sampling System Unit Two Primary Sampling System Unit Three Primary Sampling System Operating Procedure for the Post Accident Liquid Sampling (PALS)

System (EP)

Operating Procedure for the Post Accident Liquid Sampling (PALS)

System (EP)

Operating Procedure for the Post Accident Liquid Sampling (PALS)

System (EP)

Unit 1 Reactor Coolant Sampling during an Appendix "R" Accident Unit 2 Reactor Coolant Sampling during an Appendix "R" Accident Unit 3 Reactor Coolant Sampling during an Appendix "R" Accident.

Post Accident Caustic Injection into the Low Pressure Injection System Post Accident Caustic Injection into the Low Pressure Injection System Composite Sampling of #3 CTP for Radioactivity Unit One Chemical Additions for Secondary Systems for Normal Operating Conditions Unit Two Chemical Additions for Secondary Systems for Normal Operating Conditions Unit Three Chemical Additions for Secondary Systems for Normal Operating Conditions Turbine Building Sump Monitor Tank Operation Liquid Waste Release from RWF Determination of Boron by Manual Colorimetric Titration Using Phenolphthaline Indicator (EP)

Determination of Chloride by Specific Ion Electrode Boron Analysis by Mettler DL-58 Boron Titration (EP)

Secondary Lab Sampling Frequencies, Specifications, and Corrective Actions Primary Lab Sampling Frequencies, Specifications, and Corrective Actions Emergency Response Guideline Post Accident Procedure Use Guidelines CSM 5.1 Page 2 of 4

.5 CSM 5.1 Post Accident Sampling Page 3 of 4 and Analysis Checklist Obtain applicable RIA readings from the Data Acquisition System or Control Room Liason:

RIA Reading RIA Reading RIA-4 mR/hr RIA-32 CPM RIA-8 mR1hr RIA-57 R/hr RIA-10 mR/hr RIA-58 R/hr RIA-13 mRlhr SYSTEM SAMPLING:

Notify Operations Liaison an RP of support needs.

Determine number of Chemistry personnel required for sampling and analysis:

Sampling:

Analysis:

Ensure assigned personnel have sufficient remaining exposure to complete assigned tasks.

by obtaining Dose Extensions asrequired.

Determine sample transporter to be used and its location.

Conduct planning session with Chemistry, RP, and Operations personnel involved in sampling to identify / define specific roles and responsibilities:

A.

Designate Chemistry personnel to perform sampling.

B.

Designate Chemistry personnel to support sampling at the RCZ / control point.

C.

Identify Chemistry and RP personnel assigned to perform analysis.

D.

Determine required respiratory equipment and protective clothing.

E.

Determine required equipment to support sampling (eg; radios, sample bottles, flashlights, etc.).

F.

Establish Low Dose Waiting Areas / control points.

G.

Determine stay-time(s) at PALS Panels.

H.

Determine "best" route for sample transport.

Obtain equipment required to support sampling.

.5 CSM 5.1 Post Accident Sampling Page 4 of 4 and Analysis Checklist Obtain keys required for sampling (located in the Chemistry OSC Emergency Procedures Cabinet).

Establish and maintain stay-time log at the RCZ / control point.

ANALYSIS:

Determine additional RP support required during analysis.

Determine need to prepare back-up lab for analysis (RW Facility Lab).

Obtain and label carboys for storing / handling liquid waste.

Obtain lead shielding and prepare Chemistry Lab for analysis.

Ensure analytical instruments are standardized prior to use.

Ensure sufficient quantities of reagents are available; prepare as needed.

Conduct planning session with Chemistry and RP personnel involved in analysis to identify./ define specific roles and responsibilities:

A.

Designate Ctiemistry personnel required to perform specific analyses.

B.

Determine respiratory equipment and protective clothing requirements.

C.

Use Breathing Air Cylinders and set-up Air Line Header for Lab if respiratory equipment is required.

.6 CSM 5.1 Post Accident Chemical Addition Checklist Page 1 of 2 NOTE:

Do NOT use this Enclosure for documentation.

This is a time-critical task. Caustic addition must be initiated within 30 minutes of recirc mode operation.

Date:

Time:

Unit:

Caustic addition requested.

Initiate OSC Task Work Sheet (when appropriate)

Procedures / Lab Methods to be used:

CPII&2IA12002/005 Post Accident Caustic Injection into the Low Pressure Injection System CP/3/A/2002/005 Post Accident Caustic Injection into the Low Pressure Injection System CP/OIB/20011008 Chemical Safety Equipment & Spill Control Response CSM 5.2 Post Accident Procedure Use Guidelines Verify LPI System is in service and taking suction from the Reactor Building Emergency S*ump.

Obtain the following applicable RIA readings from the Data Acquisition or the Control Room. Refer to Enclosure 6.2 of CSM 5.2 for RIA information.

RIA Reading RIA Reading RIA-12 mR/hr 1RIA-32-12 CPM 3RIA-19 mR/hr 3RIA-32-3 CPM 1RIA-32-3 CPM 3RIA-32-5 CPM 1RIA-32-10 CPM RIA-57 CPM 1RIA-32-11 CPM RIA-58 CPM Notify RP, Operations Liaison, and OSC Coordinator of support needs.

Determine number of Chemistry personnel required for addition:

  1. required (minimum of two)

Ensure assigned personnel have sufficient remaining exposure to complete assigned tasks.

Obtain Dose Extensions as required.

.6 CSM 5.1 Post Accident Chemical Addition Checklist Page 2 of 2 Time permitting, conduct planning session with Chemistry, RP, Operations, and OSC personnel involved in addition to identify/define specific roles and responsibilities:

A.

Designate Chemistry personnel to perform addition.

B.

Designate additional OSC personnel to transport caustic.

C.

Designate Chemistry or OSC personnel to support addition at the RCZ/control point.

D.

Determine required respiratory equipment, protective clothing, and any additional RP requirements.

E.

Determine required equipment to support addition (eg; radios, chemical resistant suits, flash lights, etc.).

F.

Establish Low Dose Waiting Areas/control points (as required).

G.

Determine stay time(s) at caustic addition area (as required).

H.

Identify potential safety hazards to team members (eg; heat stress.

caustic spill control, caustic hazards, etc.).

Obtain equipment required to support addition.

Establish and maintain stay time log at the RCZ/control point (as requiied).

INFORMATION ONLY CHEMISTRY MANUAL 5.2 POST ACCIDENT PROCEDURE USE GUIDELINES

'A. A





REVISION NUMBER Original 1

2 3

4 5

6 7

8 9

10 ISSUE DATE 07/15/82 10/25/95 01/20/97 04/07/97 11/20/97 08/17/98 03/16/99 12/28/99 09/18/00 04/11/02 Prepared by:___Date:__________

10CFR50.59 required: Yesjvj No Approval:

l:____________

Date:

Control Copies delivered to Emergency Planning:

Date:

DUKE POWER COMPANY OCONEE CHEMISTRY MANUAL

Chemistry Manual 5.2 Page 2 of 13 Post Accident Procedure Use Guidelines

1. Purpose NOTE:
1. NSD 228 Applicability Determination and a 50.59 screening is required to make major changes to this section. Minor changes per NSD 703 can be made without a Applicability Determination.
2. Seven Control copies and one Information Only copy of this CSM shall be routed to the Emergency Preparedness Team within three (3) working days following any approved changes/modifications.

This section provides guidelines on the administration and use of chemistry post accident procedures and the precautions that should be observed during the use of these procedures.

Special attention is given to limits and precautions associated with the execution of a procedure during a projected accident. Personnel requirements and procedure work locations will be given for personnel exposure consideration. Also, a listing of RIAs of interest to Chemistry for planning and assessment activities is included in Enclosures 6.1 and 6.2. This information is intended only as guidelines with the knowledge that an actual accident situation may deviate greatly from a projected scenario.

2. Guidelines 2.1 Limits and Precautions NOTE:

These Limits and Precautions do not apply to the task for Addition of Caustic to the LPI (RCS) System. This task is a "time critical task" and therefore is not subject to the below Limits and Precautions.

2.1.1 Valve alignments should NOT be made and samples should NOT be taken without prior authorization from the TSC/OSC.

2.1.2 Do NOT attempt any phase of sampling or analysis without Radiation Protection coverage.

2.1.3 ALL personnel will need prior authorization from the OSC to exceed any exposure limit.

Chemistry Manual 5.2 Page 3 of 13 2.1.4 Radiation levels of the sampling and analysis area should be measured continuously during all phases of sampling, sample preparation, and analysis.

2.1.4.1 Air activity should be determined by use of installed air monitors or through the use of portable air sampling equipment.

2.1.4.2 Area dose rates should be established by the use of installed radiation monitors or by portable radiation survey instruments.

2.1.4.3 Portable shielding, remote handling equipment, video equipment, etc., should be used where practical during sample preparation and sample analysis.

2.1.4.4 All personnel working in the lab area and transporting samples shall monitor their personal dosimetry frequently to avoid exceeding maximum dose limits.

2.1.5 The post accident analysis should be done in a fume hood and/or other precautions should be taken to avoid the release of gaseous activity.

2.1.6 Radiation exposure to an individual during all phases of sampling should be limited so as not to exceed an annual accumulative exposure of 2 rem whole body; 50 rem skin of whole body; 50 rem extremities; or 15 rem eye respectively. All personnel will need prior authorization from the TSC/OSC to knowingly exceed any exposure limit. The exposure received may require an occupational exposure penalty and/or a medical decision as to whether an individual can continue in radiation work.

2.2 Waste Disposal 2.2.1 Determine by detailed planning meeting, the exact course of action to be taken. Under no condition should liquid or solid wastes be disposed of without prior specific RP directions.

2.2.2 Designate a sealable carboy as the "Post Accident Lab Waste" container. This container should be shielded and used as an interim liquid waste disposal container for all liquid analytical waste.

2.2.3 Request RP to designate an area where the "RCS Flush" bottle(s), "RCS Sample" bottle(s) and "Post Accident Lab Waste" container may be stored until final disposal.

2.2.4 In the event an area is grossly contaminated and cannot be decontaminated, evaluate the need for shielding or protective covering to prevent the spread of airborne activity.

Chemistry Manual 5.2 Page 4 of 13 2.3 Procedures 2.3.1 CP/1,2,3/A12002/001 - Unit One, Two, or Three Primary Sampling System Description Personnel Precautions -

Use Location -

Defines the steps necessary to sample tanks, systems, etc.,

associated with the primary system to determine various chemical concentrations and radioactive isotopes.

One (1) Chemistry technician - to sample One (1) RP technician Personnel should expect high dose rates and possible airborne activity. Use applicable RIA's listed in Enc. 6.1 and 6.2.

Some sample points will be at system pressure.

This procedure should be used to obtain reactor coolant samples when possible. Other primary systems and tanks such as LPI, BWST, SFP, etc. can be sampled using these procedures.

Third floor Aux building - Primary sample hoods; First floor Aux building - Waste sample hoods CAUTION:

If the hydrogen purge unit is in service on Unit 2 or 3 the ventilation flow path for the Primary and waste sample hoods has been isolated. The hydrogen purge unit will typically not be placed into service for about 7 days after a LOCA and then only if the hydrogen recombiner is out of service. The hydrogen purge unit must be secured prior to sampling.

Chemistry Manual 5.2 Page 5 of 13 2.3.2 CP/1,2,3/A/2002/004 C - Operating Procedure for the Post Accident Liquid Sampling System (PALSS)

Description Personnel Precautions Use -

Outlines method to sample primary coolant using the remotely operated PALSS sampling system. System can sample from RCS "J-Leg", LPI Pump Discharge, and HPI Letdown.

One (1) Chemistry technician - panel operation One (1) person to communicate with control room for LP-65 (if required)

One (1) Radiation Protection technician.

Because of location of sample panels, personnel may be in high radiation area with airborne activity. Evaluate shuttle of personnel to and from lower dose areas. Use the readings from applicable RIAs listed in Enc. 6.1 and 6.2 to plan sampling activities.

This procedure should be used to sample primary coolant when significant fuel damage is expected. System is designed to limit personnel exposure during sampling. Sample point for RCS "J-Leg" needs flow through that loop to ensure representative sample. If significant loss of coolant has occurred, need to also sample LPI Pump Discharge.

Location -

First floor auxiliary building Near 1 & 2 Waste Disposal Hood - Units 1 & 2; Near 3 Waste Disposal Hood - Unit 3

Chemistry Manual 5.2 Page 6 of 13 2.3.3 CP/1,2,3/A/2002/004E - Unit One, Two or Three Reactor Coolant Sampling During an Appendix "R" Accident Description -

This procedure provides instruction on sampling the RCS via an ice cooled sampler installed on the discharge side of valve 1, 2, 3 RC-179 of the affected unit during an Appendix "R" accident situation.

Personnel -

Two (2) Chemistry Technicians One (1) Radiation Protection Technician Two (2) I&E Technicians Precautions Use -

Personnel should expect normal dose rates and a high probability of airborne activity due to fission gas release during sample flush to floor drain. Sample temperature &

pressure will be very high & if not cooled properly will flash to steam.

This procedure should only be used during an Appendix "R" fire when all power is lost. It should be considered the last alternative for Reactor coolant sampling.

Unit 1, 2, 3 LPI Pump rooms Location -

Chemistry Manual 5.2 Page 7 of 13 2.3.4 CP/1&2,3/A12002/005 - Post Accident Caustic Injection Into the Low Pressure Injection System NOTE:

This is a "time critical task" and must be initiated immediately when recirculation mode off the RBES has been established.

Description Personnel Precautions Use Location -

Outlines the method used to raise the pH of the primary coolant to = 7.0 - 8.0 following a LOCA. Caustic additions will improve the iodine liquid partition factor and inhibit hydrogen gas formation. Use Enc. 6.3 to calculate quantity of caustic required for addition.

Two (2) Chemistry technicians (desirable, but not required)

One (1) Radiation Protection tech (desirable, but not required)

Two (2) additional OSC personnel to move Caustic (desirable, but not required)

High radiation areas and airborne activity may be a concern.

Use readings from applicable RIAs listed in Enc. 6.1 and 6.2 to plan addition. Establish Low Dose Waiting Areas as needed. Heat Stress conditions may also be a concern.

This procedure should be used when a significant loss of coolant to the Reactor Building has occurred and there is concern about an Iodine release and/or hydrogen gas formation. The LPI System MUST be in service and taking suction from the emergency sump.

Units 1&2 - 2nd floor of the Aux. Bldg, Chemical Addition Area Unit 3 - 1st floor of the Aux Bldg, Chemical Addition Area

Chemistry Manual 5.2 Page 8 of 13 2.3.5 LM/O/PO03C - Determination of Boron by Manual Colorimetric Titration Using Phenolphthaline Indicator Description Personnel Precautions Use Location -

Outlines the use of manual potentiometric titrations to determine boron concentration. The range for this analysis is between 100 and 2500 ppm. Samples with concentrations greater than 1000 ppm must be diluted for dose and time considerations.

One (1) Chemistry technician One (1) Radiation Protection technician Personnel should expect high dose rates and possible airborne activity. Use the readings from applicable RIAs listed in Enc. 6.1 and 6.2 to determine if the Primary Lab is available for use.

This procedure should be used to analyze for boron whenever conditions have resulted in the loss of the normal analytical instrumentation, such as an Appendix "R" Accident.

Rooms 329 and 330.

2.3.6 LM/O/P919 - Boron Analysis By Mettler DL-58 Titration Description Personnel Precautions Use -

This method covers the precise determination of boron concentration in the 0.2 - 10,000 ppm range in high purity water (RCS) using the Mettler DL-58 Titration System.

One (1) Chemistry technician One (1) Radiation Protection technician Personnel should expect high dose rates and possible airborne activity. Use the readings from applicable RIAs listed in Enc. 6.1 and 6.2 to determine if the Primary Lab is available for use.

This procedure should be used as the primary method for determining boron concentration.

Rooms 329 and 330.

Location -

Chemistry Manual 5.2 Page 9 of 13 2.3.7 LM/O/P914 - Ion Analysis - DX-500 IC Description Personnel Precautions Use -

Outlines the use of ion chromatograph in determination of chloride concentration in primary coolant when fuel failure is expected.

One (1) Chemistry technician One (1) Radiation Protection technician Personnel should expect high dose rates and possible airborne activity. If too much dilution is required based on dose consideration, then this procedure could not be utilized. Use the readings from applicable RIAs listed in Enc. 6.1 and 6.2 to determine if the Dionex Lab is available for use.

This procedure should be used when dose consideration allows a reasonable expectancy of being able to detect chloride at the dilution required.

Location -

Room 330.

2.3.8 LM/1OP008 - The Determination of Hydrogen Using the Carle or SRI Gas Chromatographs Description Personnel Precautions Use -

This procedure covers the use of the Carle Series and the SRI Series Analytical Gas Chromatographs to determine the concentration of hydrogen in gas samples.

One (1) Chemistry technician One (1) Radiation Protection technician Personnel should expect high dose rates and possible airborne activity. Use the readings from applicable RIAs listed in Enc. 6.1 and 6.2 to determine if the Primary Lab is available for use.

This procedure should be used in an accident situation to analyze for hydrogen concentration.

Rooms 329 and 330.

Location -

Chemistry Manual 5.2 Page 10 of 13 2.3.9 LM/O/G004 - Determination of Gamma Isotopic Activity Description Personnel Precautions Use Location -

Outline of method used to prepare sample for gamma isotopic analysis.

One (1) Chemistry technician One (1) Radiation Protection technician Personnel should expect high dose rates and possible airborne activity. Utilize remote handling when possible. Use the readings from applicable RIAs listed in Enc. 6.1 and 6.2 to determine if the Primary Lab and Count Room are available for use.

This procedure should be used when a gamma isotopic analysis is required.

Rooms 329 and 330.

Quench Tank BWST CBAST BAMT BHUT LDST CFT SFP (1&2)

SFP (3)

LiOH NaOH MWT HAWT LAWT CTP 1 CTP 2 CTP 3 CTP 3 (weir down) 5,834 gallons 388,000 gallons 22,440 gallons 2,500 gallons 82,000 gallons 4,488 gallons (31.26 gal/in) 10,470 gallons 546,000 gallons 374,000 gallons 30 gallons 100 gallons 20,200 gallons 2,000 gallons 3,000 gallons 1,300,000 gallons 1,100,000 gallons 3,000,000 gallons 4,900,000 gallons

3. Additional Information 3.1 Tank volumes:

Chemistry Manual 5.2 Page 11 of 13 3.2 System Volumes:

RCS (cold/hot)

Reactor Building CST Waste Gas Hotwell OTSG (Secondary Side) 88,000/60,000 gallons 1,910,000 ft3 free volume 30,000 gallons 23,800 ft3 150,000 gallons 28,000 gallons 3.3 Cooler Supplies:

Quench Tank Decay Heat Letdown Seal Return RBCU CC RCW Pri Sample PALSS CC LPSW CC RCW LPSW LPSW CCW RCW RCW

4. Suggested Actions 4.1 Normal Operating Conditions:

Observation: Loose part or mechanical failure has caused suspected loss of some fuel integrity.

Actions:

  • Do not over react, close coordination with OPS and RP will be necessary to understand where and how to sample coolant.

First find out exact status of unit (subcritical, pressure, temperature, # of RCP on, letdown flow rate, area monitor readings?)

If the unit is shutdown, then remember that samples will show normal coolant fission product spiking - must compare to earlier unit trip results.

Have RP survey letdown piping (if in service) and compare to normal values before deciding which method to use in sampling.

Chemistry Manual 5.2 Page 12 of 13 For truly mechanical damage, gap activity isotope should increase (Xenons, Kryptons, iodines) with much smaller increases in (Strontium, Barium, Cesium, less mobile isotopes).

With gap activity release, degassing of coolant fission gases will be much more pronounced. Appropriate respiratory protection should be considered while sampling.

4.2 Overheat Condition Without Fuel Melt Observation:

RB pressure and temperature increase. Suspect loss of coolant to Reactor Building.

Actions:

  • If ES actuation occurs, then letdown will be automatically secured thus rendering normal sample point useless (Ops may manually override)
  • Make immediate plans to move necessary equipment to RW facility or Environmental lab for chemical analysis of boron and pH. Dose rates may render Primary lab useless.

deciding which sam ple location to uise, a careful evaluation of all data should be performed.

1. Boron concentration can be calculated based on injection volumes and known concentrations.
2. RIA readings from RIA 57, 58 can closely estimate failed fuel percentage without need for sampling.
3. If recirculation of water through vessel is not available, the PALS J-leg sample will not be representative.
4. Core exit thermocouple readings and mapping can aid in estimating area and extent of core damage.
  • If electrical system load shed has occurred, then many of the normal power supplies to the Chemistry group may be unavailable without Operations assistance.

Chemistry Manual 5.2 Page 13 of 13 4.3 Fuel Melt Actions:

"* All of Section 4.2 action items are applicable.

"* Expect higher levels of Barium, Strontium and Praesyodimium from fuel inatrix loss.

"* Expect high suspended solids in any sampling attempted.

"* Both hydrogen percentage and RIA 57, 58 readings can and should be used in lieu of sampling, at least until dose levels have significantly dropped.

"* Boron as a criticality concern should be minimal - weighing the small benefit of a sample versus the extreme risk to an individual(s) should be considered.

5. References 5.1 ONS Post Accident Procedures 5.2 ONS OFD Drawings 5.3 ONS UFSAR 5.4 ONS ITS
6. Enclosures 6.1 RIAM of Interest to Chemistry 6.2 Location of Sample Points for Multipoint RIAs 6.3 Caustic Addition Calculations 6.4 E, A and R Values for 1% Failed Fuel and DBA 6.5 Technical Basis for Caustic Addition Calculations 6.6 Quarterly Inspection of Post Accident Equipment

.1 RIAs of Interest to Chemistry Chemistry Manual 5.2 Page 1 of 2 RIA #

RANGE LOCATION INFORMATION USED FOR 1RIA-4 0 1 - 10e7 mR/hr Reactor Building Entrance/

Indicates a LOCA with moderate to severe 2RIA-4 Personnel Hatch fuel damage; 2RIA-4 is located near the 3RIA-4 Primary Lab and Count Room - Readings used to assess the need to prepare alternate labs RIA-8 0.1 - 10e7 mR/hr Primary Chemistry Lab Used to assess the need to prepare the alternate Primary Lab and/or Count Room IRIA-10 0.1 - 10e7 mR/hr Unit 1 Primary Sample Hood Used for planning sampling. Readings will 2RIA-10 Unit 2 Primary Sample Hood be high once sampling is started if significant 3RIA-10 Unit 3 Primary Sample Hood fuel damage has occurred IRIA-12 0.1 - 10e7 mR/hr Unit 1&2 Boric Acid Mix Tank Readings used for planning chemical 3RIA-12 Unit 3 Boric Acid Mix Tank additions (ie: Caustic Additions)

IRIA-13 0.1 - 10e7 mR/hr Unit 1&2 Waste Sample Hood Used for planning sampling activities from 3RIA-13 Unit 3 Waste Sample Hood the PALS. Readings may be high if significant fuel damage has occurred IRIA-15 0.1 - 10e7 mR/hr Unit 1&2 BPI Pump Room Provide preliminary indications of significant 3RIA-15 Unit 3 HPI Pump Room fuel damage 1RIA-16,17 0.01 - 10e3 mR/hr Unit 2 'A & B'Main Steam Lines Readings > background from these RIAs are 2RIA-16,17 Unit 2 'A & B'Main Steam Lines indications of primait/secondary steam S3RIA-16,17 Unit 3 'A & B'Main Steam

_ines generator tube leaks 3RIA-19 0.1 - 10e7 mR/hr Laundry and Hot Shower Tank Room Used for planning Unit 3 caustic; readitgs may be high if significant fuel damage has occurred due to being near LDST 1RIA-31 10 - 10e6 CPM Behind air compressors in Turbine Multipoint RIA that monitors LPSW Building Basement, west of Unit 2 effluents from LPI Cooler, and CC Cooler.

Powdex Readings > background indicate a primary coolant leak into the LPSW System. See 3RIA-31 North of sewage ejectors at Unit 3, Enc. 6.2 for sample point locations.

west wall of Turbine Building IRIA-32 10 - 10e6 CPM Monitor on first floor of Aux Multipoint RIA that measure-; airborne 3RIA-32 Building; sample points are located activity levels in various locations (up to 24) in various room/areas throughout the through the Aux Building. Used to plan Aux Building sampling and chemical addition activities.

See Ene. 6 2 for sample point locations.

.1 RIAs of Interest to Chemistry Chemistry Manual 5.2 Page 2 of 2 RIA #

RANGE LOCATION INFORMATION USED FOR 1RIA-35 10 - 10e6 CPM Behind air compressors in Turbine Monitors LPSW discharge from the 2RIA-35 Building Basement, west of Unit 2 Building. Readings> background are Powdex indicators of primary coolant leak into the 3RIA-35 Same location as 3RIA-31 LPSW System; RIA-31 readings will increase also.

1RIA-40 10 - 10e6 CPM Unit 1 CSAE Off Gas Discharge Monitors CSAE Off Gas effluent to each unit 2RIA-40 Unit 2 CSAE Off Gas Discharge vent. Indicates steam generator tube leaks.

3RIA-40 Unit 3 CSAE Off Gas Discharge 1,2,3 RIA-1 - 10e7 R/hr Unit 1 Reactor Building Measures activity in the Rx building during a 57&58 Unit 2 Reactor Building LOCA. Readings from these RIAs can be Unit 3 Reactor Building related to % failed fuel.

.2 Location of Sample Points for Multipoint RIAs Chemistry Manual 5.2 Page 1 of 2 1RIA-31 SAMPLE POINTS IRIA-31-1 1RIA-31-2 1RIA-31-3 IRIA-31-4 1RIA-31-5 1RIA-31-6 1RIA-31-7 1RIA-31-8 1RIA-31-9 1RIA-31-10 1 RIA-3 1-11 1RIA-31-12 LPI/Decay Heat Cooler IA Outlet LPI/Decay Heat Cooler 1B Outlet RB Component Cooler 1A Outlet RB Ventilation (Cooling) Unit IA Outlet RB Ventilation (Cooling) Unit 1B Outlet RB Ventilation (Cooling) Unit IC Outlet LPI/Decav Heat Cooler 2A Outlet LPI/Decay Heat Cooler 2B Outlet RB Component Cooler 2B Outlet RB Ventilation (Cooling) Unit 2A Outlet RB Ventilation (Cooling) Unit 2B Outlet RB Ventilation (Cooling) Unit 2C Outlet LPI/Decay Heat Cooler 3A Outlet LPI/Decay Heat Cooler 3B Outlet RB Component Cooler 3B Outlet RB Ventilation (Cooling) Unit 3B Outlet RB Ventilation (Cooling) Unit 3A Outlet RB Ventilation (Cooling) Unit 3C Outlet 1RIA-32-1 1RIA-32-2 IRIA-32-3 1RIA-32-4 1RIA-32-5 IRIA-32-6 1RIA-32-7 1RIA-32-8 1RIA-32-10 IRIA-32-11 1RIA-32-12 Unit I Pipe Rooms; Elevation 758 and 771 Unit 2 Pipe Rooms; Elevation 758 and 771 Spent Resin Storage Tanks, Condensate Test Tanks, Unit 1 Letdown Storage Tank, Boric Acid Mix Tank RC Bleed Evaporator Room, Unit 1&2 Miscellaneous Waste Holdup Tank, Unit 2 Letdown Storage Tank Waste Drumming Area Miscellaneous Waste Evaporator Room Unit 1 RC Bleed Transfer Pump, Unit 1 RC Bleed Holdup Tanks, Unit 1 Concentrated Boric Acid Storage Tank Unit 2 RC Bleed Transfer Pump, Unit 2 RC Bleed Holdup Tanks, Unit 2 Concentrated Boric Acid Storage Tank Waste Gas Compressor, RC Bleed Evaporator Feed Tank Unit 1 Pipe Rooms; Elevations 783-796 Unit 2 Pipe Rooms; Elevations 783-796 3RIA-31 SAMPLE POINTS 3RIA-31-1 3RIA-31-2 3RIA-31-3 3RIA-31-4 3RIA-31-5 3RIA-31-6 IRIA-32 SAMPLE POINTS

.2 Location of Sample Points for Multipoint RIAs Chemistry Manual 5.2 Page 2 of 2 3RIA-32 SAMPLE POINTS 3RIA-32-1 Unit 3 Pipe Rooms; Elevation 758 and 771 3RIA-32-2 Unit 3 Pipe Rooms; Elevations 783-796 3RIA-32-3 RB Component Coolers, Letdown Filters, Hatches, Waste Gas Compressor Room, Waste Gas Decay Tanks 3RIA-32-4 Unit 3 RC Bleed Holdup Tanks, Unit 3 Concentrated Boric Acid Storage Tank, Unit 3 Miscellaneous Waste Holdup Tank Area 3RIA-32-5 High Activity Spent Resin Storage Tank, Boric Acid Mix Tank and Pumps, Spent Resin Storage Tank Area

.3 Chemistry Manual 5.2 Caustic Addition Calculations Page I of 3

1. Initial Conditions for Injection 1.1 An emergency is in effect due to a LOCA.

1.2 The Low Pressure Injection (LPI) system is in operation with the LPI pumps taking suction from the BWST.

1.3 The Reactor Building Emergency Spray system may or may not be in operation from the BWST through the spray headers.

1.4 The addition of caustic SHALL begin WITHIN thirty (30) minutes AFTER switchover to the recirculation mode of core cooling. The recirculation mode is in effect whenever the suction for the LPI pumps' is aligned to the Reactor Bldg. Emergency Sump.

1.5 The addition of caustic will be made upon authorization of the TSC/OSC, or upon notification by Operations when the TSC/OSC has not yet been activated.

2. Bases for Caustic Addition Calculations 2.1 Calculations for the amount of caustic required for neutralization of the borated water are dependent on:

2.1.1 An accurate estimation of the volume of borated water being used as the core flooding coolant; 2.1.2 The boron concentration of the core flooding coolant; 2.1.3 One (1) pound of caustic neutralizing seventeen (17) pounds of H3BO3 to a pH of 7.5.

2.2 If the total volumes of the CFTs and BWST are used, then the maximum amount of caustic required for neutralization of the borated water to a pH of 7.5 is 700 gallons. The amount of 700 gallons has been calculated with the following considerations:

2.2.1 Both CFTs and the BWST have a total volume of 403,000 gallons with a boron concentration of 2300 ppm; 2.2.2 The RCS has a volume of 88,000 gallons with a boron concentration of 1000 ppm.

2.3 Boric Acid for the purposes of these calculations behaves as a simple monoprotic acid.

.3 Caustic Addition Calculations Chemistry Manual 5.2 Page 2 of 3

3. Calculations of the Amount of Caustic required for Neutralization to a pH of 7.5 Based on Core Flooding Coolant Boron Content.

NOTE:

Calculate the quantity of caustic as outlined below or use the computer program by opening DAE, Department Applications, Nuclear Generation, Oconee Desktop; Oconee Information Library; Chemistry Information Library; CUG-S-19-Caustic.

Date Time Unit By CFr 'A' Boron BWST Boron CFT 'B' Boron BWST Vol. dumped to RCS 3.1 The 2 CFT's have a total volume of 15,000 gal. Average the most recent boron results for the A&B CFF's and enter the average into the equation below. Calculate the (lbs of)

H3B0 3 in the CFT's:

Lbs. CFr H3B0 3 =

(

ppm) (15,000 gal) (8.34 lbs/gal) =

(1 x 106) (0.175) 3.2 The RCS has a volume of '08.000 gal. Calculate the lbs. H3BO3 in the RCS:

Lbs. RCS H3B0 3 =

ppm) (88,000 gal) (8.34 lbs/gal) =

(1 x 106) (0.175) 3.3 The BWST has a total volume of 388,000 gal. Obtain from Operations an estimate of the volume of borated water that has been dropped from the BWST:

gal.

Calculate the lbs. H 3B0 3 added to the core from the BWST:

Lbs. BWST H3B0 3 = (

ppmn gal) (8.34 lbs/gal) =

(1 x 106) (0.175) 3.4 Calculate the Gal. NaOH required to adjust the borated water of the CFT's and the RCS to 7.5.

Gal. 35%

NaOH required = (1 lb NaOH) (lbs CFT H3BMM

+ lbs RCS HMMBO, + lbs BWST H BO 3BO) (I1 Gal 35% NaOH)

(17 lbs H3B03) (4 lbs Na0il)

= _Gallons 3.5 For the initial caustic addition, it is recommended that only half of the calculated amount should be added. Note that if using the computer program to calculate the initial addition, the results have already been halved. This is clearly stated by the computer program. Record the actual amount to be added below.

Amount of 35% NaOH to add gallons.

RCS Boron

.3 Chemistry Manual 5.2 Caustic Addition Calculations Page 3 of 3

4. Calculation of the amount of 35 % caustic required for neutralization of a pH between 7.0 and 8.0 based on core flooding coolant actual pH.

NOTE:

Calculate as outlined below or use the computer program by opening DAE, Department Applications, Nuclear Generation, Oconee Desktop; Oconee Information Library; Chemistry Information Library; CUG-S-19-Caustic.

Date Time Unit By 4.1 Core Coolant pH 4.2 Core Coolant Boron Concentration (approximately) in ppm is 4.3 Core Coolant Volume (RCS, BWST vol. dumped, CFTs) in gallons is 4.4 Calculate the volume of 35% NaOH required to adjust the core coolant water to a pH between 7.0 and 8.0.

35% NaOH = ((4.7 x 10 1.6 x 10' 3/10Pn)ppm B p1 + 10pH-14)

  • V
  • 0.0829 to Add
Where, Gallons

=

Volume in gallons of 35% NaOH to add to the Reactor Coolant B

=

Reactor Coolant boron concentration in ppm V

=

Volume of reactor cooling water (including BWST. CFT', etc.) in gallons 8.29 x 10.2 =

Conversion Factor pH

=

Actual measured pH of reactor coolant water.

Gals 35% NaOH =

Gallons NOTE:

1. This volume does not account for the associated piping volume between the caustic injection tank and the suction of the low pressure injection pump.
2. If reactor coolant pH is between 7.0 and 8.0, this fomula "MAY" produce a negative number which means that no caustic addition is necessary.

.4 Chemistry Manual 5.2 E, A and R Values for Page 1 of 1 1% Failed Fuel and DBA I% Failed Fuel:

E - 0.34 MeV/dis.

A - 0.293 mCi/ml R = 0.18 mR/hr-mCi at Im for E - 0.34 MeV 100% Failed Fuel or Design Basis Accident (DBA):

E - 1.14 MeV/dis.

A - 1.324 x 105 uCi/mL R = 0.58 R/hr-Ci at Im for E - 1.14 MeV A direct proportion should exist between E and R for any failed fuel value > 1% and < 100%.

.5 Chemistry Manual 5.2 Technical Basis for Page 1 of 3 Caustic Addition Calculations Initial Addition Based on Pounds of Boric Acid:

The initial addition is based on the ability of one pound of caustic to neutralize 17 pounds of boric acid. This value was calculated using the methodology described in the Babcock & Wilcox Water Chemistry Manual (BAW-1385), Section 8 (1990 revision) and was confirmed by benchtop titration studies. Please reference Memo to File, dated 1-24-96, "Results of Caustic Titration Study", File

  1. OS-715.00 for further details.

Subsequent Additions Based on Measured pH:

The basic assumption is that boric acid (H3BO3) behaves as a simple monoprotic acid versus the complex monoprotic acid that it is. Thus, it was assumed that when boric acid is placed in water only the H2B0 3 borate ion is produced. Typically, boric acid in water will produce 3 to 4 different borate ions (Ref.: B&W or Westinghouse literature on boric acid). The equation will therefore read as follows:

H3BO 3 <--> H+ +

H 2BO3 where the acid dissociation constant (Ka) equation would be Ka =

{H 2BO 3 "} {H'}

(Eqn. L)

{H3BO 3}

The pH equations for the hydrogen and hydroxyl ion are as follows:

pH = -Log{H+}

(Eqn. 2) 10-14 = {H÷} {OH)

(Eqn. 3)

For calculation simplification purposes, it is assumed that the only species contributing to the neutralization equation listed below are NaOH, H3BO3, and H20:

{Na÷} + {H+} -

{101} -

{H2BO3 } = 0 (Eqn. 4)

By substituting Equations 1, 2, and 3 above into equation 4 and solving for the sodium ion concentration, the amount of caustic added to the reactor coolant water can be determined given the system pH. The equation would be:

{Na+}

= Ka{H 3BO 31/(10"pH) +

1 0 14-ptq

_ IO-PH (Eqn. 5)

.5 Chemistry Manual 5.2 Technical Basis for Page 2 of 3 Caustic Addition Calculations Since it is desired to adjust the system pH to a point between 7.0 and 8.0, then the desired amount of sodium necessary to achieve a system pH of 7.5 can be determined by solving equation 5 above for a pH equal to 7.5. Therefore, subtracting the sodium concentration calculated at the actual system pH from the sodium concentration at the desired pH of 7.5 yields the amount of sodium necessary for pH adjustment.

At a pH of 7.0, the terms 10-P and 1 0 14-pH cancel each other. This leaves the following equation:

(Na+}

= (Ka'{H 3BO3 )/(10-PH)) - (Ka{H 3BO3 }(1 0-PH)

(Eqn. 6)

+

10pH-14_

1 0 -PH) where " represents the terms for when pH is 7.0.

Substituting A for the term Ka/(10PH') and B for Ka the above equation becomes,

{Nae} = (A - B/(10PH)) {H3BO3 } -

1 0 pH'14 (Eqn. 7)

+

I10"pH Next, using conversion factors and solving for sodium in terms of gallons of 35% NaOH to add, the equation becomes, 35% NaOH = ((A-B/(10-pn))ppm B - 10 pH-14 + 1 0 -pH)

(Eqn. 8) to Add (Gallons)

  • V*0.0829
where, ppm B

= boron concentration of reactor cooling water V

= volume of reactor cooling water to pH adjust, gallons pH

= pH of reactor cooling water after making initial caustic add 0.0829

= conversion factor A & B

= coefficients for boric acid dissociation constants at 250 C.

The 0.0829 conversion factor came from the conversion of Na ion concentration to gallons of 35%

NaOH. The number was reached by the following equations:

Gallons

= (moles Na / liters soln.) * (gals soln.) * (1 mole NaOH / 1 mole Na) 35%

  • 35% NaOH (3.785 liters soln. / 1 gal soln.) * (40.01 gms NaOH / 1 mole NaOH) * (100 grns soln. / 35 gms NaOH) * (I cubic centimeter / 1.38 gms) * (1 liter 35% naOH /

1000 cubic centimeters 35% NaOH) * (1 gal 35% NaOH / 3.785 liters 35% NaOH)

Gallons

= (moles Na I liters soln.) * (gals soln.)

  • 0.0829 35% NaOH (liter soln.
  • gal 35% NaOH) / (gal soln.
  • moles Na)

.5 Chemistry Manual 5.2 Technical Basis for Page 3 of 3 Caustic Addition Calculations The initial guesses for the A and B coefficients were calculated from apparent monoprotic dissociation constants using a pH - specific conductivity computer program. The initial coefficients were A = 9 x 10-6 and B = 3.09 x 10- 3. Laboratory data was then utilized to fine tune the coefficients. Titrations of various boron concentrations resulted in coefficients A = 4.7 x 10-6 and B

= 1.6 x 1013. Thus, the formula for calculating the quantity of caustic to add based on pH as shown in Enc. 6.3 is:

35% NaOH = ((4.7 x 10 1.6 x 10-13/10pH)ppm B (Eqn. 9) to Add

-10pH +

1 0 pH.14)

  • V
  • 0.0829

Reference:

Memo to File, dated 5/29/89, "pH Adjustment of Reactor Coolant During a LOCA Using Sodium Hydroxide", File #OS-715.00.

.6 Chemistry Manual 5.2 Quarterly Inspection of Page 1 of I Post Accident Equipment

1.

Caustic addition equipment stored in the brown cabinet in AB, 2nd floor -10 ft North of 1 & 2 Chemical Addition Area:

Goggles Face shield Bung Wrench Corrosive suit Gloves Flashlight Boots Stainless steel flex hose Tank to valve adapter Tape measure

2. Appendix 'R' sampling apparatus stationed in each units respective LPI room:

UNITS 1 (RM-61) 2 (RM-63) 3 (RM-82)

Sample cooler Ice container (30 gal. drum)

Glass thermometer Plastic liter bottles (3)

Tygon tubing for cooler ( 13/4", 2 1/4")

Adjustable wrench 250 mL disposable beaker Hose isolation clamp