March 28, 2002 Mr. Harold B. Ray Executive Vice President Southern California Edison Company San Onofre Nuclear Generating Station P.O. Box 128 San Clemente, CA 92674-0128

SUBJECT:

SAN ONOFRE NUCLEAR GENERATING STATION (SONGS), UNIT 2 -

UPCOMING STEAM GENERATOR TUBE INSERVICE INSPECTION (TAC NO.

MB4659)

Dear Mr. Ray:

Inservice inspections of steam generator (SG) tubes play a vital role in assuring that adequate structural integrity of the tubes is maintained. As required by the plant Technical Specifications, reporting requirements range from submitting a special report, within 15 days following completion of each inservice inspection of SG tubes, that identifies the number of tubes plugged and/or repaired; to submitting a special report, within 12 months following completion of the inspection, that provides complete results of the SG tube inservice inspection. The special report containing the complete results shall include the following:

1.

Number and extent of tubes inspected.

2.

Location and percent of wall-thickness penetration for each indication of an imperfection.

3.

Identification of tubes plugged and/or repaired.

A phone conference has been arranged with members of your staff to discuss the ongoing results of the SG tube inspections to be conducted during the upcoming SONGS Unit 2 refueling outage. This phone call will occur after the majority of the tubes have been inspected, but before the SG inspection activities have been completed. Enclosed is a list of discussion points to facilitate this phone conference.

H. Ray In response to a recommendation made in the NRCs Indian Point 2 (IP2) Lessons Learned Task Group report, the NRC staff plans to document a brief summary of the conference call as well as any material that you may have provided to the NRC staff in support of the call.

Sincerely,

/RA/

L. Raghavan, Senior Project Manager, Section 2 Project Directorate IV Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket No. 50-362

Enclosure:

As stated cc w/encl:

See next page

H. Ray In response to a recommendation made in the NRCs Indian Point 2 (IP2) Lessons Learned Task Group report, the NRC staff plans to document a brief summary of the conference call as well as any material that you may have provided to the staff in support of the call.

Sincerely,

/RA/

L. Raghavan, Senior Project Manager, Section 2 Project Directorate IV Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket Nos. 50-361 and 50-362

Enclosure:

As stated cc w/encl:

See next page DISTRIBUTION PUBLIC PDIV-2 r/f RidsNrrDlpmLpdiv (S.Richards)

RidsNrrPMLRaghavan RidsNrrLAMMcAllister RidsNrrDripRorp (R.Dennig) RidsAcrsAcnwMailCenter RidsOgcRp Ted Sullivan CLauron ZFu RidsRgn4MailCenter (K. Kennedy, L. Hurley, D. Bujol)

ACCESSION NO: ML020940039 OFFICE PDIV-2/PM PDIV-1/LA EMCB PDIV-2/SC NAME LRaghavan MMcAllister LLund for:

ESullivan JDonohew forSDembek DATE 3/28/02 3/28/02 3/28/02 3/28/02 OFFICIAL RECORD COPY

STEAM GENERATOR TUBE INSPECTION DISCUSSION POINTS PREPARED BY THE OFFICE OF NUCLEAR REACTOR REGULATION SOUTHERN CALIFORNIA EDISON COMPANY SAN ONOFRE NUCLEAR GENERATING STATION, UNIT 2 DOCKET NO. 50-362 The following discussion points have been prepared to facilitate the phone conference arranged to discuss the results of the SG tube inspections to be conducted during the upcoming SONGS, Unit 2 refueling outage. This phone call is scheduled to occur towards the end of the planned SG tube inspection interval, but before the unit exits its refueling outage.

It is our expectation that any significant results or relevant trends discussed during the phone conference, as well as any materials provided by your staff to assist us during the phone conference in the understanding of the SG tube results, will be included in one of the special reports required by the plant Technical Specifications.

1.

Discuss whether any primary to secondary leakage existed in this unit prior to shutdown.

2.

Discuss the results of secondary side hydrostatic tests.

3.

For each steam generator (SG), provide a general description of areas examined, including the expansion criteria utilized and type of probe used in each area.

4.

For analyzed eddy current results, describe bobbin indications [those not examined with rotating pancake coil (RPC)] and RPC/Plus Point/Cecco indications. Include the following information in the discussion: location, number, degradation mode, disposition, and voltages/depths/lengths of significant indications.

5.

Describe repair/plugging plans for the SG tubes that meet the repair/plugging criteria.

6.

Discuss the previous history of SG tube inspection results, including any "look backs" performed.

7.

Discuss, in general, the new inspection findings.

8.

Describe in-situ pressure test plans and results, if applicable and available, including tube selection criteria.

9.

Describe tube pull plans and preliminary results, if applicable and available; include tube selection criteria.

10.

Discuss the assessment of tube integrity for the previous operating cycle.

11.

Discuss the assessment of tube integrity for next operating cycle.

12.

Provide the schedule for SG-related activities during the remainder of the current outage.

13.

Discuss what steps have been taken, or will be taken, in response to the lessons learned from the IP2 tube failure. In addition, please be prepared to discuss the following:

(a)

Discuss the actions that are taken in response to identifying a new degradation mechanism, (b)

Discuss the actions taken to ensure that data noise levels are acceptable, and (c)

Address data quality issues and the need for criteria to address data quality.

December 17, 2001 San Onofre Nuclear Generating Station, Units 2 and 3 cc:

Mr. R. W. Krieger, Vice President Southern California Edison Company San Onofre Nuclear Generating Station P. O. Box 128 San Clemente, CA 92674-0128 Mr. Douglas K. Porter Southern California Edison Company 2244 Walnut Grove Avenue Rosemead, CA 91770 Mr. David Spath, Chief Division of Drinking Water and Environmental Management P. O. Box 942732 Sacramento, CA 94234-7320 Chairman, Board of Supervisors County of San Diego 1600 Pacific Highway, Room 335 San Diego, CA 92101 Eileen M. Teichert, Esq.

Supervising Deputy City Attorney City of Riverside 3900 Main Street Riverside, CA 92522 Mr. Gary L. Nolff Power Projects/Contracts Manager Riverside Public Utilities 2911 Adams Street Riverside, CA 92504 Regional Administrator, Region IV U.S. Nuclear Regulatory Commission 611 Ryan Plaza Drive, Suite 400 Arlington, TX 76011-8064 Mr. Michael Olson San Onofre Liaison San Diego Gas & Electric Company P.O. Box 1831 San Diego, CA 92112-4150 Mr. Steve Hsu Radiologic Health Branch State Department of Health Services Post Office Box 942732 Sacramento, CA 94327-7320 Mr. Ed Bailey, Radiation Program Director Radiologic Health Branch State Department of Health Services Post Office Box 942732 (MS 178)

Sacramento, CA 94327-7320 Resident Inspector/San Onofre NPS c/o U.S. Nuclear Regulatory Commission Post Office Box 4329 San Clemente, CA 92674 Mayor City of San Clemente 100 Avenida Presidio San Clemente, CA 92672 Mr. Dwight E. Nunn, Vice President Southern California Edison Company San Onofre Nuclear Generating Station P.O. Box 128 San Clemente, CA 92674-0128 Mr. Robert A. Laurie, Commissioner California Energy Commission 1516 Ninth Street (MS 31)

Sacramento, CA 95814