Meeting Summary to Discuss Digital Upgrades to the Keowee Hydro Units Held on December 5, 2001
ML020840725
Person / Time
Site: Oconee  
(DPR-038, DPR-047, DPR-055)
Issue date: 04/01/2002
From: Olshan L
NRC/NRR/DLPM/LPD2
To:
Olshan L N, NRR/DLPM, 415-1419
References
Download: ML020840725 (4)


Text

April 1, 2002 LICENSEE:

DUKE ENERGY CORPORATION FACILITY:

OCONEE NUCLEAR STATION, UNITS 1, 2 AND 3

SUBJECT:

MEETING

SUMMARY

TO DISCUSS DIGITAL UPGRADES TO THE KEOWEE HYDRO UNITS On December 5, 2001, the Nuclear Regulatory Commission (NRC) met with Duke Energy (the licensee) to discuss digital upgrades to the Keowee hydro units for Oconee Nuclear Station, Units 1, 2, and 3. Enclosed is a list of the meeting attendees. The handout provided by the licensee is accessible electronically from the Agencywide Documents Access and Management System (ADAMS) Public Electronic Reading Room on the internet at the NRC Web site, http://www.nrc.gov/reading-rm/adams/html under ADAMS accession number ML013400318. Persons who do not have access to ADAMS or who encounter problems in accessing the documents located in ADAMS, should contact the NRC PDR Reference staff by telephone at 1-800-397-4209 or 301-415-4737, or by e-mail to pdr@nrc.gov.

The licensee is planning to replace the Keoowee hydro units mechanical flywheel governor and static exciter/regulator, which are obsolete, with digital components. The licensee stated that these digital components will improve reliability, but the NRC questioned the ability of the licensee to demonstrate this improved reliability. The licensee believes that this replacement with digital components can be accomplished under the provisions of 10 CFR 50.59, which means that no NRC approval is required. The licensee is planning to begin the replacement in the spring of 2003.

/RA/

Leonard N. Olshan, Project Manager, Section 1 Project Directorate II Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket Nos. 50-269, 50-270 and 50-287

Enclosure:

As stated cc w/encl: See next page

April 1, 2002 LICENSEE:

DUKE ENERGY CORPORATION FACILITY:

OCONEE NUCLEAR STATION, UNITS 1, 2 AND 3

SUBJECT:

MEETING

SUMMARY

TO DISCUSS DIGITAL UPGRADES TO THE KEOWEE HYDRO UNITS On December 5, 2001, the Nuclear Regulatory Commission (NRC) met with Duke Energy (the licensee) to discuss digital upgrades to the Keowee hydro units for Oconee Nuclear Station, Units 1, 2, and 3. Enclosed is a list of the meeting attendees. The handout provided by the licensee is accessible electronically from the Agencywide Documents Access and Management System (ADAMS) Public Electronic Reading Room on the internet at the NRC Web site, http://www.nrc.gov/reading-rm/adams/html under ADAMS accession number ML013400318. Persons who do not have access to ADAMS or who encounter problems in accessing the documents located in ADAMS, should contact the NRC PDR Reference staff by telephone at 1-800-397-4209 or 301-415-4737, or by e-mail to pdr@nrc.gov.

The licensee is planning to replace the Keoowee hydro units mechanical flywheel governor and static exciter/regulator, which are obsolete, with digital components. The licensee stated that these digital components will improve reliability, but the NRC questioned the ability of the licensee to demonstrate this improved reliability. The licensee believes that this replacement with digital components can be accomplished under the provisions of 10 CFR 50.59, which means that no NRC approval is required. The licensee is planning to begin the replacement in the spring of 2003.

/RA/

Leonard N. Olshan, Project Manager, Section 1 Project Directorate II Division of Licensing Project Management Office of Nuclear Reactor Regulation Docket Nos. 50-269, 50-270 and 50-287

Enclosure:

As stated cc w/encl: See next page DISTRIBUTION:

PUBLIC RLaufer OGC DMcCain PDII-1 R/F LOlshan EMarinos SRosenberg JZwolinksi/TMarsh CHawes DNguyen HBerkow ACRS MWaterman Accession Number: ML020840725 OFC PDII-1/PM PDII-1/LA PDII-1/ASC NAME LOlshan CHawes RLaufer DATE 3/29/02 3/29/02 3/29/02 OFFICIAL RECORD COPY

Enclosure ATTENDEES LIST DECEMBER 05, 2001 MEETING WITH DUKE ENERGY TO DISCUSS DIGITAL UPGRADES TO KEOWEE HYDRO UNITS NRC Duke R. Laufer W. Busch E. Marinos B. Geddes D. Nguyen T. Grant L. Olshan M. Waterman

Oconee Nuclear Station cc:

Ms. Lisa F. Vaughn Legal Department (PBO5E)

Duke Energy Corporation 422 South Church Street Charlotte, North Carolina 28201-1006 Anne W. Cottingham, Esquire Winston and Strawn 1400 L Street, NW Washington, DC 20005 Manager, LIS NUS Corporation 2650 McCormick Drive, 3rd Floor Clearwater, Florida 34619-1035 Senior Resident Inspector U. S. Nuclear Regulatory Commission 7812B Rochester Highway Seneca, South Carolina 29672 Mr. Henry Porter, Director Division of Radioactive Waste Management Bureau of Land and Waste Management Department of Health and Environmental Control 2600 Bull Street Columbia, South Carolina 29201-1708 Mr. Michael A. Schoppman Framatome ANP 1911 North Ft. Myer Drive Suite 705 Rosslyn, VA 22209 Mr. L. E. Nicholson Compliance Manager Duke Energy Corporation Oconee Nuclear Site 7800 Rochester Highway Seneca, South Carolina 29672 Ms. Karen E. Long Assistant Attorney General North Carolina Department of Justice P. O. Box 629 Raleigh, North Carolina 27602 Mr. C. Jeffrey Thomas Manager - Nuclear Regulatory Licensing Duke Energy Corporation 526 South Church Street Charlotte, North Carolina 28201-1006 Mr. Richard M. Fry, Director Division of Radiation Protection North Carolina Department of Environment, Health, and Natural Resources 3825 Barrett Drive Raleigh, North Carolina 27609-7721 Mr. Peter R. Harden, IV VP-Customer Relations and Sales Westinghouse Electric Company 6000 Fairview Road 12th Floor Charlotte, North Carolina 28210 Mr. William R. McCollum, Jr.