ML021890567
| ML021890567 | |
| Person / Time | |
|---|---|
| Site: | Salem |
| Issue date: | 07/09/2002 |
| From: | Robert Fretz NRC/NRR/DLPM/LPD1 |
| To: | Keiser H Public Service Enterprise Group |
| Fretz, R, NRR/DLPM, 415-1324 | |
| References | |
| TAC MB2792, TAC MB2793 | |
| Download: ML021890567 (4) | |
Text
July 9, 2002 Mr. Harold W. Keiser Chief Nuclear Officer & President PSEG Nuclear LLC - X04 Post Office Box 236 Hancocks Bridge, NJ 08038
SUBJECT:
SALEM NUCLEAR GENERATING STATION, UNIT NOS. 1 AND 2, REQUEST FOR ADDITIONAL INFORMATION RE: REQUEST FOR CHANGE TO TECHNICAL SPECIFICATION 3.6.2.3 CONTAINMENT COOLING SYSTEM (TAC NOS. MB2792 AND MB2793)
Dear Mr. Keiser:
By letter dated August 17, 2001, PSEG Nuclear LLC submitted a request for a revision to Technical Specification (TS) 3.6.2.3, Containment Cooling System, at the Salem Nuclear Generating Station, Unit Nos. 1 and 2 (Salem). The proposed TS change would modify the acceptance criterion for the service water flow rate through the Containment Fan Coil Units.
The U.S. Nuclear Regulatory Commission staff is reviewing your request and has determined that additional information is necessary in order to complete its evaluation. We discussed the enclosed request for additional information with your staff during a telephone call on July 2, 2002. During the call, you agreed to respond to this letter within 30 days from the date of this letter. If circumstances result in the need to revise the target date, please contact me at (301) 415-1324, understanding that a delay in your response is likely to adversely affect our review schedule.
Sincerely,
/RA/
Robert J. Fretz, Project Manager, Section 2 Project Directorate I Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket Nos. 50-272 and 50-311
Enclosure:
Request for Additional Information cc w/encl: See next page
ML021890567 OFFICE PDI-2/PM PDI-2/LA PDI-2/SC NAME RFretz TLClark JClifford DATE 07/08/02 7/9/02 7/9/02 ENCLOSURE REQUEST FOR ADDITIONAL INFORMATION REQUEST FOR CHANGE TO TECHNICAL SPECIFICATION 3.6.2.3 CONTAINMENT COOLING SYSTEM SALEM NUCLEAR GENERATING STATION, UNIT NOS. 1 AND 2 By letter dated August 17, 2001, PSEG Nuclear LLC submitted a request for a revision to Technical Specification (TS) 3.6.2.3, Containment Cooling System, at the Salem Nuclear Generating Station, Unit Nos. 1 and 2 (Salem). The proposed TS change would modify the acceptance criterion for the service water flow rate through the Containment Fan Coil Units (CFCUs). The U.S. Nuclear Regulatory Commission staff is reviewing your request and has determined that additional information is necessary in order to complete its evaluation., Page 4 of 5, Paragraphs 1 and 4:
(1)
Briefly explain how fouling on CFCUs is monitored and controlled to remain at or below the value of 0.00285 hr deg-F ft-sq/Btu. In particular, how often is fouling on CFCUs determined? Is the measurement of fouling on all CFCUs performed during the same plant outage? If not, could some measurements of fouling on CFCUs exceed limits while others do not?
PSEG Nuclear LLC Salem Nuclear Generating Station, Unit Nos. 1 and 2 cc:
Mr. Elbert C. Simpson Senior Vice President &
Chief Administrative Officer PSEG Nuclear - N19 P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. Mark B. Bezilla Vice President - Technical Support PSEG Nuclear - N10 P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. David F. Garchow Vice President - Operations PSEG Nuclear - X10 P.O. Box 236 Hancocks Bridge, NJ 08038 Mr. Gabor Salamon Manager - Nuclear Safety and Licensing PSEG Nuclear - N21 P.O. Box 236 Hancocks Bridge, NJ 08038 Jeffrie J. Keenan, Esquire PSEG Nuclear - N21 P.O. Box 236 Hancocks Bridge, NJ 08038 Ms. R. A. Kankus Joint Owner Affairs PECO Energy Company Nuclear Group Headquarters KSA1-E 200 Exelon Way Kennett Square, PA 19348 Lower Alloways Creek Township c/o Mary O. Henderson, Clerk Municipal Building, P.O. Box 157 Hancocks Bridge, NJ 08038 Dr. Jill Lipoti, Asst. Director Radiation Protection Programs NJ Department of Environmental Protection and Energy CN 415 Trenton, NJ 08625-0415 Richard Hartung Electric Service Evaluation Board of Regulatory Commissioners 2 Gateway Center, Tenth Floor Newark, NJ 07102 Regional Administrator, Region I U.S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406 Senior Resident Inspector Salem Nuclear Generating Station U.S. Nuclear Regulatory Commission Drawer 0509 Hancocks Bridge, NJ 08038