Emergency Plan Implementing Procedures Manual, Volume C, Revision 2002-02
ML020640017
Person / Time
Site: Oconee  
(DPR-038, DPR-047, DPR-055)
Issue date: 02/25/2002
From: Mccollum W
Duke Energy Corp
To:
Document Control Desk, Office of Nuclear Security and Incident Response
References
Download: ML020640017 (65)


Text

S Duke Duke Energy Corporation Oconee Nuclear Station 7800 Rochester Highway Seneca, SC 29672 W. R. McCollum, Jr.

(864) 885-3107 OFFCE VicePresdent(864) 885-3564 FAx 1/ce President February 25, 2002 U.

S. Nuclear Regulatory Commission Document Control Desk Washington, D.

C.

20555

Subject:

Oconee Nuclear Station Docket Nos.

50-269,

-270,

-287 Emergency Plan Implementing Procedures Manual Volume C Revision 2002-02 Please find attached for your use and review copies of the revision to the Oconee Nuclear Station Emergency Plan: Volume C Revision 2002-02 February 2002.

This revision is being submitted in accordance with 10 CFR 50-54(q) and does not decrease the effectiveness of the Emergency Plan or the Emergency Plan Implementing Procedures.

Any questions or concerns pertaining to this revision please call Mike Thorne, Emergency Planning Manager at 864-885-3210.

By copy of this letter, two copies of this revision are being provided to the

NRC, Region II, Atlanta, Georgia.

Very truly yours, iW. R. McCollum, J VP,iOoee Nucl r Site xc:

(w/2 copies of attachments)

Mr. Luis Reyes, Regional Administrator, Region II U.

S. Nuclear Regulatory Commission 61 Forsyth St.,

SW, Suite 24T23 Atlanta, GA 30303 w/copy of attachments Mr.

Steven Baggett Rockville, Maryland (w/o Attachments, Oconee Nuclear Station)

l.

NRC Resident Inspector M.

D. Thorne, Manager, Emergency Planning

February 25, 2002 OCONEE NUCLEAR SITE INTRASITE LETTER

SUBJECT:

Emergency Plan Implementing Procedures Volume C, Revision 2002-02 Please make the following changes to the Emergency Plan Implementing Procedures Volume C by following the below instructions.

REMOVE ADD Cover Sheet -

Rev.

2002-01 Cover Sheet Rev. 2002-02 Table of Contents, Page 1 & 2 Table of Contents, Page 1 &2 RP/0/B/1000/009 11/15/01 RP/0/B/1000/009 -

02/19/02 RP/0/B/1000/029 11/07/01 RP/0/B/1000/029 -

02/19/02 Rev.

2 Rev.

4 NOTE:

Revision 3 was revised before distribution was made

DUKE POWER EMERGENCY PLAN IMPLEMENTING PROCEDURES VOLUME C APPROVED:

W. W. Foster, Manager Safety Assurance 02/27/02 Date Approved 02/27/02 Effective Date VOLUME C REVISION 2002-02 FEBRUARY 2002

HP/0/B/1009/018 HP/0/B/1009/020 HP/0/B/1009/021 JP/0/B/1009/022 RP/0/B/1000/001 RP/0/BI1000/002 RP/0/B/1000/003 A RP/O/B/1000/007 RP/0/B/1000/009 RP/0/B/1000/010 RP/0/B/1000/015 A RP/0/B/1000/015 B RP/0/B/1000/015 C RP/0/B/1000/016 RP/0/B/1000/017 RP/0/B/1000/018 RP/0/B/1000/019 RP/0/B/1000/020 RP/0/B/1000/021 RP/0/B/1000/022 RP/0/B/1000/024 RP/OIB/1000/028 VOLUME C TABLE OF CONTENTS Off-Site Dose Projections Estimating Food Chain Doses Under Post Accident Conditions Source Term Assessment Of A Gaseous Release From Non-Routine Release Points On Shift Off-Site Dose Projections Emergency Classification Control Room Emergency Coordinator Procedure ERDS Operation Security Event Procedure For Site Assembly Procedure For Emergency Evacuation/Relocation Of Site Personnel Offsite Communications From The Control Room Offsite Communications From The Technical Support Center Offsite Communications From The Emergency Operations Facility Medical Response Spill Response Core Damage Assessment Technical Support Center Emergency Coordinator Procedure Emergency Operations Facility Director Procedure Operations Interface (EOF)

Procedure For Site Fire Damage Assessment And Repair Protective Action Recommendations Communications & Community Relations World Of Energy Emergency Response Plan Revision 2002-02 February 2002 I

05/19/00 10/09/98 12/01/97 10/08/01 01/15/02 11/05/01 12/03/98 11/05/01 02/19/02 04/24/01 12/11/01 12/11/01 12/11/01 01/30/01 11/30/00 09/30/97 12/05/01 12/05/01 04/30/01 09/18/01 11/10/99 02/17/97

RP/0/B/1000/029 RP/0/B/1000/031 SR/0/B/2000/001 Business Management SSG Functional Area Directive 102 NSC - 110 Engineering Directive 5.1 Human Resources Procedure Radiation Protection Manual Section 11.3 Radiation Protection Manual Section 11.7 Safety Assurance Directive 6.1 Safety Assurance Directive 6.2 Training Division VOLUME C TABLE OF CONTENTS Fire Brigade Response Joint Information Center Emergency Response Plan Standard Procedure For Public Affairs Response To The Emergency Operations Facility Business Management Emergency Plan SSG Emergency Response Plan - ONS Specific Nuclear Supply Chain - SCO Emergency Response Plan Engineering Emergency Response Plan ONS Human Resources Emergency Plan Off-Site Dose Assessment And Data Evaluation Environmental Monitoring For Emergency Conditions Safety Assurance Emergency Response Organization Emergency Contingency Plan Training Division Emergency Response Guide DTG-007 Revision 2002-02 February, 2002 2

02/05/02 06/12/00 03/23/00 03/21/01 03/01/01 04/02/01 09/12/01 01/07/02 04/06/99 11/26/01 11/28/94 03/27/00 12/17/01

IN RMATION Duke Power Company (I)IDNo.

KrtUt5tIUUU/UUf O

PROCEDURE PROCESS RECORD Revisino No.

006 PREPARATION (2)

Station OCONEE NUCLEAR STATION (3)

Procedure Title Procedure for Site Assembly (4)

Prepared By Ray Waterman (Signature)

/:!

Date 02/13/02 (5)

Requires NSD 228 Applicability Determination?

D Yes (New procedure or revision with major changes)

[

No (Revision with minor changes)

LI No (To incorpora~tep Z 1 y 4

ap o v edhanges)

(6)

Reviewed By (QR)

Date

/'

02 Cross-Disciplinary Review By (QR)NA_&_rDate8 0 2.

Reactivity Mgmt Review By (QR)NA Date Mgmt Involvement Review By (Ops Supt) NA Date (7)

Additional Reviews Reviewed By Date Reviewed By Date Temporary Approval (if necessary)

"By (OSM/QR)

Date By (QR)

Date (9)

Approved By 6

t Date PERFORMANCE (Compare with control copy every 14 calendar days while work is being performed.)

(10)

Compared with Control Copy Date Compared with Control Copy Date Compared with Control Copy Date (11)

Date(s) Performed Work Order Number (WO#)

COMPLETION (12)

Procedure Completion Verification:

"[] Unit 0 El Unit 1 El Unit 2 El Unit 3 Procedure performed on what unit?

"El Yes El NA Check lists and/or blanks initialed, signed, dated, or filled in NA, as appropriate?

El Yes El NA Required enclosures attached?

El Yes El NA Data sheets attached, completed, dated, and signed?

El Yes El NA Charts, graphs, etc. attached, dated, identified, and marked?

El Yes El NA Procedure requirements met?

Verified By Date

"(13)

Procedure Completion Approved Date (14) Remarks (Attach additional pages) n I'* f."* #'11* # I lt"*t.,O./'*, I/%g*t*

Duke Power Company Oconee Nuclear Site Procedure for Site Assembly Reference Use I

I Procedure No.

RP/O/B/1000/009 Revision No.

006 Electronic Reference No.

OX002WP I

RP/OB/ 1000/009 Page 2 of 3 Procedure For Site Assembly NOTE:

This is an implementing procedure to the Oconee Nuclear Site Emergency Plan and must be forwarded to Emergency Planning within seven (7) working days of approval.

1. Symptoms 1.1 A test of response time and procedures employed in completing an accounting of onsite personnel.

1.2 An incident occurs on site and:

1.2.1 The Technical Support Center, Operational Support Center, and Emergency Operations Facility are required to be established.

1.2.2 Portions of the site require evacuation or a site evacuation may be required.

2. Immediate Actions 2.1 (Action Plan for Emergency Coordinator), Enclosure 4.1 2.2 (Action Plan for Security Supervisor), Enclosure 4.2 2.3 Make announcements over the Public Address System, Enclosure 4.3, (Public Address Announcement) 2.4 Activate the outside Site Assembly Horn to notify personnel outside the reach of the PA System.

2.5 Continue the alarm, horn, and announcements for a duration long enough to ensure all onsite personnel are aware of the Site Assembly and are responding. (No more than 6 alarm and horn activations, together with announcements, need to be made.)

2.6 (Action Plan for Offsite Communicator), Enclosure 4.5.

RP/0/B/ 1000/009 Page 3 of 3

3. Subsequent Actions 3.1 (Action Plan for Onsite Personnel), Enclosure 4.4 3.2 Record accountability results (via phone or fax) from Security on Enclosure 4.7, (Site Accountability Log).

3.2.1 It is required that personnel be accounted for within 30 minutes of initiation of site assembly. The number of unaccounted personnel can be reported first with the names being reported later.

3.3 When personnel accountability has been completed during a Site Assembly, one of the following will occur:

3.3.1 If the requirement for an assembly no longer exists, a request to return to normal duties will be given by the Emergency Coordinator.

3.3.2 Plant conditions may require evacuation of the station. Consult procedure RP/O/B/1000/010 (Procedure for Emergency Evacuation/Relocation).

4. Enclosures 4.1 Action Plan for Emergency Coordinator 4.2 Action Plan for Security Supervisor/ Designated Officer 4.3 Public Address Announcement 4.4 Action Plan for Onsite Personnel 4.5 Action Plan For Off-Site Communicator 4.6 Site Assembly Locations 4.7 Site Accountability Log 4.8 Card Reader Locations

.1 RP/O/B/1000/009 Action Plan for Emergency Coordinator Page 1 of I

1.

Action Plan For Emergency Coordinator 1.1 Alert Security Supervisor that a Site Assembly will be initiated.

1.2 Appoint a person or persons to:

1.2.1 Activate warble tone over PA System and outside Site Assembly horn located at the microwave tower.

1.2.2 Make voice announcements over the PA System per Enclosure 4.3, (Public Address Announcement).

1.3 Obtain accountability results from Security on Enclosure 4.7, (Site Accountability Log).

1.4 Direct necessary actions to account for any missing personnel.

1.4.1 MERT will be utilized for this purpose.

1.5 Examine the radiation/contamination levels established in RP/0/B/1000/010 (Procedure for Emergency Evacuation/Relocation), to determine the category of personnel that may need to be evacuated.

1.6 If the requirements for an assembly no longer exist, return the station to normal duties.

.2 RP/0/B/1000/009 Action Plan for Security Supervisor Page 1 of I

1. Action Plan For Security Supervisor 1.1 Contact the World Of Energy, Keowee Hydro, Oconee Complex, Motor Pool, Geo Technical, Crescent Resources, and the Oconee Training Center to make them aware of Site Assembly.

1.2 Initiate a patrol of the general station area within station boundaries, both inside and outside of the restricted area, to assure that personnel in remote and noise restrictive areas are aware of the Site Assembly requirement.

NOTE:

Should site assembly be initiated during high traffic ingress and egress, traffic flow will not be restricted.

1.3 Use automated gates to restrict traffic in and out of the station during Site Assembly as determined by Security.

1.4 Receive Accountability reports from all groups via phone mail ext. 5050 and complete.7, (Site Accountability Log).

1.5 Report accountability results within 30 minutes (sooner if completed) to Offsite Communicator if the TSC is activated, Control Room OSM Emergency Coordinator if TSC is not activated.

1.5.1 Provide an update of site assembly status if requested.

1.6 Fax Enclosure 4.7, (Site Accountability Log) to ext. 4308 upon completion of site accountability.

NOTE:

Report names of all unaccounted personnel. However, in the event large numbers of personnel are unaccounted for, names may not initially be provided.

1.7 Report total accountability to the TSC Offsite Communicator or Emergency Coordinator within 30 minutes of the time the assembly was initiated. Report the number(s) and name(s) of any missing person(s).

1.8 Coordinate a search and rescue effort if directed.

1.8.1 Utilize MERT for this purpose.

1.9 Contact the World of Energy, Keowee Hydro, Oconee Complex, Motor Pool, Geo Technical, Crescent Resources, and the Oconee Training Center to make them aware of Site Assembly completion.

1.10 Coordinate evacuation if so instructed.

.3 Public Address Announcement RP/O/B/1000/009 Page 1 of I CAUTION:

For drill purposes only, preface and close all announcements with, "This is a drill. This is a drill."

SITE ASSEMBLY ALARM INSTRUCTIONS:

  • Actuate Site Assembly Alarm switch, Control Board IUBI, and hold in position

+ Activate alarm for 10 seconds

+ Repeat announcements and alarm activations six times PAGE ANNOUNCEMENT INSTRUCTIONS:

+ Pick up a ROLM phone located on Unit 1&2 Control Room desk

  • Switch Office Page to ON Dial 70
  • Make Announcements #1 and #2 as required by situation
  • Switch Office Page to OFF after announcements have been made NOTE:

If any particular area of the plant is found to be unsafe during an emergency, and a Site Assembly is held, warnings should be sounded through the public address system advising the safe corridors to use.

ANNOUNCEMENT #1 "This is a Site Assembly. This is a Site Assembly. All visitors are to assemble with their permanently badged escorts. All permanently badged personnel shall report to their designated Site Assembly area. All other personnel not presently wearing security badges shall report to their supervisor. All personnel are required to remain at their site assembly locations until released."

ANNOUNCEMENT #2 Make this announcement if the Technical Support Center, Operational Support Center, and Emergency Operations Facility are to be activated. If required, specify that the Alternate TSC and/or OSC will be used.

"ACTIVATE THE TECHNICAL SUPPORT CENTER."

"ACTIVATE THE OPERATIONAL SUPPORT CENTER."

"ACTIVATE THE EMERGENCY OPERATIONS FACILITY"

.4 Action Plan For Onsite Personnel RP/O/B/1000/009 Page 1 of 2

1. Response To Site Assembly Alarm 1.1 Each person (except those noted in 1.2) shall assemble with their supervisor.

1.1.1 Assembly points for personnel onsite at Oconee Nuclear Site are identified in.6, (Site Assembly Locations).

NOTE:

In case of a reactor building evacuation alarm, the reporting requirements in 1.2 apply.

1.2 Persons working in Radiation Control Areas in protective clothing should leave their work areas, remove outer protective clothing at RCZ Exit, and go to the contaminated side of the appropriate change room.

1.2.1 In the change room, they should contact the appropriate persons as designated by 2.1.1 for personnel accountability reporting. Wait in change room for further instructions concerning the advisability of changing clothes and reporting to normal assembly areas.

NOTE:

Card reader locations are listed in Enclosure 4.8, (Card Reader Locations).

1.3 All personnel inside protected area will swipe their badges at their designated site assembly areas.

2. Normal working hours 0700-1730 (Monday - Thursday)

Supervisors should report their accountability within 8 to 10 minutes.

Superintendents/Managers shall report for their group and give names of any persons not accounted for within 20 minutes. Completion of station accountability shall be made within 30 minutes.

2.1 All personnel shall assemble at designated assembly areas and all personnel inside the protected area shall swipe badges.

2.1.1 Each supervisor shall be responsible for accounting for all assigned personnel.

A. Each reporting supervisor or designee is to report accountability by calling extension 5050 and following instructions.

"* Department name, your name and extension, your accountability, and number of missing.

"* If a large number of personnel are unaccounted for provide number of missing to Security, Security will call back for names.

.4 RP/O/B/1000/009 Action Plan For Onsite Personnel Page 2 of 2 2.1.2 Station Superintendents/Supervisors of various organizations working at Oconee (ESS, Bartlett, Communications, Power Delivery, World of Energy, Keowee Hydro, and Framatome) shall make an accountability report for their areas of accountability by calling extension 5050 and following instructions.

3. After hours, weekends, holidays 3.1 All personnel shall assemble at designated assembly areas and all personnel inside the protected area shall swipe badges.

3.1.1 Each supervisor shall be responsible for accounting for all assigned personnel.

A. Each reporting supervisor or designee is to report:

"* Department name, your name and extension, your accountability, and number of missing.

" If a large number of personnel are unaccounted provide number of missing to Security, Security will call back for names. Supervisors shall report accountability to the Security Supervisor by calling extension 5050 and following instructions.

.5 RP/O/B/ 1000/009 Action Plan For Offsite Communicator Page 1 of 1

1. Action Plan For Offsite Communicator 1.1 Obtain accountability results from the Security Shift Supervisor on Enclosure 4.7 (Site Accountability Log).

1.2 Provide 20 minute accountability to Emergency Coordinator.

Site Assembly update 1.3 Provide 30 minute accountability to Emergency Coordinator Number and names, (if available), of unaccounted for personnel.

.6 Site Assembly Locations DUKE OCONEE NUCLEAR SITE PERSONNEL RP/O/B/ 1000/009 Page 1 of 5 ASSEMBLY POINT SECTION Site Vice President's Group:

Site Vice President/Managers and Assigned Staff/Clerks:

Chemistry:

Chemistry Staff and Technicians Chemistry Shifts A,B,C.D,E (On-Duty)

Radwaste Staff and Technicians Maintenance:

I&E SPOC Crew (On-Duty Shift A,B,C.D,E)

I&E Staff, Supervisors, and Technicians I&E Plant Maintenance Mech Maintenance SPOC Crew (On-Duty Shift A,B,C.D,E)

Mech Maintenance Staff, Supervisors, and Technicians Operations:

All Radiation Protection:

RP Staff Support Functions Surveillance and Control RP Shifts A,B,C,D,E (On-Duty)

Work Control:

All Engineering:

All NSC & SSG:

All Admin Building Chemistry Offices Radwaste Facility Radwaste Facility Work Control Center/OSC I&E Offices 5th Floor Turbine Bd.

Work Control Center/OSC Mechanical Offices Control Rooms/Ops' Offices RP Offices RP Offices RP Offices RP Offices/OSC Work Control Offices Engineering Offices NSC & SSG Offices

.6 Site Assembly Locations SECTION RP/O/B/1000/009 Page 2 of 5 ASSEMBLY POINT Safety Assurance:

Safety Assurance Offices Manager/Tech Staff, RP, Chemistry, Admin Support, GET Operator Training, Simulator Support, Manager/Tech Staff I&E Mechanical Maintenance Human Resources:

All Community Relations:

All Business Management:

All Security Training Offices Oconee Training Center Maintenance Training Facility Human Resources WOE Offices Business Management Security Offices Designated Post All Training:

SECTION Engineering:

Operations:

Chemistry:

Radiation Protection:

Communications:

Keowee:

World of Energy:

Quality Verification:

NMS (Nuclear Maintenanc Personnel Inside Prote Personnel Outside Pro Transportation Department Personnel Inside Prot Personnel Outside Pr Geo-Tech Crescent Resources.6 RP/0/B/1000/009 Site Assembly Locations Page 3 of 5 DUKE NON-OCONEE NUCLEAR SITE PERSONNEL (Permanently Badged Personnel)

ASSEMBLY POINT Engineering Offices Operations' Offices Chemistry Offices RP Offices Communications' Offices Keowee Hydro Station WOE Offices Quality Assurance Offices e Support) cted Area tected Area ected Area otected Area Maint. Support Bldg Canteen Maintenance Support Building Transportation Offices/Garage Geo-Technical Offices Crescent Resources Offices

.6 Site Assembly Locations RP/0/B/1000/009 Page 4 of 5 DUKE NON-OCONEE NUCLEAR SITE PERSONNEL SECTION Engineering:

ASSEMBLY POINT Engineering Offices Maintenance:

Personnel Outside Protected Area Bartlett:

Personnel Inside Protected Area Personnel Outside Protected Area Framatome:

Maintenance Vendors:

Personnel Inside Protected Area Personnel Outside Protected Area I&E Vendors:

Radiation Protection Vendors:

Maintenance Offices 2 n Floor Maint. Support Building Maintenance Support Building Canteen Bartlett Offices Framatome Office Maintenance Support Building Canteen Station Contact Group Maintenance Support Building Canteen RP Offices NRC:

All NRC Offices Food Service Vendor:

Personnel Inside Protected Area Personnel Outside Protected Area Maintenance Support Building Canteen Admin. Bldg Canteen VISITORS Personnel Inside Protected Area with Escort Personnel Outside Protected Area Assemble with escort Assemble with Station Contact All personnel not identified above will report to their Station Contacts' area of assembly.

OTHER PERSONNEL OUTSIDE PROTECTED AREA

.6 Site Assembly Locations RP/O/B/ 1000/009 Page 5 of 5 NORTHWEST QUADRANT 1-1 Fn I

D SOUTHWEST QUADRANT NORTHEAST QUADRANT Eln 1-n6 3W 14 SOUTHEAST QUADRANT INORTHEAST QUADRANT I~ ~ ~~C b.t.'Tflr fIl A "ID A Nl'r I.

Security Building 18-Administrating Building

2.

Training/Locker Building

19.

Oconee Office Building

3. Maintenance Service Bd.
4.

Maintenance Support Building

5. Turbine Building North Offices 6-Turbine Building 1 &2 Offices
7.

Unit l&2 Control Room

8.

Keowee Hydro Station 16-World of Energy

17. Oconee Training Center SOUTHWEST QUADRANT SOUTHEAST QUADRANT
20. RP Assembly Building
21.

Interim Outage Building

22. Geo-Technical Center
23. Warehouse Offices 910.
11.

12

13.
14.
15.
24.

25.

Turbine Building 3 Offices Unit 3 Control Room Technical Support Building Radwaste Facility Oconee Garage Oconee Complex L-I Storage Yard Turbine Building South Offices Maintenance Training Facility

.7 Site Accountability Log RP/O/B/1000/009 Page 1 of 2

1. Site Accountability Log ACCOUNTAB[LITY RESULTS Work Group Contacts Name Phone 30 Names of Missing mn Business Management Chemistry NSC SSG Engineering/LIT Nuclear Maintenance Support (NMS)

Human Resources Security Keowee Hydro Mechanical Maintenance Operations Radiation Protection V. P. Staff Safety Assurance Training World of Energy Work Control Medical NOTE:

Instructions in note are for Security only unless directed otherwise.

Acquire site assembly call-ins from phone mail #5050

> Instructions: dial 4444, then 5050#, then 7318#, then 3, and listen to message

.7 Site Accountability Log RP/O/B/ 1000/009 Page 2 of 2 PERSONNEL UNACCOUNTED FOR NAME WORK GROUP LAST KNOWN LOCATION I

I I

I

-I-4

+/-

I i

t i

t I.

I-4 1

4 4

4 I

i

+

i

+ I i-

_ L____

__1 I

i

.8 Site Assembly Card Reader Listing RP/O/B/ 1000/009 Page I of I

1. Site Assembly Card Reader Listing PSC ID #

Location EP CR # 01 Locker Building - hallway near west entrance to machine shop EP CR # 02 Security Admin. Building - second level near mechanical conference room EP CR # 03 Maintenance Service Building - maintenance shop east wall near doorway leading to yard area EP CR # 04 Maintenance Service Building - canteen north/east wall near corridor to stairway EP CR # 05 Maintenance Service Building - canteen south/west wall near stairway EP CR # 06 Maintenance Service Building - second level south wall near stairway EP CR # 07 Maintenance Service Building - fourth level south wall near stairway EP CR # 08 Maintenance Service Building - fifth level south wall near stairway EP CR # 09 Turbine Building - turbine floor level, north offices located at bottom of north stairwell EP CR # 10 Turbine Building - units 1&2 turbine floor level offices located in work control/document control area near east door EP CR # 11 Unit 2 Control Room - on south side of column Q-73 EP CR # 12 Unit 2 Control Room - on south wall of corridor between kitchen and TSC entrance EP CR # 13 Unit 3 Control Room - on north side of column Q-89 EP CR # 14 Unit 3 Control Room - on south wall of corridor between kitchen and OSC EP CR # 15 Technical Support Building - fifth floor operations office area near east stairway door EP CR # 16 Technical Support Building - third floor, in corridor leading from breezeway to Chemistry area EP CR # 17 Turbine Building - Unit 3 offices, north entrance near inside door to stairway EP CR # 18 Turbine Building - south offices, bottom of stairway leading to second level offices EP CR # 19 Aux. Bldg. - Unit 1&2, third level, hot change room, located in hallway near change room door EP CR # 20 Aux. Bldg. - Unit 1&2 Spent Fuel Change Room EP CR # 21 Aux. Bldg. - Unit 3, third level, Hot Change Room, located in hallway near change room door EP CR # 22 Unit 3 Spent Fuel Change Room EP CR # 23 Warehouse #3 - first floor office area, to the left, just inside door EP CR # 24 Radiation Protection Building - lower level west stairway near outside entrance EP CR # 25 Rad Waste Building - near control room area EP CR # 26 Standby Shutdown Facility - ground level (elev. 796) in south laydown area near CAS corridor door

INFORMAITION Duke Power Company (I,

D)No.

RP/0/B/1000/029 ONLY PROCEDURE PROCESS RECORD Revision No. 003 PREPARATION (2)

Station OCONEE NUCLEAR STATION (3)

Procedure Title FIRE BRIGADE RESPONSE (4)

Prepared By ROBERT TAYLOR (Signature)

£,7 Date 01/23/02 (5)

Requires NSD 228 Applicability Determination?

[

Yes (New procedure or revision with major changes)

L] No (Revision with minor changes)

E] No (To incorporate previously approved changes)

(6)

Reviewed By 4--

(QR)

Date Cross-Disciplinary Revie By (QR)NA Date I-a4 -

PZ Reactivity Mgmt Review By (QR)NA Date Mgmt Involvement Review By (Ops Supt) NA Date (7)

Additional Reviews Reviewed By Date Reviewed By Date "j Temporary Approval (if necessary)

By (OSMIQR)

Date By QR)

Date (9)

Approved By Date

/______

PERFORMANCE (Compare with control copy every 14 calendar days while work is being performed.)

(10)

Compared with Control Copy Date Compared with Control Copy Date Compared with Control Copy Date (11)

Date(s) Performed Work Order Number (WO#)

COMPLETION (12)

Procedure Completion Verification:

El Unit 0 El Unit 1 El Unit 2 [l Unit 3 Procedure performed on what unit?

El Yes El NA Check lists and/or blanks initialed, signed, dated, or filled in NA, as appropriate?

El Yes El NA Required enclosures attached?

El Yes El NA Data sheets attached, completed, dated, and signed?

El Yes El NA Charts, graphs, etc. attached, dated, identified, and marked?

El Yes El NA Procedure requirements met?

Verified By Date (13)

Procedure Completion Approved Date (14)

Remarks (Attach additional pages)

Duke Power Company Oconee Nuclear Station Fire Brigade Response Reference Use Procedure No.

RP/O/B/1000/029 Revision No.

003 Electronic Reference No.

OX0091UU Procedure No.

RP/0/B/1000/029 Page 2 of 3 Fire Brigade Response NOTE:

This procedure is an implementing procedure to the Oconee Nuclear Site Emergency Plan and must be forwarded to Emergency Planning within three (7) working days of approval.

1. Symptoms 1.1 Fire, explosions or conditions (smoke, smoldering, burning) associated with a fire have been reported to the Control Room or to the OSC when activated.

1.2 This procedure shall provide guidance to shift personnel and Emergency Coordinator for response, actions, and coordination associated with an incident involving real or suspected fires.

2. Immediate Actions 2.1 IF Fire Brigade response is being considered during routine operations THEN Go to Enclosure 4.1 (Fire Brigade Response - Routine Operations) 2.2 IF Fire Brigade response is being considered AND The OSC/TSC are activated THEN Go to Enclosure 4.2 (Fire Brigade Response - OSC/TSC Activation).
3. Subsequent Actions 3.1 IF Fire Brigade equipment or supplies have been used, THEN Ensure that all equipment is returned to its proper place and consumable supplies are replaced or ordered.

RP/0/B/ 1000/029 Page 3 of 3 NOTE:

Original copies of the Fire Emergency Report can be located in NSD 112, Fire Brigade Organization and Training.

3.2 Complete Enclosure 4.3 (Fire Emergency Report).

3.2.1 Forward a copy to the Fire Protection Engineer.

3.2.2 Initiate a PIP if Enclosure 4.3 (Fire Emergency Report) is completed. Include all important information from Enclosure 4.3 (Fire Emergency Report) in PIP.

3.2.3 Forward this procedure to the Emergency Planning Section.

3.3 Conduct a post incident critique for events requiring full Fire Brigade activation.

4. Enclosures 4.1 Fire Brigade Response - Routine Operations 4.2 Fire Brigade Response - OSCITSC Activation 4.3 Fire Emergency Report 4.4 Fire Brigade Leader Checklist 4.5 Safety Officer's Checklist 4_6 References

.1 Fire Brigade Response - Routine Operations

1. Fire Brigade Response - Routine Operations

"* Actions may be followed in any sequence.

"* Lines left of procedure steps are used to indicate place in procedure.

"* Check marks are acceptable in these blanks.

"* Complete the procedure steps that apply to this incident.

"* N/A steps not performed.

1.1 Complete the following with information taken from the caller:

Name/Group of person reporting fire/smoke RP/O/B/ 1000/029 Page 1 of 7 Location of fire/smoke Equipment/components affected by fire/smoke Time Date Are there people in the immediate area who need to be warned or relocated to a safe area?

Are there any injured people?

Call back number Notify OSM and STA.

Refer to the Fire Plan for the location reported for fire in Step 1.1 1.3.1 Request support from an unaffected unit. (Refer to Fire Plan SOG #10 for Fire Brigade equipment locations).

1.2 1.3

.1 Fire Brigade Response - Routine Operations RP/0/B/1000/029 Page 2 of 7 NOTE:

The Operations Shift Manager (OSM) or designee may activate a full Fire Brigade response without sending someone to investigate first, if deemed necessary. Possible situations that warrant full response could include:

  • Multiple reports from individuals
  • Multiple alarms,
  • Other system indications
  • Any other indicators that the Operations Shift Manager deems significant.

1.4 IF Fire is involved or suspected INSIDE the protected area THEN Perform the following:

1.4.1 Send one operator, with a radio, to the fire/smoke location to perform one of the following:

A. Extinguish the fire (if possible) with portable extinguisher (notify Control Room)

OR B.

IF Fire Brigade response is required THEN Notify Control Room immediately.

1.4.2 IF Fire Brigade response is NOT needed THEN Perform the following:

A. Direct NEO to Search affected area for victims Activate MERT if required per RP/0/B/1000/016, Medical Response.

IF NO fire was discovered then exit this procedure.

If fire was discovered then GO TO Step 1.4.8.

.1 RP/O/B/1000/029 Fire Brigade Response - Routine Operations Page 3 of 7 1.4.3 IF A full Fire Brigade response is needed THEN Perform the following:

A. Direct NEO to:

"* Search effected area for victims

"* Evacuate surrounding areas

"* Pre-stage nearby equipment for Fire Brigade

"* Report to Fire Brigade Leader for further instructions B.

Use plant page to request all Fire Brigade and MIERT members to respond to the fire.

1. Include any information, if known, that would be important to Fire Brigade members responding to the incident location. (eg. Hazardous materials, smoke, structural damage, etc.)
2.

Include the statement "All non-Fire Brigade personnel please avoid the "f

." (fire location area) 1.4.4 Use the following directions to activate radios and pagers.

A. Transmit "Standby for Emergency Message" B.

Press the "Instant Call" button labeled "Fire Brigade" C. Wait for the red "Transmit" light on the radio to turn off D. Transmit message including information, if known, that would be important to Fire Brigade members responding to the staging area (e.g. hazardous materials, smoke, structural damage, etc.).

1.4.5 Get staging area location from the Fire Brigade Leader then repeat Steps 1.4.3.B & 1.4.4.

1.4.6 Notify SRO to evaluate the need for staging personnel at the SSF.

1.4.7 Establish and maintain communications with Fire Brigade Leader to provide assistance as needed. {3}

A.

Available equipment, refer to SOG #10 in the Fire Plan.

B.

Critical equipment in vicinity of fire (Fire Plan)

1.4.8 II T

1.4.9 II T.1 RP/O/B/1000/029 Fire Brigade Response - Routine Operations Page 4 of 7 T

Hazardous materials are involved, HEN Refer to RP/O/B/1000/017 (Spill Response Procedure).

F An oil filled transformer is involved in a fire, "HEN Request Oconee County Fire Department to dispatch the Keowee Key Fire Department to the site.

Dial 9-911 from Ext. 3271 Operations Shift Manager's phone Dial 9-911 from Ext. 2159 Unit I Control Room SRO's phone or Dial 911 from 882-7076 Units 1, 2 and 3 Control Rooms, Bell South lines 1.4.10 IF The Fire Brigade identifies a fire requiring application of water for extinguishment, THEN perform the following:

A. Operate HPSW pumps as required to boost pressure (refer to OP/O/A/1104/01, High Pressure Service Water). {f1 }

B.

Make a PA announcement to discontinue use of HPSW for non-essential purposes. { 1 }

C. Evaluate any Auxiliary Building Flooding Concerns (Refer to Auxiliary Building Flood AP). {2}

1.4.11 IF Fire occurs on backshifts or weekends AND Additional Fire Brigade support is needed, THEN Perform the following:

A. Select the off duty shift(s) that will impact the safe operation of the plant the least by being recalled (i.e., shifts other than on coming shift).

A B

C D

E B.

Call the Switchboard Operator and request them to call the shift(s) selected in Step A.

.1 RP/0/B/1000/029 Fire Brigade Response - Routine Operations Page 5 of 7 NOTE:

All site phones except for the following are blocked from accessing the public 911 emergency service line.

1.4.12 IF Oconee County Fire Department assistance is needed, THEN Dial 9-911 from Ext. 3271 Operations Shift Manager's phone Dial 9-911 from Ext. 2159 Unit 1 Control Room SRO's phone Or Dial 911 from 882-7076 Units 1/2 and 3 Control Rooms, Bell South lines A. Request a response from:

Keowee Key Fire Department Keowee Ebenezer Fire Department Corinth-Shiloh Fire Department

"* Give the fire location (building, parking lot, etc.) and best gate for entry to the fire department dispatch.

"* Call Security (ext. 2222) and request that they have a Security Officer escort the fire department to the fire location.

.1 RP/O/B/1000/029 Fire Brigade Response - Routine Operations Page 6 of 7 NOTE:

Offsite fire departments are normally responsible for fire suppression activities outside the Protected Area. The Fire Brigade may provide limited support for a fire outside the Protected Area if resources allow.

"* The Fire Plan for Keowee Hydro calls for sending the Fire Brigade to extinguish fires there.

Security will automatically send a Security Officer to investigate alarms on fire detection systems that are monitored by Security in the PAP. Security will call the emergency line to report the existence of a fire or a need for further investigation by plant personnel as needed.

1.5 IF Fire is involved or suspected OUTSIDE the Protected Area, THEN Call Security (ext. 2222) and request that a Security Officer be dispatched to the suspected fire location to verify fire location and nature of the fire.

Request Security Shift Supervisor to relay information back to the Control Room via the emergency line (4911).

1.5.1 IF Security confirms that there is a fire or the situation has the potential for developing into one, THEN Send a Fire Brigade Leader and one Fire Brigade Member or the full Fire Brigade if resources allow.

1.5.2 IF The Fire Brigade identifies a fire requiring application of water for extinguishment THEN Perform the following:

A. Operate HPSW pumps as required to boost pressure (refer to OP/O/A/ 1104/01, High Pressure Service Water). ). {I1 }

B. Make a PA announcement to discontinue use of HPSW for non-essential purposes. { 1 }

.1 Fire Brigade Response - Routine Operations RP/O/B/ 1000/029 Page 7 of 7 NOTE:

All site phones except for the following are blocked from accessing the public 911 emergency service line.

1.5.3 IF Oconee County Fire Department assistance is needed, THEN Dial 9-911 from Ext. 3271 Operations Shift Manager's phone Dial 9-911 from Ext. 2159 Unit 1 Control Room SRO's phone or Dial 911 from 882-7076 Units 1/2 and 3 Control Rooms, Bell South line 1.5.4 Request a response from:

Keowee Key Fire Department Keowee Ebenezer Fire Department Corinth-Shiloh Fire Department Give the fire location (building, parking lot, etc.) and best gate for entry to the fire department dispatch.

Call Security (ext. 2222) and request that they have a Security Officer escort the fire department to the fire location.

NOTE:

Keowee Hydro Station is located in Pickens County. Dialing 9-911 will NOT access the Pickens County Fire Dispatch.

1.5.5 IF Six Mile Fire Department assistance is needed for a fire at Keowee Hydro Station, THEN Call the Pickens County Sheriffs Department (898-5500) and request the response of Six Mile Fire Department to Keowee Hydro Station.

  • Call Security (ext. 2222) and request that they have a Security Officer escort the fire department to the fire location.

1.6 Return to Section 3, Subsequent Actions.

.2 RP/O/B/1000/029 Fire Brigade Response - OSC/TSC Activation Page I of 6

1. Fire Brigade Response - OSC/TSC Activation

"* Actions may be followed in any sequence.

"* Lines left of procedure steps are used to indicate place in procedure.

"* Check marks are acceptable in these blanks.

"* Complete the procedure steps that apply to this incident.

"* N/A steps not performed.

1.1 Complete the following with information taken from the Work Control Assistant who received the emergency line call:

Name/Group of person reporting fire/smoke Location of fire/smoke Equipment/components affected by fire/smoke Time Date Are there people in the immediate area who need to be warned or relocated to a safe area?

Are there any injured people?

Call back number 1.2 Refer to Fire Plan for the location reported for fire in Step 1.1.

1.2.1 Request support from an unaffected unit. (Refer to Fire Plan SOG#10 for Fire Brigade Equipment locations).

.2 Fire Brigade Response - OSC/TSC Activation RP/0/B/1000/029 Page 2 of 6 NOTE:

The Emergency Coordinator or designee may activate a full Fire Brigade response without sending someone to investigate first, if deemed necessary. Possible situations that warrant full response could include:

Multiple reports from individuals Multiple alarms, Other system indications Any other indicators that the Emergency Coordinator deems significant.

1.3 IF Fire is involved or suspected INSIDE the Protected Area, THEN Perform one of the following as required.

1.3.1 Send one operator, with a radio, to the fire/smoke location to perform one of the following:

A. Extinguish the fire (if possible) with portable extinguisher (notify Control Room)

OR B.

IF Fire Brigade response is required THEN Notify Control Room immediately.

1.3.2 IF Fire Brigade response is NOT needed, THEN Perform the following:

A. Direct NEO to search affected area for victims B.

Activate MERT if required per RP /0/B/1000/016 (Medical Response)

C.

IF NO fire was discovered then exit this procedure.

D. If fire was discovered then GO TO Step 1.3.5.

.2 RP/O/B/1000/029 Fire Brigade Response - OSC/TSC Activation Page 3 of 6 1.3.3 IF A full Fire Brigade response is needed, THEN Perform the following:

A. Direct NEO to:

"* Search effected area for victims

"* Evacuate surrounding areas

"* Pre-stage nearby equipment for Fire Brigade

"* Report to Fire Brigade Leader for further instructions B. Dispatch Fire Brigade Members assigned to the OSC to respond to the fire.

C.

Request the OSC Security Manager to have MERT respond along with the Fire Brigade to the fire location.

1.3.4 Establish and maintain communications with Fire Brigade Leader to provide assistance as needed. {3}

A. Available equipment (Refer to SOG #10 in the Fire Plan)

B.

Critical equipment in vicinity of fire (Fire Plan) 1.3.5 IF Hazardous materials are involved, THEN Refer to RP/0/B/1000/017 (Spill Response Procedure).

1.3.6 IF An oil filled transformer is involved in a fire, THEN Request Oconee County Fire Department to dispatch the Keowee Key Fire Department to the site.

Dial 9-911 from Ext. 3271 Operations Shift Manager's phone Dial 9-911 from Ext. 2159 Unit 1 Control Room SRO's phone or Dial 911 from 882-7076 Units 1, 2 and 3 Control Rooms, Bell South lines

.2 Fire Brigade Response - OSC/TSC Activation RP/0/B/1000/029 Page 4 of 6 1.3.7 IF The Fire Brigade identifies a fire requiring application of water for extinguishment, THEN Perform the following:

A. Operate HPSW pumps as required to boost pressure (Refer to OP/0/A/1104/01 High Pressure Service Water). {I1 }

B.

Make a PA announcement to discontinue use of HPSW for non-essential purposes. { 1 }

C. Evaluate any Auxiliary Building Flooding Concerns (Refer to Auxiliary Building Flood AP). {2}

1.3.8 Notify SRO to evaluate the need for staging personnel at the SSF..

1.3.9 IF Fire occurs on backshifts or weekends AND Additional Fire Brigade support is needed, THEN Perform the following:

A. Select the off duty shift(s) that will impact the safe operation of the plant the least by being recalled (i.e., shifts other than on coming shift).

A B

C D

E B.

Call the Switchboard Operator and request them to recall the shift(s) selected in Step A.

1.3.10 IF Oconee County Fire Department assistance is needed, THEN Request that the Offsite Communicator call and request a fire department response from:

Keowee Key Fire Department

"* Keowee-Ebenezer Fire Department

"* Corinth Shiloh Fire Department A.

Give the fire location (building, parking lot, etc.) and best gate for entry to the Offsite Communicator so that it can be given to the fire department dispatcher.

B.

Request that a Security Officer meet and escort the fire department to the fire location.

.2 RP/O/B/1000/029 Fire Brigade Response - OSC/TSC Activation Page 5 of 6 NOTE:

e Offsite fire departments are normally responsible for fire suppression activities outside the Protected Area. The Fire Brigade may provide limited support for a fire outside the Protected Area if resources allow.

"* The Fire Plan for Keowee Hydro calls for sending the Fire Brigade to extinguish fires there.

"* Security will automatically send a Security Officer to investigate alarms on fire detection systems that are monitored by Security in the PAP. Security will call the emergency line to report the existence of a fire or a need for further investigation by plant personnel as needed.

1.4 IF Fire is involved or suspected OUTSIDE the Protected Area, THEN Request that a Security Officer be dispatched to the suspected fire location to verify the location and status of the fire. Request that information be relayed back to the OSC via the emergency line (4911).

1.4.1 IF Security confirms that there is a fire or the situation has the potential for developing into one, THEN Send a Fire Brigade Leader and one Fire Brigade Member or the full Fire Brigade if resources allow.

1.4.2 IF The Fire Brigade identifies a fire requiring application of water for extinguishment, THEN Perform the following:

A. Operate HPSW pumps as required to boost pressure (refer to OP/O/A/ 1104/0 1, High Pressure Service Water). { I }

B.

Make a PA announcement to discontinue use of HIPSW for non-essential purposes. { 1 }

.2 RP/O/B/1000/029 Fire Brigade Response - OSC/TSC Activation Page 6 of 6 1.4.3 IF Oconee County Fire Department assistance is needed, THEN Request that the Offsite Communicator call and request a fire department response from:

"* Keowee Key Fire Department Keowee-Ebenezer Fire Department Corinth Shiloh Fire Department A. Give the fire location (building, parking lot, etc.) and best gate for entry to the Offsite Communicator so that it can be given to the fire department dispatcher.

B. Request that a Security Officer meet and escort the fire department to the fire location.

NOTE:

Keowee Hydro Station is located in Pickens County.

1.4.4 IF Six Mile Fire Department assistance is needed for a fire at Keowee Hydro

Station, THEN Request the Offsite Communicator call the Pickens County Sheriffs Department (898-5500) and request Six Mile Fire Department to respond to Keowee Hydro Station.

Request that a Security Officer meet and escort the fire department to the fire location.

1.5 Return to Section 3, Subsequent Actions.

.3 Fire Emergency Report FIRE EMERGENCY REPORT Rp/0/B/ 1000/029 Page 1 of 1 StationlLocation:

Location (Unit/Area):

Time Discovered:

Operations Shift Manager:

Date:

Discovered By:

Evacuation: Yes No Partial Fire Brigade Response: Yes No Other Time Fire Extinguished:

List All Fire Protection Equipment Used Operation Satisfactory: Yes No (Use Back For Details)

Equipment Restored For Use: Yes No If no, Explain (Use Back for Details)

Outside Assistance Called: No Yes Agency(s)

Area Involved: "

Point of Origin (If known):

Cause (If known Damage To:

Building Equipment Personal Other Injuries Reported:

Briefly Describe What Happened:

  • Signature of Fire Brigade Leader
  • Signature of Operations Shift Manager
  • Notify Safety Representative of Fires Involving Personal Injury (Refer to Duty List for after hours).

.4 RP/0/1B/1000/029 Fire Brigade Leader Checklist Page 1 of I TASK 0

Don Fire Brigade Leader Vest Determine Staging Area and Communicate to Control Room

"* Safe accessibility

"* Minimal distractions 0

Appropriate vicinity Establish The Following Teams/Priorities:

"* Entry Team - Priority = search & rescue/fight fire

"* Backup Team - Priority = backup Entry Team/help fight fire Rapid Intervention Team - Priority = Rescue Fire Fighters (if required)

Stress The Following Items With All Teams Prior To Dispatching To Fire:

"* Safety of Team is top priority

"* Stay with the hose/rescue line at all times

"* Maintain contact with your team at all times

"* All teams report to Safety Officer prior to entering fire zone and after exiting fire zone for accountability Assess The Fire:

"* Request CR to dispatch additional resources as required:

Off Duty Shifts and/or Offsite Fire Departments Outside Equipment Truck and/or Equipment Carts C02 or Wheeled Dry Chemical Extinguishers Foam Units

"* Exposures - Critical Equipment Concerns Above/Below Fire?, Fire/Smoke/Water?, Electrical Hazards?

"* Report Critical Equipment Concerns to CR for Emergency Plan Consideration Request Location of Nearest Fire Hose Locations From Control Room:

"* Elevation/column #

"* Communicate locations to teams Request Assistance From RP/Security 0

Request Security At The Scene To Control Access To The Area If Radiological Concerns Exist, Request CR To Notify RP Refer To Fire Plan As Required:

Hazards/Ventilation Refer To SOG #10 for Fire Brigade equipment locations If Hazardous Materials Involved, Request CR to Dispatch Haz-Mat Team

.5 Safety Officer's Checklist RP/O/B/1000/029 Page 1 of I TASK Don Safety Officer Vest Establish Accountability For FB Members

  • Name tags/accountability board Perform PPE Checks of Fire Fighters

"* All skin covered

"* All turnout gear openings closed

"* SCBA cylinder full ( > 4000 psi)

"* SCBA cylinder valves fully open

"* PASS device operational Log Team Assignments on Accountability Board

"* Log time on air

"* Log entry times

"* Log team assignments Assign MERT Responsibilities

"* Stand by with medical equipment

"* Monitor FB members for signs of heat exhaustionlstress/etc.

"* Provide drinking water for fire fighters Maintain Continuos Contact With Fire Brigade Leader Evaluate SCBA Needs

"* If required, request CR to have SCBA cylinder fill trailer delivered

"* If required, request CR to have Spare SCBA cylinders delivered.

"* If required, request CR to have spare SCBAs (for additional responders) delivered

.6 References RP/O/B/1000/029 Page 1 of 1

References:

{1}

PIP 01-0405

{2}

PEP 99-1286

{3}

PIP 01-1220

.INP{UP6(X#lON ONLY

"-PREPARATION (2)

Station (3)

Procedure Title Duke Power Company (1),D PROCEDURE PROCESS RECORD R,

OCONEE NUCLEAR STATION FIRE BRIGADE RESPONSE No.

RP/O/B/1000/029 vision No. 004 (4)

Prepared By ROBERT TAYLOR (Signature)

X--Date 02/05U/U (5)

Requires NSD 228 Applicability Determination?

/

Yes (New procedure or revision with major changes)

No (Revision with minor changes)

No (To incorpaoved changes)

(6)

Reviewed By

'\\_.

o a

(QR)

Date

/

Cross-Disciplinary Review By (QR)NA

.Date Reactivity Mgmt Review By (QR)NA-

-Date Mgmt Involvement Review By (Ops Supt) NA Date (7)

Additional Reviews Reviewed By Date Reviewed By Date Temporary Approval (if necessary)

By (OSM/QR)

Date By A_(QR)

Date (9)

Approved By Date

,-"02, PERFORMANCE (Compare with control copy every 14 calendar days while work is being performed.)

(10)

Compared with Control Copy Date Compared with Control Copy Date Compared with Control Copy Date (11)

Date(s) Performed Work Order Number (WO#)

COMPLETION (12)

Procedure Completion Verification:

El Unit 0 [] Unit 1 El Unit 2 El Unit 3 Procedure performed on what unit?

El Yes El NA Check lists and/or blanks initialed, signed, dated, or filled in NA, as appropriate?

El Yes El NA Required enclosures attached?

El Yes El NA Data sheets attached, completed, dated, and signed?

El Yes El NA Charts, graphs, etc. attached. dated, identified, and marked?

El Yes El NA Procedure requirements met?

Verified By Date (13)

Procedure Completion Approved Date (14) Remarks (Attach additional pages)

Duke Power Company Oconee Nuclear Station Fire Brigade Response Reference Use I Procedure No.

RP/O/B/1000/029 Revision No.

004 Electronic Reference No.

OX0091UU

RP/O/B/1000/029 Page 2 of 3 Fire Brigade Response NOTE:

This procedure is an implementing procedure to the Oconee Nuclear Site Emergency Plan and must be forwarded to Emergency Planning within three (7) working days of approval.

1. Symptoms 1.1 Fire, explosions or conditions (smoke, smoldering, burning) associated with a fire have been reported to the Control Room or to the OSC when activated.

1.2 This procedure shall provide guidance to shift personnel and Emergency Coordinator for response, actions, and coordination associated with an incident involving real or suspected fires.

2. Immediate Actions 2.1 IF Fire Brigade response is being considered during routine operations THEN Go to Enclosure 4.1 (Fire Brigade Response - Routine Operations) 2.2 IF Fire Brigade response is being considered AND The OSC/TSC are activated THEN Go to Enclosure 4.2 (Fire Brigade Response - OSC/TSC Activation).
3. Subsequent Actions 3.1 IF Fire Brigade equipment or supplies have been used, THEN Ensure that all equipment is returned to its proper place and consumable supplies are replaced or ordered.

RP/0/B/ 1000/029 Page 3 of 3 NOTE:

Original copies of the Fire Emergency Report can be located in NSD 112, Fire Brigade Organization and Training.

3.2 Complete Enclosure 4.3 (Fire Emergency Report).

3.2.1 Forward a copy to the Fire Protection Engineer.

3.2.2 Initiate a PIP if Enclosure 4.3 (Fire Emergency Report) is completed. Include all important information from Enclosure 4.3 (Fire Emergency Report) in PIP.

3.2.3 Forward this procedure to the Emergency Planning Section.

3.3 Conduct a post incident critique for events requiring full Fire Brigade activation.

4. Enclosures 4.1 Fire Brigade Response - Routine Operations 4.2 Fire Brigade Response - OSC/TSC Activation 4.3 Fire Emergency Report 4.4 Fire Brigade Leader Checklist 4.5 Safety Officer's Checklist 4.6 References

.1 Fire Brigade Response - Routine Operations

1. Fire Brigade Response - Routine Operations

"* Actions may be followed in any sequence.

"* Lines left of procedure steps are used to indicate place in procedure.

"* Check marks are acceptable in these blanks.

"* Complete the procedure steps that apply to this incident.

"* N/A steps not performed.

1.1 Complete the following with information taken from the caller:

Name/Group of person reporting fire/smoke RP/0/B/ 1000/029 Page 1 of 7 Location of fire/smoke Equipment/components affected by fire/smoke 1.2 1.3 Time Date Are there people in the immediate area who need to be warned or relocated to a safe area?

Are there any injured people?

Call back number Notify OSM and STA.

Refer to the Fire Plan for the location reported for fire in Step 1.1 1.3.1 Request support from an unaffected unit. (Refer to Fire Plan SOG #10 for Fire Brigade equipment locations).

.1 Fire Brigade Response - Routine Operations RP/O/B/ 1000/029 Page 2 of 7 1.4 IF Fire is involved or suspected INSIDE the protected area THEN Perform the following:

1.4.1 Send one operator, with a radio, to the fire/smoke location to perform one of the following:

A. Extinguish the fire (if possible) with portable extinguisher (notify Control Room)

OR B.

IF Fire Brigade response is required THEN Notify Control Room immediately.

1.4.2 IF Fire Brigade response is NOT needed THEN Perform the following:

A. Direct NED to

"* Search affected area for victims

"* Activate MERT if required per RP/O/B/IO00/O16, Medical Response.

"* IF NO fire was discovered then exit this procedure.

"* If fire was discovered then GO TO Step 1.4.8.

NOTE:

The Operations Shift Manager (OSM) or designee may activate a full Fire Brigade response without sending someone to investigate first, if deemed necessary. Possible situations that warrant full response could include:

"* Multiple reports from individuals

"* Multiple alarms,

"* Other system indications

"* Any other indicators that the Operations Shift Manager deems significant.

.1 RP/O/B/1000/029 Fire Brigade Response - Routine Operations Page 3 of 7 1.4.3 IF A full Fire Brigade response is needed THEN Perform the following:

A.

Direct NEO to:

"* Search effected area for victims

"* Evacuate surrounding areas

"* Pre-stage nearby equipment for Fire Brigade

"* Report to Fire Brigade Leader for further instructions B.

Use plant page to request all Fire Brigade and MERT members to respond to the fire.

1.

Include any information, if known, that would be important to Fire Brigade members responding to the incident location. (eg. Hazardous materials, smoke, structural damage, etc.)

2.

Include the statement "All non-Fire Brigade personnel please avoid the

" (fire location area) 1.4.4 Use the following directions to activate radios and pagers.

A. Transmit "Standby for Emergency Message" B.

Press the "Instant Call" button labeled "Fire Brigade" C. Wait for the red "Transmit" light on the radio to turn off D. Transmit message including information, if known, that would be important to Fire Brigade members responding to the staging area (e.g. hazardous materials, smoke, structural damage, etc.).

1.4.5 Get staging area location from the Fire Brigade Leader then repeat Steps 1.4.3.B & 1.4.4.

1.4.6 Notify SRO to evaluate the need for staging personnel at the SSF.

1.4.7 Establish and maintain communications with Fire Brigade Leader to provide assistance as needed. {3}

A. Available equipment, refer to SOG #10 in the Fire Plan.

B.

Critical equipment in vicinity of fire (Fire Plan)

1.4.8 II T

1.4.9 I1 T.1 RP/0/B/1000/029 Fire Brigade Response - Routine Operations Page 4 of 7 F

Hazardous materials are involved, HEN Refer to RP/O/B/1000/017 (Spill Response Procedure).

F An oil filled transformer is involved in a fire, "HEN Request Oconee County Fire Department to dispatch the Keowee Key Fire Department to the site.

Dial 9-911 from Ext. 3271 Operations Shift Manager's phone Dial 9-911 from Ext. 2159 Unit 1 Control Room SRO's phone or Dial 911 from 882-7076 Units 1, 2 and 3 Control Rooms, Bell South lines 1.4.10 IF The Fire Brigade identifies a fire requiring application of water for extinguishment, THEN perform the following:

A. Operate HPSW pumps as required to boost pressure (refer to OP/0/A/1 104/011, High Pressure Service Water). {I1 }

B. Make a PA announcement to discontinue use of HPSW for non-essential purposes. { 1 }

C.

Evaluate any Auxiliary Building Flooding Concerns (Refer to Auxiliary Building Flood AP). {2}

1.4.11 IF Fire occurs on backshifts or weekends AND Additional Fire Brigade support is needed, THEN Perform the following:

A. Select the off duty shift(s) that will impact the safe operation of the plant the least by being recalled (i.e., shifts other than on coming shift).

A B

C D

E B.

Call the Switchboard Operator and request them to call the shift(s) selected in Step A.

.1 RP/0/B/1000/029 Fire Brigade Response - Routine Operations Page 5 of 7 NOTE:

All site phones except for the following are blocked from accessing the public 911 emergency service line.

1.4.12 IF Oconee County Fire Department assistance is needed, THEN Dial 9-911 from Ext. 3271 Operations Shift Manager's phone Dial 9-911 from Ext. 2159 Unit 1 Control Room SRO's phone Or Dial 911 from 882-7076 Units 1/2 and 3 Control Rooms, Bell South lines A. Request a response from:

Keowee Key Fire Department Keowee Ebenezer Fire Department Corinth-Shiloh Fire Department

"* Give the fire location (building, parking lot, etc.) and best gate for entry to the fire department dispatch.

"* Call Security (ext. 2222) and request that they have a Security Officer escort the fire department to the fire location.

RP/O/B/1000/029 Page 6 of 7 Offsite fire departments are normally responsible for fire suppression activities outside the Protected Area. The Fire Brigade may provide limited support for a fire outside the Protected Area if resources allow.

"* The Fire Plan for Keowee Hydro calls for sending the Fire Brigade to extinguish fires there.

"* Security will automatically send a Security Officer to investigate alarms on fire detection systems that are monitored by Security in the PAP. Security will call the emergency line to report the existence of a fire or a need for further investigation by plant personnel as needed.

1.5 IF Fire is involved or suspected OUTSIDE the Protected Area, THEN Call Security (ext. 2222) and request that a Security Officer be dispatched to the suspected fire location to verify fire location and nature of the fire.

Request Security Shift Supervisor to relay information back to the Control Room via the emergency line (4911).

1.5.1 1.5.2 IF Security confirms that there is a fire or the situation has the potential for developing into one, THEN Send a Fire Brigade Leader and one Fire Brigade Member or the full Fire Brigade if resources allow.

IF The Fire Brigade identifies a fire requiring application of water for extinguishment THEN Perform the following:

A. Operate HPSW pumps as required to boost pressure (refer to OP/0/A/1 104/011, High Pressure Service Water). { I }

B.

Make a PA announcement to discontinue use of HPSW for non-essential purposes. { 1 }

NOTE:

9.1 Fire Brigade Response - Routine Operations

.1 Fire Brigade Response - Routine Operations RP/0/B/1000/029 Page 7 of 7 NOTE:

All site phones except for the following are blocked from accessing the public 911 emergency service line.

1.5.3 IF Oconee County Fire Department assistance is needed, THEN Dial 9-911 Dial 9-911 from Ext. 3271 Operations Shift Manager's phone from Ext. 2159 Unit I Control Room SRO's phone or from 882-7076 Units 1/2 and 3 Control Rooms, Bell South line 1.5.4 Request a response from:

Keowee Key Fire Department Keowee Ebenezer Fire Department Corinth-Shiloh Fire Department

"* Give the fire location (building, parking lot, etc.) and best gate for entry to the fire department dispatch.

"* Call Security (ext. 2222) and request that they have a Security Officer escort the fire department to the fire location.

NOTE:

Keowee Hydro Station is located in Pickens County. Dialing 9-911 will NOT access the Pickens County Fire Dispatch.

1.5.5 IF Six Mile Fire Department assistance is needed for a fire at Keowee Hydro Station, THEN Call the Pickens County Sheriffs Department (898-5500) and request the response of Six Mile Fire Department to Keowee Hydro Station.

  • Call Security (ext. 2222) and request that they have a Security Officer escort the fire department to the fire location.

1.6 Return to Section 3, Subsequent Actions.

Dial 911

.2 RP/O/B/1000/029 Fire Brigade Response - OSC/TSC Activation Page 1 of 6

1. Fire Brigade Response - OSC/TSC Activation

"* Actions may be followed in any sequence.

"* Lines left of procedure steps are used to indicate place in procedure.

"* Check marks are acceptable in these blanks.

"* Complete the procedure steps that apply to this incident.

"* N/A steps not performed.

1.1 Complete the following with information taken from the Work Control Assistant who received the emergency line call:

Name/Group of person reporting fire/smoke Location of fire/smoke Equipment/components affected by fire/smok Time Date Are there people in the immediate area who need to be warned or relocated to a safe area?

Are there any injured people?

Call back number 1.2 Refer to Fire Plan for the location reported for fire in Step 1.1.

1.2.1 Request support from an unaffected unit. (Refer to Fire Plan SOG#10 for Fire Brigade Equipment locations).

  • e

.2 Fire Brigade Response - OSC/TSC Activation RP/0/B/ 1000/029 Page 2 of 6 NOTE:

The Emergency Coordinator or designee may activate a full Fire Brigade response without sending someone to investigate first, if deemed necessary. Possible situations that warrant full response could include:

  • Multiple reports from individuals
  • Multiple alarms,
  • Other system indications
  • Any other indicators that the Emergency Coordinator deems significant.

1.3 IF Fire is involved or suspected INSIDE the Protected Area, THEN Perform one of the following as required.

1.3.1 Send one operator, with a radio, to the fire/smoke location to perform one of the following:

A. Extinguish the fire (if possible) with portable extinguisher (notify Control Room)

OR B.

IF Fire Brigade response is required THEN Notify Control Room immediately.

1.3.2 IF Fire Brigade response is NOT needed, THEN Perform the following:

A. Direct NEO to search affected area for victims B.

Activate MERT if required per RP IO/B131000/016 (Medical Response)

C. IF NO fire was discovered then exit this procedure.

D. If fire was discovered then GO TO Step 1.3.5.

.2 RP/O/B/1000/029 Fire Brigade Response - OSC/TSC Activation Page 3 of 6 1.3.3 IF A full Fire Brigade response is needed, THEN Perform the following:

A. Direct NEO to:

"* Search effected area for victims

"* Evacuate surrounding areas

"* Pre-stage nearby equipment for Fire Brigade

"* Report to Fire Brigade Leader for further instructions B.

Dispatch Fire Brigade Members assigned to the OSC to respond to the fire.

C.

Request the OSC Security Manager to have MERT respond along with the Fire Brigade to the fire location.

1.3.4 Establish and maintain communications with Fire Brigade Leader to provide assistance as needed. {3}

A. Available equipment (Refer to SOG #10 in the Fire Plan)

B.

Critical equipment in vicinity of fire (Fire Plan) 1.3.5 IF Hazardous materials are involved, THEN Refer to RP/0/B/1000/017 (Spill Response Procedure).

1.3.6 IF An oil filled transformer is involved in a fire, THEN Request Oconee County Fire Department to dispatch the Keowee Key Fire Department to the site.

Dial 9-911 from Ext. 3271 Operations Shift Manager's phone Dial 9-911 from Ext. 2159 Unit 1 Control Room SRO's phone or Dial 911 from 882-7076 Units 1, 2 and 3 Control Rooms, Bell South lines

.2 Fire Brigade Response - OSC/TSC Activation RP/O/B/1000/029 Page 4 of 6 1.3.7 IF The Fire Brigade identifies a fire requiring application of water for extinguishment, THEN Perform the following:

A. Operate HPSW pumps as required to boost pressure (Refer to OP/O/A/1104/011, High Pressure Service Water). {I1 }

B.

Make a PA announcement to discontinue use of HPSW for non-essential purposes. { I }

C. Evaluate any Auxiliary Building Flooding Concerns (Refer to Auxiliary Building Flood AP). {2}

1.3.8 Notify SRO to evaluate the need for staging personnel at the SSF..

1.3.9 IF Fire occurs on backshifts or weekends AND Additional Fire Brigade support is needed, THEN Perform the following:

A. Select the off duty shift(s) that will impact the safe operation of the plant the least by being recalled (i.e., shifts other than on coming shift).

A B

C D

E B.

Call the Switchboard Operator and request them to recall the shift(s) selected in Step A.

1.3.10 IF Oconee County Fire Department assistance is needed, THEN Request that the Offsite Communicator call and request a fire department response from:

Keowee Key Fire Department Keowee-Ebenezer Fire Department Corinth Shiloh Fire Department A. Give the fire location (building, parking lot, etc.) and best gate for entry to the Offsite Communicator so that it can be given to the fire department dispatcher.

B.

Request that a Security Officer meet and escort the fire department to the fire location.

.2 RP/O/B/1000/029 Fire Brigade Response - OSC/TSC Activation Page 5 of 6 NOTE:

Offsite fire departments are normally responsible for fire suppression activities outside the Protected Area. The Fire Brigade may provide limited support for a fire outside the Protected Area if resources allow.

The Fire Plan for Keowee Hydro calls for sending the Fire Brigade to extinguish fires there.

Security will automatically send a Security Officer to investigate alarns on fire detection systems that are monitored by Security in the PAP. Security will call the emergency line to report the existence of a fire or a need for further investigation by plant personnel as needed.

1.4 IF Fire is involved or suspected OUTSIDE the Protected Area, THEN Request that a Security Officer be dispatched to the suspected fire location to verify the location and status of the fire. Request that information be relayed back to the OSC via the emergency line (4911).

1.4.1 IF Security confirms that there is a fire or the situation has the potential for developing into one, THEN Send a Fire Brigade Leader and one Fire Brigade Member or the full Fire Brigade if resources allow.

1.4.2 IF The Fire Brigade identifies a fire requiring application of water for extinguishment, THEN Perform the following:

A. Operate HPSW pumps as required to boost pressure (refer to OP/O/A/1 104/011, High Pressure Service Water). { 1 }

B.

Make a PA announcement to discontinue use of HPSW for non-essential purposes. { I }

.2 RP/0/B/1000/029 Fire Brigade Response - OSC/TSC Activation Page 6 of 6 1.4.3 IF Oconee County Fire Department assistance is needed, THEN Request that the Offsite Communicator call and request a fire department response from:

"* Keowee Key Fire Department

"* Keowee-Ebenezer Fire Department

"* Corinth Shiloh Fire Department A. Give the fire location (building, parking lot, etc.) and best gate for entry to the Offsite Communicator so that it can be given to the fire department dispatcher.

B. Request that a Security Officer meet and escort the fire department to the fire location.

NOTE:

Keowee Hydro Station is located in Pickens County.

1.4.4 IF Six Mile Fire Department assistance is needed for a fire at Keowee Hydro

Station, THEN Request the Offsite Communicator call the Pickens County Sheriffs Department (898-5500) and request Six Mile Fire Department to respond to Keowee Hydro Station.

Request that a Security Officer meet and escort the fire department to the fire location.

1.5 Return to Section 3, Subsequent Actions.

.3 Fire Emergency Report FIRE EMERGENCY REPORT Rp/0/B/ 1000/029 Page 1 of 1 Station/Location:

Location (Unit/Area):

Time Discovered:

Operations Shift Manager:

Date:

Discovered By:

Evacuation: Yes No Partial Fire Brigade Response: Yes No Other Time Fire Extinguished:

List All Fire Protection Equipment Used Operation Satisfactory: Yes No (Use Back For Details)

Equipment Restored For Use: Yes No If no, Explain (Use Back for Details)

Outside Assistance Called: No Yes Agency(s)

Area Involved: "

Point of Origin (If known):

Cause (If known Damage To:

Building Equipment Personal Other Injuries Reported:

Briefly Describe What Happened:

  • Signature of Fire Brigade Leader
  • Signature of Operations Shift Manager
  • Notify Safety Representative of Fires Involving Personal Injury (Refer to Duty List for after hours).

.4 RP/O/B/1000/029 Fire Brigade Leader Checklist Page 1 of 1 TASK Don Fire Brigade Leader Vest Determine Staging Area and Communicate to Control Room

"* Safe accessibility

"* Minimal distractions

"* Appropriate vicinity Establish The Following Teams/Priorities:

"* Entry Team - Priority = search & rescue/fight fire

"* Backup Team - Priority = backup Entry Team/help fight fire

"* Rapid Intervention Team - Priority = Rescue Fire Fighters (if required)

Stress The Following Items With All Teams Prior To Dispatching To Fire:

"* Safety of Team is top priority

"* Stay with the hose/rescue line at all times

"* Maintain contact with your team at all times

"* All teams report to Safety Officer prior to entering fire zone and after exiting fire zone for accountability Assess The Fire:

"* Request CR to dispatch additional resources as required:

Off Duty Shifts and/or Offsite Fire Departments Outside Equipment Truck and/or Equipment Carts C02 or Wheeled Dry Chemical Extinguishers Foam Units

"* Exposures - Critical Equipment Concerns Above/Below Fire?, Fire/Smoke/Water?, Electrical Hazards?

"* Report Critical Equipment Concerns to CR for Emergency Plan Consideration Request Location of Nearest Fire Hose Locations From Control Room:

"* Elevation/column #

"* Communicate locations to teams Request Assistance From RP/Security

"* Request Security At The Scene To Control Access To The Area

"* If Radiological Concerns Exist, Request CR To Notify RP Refer To Fire Plan As Required:

0 Hazards/Ventilation 0 Refer To SOG #10 for Fire Brigade equipment locations If Hazardous Materials Involved, Request CR to Dispatch Haz-Mat Team

.5 RP/O/B/1000/029 Safety Officer's Checklist Page I of I TASK Don Safety Officer Vest Establish Accountability For FB Members Name tags/accountability board Perform PPE Checks of Fire Fighters

"* All skin covered

"* All turnout gear openings closed

"* SCBA cylinder full ( > 4000 psi)

  • SCBA cylinder valves fully open
  • PASS device operational Log Team Assignments on Accountability Board

"* Log time on air

"* Log entry times

"* Log team assignments Assign MERT Responsibilities

"* Stand by with medical equipment

"* Monitor FB members for signs of heat exhaustion/stress/etc.

"* Provide drinking water for fire fighters Maintain Continuos Contact With Fire Brigade Leader Evaluate SCBA Needs

"* If required, request CR to have SCBA cylinder fill trailer delivered

"* If required, request CR to have Spare SCBA cylinders delivered.

"* If required, request CR to have spare SCBAs (for additional responders) delivered

.6 References RP/0/B/ 1000/029 Page 1 of I

References:

{1}

PIP 01-0405

{2}

PIP 99-1286

{3}

PIP 0O1-1220