ECCS Instrumentation 3.3.5.1 Table 3.3.5.1-1 (page 3 of 6)

Emergency Core Cooling System Instrumentation APPLICABLE CONDITIONS MODES OR REFERENCED OTHER REQUIRED FROM SPECIFIED CHANNELS PER REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS FUNCTION ACTION A.1 REQUIREMENTS VALUE 2.LPCI System (continued)

f.

Manual Initiation

3.

High Pressure Coolant Injection (HPCI)

System

a. Reactor Vessel Water Level-Low, Level 2
b. Drywell Pressure High
c. Reactor Vessel Water Level-High, Level 8
d. Condensate Storage Tank Level-Low 2

1 per subsystem 4

4 2

2 C

SR 3.3.5.1.5 B

SR 3.3.5.1.1 SR 3.3.5.1.2 SR 3.3.5.1.4 SR 3.3.5.1.5 B

SR 3.3.5.1.2 SR 3.3.5.1.3 SR 3.3.5.1.5 C

SR 3.3.5.1.2 SR 3.3.5.1.3 SR 3.3.5.1.5 D

SR 3.3.5.1.2 SR 3.3.5.1.3 SR 3.3.5.1.5 NA

> -45 inches

  • 1.88 psig
  • 55.5 inches

_ 36.0 inches above tank bottom (a) When the associated subsystem(s) are required to be OPERABLE.

(e)

With reactor steam dome pressure > 150 psig.

SUSQUEHANNA - UNIT 1 3.3-44 Amendment No.

-- 8, 204 1,2,3, 4(a), 5(a) 1, 2(e), 3(e) 1, 2(e),3(e) 1, 2(e), 3(e) 1, 2(e), 3(e)

ECCS Instrumentation 3.3.5.1 Table 3.3.5.1-1 (page 4 of 6)

Emergency Core Cooling System Instrumentation APPLICABLE CONDITIONS MODES OR REFERENCED OTHER REQUIRED FROM SPECIFIED CHANNELS PER REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS FUNCTION ACTION A.1 REQUIREMENTS VALUE

3.

HPCI System (continued)

e. Manual Initiation
4.

Automatic Depressurization System (ADS) Trip System A

a. Reactor Vessel Water Level--Low Low Low, Level 1
b. Drywell Pressure High
c. Automatic Depressurization System Initiation Timer
d. Reactor Vessel Water Level-Low, Level 3 (Confirmatory)
e. Core Spray Pump Discharge Pressure-High C

SR 3.3.5.1.5 1,

2(e), 3(e) 1, 2(e), 3(e) 1, 2(e), 3(e) 1, 2(e), 3(e) 1, 2(e), 3(e) 1, 2(e), 3(e) 2 2

2 E

SR 3.3.5.1.1 SR 3.3.5.1.2 SR 3.3.5.1.4 SR 3.3.5.1.5 E

SR 3.3.5.1.2 SR 3.3.5.1.3 SR 3.3.5.1.5 F

SR 3.3.5.1.2 SR 3.3.5.1.3 SR 3.3.5.1.5 E

SR 3.3.5.1.1 SR 3.3.5.1.2 SR 3.3.5.1.4 SR 3.3.5.1.5 F

SR 3.3.5.1.2 SR 3.3.5.1.3 SR 3.3.5.1.5 NA

> -136 inches

  • 1.88 psig

< 114 seconds

> 11.5 inches

> 125 psig and

!5 165 psig (continued)

(e)

With reactor steam dome pressure > 150 psig.

SUSQUEHANNA - UNIT 1 Amendment No.

174, 204 1

1 3.3-45

ECCS Instrumentation 3.3.5.1 Table 3.3.5.1-1 (page 5 of 6)

Emergency Core Cooling System Instrumentation APPLICABLE CONDITIONS MODES OR REFERENCED OTHER REQUIRED FROM SPECIFIED CHANNELS PER REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS FUNCTION ACTION A.1 REQUIREMENTS VALUE

4.

ADS Trip System A (continued)

f.

Low Pressure Coolant Injection Pump Discharge Pressure-High

g.

Automatic Depressurization System Drywell Pressure Bypass Actuation Timer

h.

Manual Initiation

5.

ADS Trip System B

a.

Reactor Vessel Water Level Low Low Low, Level 1

b.

Drywell Pressure-High

c.

Automatic Depressurization System Initiation Timer

d.

Reactor Vessel Water Level-Low, Level 3 (Confirmatory)

e.

Core Spray Pump Discharge Pressure-High 1,

2(e), 3(e) 1, 2(e), 3(e) 1, 2(e), 3(e) 1, 2(e), 3(e) 1, 2(e), 3(e) 1, 2(e), 3(e) 1, 2(e), 3(e) 1, 2(e), 3(e) 2 2

2 2

2 2

F SR 3.3.5.1.2 SR 3.3.5.1.3 SR 3.3.5.1.5 F

SR 3.3.5.1.2 SR 3.3.5.1.3 SR 3.3.5.1.5 F

SR 3.3.5.1.5 E

SR 3.3.5.1.1 SR 3.3.5.1.2 SR 3.3.5.1.4 SR 3.3.5.1.5 E

SR 3.3.5.1.2 SR 3.3.5.1.3 SR 3.3.5.1.5 F

SR 3.3.5.1.2 SR 3.3.5.1.3 SR 3.3.5.1.5 E

SR 3.3.5.1.1 SR 3.3.5.1.2 SR 3.3.5.1.4 SR 3.3.5.1.5 F

SR 3.3.5.1.2 SR 3.3.5.1.3 SR 3.3.5.1.5

> 115 psig and

<135 psig

<450 sec NA

> -136 inches

< 1.88 psig

_ 114 sec

>11.5 inches

> 125 psig and f: 165 psig (continued)

(e)

With reactor steam dome pressure > 150 psig.

SUSQUEHANNA - UNIT 1 3.3-46 Amendment No.

1-78 204

ECCS Instrumentation 3.3.5.1 Table 3.3.5. 1-1 (page 3 of 5)

Emergency Core Cooling System Instrumentation APPLICABLE CONDITIONS MODES OR REFERENCED OTHER REQUIRED FROM SPECIFIED CHANNELS PER REQUIRED SURVEILLANCE ALLOWABLE FUNCTION CONDITIONS FUNCTION ACTION A.1 REQUIREMENTS VALUE

3. High Pressure Coolant Injection (HPCI)

System

a. Reactor Vessel 1,

4 B

SR 3.3.5.1.1

>-45inches Water Level--Low 2(e), 3(e)

SR 3.3.5.1.2 Low, Level 2 SR 3.3.5.1.4 SR 3.3.5.1.5

b. Drywell Pressure-1,4 B

SR 3.3.5.1.2

< 1.88 psig High 2(e),3(e)

SR 3.3.5.1.3 SR 3.3.5.1.5

c.

Reactor Vessel 1

2 C

SR 3.3.5.1.2

<55.5 inches Water Level--

2(e), 3(e)

SR 3.3.5.1.3 High, Level 8 SR 3.3.5.1.5

d. Condensate 1,

2 D

SR 3.3.5.1.2

>36.0 inches Storage Tank 2(e), 3(e)

SR 3.3.5.1.3 above tank bottom Level--Low SR 3.3.5.1.5

e. Manual Initiation 1,

1 D

SR 3.3.5.1.5 NA 2(e), 3(e)

(continued)

(a) When the associated subsystem(s) are required to be OPERABLE.

(e)

With reactor steam dome pressure > 150 psig.

SUSQUEHANNA - UNIT 2 TS / 3.3-45 Amendment No.

178