{{#Wiki_filter:10.0 Class 1 and 2 Repairs and Replacements As required by ASME Section Xl 1989 Edition, with no Addenda, a record (Form NIS-2) of Class 1 and 2 Repairs and Replacements for work performed from April 8, 2000 to October 22, 2001 is included in this section of the report. The individual work request documents and manufacturers' data reports are on file at Catawba Nuclear Station. 10.1 Class 1 and 2 PreserviceExaminations As required by ASME Section XI 1989 Edition, with no Addenda, Preservice Inspection (PSI) Examinations were performed on ISI Class 1 and 2 items during the EOC 11 refueling cycle. All Class 1 and 2 PSI examination data listed below is on file at the Catawba Nuclear Station QA Vault. The following is a list of Class 1 and 2 items that received PSI examinations during the EOC 11 refueling cycle. Work Order Number Weld / Component ID Class Comments 98428702-01 S/G 2B Bowl drain A repair 98369054-06 SNUBBER 2-R-NC- A 1707 98374330-05 VALVE 2NC2 A 98188260-05 VALVE 2NC-2 A 98188261-03 VALVE 2NC3 A 98104792-01 HANGER WELD 2-R- B BB-1063-4 98260092-01 SNUBBER 2-R-CF- B 1011 98265766-01 SNUBBER 2-R-CF- B 1523 98265764-01 SNUBBER 2-R-CF- B 1586 98406023-01 SNUBBER 2-R-ND- B 0277 98265763-01 SNUBBER 2-R-NM- B 1079 Refueling Outage Report EOC 11 Page 1 of 2 Catawba Unit 2 Revision 0 Section 10 December 6, 2001
Work Order Number Weld / Component ID Class Comments 98188215-09 SNUBBER 2-R-NM- B 1379 PIVOT PIN 98364944-05/09 SNUBBER 2-R-NV- B 0240 98188027-07 SNUBBER 2-R-NV- B 0243 98430375-01 SNUBBER 2-R-SA- B 1504 98428722-01 VALVE 2KC340 B 98175630-04/07 VALVE 2NV186A B WELDS 2NV298-6; 2NV297-3,4 98431053-01 VALVE 2NV221 B WELDS 2NV20-10, 2NV22-1 98174833-06 VALVE 2NV-269 B WELDS 2NV405-1,2,3 98368427-01/04 VALVE 2NV326 B WELDS 2NV625 14,15,16 98268605-01/05 VALVE 2RN405 B 98197169-15 VALVE BONNET 2NI- B 11 8A 98095354-01/12 WELDS 2NV196- B 55,56 98364944-05/09 WELDS 2NV36-4 B 2NV56-15 Refueling Outage Report EOC 11 Page 2 of 2 Revision 0 Catawba Unit 2 December 6, 2001 Section 10
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 06/26/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit [- 1 [ *2 F[]3 [-] Shared (specify Units-] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981 88262-02 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A 4 Identification of System NC REACTOR COOLANT SYSTEM Class A
- 5. (a) Applicable Construction Code III 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Replacement Stamped A Bolting Number Rod- SA193, Hex Nuts- SA194 REPLACEM g4//
(yes or no) B REPAIRED /1Mt C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1/2in. x II in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work: Replaced bolting-
- 8. Test Conducted: Hydrostatic - Pneumatic -l] Nominal Operating Pressure D Other [ Exempt 0 Pressure NA psig Test Temp. NA deg.F.
- 9. Remarks _ Code Cases __NONE This form was reproduced. The original was lost. 7- ' /&i/o 7, 4 (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed dd -'TECHý- SPEC Date , -.20_6 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION the I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have to the best inspected the components described in this Owners Report during the period .3-Z,4-0 C, to I /16-('2-and state that examinations and taken corrective measures described in this Owner's of my knowledge and belief, the Owner has performed Report in accordance with the requirements of the ASME Code, Section XI. the By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall examinations and corrective this be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with inspection.
*-..*-% (j fL- Commissions NC 978 Inspector's Signature Date 1 - 1(2 _20_t - -
Page 2 of 2 Revision 6
( ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 11/29/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit El-i F ]2 [:] 3 D-- Shared (specify UnitsD-] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 982 72153-46 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class C RN NUCLEAR SERVICE WATER SYSTEM
- 5. (a) Applicable Construction Code II1 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE g Tde~ntifh-cition o~f Corn onentF* Renaired or Renlacement Comnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped Number _(yes or no)
A Bolting Threaded Rod- SA193, Hex Nuts-SA194 REPLACEM] for valve 2RN67A _ __ _ B REPAIRED C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Install Refurbished Valve 2RN67A_
- 8. Test Conducted: Hydrostatic El] Pneumatic R Nominal Operating Pressure L Other - Exempt E Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed TECH SPEC Date /& ' ,2060 S Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 1b-?,S,-o0 to 1-2!tL" J and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. U gox yyv " Commissions NC 978 Inspector's Signature Date_) -2ý_,20_0) _ Page 2 of 2 Revision 6
/
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 12/13/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit -I 1 [ 92 [-- 3 [-I Shared (specify Units[:] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 982 54178-21 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class C RN NUCLEAR SERVICE WATER SYSTEM
- 5. (a) Applicable Construction Code III 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped Number __(yes or no)
A Bolting Threaded Rod-SA193 Hex Nuts-SA194 REPLACEM] A/ for valve 2RN0232A _ B REPAIRED "7;41-1ý C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Install Refurbished Valve 2RN0232A_
- 8. Test Conducted: Hydrostatic ] Pneumatic - Nominal Operating Pressure D Other[:] Exempt M Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed .kz5ý 72o TECH SPEC Date / 7 ,20 vo Owner or Owner's Designee, Title
/
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period ID-2,2-ot to I-ZA-cM and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
* -i* W U Commissions NC 978 Inspector's Signature Date _[-2HA ,20_0)) _
Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 11/28/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 12. Plant CATAWBA NUCLEAR STATION 2a Unit 'l 1 *2 D Shared (specify Units- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 982 54184-36 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class C RN NUCLEAR SERVICE WATER SYSTEM
- 5. (a) Applicable Construction Code 1m1 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE i TrrAP~i~rtI'nA nf"(2mnnnn~nt* R chaired or Renlacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Serial Number Built Replaced. or Code Stamped Component Manufacturer Replacement Number (yes or no)
A Bolting Rod-SA193, Hex Nuts-SA194 for valve REPLACEM /l 2RN-039 A"0 B REPAIRED 7AP"*ý C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (I) size is 81/2in. x 11 in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Install Refurbished Valve 2RN039_
- 8. Test Conducted: Hydrostatic F-- Pneumatic E' Nominal Operating Pressure ED Other L] Exempt Z Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed "* YA2Z* TECH SPEC Date I ,2 20 9 0
/ Ovri wner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period jb-*)-c* to I -l-o 1 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
"JefYX tY¥V t.L& Commissions NC 978 Inspector's Signature Date _ ).-?A ,20_ 01 _
Page 2 of 2 Revision 6
ASME Section -x Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI la Date 11/28/00 Sheet 1 of 4-
- 1. Owner DUKE POWER COMPANY Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit 0-' 1 F *2 r] 3 n Shared (specify Units[:] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order# 982 13419-01,07 98240957-03 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # CE 21396 Expiration Date N/A 4 Identification of System Class C RN NUCLEAR SERVICE WATER SYSTEM
- 5. (a) Applicable Construction Code III 1974 Edition, S'75 Addenda, N-416-1 Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE 6 Identification of Comnonent.s Renaired or Renlacement Components Column I Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Manufacturer Serial Number Built Replaced. or Code Component Replacement Stamped Number (yes or no)
A Pipe Duke Power C-2RN 160 8"pipe-SA106,SB675 2"pipe- 9 R i(--.* __________Co. SAl 06,5A376 _____ B Pipe Fittings Duke Power C-2RN 160 90 EIl-SA234,SA182,SB366 45 Ell ________Co. B366 8x6 Red.-SA234 S_____ ) 'tf /VSs4 C Pipe Fittings Duke Power C-2RN 160 Flanges-SB462,SA105 Cap- P3 E.-.., ! Col SA234,SA105 H/Coupl.-SB462 fl2-b ,__ fAý D Pipe Welds Duke Power C-2RN 160 2CA184-24,25,1,2,3,4,5,6,8,9,10 Co. 2CA186-1,2,3,4,5,6,9 I A{e. 1110>2' E Pipe Welds Duke Power C-2RN 160 2RN449-10,8,7,6,5,4,3,2,1 2CA185-7 Co. 2RN57-24,25,26,27,28,29 I - 44;. F ,,o-s'4/9.,qj/9% ~t Page 1 of2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 11/28/00 Sheet I-of 1+
Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit El I 32 - 3 R Shared (specify Units- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 982 13419-01,07 98240957-03 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # CE 21396 Expiration Date N/A 4 Identification of System CA AUXILIARY FEEDWATER SYSTEM Class C
- 5. (a) Applicable Construction Code III 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE 6 Tdentific.*tion nfl'o.nn nnent* Ppnniired or Re~nlhement Comnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Number_____(yes Replacement Stamped or no)
A Sway Strut Anvil Inter. 2000-49 41- 2-R-CA-0271 *EPA.RED) 42662 Ale W jz B Sway Strut Grinnell 1994-508 41- 2-R-CA-0266 R-EPA-RE 18129 Me____ //AID C Sway Strut Grinnell 1994-37141- 2-R-CA-0265 'REPAIRF1Y 16815 A/,]e P~~1 D Sway Strut Grinnell 1994-509 41- 2-R-CA-0265 -R..E1?A4RE,9 ____________18129 No___ 0j E Sway Strut Grinnell 2000-36 41- 2-R-CA-0264 RPAIREE, / 41118 Ale_) Ale'/ F Sway Strut Grinnell 2000-3441 2-R-CA-0264 REPAIRED 141118 _A/_,.) ,.__/ Page 1 of2 Revision 6
ASME Sectio1 .. - Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI 1.Owner DUKE POWER COMPANY la Date 11/28/00 Sheet 3 of+ Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit El- I 2 [-] 3 ] Shared (specify Units- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 982 13419-01,07 98240957-03 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # CE 21396 Expiration Date N/A 4 Identification of System CA AUXILIARY FEEDWATER SYSTEM Class C
- 5. (a) Applicable Construction Code III 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped Number _(yes or no)
A Fig 640 Clamp Anvil Inter. 2-R-CA-0217, 2-R-CA-270 REPAARED, NVe co Ic B Fig 640 Clamp Grinnell 2-R-CA-266, 2-R-CA-0265, 2-R-CA- -REPAIRE 0264 /'/ec' / C Fig 295N Clamp Grinnell 2-R-CA-0269 D Rear Bracket Grinnell 2-R-CA-0266, 2-R-CA-0265 -RE.PA.RED E Hanger Welds Duke Power C-2CA 159 2-R-CA-264-1,2,3,4 2-R-CA-269-1 2- REPAIRED" Co. R-CA-271-4,3 2-R-CA-266-1,2 Ileej ^[6_s F Hanger Welds Duke Power C-2CA 159 2-R-CA-265-1,,2,3,4 RfP,/ft,/ Co. __41t'e r) Page I of 2 Revision 6
Section E Exhibit A ASME Sectiolk Al Manual FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Sheet A+of 4
- 1. Owner DUKE POWER COMPANY la Date 11/28/00 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit L- 1 2 - 3 [-7 Shared (specify Units[:] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 982 13419-01,07 98240957-03 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # CE 21396 Expiration Date N/A 4 Identification of System CA AUXILIARY FEEDWATER SYSTEM Class C
- 5. (a) Applicable Construction Code III 1974 Edition, S'75 Addenda, N-416-1 Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE Column 3 Column Column 5 Column Column 7 Column Column 1 Column 2 8 4 6 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Serial Number Built Replaced. or Code Component Manufacturer Replacement Stamped Number (yes or no)
A Valve Flowserve EOOIT- 1-4 2472 For valve tag 2RN-30OB 2000 REPAiRE-, B Valve BNL A981103-9-6 For valve tag 2RNE98 5/99 R7EPA{RE / C Valve Fisher 9584B-020A 374 For valve tag 2RNE93 1999 RE-PMRHED j D Sway Strut Grinnell 41-16815 2-R-RN-130 Al' E Sway Strut Grinnell M5452 2-R-RN-130 AjRA F Clamps 2-R-RN-140 2-R-RN-130 2-R-RN-163 R-E D 3 rage .i rage I oi6 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x I1 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Install 2RN310B to RN Header& Change to 8"_
- 8. Test Conducted: Hydrostatic E- Pneumatic F Nominal Operating Pressure [\ Other '] Exempt L Pressure 65 psig Test Temp. 68 deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of uthorization No. N/A Signed TECH SPEC Date /Z& / r,220 d
.1 / Owner oFOwner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period - "18 - ),? to 2- -6 v and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions NC 978 Inspector's Signature Datek?_ .- :_ ,20 _: Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 11/08/00 Sheet 1 of 4 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit Ii" 1 32 [' 3 - Shared (specify Units[-' )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 982,40950-03 98213418-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # CN 21396 Expiration Date N/A 4 Identification of System Class .A-C,,
SYSTEM C)..& RN NUCLEAR SERVICE WATER
- 5. (a) Applicable Construction Code 11I 1974 Edition, S'75 Addenda, N-416-1 Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE 6 Identification of Con onents Renaired or Replacement Comnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Replacement Stamped Number_ (yes or no)
A Pipe Duke Power C-2RN 160 8" Pipe-SB675, 8" Pipe-SA106, 2" Pipe- REPLACEM] Co. C-2CA 159 SA376 _ 1_Y B Pipe Fittings Duke Power C-2RN 160 8" 90 Ell (LR,SR)-SB366, SA234 & 45 REPLACEM Co. C-2CA 159 Ell- SA234, 2" H/Cplg.-SB462 _______ C Pipe Fittings Duke Power C-2RN 160 2" Pipe Cap-SA106, 8x6 Red.-SA234, REPLACEM.. Co. C-2CA 159 8"SO Flange- SB462,SA105 REPLACEM D Bolting Duke Power C-2RN 160 Hex Nuts-SA194, Studs- SA193 C) REPLACEMI Co. C-2CA 159 F REPAIRED FREPA IRED Page 1 of 2 Revision 6
Section E Exhibit A ASME Section XI Manual FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 11/08/00 Sheet lof l Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit E- 1 232 [* 3 [] Shared (specify Units- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 982,40950-03 98213418-01 Address 526 S. ChurchSt. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # CN 21396 Expiration Date N/A 4 Identification of System Class C RN NUCLEAR SERVICE WATER SYSTEM
- 5. (a) Applicable Construction Code 11U1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE iK ,TAt!f÷i~t-irtn nfC"*m rinont'* Pannirad or R enlacement Components Column 2 Column 3 Column Column 5 Column Column 7 Column Column 1 8 6
I_ _ _4 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped Number (yes or no) A Strut Grinnell 41-42662 2-R-CA-302 -R/TA _ _____ Ale___ w________________ -IwNi __________2000-45 B Strut Grinnell 41-42662 2-R-CA-303 RPAl- EB " 2000-47 Ake__ Strut Grinnell 41-42662 2-R-CA-304 APC/e tM5 D 4______ ___________2000-50 Grinnell 41-42662 2-R-CA-305 REpAI f.)___ A(I rill D Strut 2000-51 ,M,,e IV, Fig. 640N for 2-R-CA-302, 305, 303, EP AH-- E Pipe Clamps 304 Ae) /.A! F Pipe Clamps Fig. 295N for 2-R-CA-299 't" Page 1 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 11/08/00 Sheet 3 of t-Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit -1 1 [ 32 E-] 3 E-l Shared (specify Units[-l )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 982,40950-03 98213418-01 Address 526 S. Church.St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # CN 21396 Expiration Date N/A 4 Identification of System Class C RN NUCLEAR SERVICE WATER SYSTEM
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, N-416-1 Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE T&.nnirecl nr Renlneement Comnonents i T~ptt~ fi-rot inn Af Cnmnnno~mt~l
.Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped Number ____________________________ _______(yes or no)
A Valve Flowserve EOOIT-1-3 2471 8" Gate Valve tag #2RNE250A 2000 *E9A4Fd---o B Valve BNL A981103-9-5 2" Ball Valve tag 2RNE97 1999 PtPhpA g'- AO C Pipe Welds Duke Power C-2RN 160 2RN448-1,2,3,4,5,6,7,8,10 2CA170-2, 8-S R._AB / Co. C-2CA 159 3,6,7,8,9,10,11,12,14,15,16, S A/e &) /6.5 JA 10 D 2CA171-39,40,41,42,43,44,38,45, 2CA170-17,13,1 2RN61-48 (eS E REPAIRED REPAIRED Page 1 of2 Revision 6
Section E Exhibit A ASME Section XI Manual FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 11/08/00 Sheet 4 of 4 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit I-- 1 F 2 0---3 E] Shared (specify UnitsD- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 982,40950-03 98213418-01 Address 526 S. Church.St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # CN 21396 Expiration Date N/A 4 Identification of System Class C RN NUCLEAR SERVICE WATER SYSTEM
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
. o1 L V iom2 Cln Column 5Cln oun7 lm Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 6 8 I_ _ _ 4 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Serial Number Built Replaced. or Code Component Manufacturer Replacement Stamped Number (yes or no)
A Valve Fisher 95848-490 375 Butterfly Valve tag#2RNE95 1999 R \PARFB B Strut Grinnell ECQ-K27 2-R-RN-282 1983 RE AittTr C Strut Grinnell ECQ-K27 2-R-RN-283 1983 FEP*HD v D Hanger welds Duke Power C-2CA 159 2-R-CA-305-1,2 2-R-CA-303-1,2 - RE-PA*tED Ves.&> l"~ ~ _______Co. REPAIRED E F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form F NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Install 2RN250A at RN Header & Change to 8"_
- 8. Test Conducted: Hydrostatic [] Pneumatic LI Nominal Operating Pressure 1n Other [-- Exempt E]
Pressure 50 psig Test Temp. 65 deg.F.
- 9. Remarks _Functional completed on work orders 98213418-07 (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed A 0 /,C TECH SPEC Date 4Jffi,20 00
/ Owner -r Owner's Designee, Title I
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period S - I -oo to t1" 0 -0 0 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. ____ Commissions NC 978 In*pector's Signature Date _1- ?, ,20oo _ Page 2 of 2 Revision 6
Section E Exhibit A ASME Section XI Manual FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI Sheet 1 of 1 la Date 06/19/00 Sheet 1 of I
- 1. Owner DUKE POWER COMPANY Address 526 S. CHURCH STREET. CHARLOTTE N.C.
28201-1006 2 E-] 3 [] Shared (specify Units- )
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit 1 [
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 980ýg3234-01/02 Address 526 S. Church St. Charlotte, N.C. 28201-1006 0986 Type Code Symbol StamP N/A Authorization No. N/A 3b NSM or MN # CE1 Expiration Date N/A Class C 4 Identification of System RN NUCLEAR SERVICE WATER SYSTEM Cases
- 5. (a) Applicable Construction Code III 1974 Edition, S'75 Addenda, N-416-1 Code NONE (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda
- 6. Identitication o0t Lomponenis tKepuredu or Riep .av *,i ,ri.... Column Column 7 Column Column 2 Column 3 Column Column 5 Column 1 6 8 4
N B Other Identification (Size) Year Repaired. ASME Name of Name of Manufacturer Replaced. or Code Number Built Replacement Stamped Component Manufacturer Serial (yes or no) Number A Valve Pacific Valve 0422-6 136 Valve tag #2RN46 1977 REPLACED y/6 90-58890 Valve tag #2RN46 1990 REPLACEM B Valve ITT Valve AID 14 C-2RN 160 3" Pipe- SA106, 2" Pipe-SA312, Elbow- REPLACEM C Pipe Duke Power __k _ Co. SA182 160 ORN121-16,8, 0RN122-1,3,2,15,9,4 REPLACEM , D Pipe Welds Duke Power C-2RN Co. ORN 139-40 1' E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replace valve 2RN46_
- 8. Test Conducted: Hydrostatic - Pneumatic L-1 Nominal Operating Pressure 1`7 Other [1 Exempt []
Pressure 73 psig Test Temp. 57 deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. N/A Expiration Date N/A Type Code Symbol Stamp Certificate of Authorization No. N/A Signed TECH SPEC Date " ,20oo I e Owner or Owner's Designee, Titl
/
CERTIFICATE OF INSERVICE INSPECTION the I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 2-ýZ8b 0) to (, -i - OV and state that to the best in this Owner's of my knowledge and belief, the Owner has performed examinations and taken corrective measures described Report in accordance with the requirements of the ASME Code, Section XI. the By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the Inspector nor his employer shall examinations and corrective measure described in this Owners Report. Furthermore, neither kind arising from or connected with this be liable in any manner for any personal injury or property damage or a loss of any inspection.
ý" W41 U Inspector's lSignature Commissions NC 978 Date _b.Vý\_ ,20_ CV -
Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI la D*ite 06/19/00 Sheet of
- 1. Owner DUKE POWER COMPANY Address 526 S. CHURCH STREET. CHARLOTTE NC 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Ut lit [-] 1 Z2 E] 3 E" Shared (specify Units Address 4800 CONCORD RD. YORK, SC 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98188261-03 Address 526 S. Chtirch St. Charlotte, NC 28201-1006 Type Code SymbolfStamp N/A Authorization No. N/A 3b N.SM or MN # N/A Expiration Date N/A 4 Identification of System NC REACTOR COOLANT SYSTEM Class A
- 5. (a) Applicable Construction Code III 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column 4 Column 5 Col 6 Column 7 Column 8 Name of Component Name of Mfg. Mfg. Serial No. National Board Other Identification Year Repaired. ASME No. (Size) Built Replaced. or Code Replacement Stamped (yes or no)
Dresser BS-2865 N/A INC-001 1979 ** L] NO A Safety Relief Valve [:]YES Dresser BS-2866 N/A 1NC-002 1979 ** LI NO B Safety Relief Valve _EYES
'Kind(
C Safety Relief Valve Dresser BS-2867 N/A 1NC-003 V1/V Li F-; KE S 19I, D Safety Relief Valve Dresser BS-2868 N/A NFARE 1Y/V EYES rl'" BS-2869 N/A 2NC-001 1980 ** E] NO E Safety Relief Valve Dresser [-]YES Dresser BS-2870 N/A 2-NC-002 1980 ** E] NO F Safety Relief Valve [-]YES G Safety Relief Valve Dresser BS-2871 N/A 2-NC-003 1980 ** I OES Dresser BS-2872 N/A SPARE 1979 E[tNO v [] -- H Safety Relief Valve __-]YES rage i oi66 Revision
( ASME Section X1 Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 06/21/00 Sheet Zof3 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit [- 1 [ (]2 [-03 E" Shared (specify UnitsD'] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981 88261-03 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/Ak Expiration Date N/A 4 Identification of System NC REACTOR COOLANT SYSTEM Class A
- 5. (a) Applicable Construction Code III 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column I Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Replacement Stamped Number_ (yes or no)
A Bolting Rod- SA-193, Hex Nuts- SA194 * /,. B REPAIRED 5-"
/REAIE C REPAIRED E REPAIRED F REPAIRED F REPAIRED Page I of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 l/2in. x I I in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work: Replace safety relief valve 2NC-003 with existing spare.
- 8. Test Conducted: Hydrostatic - Pneumatic E Nominal Operating Pressure
- Other [- Exempt D]
Pressure 2235 psig Test Temp. 648 deg.F.
- 9. Remarks *
- These valves are interchangeable and can be used in any of the valve applications / locations listed.
(Applicable Manufacturers Data Records to be attached) CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/__A Expiration Date N/A Certificate of Authorization No. N/A Signed Z,2& Date _4 Oo
/ - Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Providence of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period l Uoo to 6' 20-6'0 ; and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
- YV\, A) Commissions NC 978 Inspector's Signature Date -b- 2-0-ov Page 2 of 2 Revision 6
( ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 06/26/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit 1 [ 2 E-] 3 E] Shared (specify Units[] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981 97169-15 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/M\
Expiration Date N/A 4 Identification of System NI SAFETY INJECTION SYSTEM Class B
- 5. (a) Applicable Construction Code III 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Replacement Stamped Number_ (yes or no)
A Valve Bonnet Borg Warner For valve tag #2NI 11 8A REPLACED , B Valve Bonnet Borg Warner For valve tag #2NI1 18A REPLACEM A C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work R/R Valve 2NI 118A_
- 8. Test Conducted: Hydrostatic [] Pneumatic [] Nominal Operating Pressure Z Other [] Exempt E]
Pressure 1530 psig Test Temp. 79 deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed A*__*_: TECH SPEC Date ,20 0o
/ - Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period , 4-' to ( 24-v and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. ___, __ _ -J__ _ . _ Commissions NC 978 Invs'ector's Signature Date_(&Z-U_ 20_OM__- Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section Xl
- 1. Owner DUKE POWER COMPANY la Date 06/28/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit - 1 2 --] 3 - Shared (specify Units- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981 80586-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A 4 Identification of System KC COMPONENT COOLING SYSTEM Class C
- 5. (a) Applicable Construction Code III 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Number(yes Replacement Stamped or no)
A Valve BIF N-1697-1 474 For valve tag # 2KC006 1980 REPLACED (sn B Valve Fisher 95843-01 373 For valve tag # 2KC006 1999 REPLACEM C Bolting Rod- SA193, Hex Nuts- SA194 REPLACEM dibW' D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replace Valve 2KC006_
- 8. Test Conducted: Hydrostatic - Pneumatic [] Nominal Operating Pressure [ Other - Exempt LI Pressure 88.6 psig Test Temp. 73 deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A SignedAd TECH SPEC Date _,20 6 0 Owner or Owner's Designee, Title
/
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 3 18 -o > to GZ1 -a!) and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
& ",&V .. t Commissions NC 978 Inspector's Signature Date _j - ,20_O Page 2 of 2 Revision 6
Section E Exhibit A ASME Section XI Manual FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI 1a Date 06/20/00 Sheet I of I
- 1. Owner DUKE POWER COMPANY Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006 2a Unit 1 1I *2 [-ý 3 n Shared (specify Units[] )
- 2. Plant CATAWBA NUCLEAR STATION Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981 87703-01 Address 526 S. Church St. 'Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A 4 Identification of System KC COMPONENT COOLING SYSTEM Class C
- 5. (a) Applicable Construction Code III 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE A fA"+at÷,-Aa;ie 4v farn -nAntP Renaired or Renlacement Comnonents Column 3 Column Column 5 Column Column 7 Column Column 1 Column 2 8 4 6 Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Name of Replaced. or Code Serial Number Built Component Manufacturer Replacement Stamped Number (yes or no)
A Disc Assembly Pacific For valve tag # 2KC005 REPLACED B Disc Assembly Pacific 001804F81 For valve tag # 2KC005 1995 REPLACEM C REPAIRED D REPAIRED E REPAIRED REPAIRED F Page 1of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x I I in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work I/R Valve 2KC005_
- 8. Test Conducted: Hydrostatic [] Pneumatic L] Nominal Operating Pressure - Other [] Exempt [
Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/.A Expiration Date N/A Certificate of Authorization No. N/A Signed X4/ TECH SPEC Date A ,, L* ,20 oc)
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 1 - b -to (b.2- W and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions NC 978 I Insector's Signature Date _j */1_,20_ 00 _ Page 2 of 2 Revision 6
( ( ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 11/09/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Piant CATAWBA NUCLEAR STATION 2a Unit I--1 j2 [] 3 ["1 Shared (specify Units- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981 88260-05 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System NC REACTOR COOLANT SYSTEM Class A
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Comnonents Renaired or Renlacement Comnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8
- Name of Name of Manufacturer N B' Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code C pe M ucrReplacement Stamped
_Number (yes or no) A Valve Dresser BS-02871 Valve tag #2NC-002 1980 R"PA -_ED 1_ _ _ _ _ __ __ _ __ PLAC-cCý __ _ B Valve Dresser BS-02872 Valve tag #2NC-002 1979 REPAIRED P-..-. PLAce-_,C-V,7.T ftll I, C Bolting Rod-SA193, Nuts-SA194 iREPAiRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (I) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on'each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work R/R Valve 2NC-002_
- 8. Test Conducted: Hydrostatic El Pneumatic [l Nontinal O'erating Pressure Other E- Exempt []
Pressure 2235 psig Test Temp. 648 deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed J v
- v z -- TECH SPEC Date ///I.f ,20 &O / Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period , -/fi to "cto and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employermakes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. _______ ]___ Commissions NC 978 Inspector's Signature Date j4' f,20-c)-',) Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 04/26/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit 1 2 [-R 3 [-] Shared (specify Units- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981 93484-06 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A.L Expiration Date N/A 4 Identification of System CA AUXILIARY FEEDWATER SYSTEM Class C
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Tdentification of Comn*onents Renaired or Rernlacement Comnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped
_Number (yes or no) A NF Weld Duke Power C-2CA 159 Weld #2-R-CA-0192-1 for hanger 2-R- REPLACEM] Co. CA-0192-1 H&____ ' B REPAIRED 7" C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 I/2in. x 11 in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Restore Hanger 2-R-CA-0 192_
- 8. Test Conducted: Hydrostatic D Pneumatic -7Nominal Operating Pressure Other [] Exempt [
Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed 4 J6De, TECH SPEC Date zi/ 20 00o
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Comvany of Hartford Connecticut have inspected the components described in this Owners Report during the period.) -',J- O0 to 4 60 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. PA Commissions NC 978 tor's Signature Date _4, 2111),20_ U-0_ Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 04/26/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit -] 1 32 F-] 3 n' Shared (specify Units[:] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 982 16523-04 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A 4 Identification of System Class C RN NUCLEAR SERVICE WATER SYSTEM
- 5. (a) Applicable Construction Code 11I 1974 Edition, S'75 Addenda, N-416-1 Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped Number _(yes or no)
A Pipe Duke Power C-2RN 160 2" Flange- SA182, Red Insert- SA182 19 REPLACEM] Co. ____C B Pipe Welds Duke Power C-2RN 160 1318.20-008-1,2,3,4 REPLACEM] //fi/ __ __ __ _ _ Co. ___ ____ __ C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Repair Motor Cooler Flanges_
- 8. Test Conducted: Hydrostatic E] Pneumatic L] Nominal Operating Pressure ,2 Other [] Exempt El Pressure 75 psig Test Temp. 63 deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A la&~5 TECH SPEC Date Z! . ,20 O Signed 9~~i6
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 315-o.. to 4-2-cvand state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. __ _*_ Commissions NC 978 In~pector's Signature Date __4 2.__ 20_001 Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. owner DUKE POWER COMPANY la Date 04/25/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit E' 1 F92 -] 3 E] Shared (specify Units[-- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981 95977-05 Address 526 S. Church-St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # CE -10212 Expiration Date N/A 4 Identification of System KC COMPONENT COOLING SYSTEM Class C
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, N-416-1 Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- f. Tdentification of Corn onentF* Renaired or Renlacement Comnonent.
Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 1 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped Number _(yes or no) A Valve BIF N-59033-11 276 Valve tag # 2KC-336 1979 REPLACED y6 B Valve Fisher 61300-010A 378 Valve tag #2KC-336 1979 REPLACEM_. C Pipe Duke Power C-2KC 166 8"Pipe-SA106, Flange-SA105 t98s- REPLACEM D Pipewelds DukePower C-2KC 166 Welds-2KC101-1 2KC101-11 REPLACEM] Co. ____5___ __ E 4/m&fS 19ý e.o,/ 5 4., r, REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replace Valve 2KC336_
- 8. Test Conducted: Hydrostatic [] Pneumatic F Nominal Operating Pressure Other [] Exempt []
Pressure 102 psig Test Temp. 62 deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed & Ag ,- 6- TECH SPEC Date C'*-S-,20 412 oa o 7 O*wner "orOwner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 2-4-to to 412kt *'and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. _ i _ ., "."a_ _ _ _ _ Commissions NC 978 ns'pector's Signature Date 4zJ L
,20_U-Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 05/03/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit Di1 32 F-1 3 [] Shared (specify UnitsE] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981 86574-07 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/Ak Expiration Date N/A 4 Identification of System CF MAIN FEEDWATER SYSTEM Class B
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code
_Number Replacement Stamped (yes or no) A Base Metal Duke Power C-2CF 158 Weld repair to valve disc with serial REPAIRED Repair Co. #C581 for valve tag 2CF168 _ _ __-5 B REPAIRED C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Repair Valve 2CF-168_
- 8. Test Conducted: Hydrostatic E] Pneumatic [ Nominal Operating Pressure L-- Other LI Exempt [
Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of uthorization No. N/A Signed :a**" TECH SPEC Date . ,20 0O
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 3__,o to .- 8-uo and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. p/ 1 L*J_ Commissions NC 978 Inspector"ý Signature Date _- Pj_ ,2_O __ Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 05/03/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit 1-1 J2 [-] 3 [-] Shared (specify Units[-- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981 04792-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/I \
Expiration Date N/A
- 4. Identification of System BB Steam Generator Blowdown Class B
- 5. (a) Applicable Construction Code I1 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE 6 Tdentiliesition of romnonent* Renaired or Renlacement Comnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Ceeril Number Built Replaced.
Replacementor Code Stamped Number _ (yes or no) A Rear Bracket Grinnell For hanger 2-R-BB-1063 REPLACEM] ./]o B Welds Duke Power C- 2BB 155 Weld- 2-R-BB-1063-4 for hanger 2-R- REPLACEM , S17 Co. BB-1063 _ _/ C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replace Hanger Bracket_
- 8. Test Conducted: Hydrostatic [l Pneumatic [-] Nominal Operating Pressure [-' Other [] Exempt [0 Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed 1"A Yg TECH SPEC Date 5- ,20 6
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 10 -2& 9*Qto U-f-_ and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. I* )194w Commissions NC 978 Inspector's Signature Date _*'ý- l _ 20_0-J Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 05/10/00 Sheet 1 of "t"Z-Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit [F-1 E 12 E-] 3 [] Shared (specify Units[-] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981 69751-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # CN -21289 Expiration Date N/A 4 Identification of System KC COMPONENT COOLING SYSTEM Class C
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, N-416-1 Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Ceeril Replacement Stamped Number or no)
/
_(yes A Pipe Duke Power C-2KC 166 2"& 3" Pipe-SA106, Tee,Reducer,90 Ell, ,* REPLACEM. Co. 45 Ell- SA106 ! B Pipe Welds Duke Power C-2KC 166 2492-KC.00-373-1 thru 8 2KC831- REPLACEM Co. 14,18,19,51,52 2492-KC.00-372-1 thru 10 2KC856-24,25,35 2492-KC.00-375- 8-S 1 thru 9 2KC850-47,48,49,50 C Valve BNL 981103-14-2 Valve tag #2KC-E29 1999 ,- A-' D Valve BNL 981103-4-4 Valve tag #2KC-E30 1999 REP-fREo E Valve BNL 981103-4-6 Valve tag #2KC-E33 1999 HPA~Et,E*" 4/ F Valve BNL 981103-4-5 Valve tag #2KC-E32 1999 A BP/,.- ' Page 1 of 2 Revision 6
( ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. owner DUKE POWER COMPANY la Date 05/10/00 S-Z -1 Sheet -47rof 4-Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit - 1 2 -1 3 -- Shared (specify UnitsE-] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981 69751-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # CN,-21389 Expiration Date N/A 4 Identification of System KC COMPONENT COOLING SYSTEM Class A
- 5. (a) Applicable Construction Code III 1974 Edition, S'75 Addenda, N-416-1 Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 1 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code N_(yes Number Replacement Stamped or no)
A Valve Grinnell 82-53876 8739 Valve tag #2KC-A53 1983 REPLACED B Valve BNL 76*( A981103 Valve tag #2KC-A53 1999 REPLACEM]
)
C Valve Grinnell 82-53876 6683 Valve tag #2KC-A59 1983 REPLACED 4 20 _ ___ D Valve BNL 981103-13-4 Valve tag #2KC-A59 1999 REPLACEM] E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A 4OTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work KC System Tie-in_
- 8. Test Conducted: Hydrostatic
- Pneumatic [] Nominal Operating Pressure [2 Other F] Exempt EL Pressure 95.6 psig Test Temp. 63.4 deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of/uthorization No. N/A Signed -Zz TECH SPEC Date /° ,20
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period ID)S-ý- to S, 10- c oand state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. _ _ _ wxCommissions _ _ _ NC 978
'I'fspector's Signature Date _ S- 'U ,20bO __
Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI 1.Owner DUKE POWER COMPANY la Date 10/23/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit F 1 Z2 [-1 3 -- Shared (specify Units[:] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98338691-02 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A 4 Identification of System KC COMPONENT COOLING SYSTEM Class C
- 5. (a) Applicable Construction Code I1 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Reoaired or Renlacement Comr~onents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped
_ Number (yes or no) A Valve Disc Pacific 5086 Valve 2KC 11 1992 REPLACED -,-*, b 7-B Valve Disc Pacific 01 Valve 2KC 11 1992 REPLACEM] C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replaced Valv Disc in Valve IKC I1
- 8. Test Conducted: Hydrostatic [] Pneumatic [ Nominal Operating Pressure Other [I] Exempt [
Pressure psig Test Temp. deg.F.
- 9. Remarks _ Code Cases _NONE (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed 1L4 2 S~jJ-~.~- TECH SPEC Date 20 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period q 2-01 to I -2.S - I and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. __ ý___ W ý J Commissions NC 978 Inspector's Signature Date1V$,20_- Page 2 of 2 Revision 6
( ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/23/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit 7-l 1 Z2 - 3 " Shared (specify UnitsL--- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98338690-01 Address 526 S. Church-St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A 4 Identification of System KC COMPONENT COOLING SYSTEM Class C
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code ComonntReplacement Stamped Number
_ (yes or no) A Valve Disc Pacific 5126 Valve 2KC14 1992 REPLACED B Valve Disc Pacific 02 Valve 2KC14 1992 REPLACEM} C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replaced Valve Disc in valve 2KC14_
- 8. Test Conducted: Hydrostatic El Pneumatic Z] Nominal Operating Pressure D Other [-I Exempt 0 Pressure N/A psig Test Temp. N/A deg.F.
- 9. Remarks _ Code Cases _NONE (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed -- M /) TECH SPEC Date 16 1 ,20_4 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 22 -01 to I E)*&S
- and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. ____ _ __ _ om i Commissions NC 978 Inspector's Signature Date _1 S 20_'- Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/23/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit F-- 1 02 E"] 3 E] Shared (specify UnitsD] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98268602-01/05 Address 526 S. Church-St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A 4 Identification of System Class B RN NUCLEAR SERVICE WATER SYSTEM
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Replacement Stamped SNumbe (yes or no)
A Valve Anderson 19085 2567 2RN405 1997 REPLACED Greenwood 4-- B Valve Anderson 26257 2574 2RN405 1998 REPLACEM ]j Greenwood C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x II in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replaced Valve 2RN405._
- 8. Test Conducted: Hydrostatic 0I] Pneumatic [I Nominal Operating Pressurek[* Other I] Exempt E]
Pressure 106 psig Test Temp. 43.9 deg.F.
- 9. Remarks _ Code Cases _NONE_
(Applicable Manufacturers Data Records to be attached) CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A TECH SPEC Date 2- - ,20__ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 1to - ..0 to 10,2-S -- and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
"" Commissions NC 978 Inspector's Signature Date _iV-2S_ 20_0l1 Page 2 of 2 Revision 6
(1 ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/09/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit I--1 Z2 R' 3 [ Shared (specify Units-- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 9833075 1-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class B SV MAIN STEAM VENT TO ATMOSPHERE
- 5. (a) Applicable Construction Code 11 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped Number _(yes or no)
A Disc Dresser AAH81 For valve tag 2SV010 REPLACED B Disc Dresser ADE97 For valve tag 2SV010 REPLACEM] C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/10/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit [-I 1 Z2 II 3 E- Shared (specify UnitsD' )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98267769-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System NI SAFETY INJECTION SYSTEM Class A
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Ren~aired or Renlacerment Cnmornnnnnt*
Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped Number (yes or no) A Disc Westinghous 19261307C7 For valve 2NI94 REPLACED e 9-GO1-3 _/____ B Disc Westinghous 19671307C7 For valve 2NI94 REPLACEM] _'1,44 e 9-G01-3 A10 C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x II in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Inspect Valve 2NI94_
- 8. Test Conducted: Hydrostatic L- Pneumatic -] Nominal Operating Pressure [ Other M Exempt 0 Pressure psig Test Temp. deg.F.
- 9. Remarks _ Code Cases NONE (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of uthorization No. N/A Signed /1Ii Jf-/j W TECH SPEC Date ,1// ,200/_
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 4 -?L-k-0 to It:-l&'c1 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
- ,- '4 ) Commissions NC 978 Inspector's Signature Date _W-IS- 20_u )
Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. owner DUKE POWER COMPANY la Date 10/09/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit [-1 1 02 [-' 3 F-] Shared (specify UnitsD-] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98330749-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class B SV MAIN STEAM VENT TO ATMOSPHERE
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Numbery1(yes Replacement Stamped or no)
A Disc Dresser AAL61 For valve tag 2SV008 REPLACED V0,:) ,- B Disc Dresser ADE94 For valve tag 2SV008 REPLACEMI /1A C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Refurbish Valve 2SVO08_
- 8. Test Conducted: Hydrostatic [I- Pneumatic - Nominal Operating PressureE] Other [] Exempt Z Pressure psig Test Temp. deg.F.
- 9. Remarks _ Code Cases _NONE__
(Applicable Manufacturers Data Records to be attached) CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed TECH SPEC Date 20.dZ. SPEC
/ Owner or Owner's Designee, Title TECH CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period C,) . to ) -/S' and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
" j I"- A Commissions NC 978 Inspector's Signature Date _0 c____,20_0O Page 2 of 2 Revision 6
( (I ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/10/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Piant CATAWBA NUCLEAR STATION 2a Unit 1-I 1 Z2 M"2 3 E] Shared (specify Units- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98372700-03 Address 526 S. Church -St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System CF MAIN FEEDWATER SYSTEM Class C
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Replacement Stamped (yes or no)
A Bolting Duke Power Rod- SA193, Nut- SA194 for valve Co. 2CF46 REPLACEM] 14"2.,: A.. 4* B REPAIRED C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Rebuild Valve 2CF46_
- 8. Test Conducted: Hydrostatic F] Pneumatic El" Nominal Operating Pressure E" Other [: Exempt 0 Pressure psig Test Temp. deg.F.
- 9. Remarks _ Code Cases _NONE_
(Applicable Manufacturers Data Records to be attached) CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A TECH SPEC Date /20_a_ Owner or Owner's Designee, Title
/7.-
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period '9 --1c) -0) to JV -, S-6l and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. b .-* &4 ,,,I Commissions NC 978 Inspector's Signature Date .J*-YA ,20_ r- __I Page 2 of 2 Revision 6
/ (
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/08/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit ['-1 Z2 D 3 [El Shared (specify Units-- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98372510-03 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification -of System Class B NV CNEMICAL VOLUME CONTROL SYSTEM
- 5. (a) Applicable Construction Code 1I1 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Com onents Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped Number _(yes or no)
A Bolting Duke Power Hex Nut-SA194 for hanger 2-R-NV-094 REPLACEM] A/l " Co. __ .___ B REPAIRED C REPAIRED D REPAIRED E REPAIRED REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Restore Support 2-R-NV-094_
- 8. Test Conducted: Hydrostatic [-Z Pneumatic [ Nominal Operating Pressure -' OtherE
[Exempt 0 Pressure psig Test Temp. deg.F.
- 9. Remarks _ Code Cases _NONE (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed TECH SPEC Date _AA _200/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period Ib-'A-ol to I C- IS-0\ and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. R1ý2" YYXLJ? 1 Commissions NC 978 Inspector's Signature Date A0-J - ,200_ __ Page 2 of 2 Revision 6
( ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/09/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit I"] 1 [E2 E 3 - Shared (specify Units- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98197786-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class B SV MAIN STEAM VENT TO ATMOSPHERE
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Replacement Stamped Number_ (yes or no)
ADisc Dresser AAH85 For valve tag 2SVOI 1 REPLACED j B Disc Dresser ADD83 For valve tag 2SVO 11 REPLACEM] C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Refurbish Valve 2SV01 1
- 8. Test Conducted: Hydrostatic -- Pneumatic - Nominal Operating Pressure E] Other [] Exempt E Pressure psig Test Temp. deg.F.
- 9. Remarks _ Code Cases _NONE (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed /4 TECH SPEC Date 1,019 ff ,200/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 9 -22,01 to 1 -/ S '- and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
& - YA nwx Commissions NC 978 Inspector's Signature Date JD- I_ ,200 -
Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY Ia Date 10/09/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit [1- 1 E2 Fl 3 - Shared (specify Units-'- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98330758-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol StaImp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class B SV MAIN STEAM VENT TO ATMOSPHERE
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
&. Tde~ntifiec*tion of ComnrnInent.* Renairedl or Renlacement Comnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Replacement Stamped Number_ (yes or no) A Disc Dresser AAA90 For valve tag 2SV018 REPLACED B Disc Dresser ADD81 For valve tag 2SV018 REPLACEM] C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
( ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/11/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit IR- 1 Z2 [1 3 E- Shared (specify Units[-] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98351383-01/06 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # CE70630 Expiration Date N/A 4 Identification of System KC COMPONENT COOLING SYSTEM Class C
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 1 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number umbe
_______________________________ _____________________________________ __(y__s_ Replacement Stamped onno oes 44462-21 127 For valve 2KC-7 1977 REPLACED "*ei, A Valve BIF B Valve Fisher 5238E-0/OA 402 For valve 2KC-7 2001 REPLACEMI, C Bolting Duke Power Rod- SA193 Nuts- SA194 for valve REPLACEMI Co. 2KC-7 A/0 D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replace 2KC-7_
- 8. Test Conducted: Hydrostatic ] Pneumatic 10 Nominal Operating Pressure Other R Exempt F1 Pressure 96 psig Test Temp. 89.6 deg.F.
- 9. Remarks _ Code Cases _NONE (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of uthorization No. N/A Signed a K TECH SPEC Date -,20P__
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 9- 2-4-0 to 10- ,5 -ý I and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. (*V I t , Commissions NC 978 Inspector's Signature Date )_UI-S_, 2 0.-03 - Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/11/01 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006 Sheet 1 of 1
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit [ 1 02 F-13 Address 4800 CONCORD RD. YORK, S.C. 29745 D Shared (specify Units- )
- 3. Work Performed By Duke Power Company 3a Work Order # 98064577-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class B ND RESIDUAL HEAT REMOVAL SYSTEM
- 5. (a) Applicable Construction Code 11I 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Comoonents ReDaired or Replacement Cnmnnsmntct Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Replacement Stamped (y¢es or no)
A Bolting Duke Power Rod & Nuts - SA564 Gr. 630 for RHR REPLACEMI 7,eorn Co. Pump 2A B A10//O/6,2.- REPAIRED C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page I of 2 Revision 6
( ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 11/13/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit DI Z2 R 3 E] Shared (specify Units-- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98428722-01 Address 526 S. Church -St.Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A 4 Identification of System KC COMPONENT COOLING SYSTEM Class B
- 5. (a) Applicable Construction Code H11 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Comr*onents~ Reroaired or Renlacement Comrnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Number(yes Replacement Stamped or no)
A Valve 2KC340 Anderson N22767 1590 2KC340 (8" valve) 1985 REPLACED Greenwood K ( a1E B Valve 2KC340 Anderson 96-63711 2540 2KC340 (8" valve) 1996 REPLACEM] Greenwood GS C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replaced valve 2KC340._
- 8. Test Conducted: Hydrostatic El- Pneumatic -- Nominal Operating Pressure [\ Other [I] Exempt E]
Pressure 95 psig Test Temp. 88 deg.F.
- 9. Remarks _ Code Cases _NONE (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorizationt N/A Signed I 1,. fi4*a * .< TECH SPEC Date I I 2-- ,2A0 OWner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period J**10 -*Lto /I-/L; 0)J and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. 0 (Vi' N 5q!Commissions NC 978 Inspector's Signature Date il" S ,200) - Page 2 of 2 Revision 6
( ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 11/07/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit [ 1 H2 [-13 [-] Shared (specify UnitsD-- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98368427-01/04 Address 526 S. Church -St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class B NV CNEMICAL VOLUME CONTROL SYSTEM
- 5. (a) Applicable Construction Code 11I 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1992 Addenda NONE
- 6. Identification of Co ponents Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Replacement Stamped Number_ (yes or no)
A Pipe & Welds Duke Power C-2NV 170 2' Pipe-SA376 Tp 304, Pipe welds REPLACEM] No Co. 2NV625-14,15,16 B Valve Kerotest YG4-10 22232 Valve tag 2NV326 1978 REPLACED Yes C Valve Arqderson 98-14848 2628 Valve tag 2NV326 1998 REPLACEM] Yes Greenwood D REPAIRED E REPAIRED F 'REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replace Valve 2NV326
- 8. Test Conducted: Hydrostatic 1I Pneumatic-] Nominal Operating Pressure [7 Other ] Exempt []
Pressure 2333 psig Test Temp. 97.7 deg.F.
- 9. Remarks _ Code Cases _N-416-1__
(Applicable Manufacturers Data Records to be attached) CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed , ' **ce TECH SPEC Date //A 7If ,200/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period S- 3' -C' to I- -c, i and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. _ _ __ _ _ _ _ _ Commissions NC 978 Inspector's Signature DateJH &__ 200 ) _ Page 2 of 2 Revision 6
( ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 11/07/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit El] 1 92 [1 3 F-- Shared (specify Units[:] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98095354-01/12 Address 526 S. Church,St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class B NV CNEMICAL VOLUME CONTROL SYSTEM
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1992 Addenda NONE
- 6. Identification of Com ponents Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Replacement Stamped Number (yes or no)
A Pipe Duke Power C-2NV 170 2" Pipe - SA376 Tp 304 REPLACEM] No Co. B Pipe Welds Duke Power C-2NV 170 2NV196-55 2NV196-56 REPLACEM] No Co. C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work hR Reduced Flow_
- 8. Test Conducted: Hydrostatic F- Pneumatic [ Nominal Operating Pressure Other - Exempt E]
Pressure 345.8 psig Test Temp. 283.2 deg.F.
- 9. Remarks _ Code Cases _N-416-1 (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed AZ XAý TECH SPEC Date ZJ If20 ,2O Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 2- -2 i to I I - 6') and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
- Y i') Commissions NC 978 Inspector's Signature Date -l" b- 6 ,20 0 _J Page 2 of 2 Revision 6
(I ( ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 11/06/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit [-- 1 H2 Eli 3 -7 Shared (specify Units- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98330756-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class B SV MAIN STEAM VENT TO ATMOSPHERE
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Corn onents Renaired or Renlacement Comnonent*
Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Replacement Stamped (yes or no) A Disc Dresser AAA80 For valve 2SV-16 REPLACED No B Disc Dresser ADD82 For valve 2SV-16 REPLACEM] No C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Refurbish Valve 2SV- 16_
- 8. Test Conducted: Hydrostatic [ Pneumatic-] Nominal Operating Pressure Other 0 Exempt M Pressure psig Test Temp. deg.F.
- 9. Remarks _ Code Cases _NONE (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed 4A --
- TECH SPEC Date //A1 Z
,20,0_ / - Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period ý -212-0 to I 1- A -) ) and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. SL.,'*- gV\J ) Commissions NC 978 Inspector's Signature Date -\- S ,20 0 1] Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 11/06/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit El- 1 Z2 [: ] 3 E- Shared (specify Units[] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98437219-01 Address 526 S. ChurchSt. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class B NV CNEMICAL VOLUME CONTROL SYSTEM
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Comnonents Repaired or Renlaeement C~omnonent.*
Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Replacement Stamped (yes or no) A Bolting Duke Power Studs-SA193 Nuts-SA194 for REPLACEM] NO Co 2NVFE5130 B REPAIRED C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Bolting Inspection 2NVFE5130_
- 8. Test Conducted: Hydrostaticl [ PneumaticE[ Nominal Operating Pressure ] Other D Exempt [A Pressure psig Test Temp. deg.F.
- 9. Remarks _ Code Cases _NONE (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed -A T TECH SPEC Date ///6 -,206Z__ Z
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period O0-22,AI to I I --1 -0oi and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. R cP-4\1/2yVV 4 ?J4 Commissions NC 978 Inspectorss*ignature" Date _-L I ,20_0 _ Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY Ia Date 10/31/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit I 11 Z2 ["13 [-] Shared (specify Units- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98303131-09 Address 526 S. Church-St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class B NV CNEMICAL VOLUME CONTROL SYSTEM
- 5. (a) Applicable Construction Code 11I 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Number Replacement Stamped
_(yes or no) A Bolting Duke Power Bolt- A325 Nut- SA194 for hanger 2-R- REPLACEM , /I Co. NV-1242 0_/% B REPAIRED C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Restore Support 2-R-NV- 1242
- 8. Test Conducted: Hydrostatic El Pneumatic V] Nominal Operating Pressure El OtherE] Exempt 0 Pressure psig Test Temp. deg.F.
- 9. Remarks _ Code Cases _NONE (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed I A X_ ý TECH SPEC Date i/ 3/ ,200/
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 10- 6 -0 1 to it' &I and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. (Th--- 7 _ V\J'\IS Commissions NC 978 _nspector's Signature Date _o-' L,20_o)$ - Page 2 of 2 Revision 6
( ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/29/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit El I Z2 [I 3 L-i Shared (specify Units'- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98374331-05 Address 526 S. ChurchSt. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A 4 Identification of System NC REACTOR COOLANT SYSTEM Class A
- 5. (a) Applicable Construction Code 11 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identifie.ztion of Cornonannt* Ro~nr*.rfl or Ro~n1nicrn~nt (-'mnnnn~ntv Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped Number (yes or no)
A Nut 2", SA 194 Gr 7 REPLACED B Nut 2", SA 194 Gr 7 REPLACEMi I Valve Dr r B 6 NCd r C Valve Dresser B$02868 N/A Valve Tag 2NC3 eREPLACED
/
a__t&_1__2_I_& 97d7 D Valve Dresser B#-2870 N/A Valve Tag 2NC3 WTjA %th REPLACEM] E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replaced Valve 2NC3_
- 8. Test Conducted: Hydrostatic -] Pneumatic E] Nominal Operating Pressure 17 Other R Exempt El Pressure 2233 psig Test Temp. 651 deg.F.
- 9. Remarks _ Code Cases _NONE (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed r 2-A ,A _ -r--v--TECHSPEC Date Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period ') ZI-'-) I to (O-O1 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. _ ___ Commissions NC 978 Inspector's Signature Date :\0 -' Q_ 20_0 1 _ Page 2 of 2 Revision 6
/
( ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/29/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit I-- 1 ]2 E-" F--
3 Shared (specify UnitsF--] ) Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98374330-05 Address 526 S. Church-St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A 4 Identification of System NC REACTOR COOLANT SYSTEM Class A
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE 6 ldeantificeitinn of rom none.nt. Re~n~irted or Renlacement Comnonents*
Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Replacement Stamped N (yes or no) A Valve Dresser BS-2869 N/A Valve Tag No. 2NC2 1980 REPLACED B Valve Dresser BS-2872 N/A Valve Tag No. 2NC2 1979 REPLACEM_ C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replaced Valve 2NC2_
- 8. Test Conducted: HydrostaticF - Pneumatic n Nominal Operating Pressure [n] Other - Exempt E]
Pressure 2233 psig Test Temp. 651 deg.F.
- 9. Remarks _ Code Cases _NONE (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed , v TECH SPEC Date 4J 20_fL Owner or Uwner s Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period ý,21-0 I to /0 -3,P-6 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. U& *YXtb M Commissions NC 978 Inspector's Signature Date_0-OD _20JI - Page 2 of 2 Revision 6
( ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/29/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit F- 1 Z2 EL3 Li Shared (specify Units'-] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98374332-03 Address 526 S. Church-St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A 4 Identification of System NC REACTOR COOLANT SYSTEM Class A
- 5. (a) Applicable Construction Code I1 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Replacement Stamped A Nut 2", SA 194 Gr 7 - Inlet flange at valve REPLACED 2NC1 .A10_
B Nut 2", SA 194 Gr 7 - Inlet flange at valve REPLACEM] I 2NC 1A1/0/_ C Nut 2", SA 194 Gr 7 - Inlet flange at valve REPLACED 2NC1 AlO DNut 2", SA 194 Gr 7 - Inlet flange at valve REPLACEM] 2NC1 _ _,/_ E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit *A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 l/2in. x 11 in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replaced 2 nuts at inlet flange for valve INCI_
- 8. Test Conducted: Hydrostatic 1s Pneumatic [ Nominal Operating Pressure F1 Other 1- Exempt [
Pressure psig Test Temp. deg.F.
- 9. Remarks _ Code Cases _NONE (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed 1A4 " / .. E--t ý---,.
-ý-TECH
_ SPEC Date /0,20 _ Ownei or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period ) -ZI - ') to i U10 -Q)and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions NC 978 Inspector's Signature Date _LJ __%
,20-0_)
Page 2 of 2 Revision 6
Section E Exhibit A ASME Section XI Manual FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI la Date 10/29/01 Sheet 1 of I
- 1. Owner DUKE POWER COMPANY Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit I--1 02 El 3 E] Shared (specify Units- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98370362-01 Address 526 S. Church*St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System KC COMPONENT COOLING SYSTEM Class B
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE Column 2 Column 3 Column Column 5 Column Column 7 Column Column 1 8 4 6 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Number Built Replaced. or Code Component Manufacturer Serial Replacement Stamped Number (yes or no)
A Disc Kerotest S/N 24 Valve 2KC393 REPLACEM] B Disc Kerotest NA Valve 2KC393 REPLACED I/O C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/29/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit I-1 [E2 3 -l Shared (specify Units-- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98431968-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class B BB STEAM GERATOR BLOWDOWN SYSTEM
- 5. (a) Applicable Construction Code I1I 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Comoonents Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Replacement Code Stamped Number (yes or no)
A Disc Anchor S/N 45 S/N9 Valve 2BB-008A REPLACED Darling A1 B Disc Anchor S/N 10 S/N Valve 2BB-008A REPLACEM] A/i//bi Darling 47 /V) C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit.A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work I/R Valve 2BB008A_
- 8. Test Conducted: Hydrostatic F- Pneumatic --] Nominal Operating Pressure - Other - Exempt M Pressure psig Test Temp. deg.F.
- 9. Remarks _ Code Cases _NONE_
(Applicable Manufacturers Data Records to be attached) CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed TECH SPEC Date L2o IL
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 16-1-&1 to 1 V 30 -0 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
&*-?_&J\ AýA5 Commissions NC 978 Inspector's Signature .
Date _ _,200 Page 2 of 2 Revision 6
ASME Section XI Manual FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS Section E Exhibit A As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/23/01 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006 Sheet 1 of 1
- 2. Piant CATAWBA NUCLEAR STATION 2a Unit EI] 1 Z2 E] 3 [] Shared (specify Units[] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98223763-01 Address 526 S. Church.St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # CE-61695 Expiration Date N/A 4 Identification of System Class C NV CNEMICAL VOLUME CONTROL SYSTEM
- 5. (a) Applicable Construction Code II 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 14 Column Column 7 1 Column
-I -- *1* 4 I _________ J 6 8 Name of Name of Manufacturer NB Other Identification (Size)
Component Year Repaired. ASME Manufacturer Serial Number Replaced. or Built Code -t .1. Number I Replacement Stamped A Bolting (yes or no) Duke Power 3/4" Threaded Rod- SA193 Nuts-SA 194 REPLACEM' ///t Co. t I for NV Demin. Strainer B REPAIRED 4-I __ _ __ _ I _ C REPAIRED
+ 4-_________
D REPAIRED i 4. 1- __ __ __ __I E REPAIRED t ______________ F REPAIRED I. _______________________ I _______________ I _________________________________________________________________ I_______________ I REPAIRED [ Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Delete NV Mixed Bed Demin. Strainer_
- 8. Test Conducted: Hydrostatic F Pneumatic -" Nominal Operating Pressure [ Other[] Exempt E Pressure psig Test Temp. deg.F.
- 9. Remarks _ Code Cases NONE (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Rio~nfed W TECH SPEC Date Z YZ ,2 0-,/_
- Owner or'Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period ii-16 -0) to I -Z"i -01 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. VI A M' ` ) Commissions NC 978 Inspector's Signature Date _Lb -2___,20_ ') - Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/23/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit [- 1 N2 [-- 3 F-- Shared (specify Units[-] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98356336-01/04 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System KC COMPONENT COOLING SYSTEM Class C
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Tdentification of C~omn*onents Renaired or Renlacemrent Comnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Replacement Stamped Number (yes or no)
A Bolting Seal Gland Bolting for Componenet REPLACEM] / Cooling Pump 2B 1/V' /_//0, B REPAIRED C REPAIRED D REPAIRED E, REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work
- 8. Test Conducted: Hydrostatic[-- Pneumatic [" Nominal Operating Pressure [s Other -" Exempt D Pressure 96 psig Test Temp. 76 deg.F.
- 9. Remarks _ Code Cases _NONE_--
(Applicable Manufacturers Data Records to be attached) CERTIFICATE OF COMPLIANCE We certify that the statements made the report are correct and this repair or replacement conforms to the rules of the in rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of thorization No. N/A TECH SPEC Date Z042 ,20.,0/
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 9.).--1 to i l*"- <1 ] and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. f*.r VY'vvxt' Commissions NC 978 Inspector's Signature Date t' 2 )-- ,20_.) - Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/25/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit -l- 1 Z2 -1]3 [-] Shared (specify Units[:] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98338480-05 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # CNCE-61628 Expiration Date N/A 4 Identification of System Class B NV CNEMICAL VOLUME CONTROL SYSTEM
- 5. (a) Applicable Construction Code EII 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped Number _(yes or no)
A Seal Housing Pacific NR40044IT- Inboard (Inner housing) for NV CCP 2B REPLACED 13 /_. B Seal Housing Pacific BN5214JTG Inboard (Outer housing) for NV CCP 2B REPLACED 14P C Seal Housing Pacific NR45018IT3 Outboard (Inner housing) for NV CCP REPLACED S 2B _0Ai D Seal Housing Pacific NR45018ITS Outboard (Outer housing) for NV CCP REPLACED
,_o \ bl '
2B E Seal Housing John Crane 99P90046 1125 Inboard housing for NV CCP 2B REPLACEM] F Seal Housing John Crane RLSA01554- Outboard housing for NV CCP 2B REPLACEM] 1__ Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replace Seal Housing For CCP 2B1
- 8. Test Conducted: Hydrostatic - Pneumatic n- Nominal Operating Pressure [ Other -- Exempt []
Pressure 2460 psig Test Temp. 87 deg.F.
- 9. Remarks _ Code Cases _NONE____
(Applicable Manufacturers Data Records to be attached) CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of thorization No. N/A Signed Xý12ý TECHTECHI SPEC Date A017-.*,20 0__
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 9-?l -0' to I C 7 - and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Pc\J vJi"4AA Commissions NC 978 Inspector's Signature Date J_] ,20_0) Page 2 of 2 Revision 6
f Section E Exhibit A ASME Section XI Manual FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI la Date 10/25/01 Sheet 1 of 1
- 1. Owner DUKE POWER COMPANY Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit - 1 02 El 3 E] Shared (specify Units-] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98338431-05 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # CNCE-61627 Expiration Date N/A 4 Identification of System Class B NV CNEMICAL VOLUME CONTROL SYSTEM
- 5. (a) Applicable Construction Code 1II 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE A TrdInt~fiontlnn nf (C*nm nents Reanir d or Renlacement Comnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Serial Number Built Replaced. or Code Component Manufacturer Replacement Stamped Number (yes or no)
A Seal Housing Pacific BE49224 Inboard housing for NV CCP 2A REPLACED A" B Seal Housing Pacific BF49224 Outboard housing for NV CCP 2A REPLACED C Seal Housing John Crane RLSA01554- Inboard housing for NV CCP 2A REPLACEM / 2A/ V D Seal Housing John Crane NR44854 Outboard housing for NV CCP 2A REPLACEMI E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replace Seal Housing for CCP 2A_
- 8. Test Conducted: Hydrostatic - Pneumatic " Nominal Operating Pressure [* Other E] Exempt []
Pressure 2560 psig Test Temp. 87 deg.F.
- 9. Remarks _ Code Cases _NONE (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed TECH SPEC Date /0 7/3 ,200/L_ Owner or Owner's Designee, Title
/
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 9 -21. - , to ,c) *2 - ' and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. _____-__-_,____________Commissions NC 978 nspector's Signature Date _*Yt,20_0" - Page 2 of 2 Revision 6
( ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/25/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit [-] 1 Z2 [- 3 n Shared (specify Units[] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98369054-06 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A 4 Identification of System NC REACTOR COOLANT SYSTEM Class A
- 5. (a) Applicable Construction Code II 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Renaired or Renlacement Comnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 _ 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Number(yes Replacement Stamped or no)
A Snubber PSA 12843 S/R 2-R-NC 1707:3 KIP Mechanical 1980 REPLACED Shock suppressor. A/ >.,j1r B Snubber PSA 9503 S/R 2-R-NC-1707: 3 KIPMechanical 1979 REPLACEM , Shock suppressor. A10 C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work
- 8. Test Conducted: Hydrostatic F-' Pneumatic - Nominal Operating Pressure D Other 1i- Exempt 1E Pressure N/A psig Test Temp. NIA deg.F.
- 9. Remarks _ Code Cases _NONE_
(Applicable Manufacturers Data Records to be attached) CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Sqioneri IbAA iA A TECHSPEC Date ,20 a(I Owner or Owner's Designee, Tit] CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 9 -'s, 0 k to K¢-2)10i and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. __ 2_____________Commissions _ NC 978 Inspector's Signature Date A*.J-ý-._ ,20OQA - Page 2 of 2 Revision 6
Section E Exhibit A ASME Section XI Manual FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/23/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit [-' 1 N2 [:13 " Shared (specify UnitsD-] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98374408-01/03 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A 4 Identification of System CA AUXILIARY FEEDWATER SYSTEM Class C
- 5. (a) Applicable Construction Code 1m1 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE A* TA,-nt;iFvtcNn nf C*nm nniwnts Renair d or Renlacement Comnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code C Replacement Stamped Number (yes or no)
A Valve Anderson 49919 2498 2CA291 1996 REPLACED Greenwood 4'- B Valve Anderson N20383 394 2CA291 1983 REPLACEM] Greenwood C REPAIRED Dj REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replaced valve 2CA29 1
- 8. Test Conducted: Hydrostatic E- Pneumatic E] Nominal Operating Pressure Other [-" Exempt El Pressure 50 psig TestTemp. 118.8 deg.F.
- 9. Remarks _ Code Cases _NONE__
(Applicable Manufacturers Data Records to be attached) CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. Signed I" A I.A a ", -".,- TECH SPEC Date L "20.4 Title Owner or Owner's Designee, CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period ý -LZ ---) to le -2 1 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
.4-*YrV1 ,4) Commissions NC 978 Inspector's Signature Date _L,0-'ý1_20_O Page 2 of 2 Revision 6
( K ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/24/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit I-] 1 Z2 [- 3 -- Shared (specify UnitsL-- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98431053=01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # CE-71222 Expiration Date N/A 4 Identification of System Class B NV CNEMICAL VOLUME CONTROL SYSTEM
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1992 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 1 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Replacement Stamped Number _(yes or no)
A Valve Borg Warner 49686 1533 Valve 2NV221 1979 REPLACED _0 B Valve Walworth A2778 933 Valve 2NV221 1977 REPLACEM] C Pipe Weld CraneAloyco DPCo C-2NV 170 Welds: 2NV20-10, and 2NV22-1 REPAIRED / DI REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replaced Valve 2NV221._
- 8. Test Conducted: Hydrostatic L-- Pneumatic - Nominal Operating Pressure Other - Exempt D1 Pressure 20 psig Test Temp. 87 deg.F.
- 9. Remarks _ Code Cases _N-416-1 (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed I /iA" TECH SPEC Date 16 -2,20_4 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period J), 4--e0i to ICO2.-S-C) and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
. '\'X.A.Commissions NC 978 Inspector's Signature Date -2,-ZS ,20_0 __
Page 2 of 2 Revision 6
( ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/03/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit -- 1 Z2 [113 [1- Shared (specify Units' )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98351969-05/07 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # CE-61683 Expiration Date N/A 4 Identification of System Class C RN NUCLEAR SERVICE WATER SYSTEM
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- Trpntif'irntinn Af C'*m nnnE~nt* Re~nniread nr Renlacement Comnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 6 8 4
Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped Number (yes or no) A 4" Pipe Duke Power C-2RN 160 SB-675 Gr. UNS N08367 REPLACEM] Co. __9_ __ _ _ _ _ __ _ _ _ _ _ i9 S _ _ _ B 4" Tee/ 4" Ell Duke Power C-2RN 160 SB-366 Gr. WP6XN 185 REPLACEM]\_ Duke Power C-2RN 160 2RN337-35,36,37,38,39,41 2RN433- REPLACEM] Y
)1blo C Welds Co. 9,10,11,12,13,14,15,16 ] _ _ _-_- _
D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work
- 8. Test Conducted: Hydrostatics] Pneumatic 2 Nominal Operating Pressure D Other[] Exempt [I Pressure 71 psig Test Temp. 83 deg.F.
- 9. Remarks _ Code Cases _N-416-1__
(Applicable Manufacturers Data Records to be attached) CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate ofuthorization No. N/A Signed TECH SPEC Date ,200_
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 3"- /D' 4 I to (0 -' and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. _______ ___-___ Commissions NC 978 Inspector's Signature DatejO "1_ ,2 0 _n Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 08/30/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit - 1 Z2 0I ] 3 IF- Shared (specify Units- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98398647-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class B ND RESIDUAL HEAT REMOVAL SYSTEM
- 5. (a) Applicable Construction Code I11 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Com ponents Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped Number _ (yes or no)
A Bolting Studs-SA193 & Nuts-SA194 for valve 2 REPLACEM' #kt ND-60 A/0 B REPAIRED C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work I/R Boron Build up-
- 8. Test Conducted: Hydrostatic D Pneumatic [] Nominal Operating Pressure l] Other [: Exempt Z Pressure psig Test Temp. deg.F.
- 9. Remarks _ Code Cases __NONE (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed TECH SPEC Date W36 _,20 6
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 8-2-0 -0 1 to 9 -J) I and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. ____Commissions NC 978 Inspector's Signature Date "J_ ,20_0 1 Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 08/28/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit E-- 1 02 IE 3 E] Shared (specify UnitsD- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98406023-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class B ND RESIDUAL HEAT REMOVAL SYSTEM
- 5. (a) Applicable Construction Code 1T1 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
~ Itcntifrntlnn Af C'nrnnnn~int¢ R*.nnire~rl or Pean12cement Comnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Manufacturer Serial Number Built Replaced. or Code Component Number Replacement Stamped Number_ (yes or no) A Snubber PSA 4364 Hanger 2-R-ND-277 1978 Replaced . B Snubber PSA 41424 Hanger 2-R-ND-277 2000 Replacemen /1/[ tCRPIE C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x II in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replace 2-R-ND-277_
- 8. Test Conducted: Hydrostatic E- Pneumatic L"' Nominal Operating Pressure [l] Other [*]Exempt M Pressure psig Test Temp. deg.F.
- 9. Remarks _ Code Cases _NONE (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of uthorization No. N/A Signed TECH SPEC Date F 'FA-- - ,20'b/) Owner or Owner's Designee, Title d CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 9- -4 1 to 6 "--) and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. ____ Commissions NC 978 inspector's Signature Date _N _,20_0 Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 04/17/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit L--i1 32 [-] 3 [-] Shared (specify Units-] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 982'06733-04 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class B NV CNEMICAL VOLUME CONTROL SYSTEM
- 5. (a) Applicable Construction Code If1 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Coponents Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped Number __ (yes or no)
A Disc Kerotest S/N 11 For valve tag #2NV 181 A REPLACED B Disc Kerotest S/N 13 For valve tag #2NV 181 A REPLACEM / 11111i C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
Form NIS-2 (Back) Section E Exibit A ASME Section XI Manual NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work hR Valve 2NV181A_
- 8. Test Conducted: Hydrostatic 1i Pneumatic r- Nominal Operating Pressure El] Other - Exempt E Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed " AZ i Owner or Owner's Designee, Title TECH SPEC Date 1/i17 20 O__ CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 1 -Z 0 to 4 7-o i and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
*A '" ,\NKLU.2 ) Commissions NC 978 Irnspector's Signature Date -A ..1---,20-0 _
Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 12/07/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit El I E ]2 ['E 3 ] Shared (specify Units'-] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 982*54179-55 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class C RN NUCLEAR SERVICE WATER SYSTEM
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
, TA~t,**i~lr-i,a cnfCrmnrnrwnt* PEannir*.c At Pen1aeement Comnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Serial Number Built Replaced. or Code Component Manufacturer Replacement Stamped Number (yes or no) A Bolting Bolt-SA325, Hex/Swing Nuts-SA193 for REPLACEM" Manway M-7-1 M-6-1-M-8-+ _ / ;AU)0 B REPAIRED C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Restore Manway Covers_
- 8. Test Conducted: Hydrostatic ED Pneumatic ] Nominal Operating Pressure L Other -- Exempt Z Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed / TECH SPEC Date /Z ,20o_ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 1 00 to I - Z- o / and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. SYYA{* Commissions NC 978 Inspector's Signature Date_ I --ZL ,200 ) - Page 2 of 2 Revision 6
( ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 01/09/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit [I-- 1 2 [--] 3 [-] Shared (specify Units"] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order# 982'72154-37 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class C RN NUCLEAR SERVICE WATER SYSTEM
- 5. (a) Applicable Construction Code 11- 1974 Edition, S'75 Addenda, N-416-1 Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Number(yes Replacement Stamped or no)
A Pipe Welds Duke Power C-2RN 160 Weld #2RN375-21 REPLACEM e or-o Co.--_ B REPAIRED C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Reinstalled RN Piping_
- 8. Test Conducted: Hydrostatic [L Pneumatic ENominal Operating Pressure [* Other [-] Exempt []
Pressure 75 psig Test Temp. 44 deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed TECH SPEC Date J/ ,20 0/
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 1O*-c c' D to I -1Z-6 i and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. _Commissions NC 978 Inspector'" Signature Date V 2 ,ý", 20_0 _ Page 2 of 2 Revision 6
/
i ( Section E Exhibit A ASME Section XI Manual FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI la Date 10/12/00 Sheet 1 of 1
- 1. Owner DUKE POWER COMPANY Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit E--i E 12 L-- 3 R Shared (specify Units' )
Address 4800 CONCORD RD. YORK, S.C. 29745 C78 56Z07o 56047-01
-01
- 3. Work Performed By Duke Power Company 3a Work Order # 982 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/Ak Expiration Date N/A 4 Identification of SystemVG Diesel Generator Starting Air System Class C
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, N-416-1 Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE t Tn fi,,n ACnn mfnnts RPenaired or Renlacement Comnonents Column 2 Column 3 Column Column 5 Column Column 7 Column Column 1 8 4 6 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Serial Number Built Replaced. or Code Stamped Component Manufacturer Replacement Number (yes or no)
A Endcap Process F01678 5318 DG Aftercooler "2A1" 1979 REPAIRED Engineering.__-__ B Flange Duke Power Co. C-2VG 161 Flange- 6" CS 150# WN REPLACEM'
/tw C Plate Duke Power C-2VG 161 Plate 1/2/2" CS SA-515 REPLACEM' ,t Co. ____
D Weld Duke Power C-2VG 161 Weld #1212.03-003.001-2A1-13 REPLACEM / D WeldRCo.E F REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work I/R Studs Corrosion_
- 8. Test Conducted: Hydrostatic D Pneumatic - Nominal Operating Pressure fli Other "' Exempt JE Pressure psig Test Temp. deg.F.
- 9. Remarks _ Code Cases _NONE (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate ofuthorization No. N/A Signedm~cý TECH SPEC Date 6 1/ ,20_0.
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period J -2P-L- - to /0"/,1-'11 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspe n. L_ _*__ Commissions NC 978 IDate _I-i ý_,20_0 ) Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/09/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit [-- 1 Z2 E] 3 F-- Shared (specify Units'-D )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98265764-01 Address 526 S. ChurchSt. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System CF MAIN FEEDWATER SYSTEM Class B
- 5. (a) Applicable Construction Code I1 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped Number _(yes or no)
A Snubber PSA 8685 2-R-CF-1586 1979 REPLACED B Snubber PSA 4052 2-R-CF-1586 1978 REPLACEM , C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Test/Replace Snubber_
- 8. Test Conducted: Hydrostatic -' Pneumatic E- Nominal Operating Pressure [-] Other [I] Exempt [
Pressure psig Test Temp. deg.F.
- 9. Remarks _ Code Cases _NONE (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed i/e* afW TECH SPEC Date ZJ 2 ,200/ S/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period _ - 0 to /t-/ Si(- and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. P" M_" Commissions NC 978 Inspector's Signature . Date-) b-1S,20_ (- ) Page 2 of 2 Revision 6
Section E Exhibit A ASME Section XI Manual FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/09/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit [: 1 N2 0 3 E-] Shared (specify Units[] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98265766-01 Address 526 S. Church'St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System CF MAIN FEEDWATER SYSTEM Class B
- 5. (a) Applicable Construction Code 1I 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE IN TrAtnt-.*e~n r~ff r~~nn,ntg Re~n2lr~ci Ar Panlzctement Comrnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 6 8 4
Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Serial Number Built Replaced. or Code Stamped Component Manufacturer NumerReplacement_ Number __yes or no) A Snubber PSA 2585 2-R-CF-1523 1977 REPLACED 2-B Snubber PSA 41276 2-R-CF-1523 2000 REPLACEM] B REPAIRED C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI la Date 10/10/01 Sheet 1 of 1
- 1. Owner DUKE POWER COMPANY Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit E- 1 N2 [: 3 ['] Shared (specify Units[] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98374335-01 Address 526 S. Church'St. Charlotte, N.C. 28201-1006 Type Code Symbol Statnp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System NI SAFETY INJECTION SYSTEM Class A
- 5. (a) Applicable Construction Code I11 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE HL iV11
%UALI~., VJ Vý1 SF r-__Column Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 6 8 4
Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Serial Number Built Replaced. or Code Component Manufacturer Replacement Stamped Number (yes or no) A Disc Westinghous 1307C79- For valve tag 2NI-082 REPLACED / e G01-3 B Disc Westinghous 1307C79- For valve tag 2NI-082 REPLACEM] ,, e' G01 A/c C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/08/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. P*ant CATAWBA NUCLEAR STATION 2a Unit I-- 1 [2 R] 3 n Shared (specify Units- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98373518-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System SM MAIN STEAM SYSTEM Class B
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Comnonent.* Re,hinted or Renlnct~me~nt "Crnmnonn'.nt' Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Replacement Stamped (yes or no)
A Bolting Duke Power Hex Nut-SA193 for Steam Generator REPLACEM / Co. REA2B9 L. Vc-B REPAIRED C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work R/R Handhole/ Insp. Cover_
- 8. Test Conducted: Hydrostatic -l- Pneumatic - Nominal Operating Pressure El Other Ln Exempt 0 Pressure psig Test Temp. deg.F.
- 9. Remarks _ Code Cases _NONE_
(Applicable Manufacturers Data Records to be attached) CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed TECH SPEC Date ,jA' ,20.___l Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 9-2.6 - I to I 1[-0 1 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. _ _ __ _ _ _ Commissions NC 978 Inspector's Signature " Date _4 - -,20_0) _ Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/11/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit [ 1 02 - 3 -] Shared (specify UnitsE[[ )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98351382-01 Address 526 S. Church.St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # CE70630 Expiration Date N/A 4 Identification of System KC COMPONENT COOLING SYSTEM Class C
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE A Idehntifiection of Comnonents Renaired or Replacement Comnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Replacement Stamped REPLACEM] n (e or no)
Rod- SA193 Nut- SA194 for valve ___________ ______________(yes A Bolting Duke Power Co. ____2KC-9_____/4 B Valve BIF 44462-11 Valve tag 2KC-9 1977 REPLACED C Valve Fisher 5238E-010B Valve tag 2KC-9 2001 REPLACEM] AIC? D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replace 2KC-9_
- 8. Test Conducted: Hydrostatic El Pneumatic Rli Nominal Operating Pressure 1s Other - Exempt L Pressure 96 psig Test Temp. 89.6 deg.F.
- 9. Remarks _Code Cases _NONE (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A TECH SPEC Date A9111J,
,20-12__
Signed
/ Owner *r Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period to and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions NC 978 Inspector's Signature Date _,20 - Page 2 of 2 Revision 6
( ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/05/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit E-- 1 E2 R-' 3 E] Shared (specify Units[:] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98265763-01 Address 526 S. Church, St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System NM NUCLEAR SAMPLING SYSTEM Class B
- 5. (a) Applicable Construction Code I1 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Tdentification of Comnonents Renaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Replacement Stamped Number _(yes or no)
A Snubber PSA 3341 2-R-NM-1079 1978 REPLACED B Snubber PSA 41425 2-R-NM-1079 2000 REPLACEMI ARPIE C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of62 Revision
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work R/r Snubber 2-R-NM- 1079
- 8. Test Conducted: Hydrostatic [-- Pneumatic [L Nominal Operating Pressure [' Other [I] Exempt Z Pressure psig Test Temp. deg.F.
- 9. Remarks _ Code Cases _NONE (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed A Zet
& TECH SPEC Date - ,20o-/ / Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 9 -111ý1 to i bt - and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
" 'n 1 :ki Commissions NC 978 Inspector's Signature Date ý6- 10_ ,200] -
Page 2 of 2 Revision 6
K ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/04/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit " 1 Z2 [:13 E] Shared (specify Units' )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98430375-01 Address 526 S. ChurchSt. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System SA MAIN STEAM SUPPLY TO AUX EQUP Class B
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Ceeril Replacement Stamped Number
_ (yes or no) A Snubber PSA 17527 2-R-SA-1504 1981 REPLACED Ah/-, 4-B Snubber PSA 41706 2-R-SA-1504 2000 REPLACEMl '/ C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work RIR 2-R-SA-1504_
- 8. Test Conducted: Hydrostatic ' Pneumatic E- Nominal Operating Pressure [l" Other F Exempt 0 Pressure psig Test Temp. deg.F.
- 9. Remarks _ Code Cases _NONE (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of uthorization No. N/A Signed TECH SPEC Date 4 &V ,20_PL
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 9- -(-,I to /& 9 -) i and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. 4 (Vi LiJ Commissions NC 978 Inspector's Signature Date _J6 - ,2Oj20') _ Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 09/27/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Piant CATAWBA NUCLEAR STATION 2a Unit D 1 02 E" 3 R Shared (specify Units" )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98416741-01 Address 526 S. ChurchSt. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class C RN NUCLEAR SERVICE WATER SYSTEM
- 5. (a) Applicable Construction Code II 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Comt*onents Repaired or Renlacement Comnone~nt*
Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped Number _(yes or no) A Snubber Pacific 8595 Tag # 2-R-RN-0036 1879 REPLACED Scientific __.7_ B Snubber Basic PSA 41705 Tag # 2-R-RN-0036 2000 REPLACEM] 4-C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (I) size is 8 1/2in. information in items 1 through 6 on this reports included on each sheet, x 11 in. (2) and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work R/R Snubber 2-R-RN-0036_
- 8. Test Conducted: Hydrostatic F Pneumatic 'Nominal Operating Pressure Other - Exempt Pressure psig Test Temp. deg.F.
- 9. Remarks - Code Cases __NONE (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of uthorization No. N/A Signed TECH SPEC Date ,7 ,20__/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company inspected the components described in this Owners Report during the of Hartford Connecticut have period 9-+/-C11 to t( - i and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section By signing this certificate neither the Inspector nor his employer makes XI. any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. f9-XA*)* Commissions NC 978 Inspector's Signature Date j- 20 - 0_ _ Page 2 of 2 Revision 6
f ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/05/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit El 1 H2 E 3 F1- Shared (specify Units'- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98374351-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class B NV CNEMICAL VOLUME CONTROL SYSTEM
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Cop onents Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Number(yes Replacement Stamped or no)
A Disc Westinghous 5740028 W10838 For valve tag 2NV-290 1976 REPLACED j/-so/no ( B Disc Westinghous 1742C09601 NA For valve tag 2NV-290 NA REPLACEM 1114 e -S /1/0 C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work R/R Valve 2NV-290_
- 8. Test Conducted: Hydrostatic El Pneumatic R"I Nominal Operating Pressure E Other [] Exempt Z Pressure psig Test Temp. deg.F.
- 9. Remarks'_ Code Cases _NONE (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed A A ý6_ ý ý TECH SPEC Date 45ffi ,20 0/
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 1.23 -) 1 to le 1 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. _______________ o Commissions NC 978 Inspector's Signature Date 10-I ,2DO - Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/05/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Piant CATAWBA NUCLEAR STATION 2a Unit -l 1 N2 [:13 -] Shared (specify Units-- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98430243-01 Address 526 S. Church.St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class C NV CNEMICAL VOLUME CONTROL SYSTEM
- 5. (a) Applicable Construction Code MII1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Com ponents Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped Number _(yes or no)
A Snubber PSA 15885 2-A-NV-3631 1982 REPLACED B Snubber PSA 41241 2-A-NV-3631 1999 REPLACEM] C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work RJR Snubber 2-A-NV-363 1
- 8. Test Conducted: Hydrostatic [- Pneumatic - Nominal Operating Pressure [l Other - Exempt 0 Pressure psig Test Temp. deg.F.
- 9. Remarks _ Code Cases _NONE (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed X 5 X--W
-- TECH SPEC Date yA/_T{ ,2.0_/
1 4Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 5 Z.) -" \ to A) -;0 - .I and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. ___ ___ __ ___ __ Commissions NC 978 19spector's Signature Date _) ,20_0 '_ Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 11/15/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit I[1 M2 [-1 3 F-D Shared (specify Units[:] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98428702-01 Address 526 S. ChurchSt. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # CNCE-61840 Expiration Date N/A 4 Identification of System NC REACTOR COOLANT SYSTEM Class A
- 5. (a) Applicable Construction Code IIE 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Com ponents Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 1 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped Number _(yes or no)
A Steam Generator Westinghous 1922 3 Replace Alloy 600 filler material with REPLACEM _
"2"" e Alloy 690 (Inconel 52/152) on the //
B SG 2B Bowl Drain Nozzle. REPAIRED C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Repair SG 2B Bowl Drain Nozzle_
- 8. Test Conducted: Hydrostatic -" Pneumatic []Nominal Operating Pressure [n Other L-- Exempt E]
Pressure 2238 psig Test Temp. 559.2 deg.F.
- 9. Remarks _ Code Cases _N-416-1 (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed A TECH SPEC Date , 4/ ,2(kL
/ Owner -or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period C .2_) <* to I -? ýoand state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. 2 *CJ "kYY Commissions NC 978 Inspector's Signature Date j I- ,20O ) - Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 11/15/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. PMant CATAWBA NUCLEAR STATION 2a Unit 1 Z2 3 F-- Shared (specify Units] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98355856-01 Address 526 S. ChurchSt. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class B SV MAIN STEAM VENT TO ATMOSPHERE
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer SerialNumberNumber Built Replaced. or Code Replacement Stamped Number
_ (yes or no) A Plug Assembly CCI HTF-2318 For valve 2SV00 1 REPLACED Yes B Plug Assembly CCI S/N 8 For valve 2SV001 REPLACEM] Yes C REPAIRED D REPAIRED E REPAIRED REPAIRED Page 1.of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work R/R Valve 2SV00_ I
- 8. Test Conducted: Hydrostatic 1- Pneumatic L-- Nominal Operating Pressure - Other -] Exempt N Pressure psig Test Temp. deg.F.
- 9. Remarks _ Code Cases _NONE (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate ofAnthorization No. N/A Signed --- C:'....
/ket7 =*f- v -- ....... TECH SPEC Date ////.7" 20_ _ / Owner or Owner's esignee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 9 "22-6i to /[-I-] - and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. (*PLY &U Commissions NC 978 Inspector's Signature Date 1[- I ý - 2,2OS' _ Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 11/15/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit E] 1 Z2 L"] 3 E'] Shared (specify Units[-- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98364944-05/09 Address 526 S. Church-St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # CN-21392 Expiration Date N/A 4 Identification of System Class B NV CNEMICAL VOLUME CONTROL SYSTEM
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1992 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Ceeril Number Built Replaced.
Replacement or Code Stamped Number _(yes or no) A Sway Strut, Anvil 1995-8 2-R-NV-0240 REPAIIED No bracket & Clamp International __A/_et_ _ B Sway Strut, Anvil 1994-449 2-R-NV-0240 REP No bracket & Clamp International "ILj _,/____ C Pipe Cap Duke Power C-2NV 170 3" & 4" SA403 bZb' REPA.I'ED No Co. L-______ D Pipe Welds Duke Power C-2NV 170 2NV36-4 2NV56-15 REPLACED No Co. E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Abandonment NV Piping-
- 8. Test Conducted: Hydrostatic L- Pneumatic -- Nominal Operating Pressure ,n Other E] Exempt El Pressure 693 psig Test Temp. 90.1 deg.F.
- 9. Remarks _ Code Cases _N-416-1 (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed TECH SPEC Date 7/,Alel 6o ,2061
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period ?- - ý-5 - to II- 6 .6 ' and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
- -fMJ*N4J Commissions NC 978 Inspector's Signature Dat&k* *ý ,20_0 _
Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 10/11/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit El- 1 E2 I 3 n Shared (specify Units"- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98267771-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System NI SAFETY INJECTION SYSTEM Class A
- 5. (a) Applicable Construction Code I1 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Com ponents Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped Number _ _ (yes or no)
A Disc Westinghous 19681307C7 For valve 2NI-60 REPLACED e 9G01-3__ ,_ B Disc Westinghous 41671307C7 For valve 2NI-60 REPLACEMI/ 9G01-3 0 e C Bolting Duke Power Studs & Nuts- SA453 Gr. 660 for valve REPLACEM Co. 2NI-60 /0 D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 l/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Inspect Check Valve 2NI-60_
- 8. Test Conducted: Hydrostatic EF- Pneumatic 0] Nominal Operating Pressure Other [-]Exempt Z Pressure psig Test Temp. deg.F.
- 9. Remarks _ Code Cases NONE (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate o*f uthorization No. N/A TECH SPEC Date /_'" ,20 el Sioned
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period to _and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions NC 978 Inspector's Signature Date _20_ Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 11/14/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit 0 1 [D2 "' 3 " Shared (specify Units-] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98225463-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class B ND RESIDUAL HEAT REMOVAL SYSTEM
- 5. (a) Applicable Construction Code 11I 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE f Tdosntificsntion nf Comnonent,* Renaired or Renlacement Comnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped Number _(yes or no)
A Bolting Duke Power Threaded Rod & Nuts - SA564 for RHR REPLACEM, Co. Pump 2B AIO,//1* 7-- B REPAIRED C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replace studs and nuts for RHR Pump 2B1
- 8. Test Conducted: Hydrostatic -- Pneumatic r--] Nominal Operating Pressure E] Other RI Exempt Z Pressure psig Test Temp. deg.F.
- 9. Remarks _ Code Ce*e 4 1 (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed 1AA* TECH SPEC Date " A- ,20 _/ ý11=
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period Ic-10"01 to ils-o ) and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. _ _ _, _ _ Commissions NC 978 Inspector's Signature Date*,"
\ -I ,20_0 )
Page 2 of 2 Revision 6
( , ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 11/13/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit Z 1 [2 3 E] Shared (specify Units[] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98362520-02 Address 526 S. Church'St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN #,N/A Expiration Date N/A 4 Identification of System Class B BB STEAM GERATOR BLOWDOWN SYSTEM
- 5. (a) Applicable Construction Code 11 1974 Edition, S'75 Addenda, Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- Td~ntific~tion of Cnm non~nt* Renziired nr Renlacement Comnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Replacement Stamped Number_ (yes or no)
A Valve Disc Anchor 61 2 2BB56 (4" valve) REPLACED NO Darling _ _ - f B Valve Disc Anchor 62 2 2BB56 (4" valve) REPLACEM] 111k1 Darling C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work: Replaced Valve DISC in 2BB56._
- 8. Test Conducted: HydrostaticF] Pneumatic ] Nominal Operating Pressure E] Other - Exempt El Pressure psig Test Temp. deg.F.
- 9. Remarks _ Code Cases _NONE (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed I *,'*. 6Q
*ý TECH SPEC Date 3- 20 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period i0-2-'<i to /[ -&;L-I and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. U ]A Me$t.j* Commissions NC 978 Inspector's Signature Date
- I S_ ,2S0_0) -
Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI 1.Owner DUKE POWER COMPANY la Date 05/04/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit [l 1 ]2 E] 3 E] Shared (specify Units-] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 980 17720-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # CE -9400 Expiration Date N/A 4 Identification of System KC COMPONENT COOLING SYSTEM Class C
- 5. (a) Applicable Construction Code 1II 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
~ TI nt pairtnrn* Cnm no~nmit P naired or Renlacement Comnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Manufacturer Serial Number NumerReplacement Built Replaced. or Code Stamped Component Number _(yes or no) A Valve Fisher 44462-1 113 Valve tag #2KC-80 1977 REPLACED -/ B Valve Anchor- E2-690-1-2 1945 1996 REPLACEM . Darling C Bolting Nuts-SA194, Rod-SA193 REPLACEM] D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x I1 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replace Valve 2KC-80_
- 8. Test Conducted: Hydrostatic [] Pneumatic [] Nominal Operating Pressure M Other-] Exempt El Pressure 96.5 psig Test Temp. 63.3 deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed /
- TECH SPEC Date 5 ,20o-o Owner or Owner's Designee, Title
/
a CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 3- 16-W to 5 -9. W and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. U Y,,i Commissions NC 978 Inspector's Signature Date _£- c9 _ ,20O0U Page 2 of 2 Revision 6
( ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 04/27/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit i-]1 [ 2 [- 3 E] Shared (specify Units- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981L86575-07 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/AL Expiration Date N/A 4 Identification of System CF MAIN FEEDWATER SYSTEM Class B
- 5. (a) Applicable Construction Code I11 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE i* TAtnfotifAnln nfCnmnnnent* Pe~nniredl Ar Renlacement Comnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped Number _(yes or no)
A Base Metal Duke Power C-2CF 158 Repair valve disc with serial number REPAIRED /, Repair Co. C583 5 B REPAIRED C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Repair Valve Disc for 2CF 167_
- 8. Test Conducted: Hydrostatic --] Pneumatic "- Nominal Operating Pressure Other [- Exempt 0 Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed A_* TECH SPEC Date 4iZ ,20 co
// Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 3-2-'-'* to -- ,and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions NC 978 InDptctor's Signature Date _S - I ,200x)U Page 2 of 2 Revision 6
Section E Exhibit A ASME Section XI Manual FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. owner DUKE POWER COMPANY la Date 05/04/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Pmait CATAWBA NUCLEAR STATION 2a Unit [" 1 E 2 E-] 3 E] Shared (specify Units- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981 80587-01/02 Address 526 S. Church St. Charlotte, N.C. 28201-1006 -10211 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # CE Expiration Date N/A 4 Identification of System KC COMPONENT COOLING SYSTEM Class C
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE 4 TApnt-iFuntirn nf C'nrnnne'ntq Renaired or Renlacement Comnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 6 8 1_1_4 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Serial Number Built Replaced. or Code Component Manufacturer Replacement Stamped (yes or no)
A Valve BFF N7169-1 472 Valve tag #2KC-4 1980 REPLACED B Valve Fisher 7312C-01 381 Valve tag #2KC-4 1999 REPLACEM' _ C Bolting Nuts-SA194, Rod-SA193 REPLACEM'.,/k D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section X1 Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replace 2KC-4_
- 8. Test Conducted: Hydrostatic -l Pneumatic I Nominal Operating Pressure - Other -] Exempt El Pressure 14 psig Test Temp. 73 deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed /Z _,*.*' TECH SPEC Date 42Y ,20 6 e)
/ Owner o"TOwner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 3 -)9-Ou to S t-).u and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions NC 97g Inspector's Signature DateS-~'ý -,20-" - Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 12/13/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit [1]11i 92 ['] 3 E-] Shared (specify Units- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 982 72154-41 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp NL/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class C RN NUCLEAR SERVICE WATER SYSTEM
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, NONE Code Cases or Replacements 1989 Addenda NONE (b) Applicable Edition of Section XI Utilized for RepairsComnonents STAlr~ofhqr, tin nf Cnmnnnent* P enztired nr Renlacement Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Serial Number Built Replaced. or Code Component Manufacturer Replacement Stamped Number (yes or no)
A Bolting Threaded Rod-SA193 Hex Nuts-SA194 REPLACEM / for valve 2RN347B B REPAIRED C REPAIRED D' REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (I) size is 81/2in. x 11 in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Install refurbished valve 2RN347B_
- 8. Test Conducted: Hydrostatic L-" Pneumatic - Nominal Operating Pressure Other -- Exempt E Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed /" O-14:C0 TECH SPEC Date /// ,20 OC) Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period /P-4 "06 to ) 2-9 -o I and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. ,20_(3 Commissions NC 978 _/-2_% Inispector's Signature IDate DateZ 1 2)_20 01 __ Page 2 of 2 Revision 6
( ( ( ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 12/06/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Piant CATAWBA NUCLEAR STATION 2a Unit [-- 1 [ 32 E--] 3 E] Shared (specify Units[] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 982'72153-43 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class C RN NUCLEAR SERVICE WATER SYSTEM
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE i Trlpntfp~i~rn nfCnmnAn1.nt* Pen~ire~d or Renlacement Comnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column
_ 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Replacement Stamped Number(yes or no) A Bolting Rod-SA193, Hex Nuts-SA194 for valve REPLACEM / 2RN- 144A /t/C) B REPAIRED 17?tf$ C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Install Re-furbisned Valve 2RN-144A_
- 8. Test Conducted: Hydrostatic [-I Pneumatic [-" Nominal Operating Pressure E OtherF-Exempt N Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed TECHSPEC Date / ,2000
.OwnerorOwner, s Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 9,2-S -Z' to I - 29 o&) and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions NC 978 InDater's Si nature Date _ V7_,20-0 I_ Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS I As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 11/28/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit I[1 E]2 L-] 3 - Shared (specify Units- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order# 982'72154-44 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class C RN NUCLEAR SERVICE WATER SYSTEM
- 5. (a) Applicable Construction Code Ill 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Tdentification of Comnonents Renaired or Renlacement Comnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped Number (yes or no)
A Bolting Rod-SA193, Hex Nuts-SA 194 for valve REPLACEM /./ 2RN-069B/, L B REPAIRED 7"t' il//lo Z C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Install Refurbished Valve IRN-069B_
Pneumatic E] Nominal Operating Pressure Other - Exempt 0
- 8. Test Conducted: Hydrostatic -
Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed TECH SPEC Date /ZZ1/ ,20 o0
/ " Own- or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period )D-9) -6b to ) 0 ) and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions NC 978 Inspector's Signature Date _L/2n ,20_ 01 _ Page 2 of 2 Revision 6
( ( Section E Exhibit A ASME Section XI Manual FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 11/27/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Piant CATAWBA NUCLEAR STATION 2a Unit Li' 1 2 F-1 3 L] Shared (specify Unitsoi )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 982 72154-71 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class C RN NUCLEAR SERVICE WATER SYSTEM
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Manufacturer Serial Number Built Replaced. or Code Component Replacement Stamped Number (yes or no)
A Bolting Threaded Rod- SA193, Hex Nut- SA- REPLACEM] / 194 for valve 2RN047A I/P B REPAIRED C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Install Refurbished Valve 2RN047A_
- 8. Test Conducted: Hydrostatic [ Pneumatic "' Nominal Operating Pressure El Other [-] Exempt 0 Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made the report are correct and this repair or replacement conforms to the rules of the in rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed/4-c TECH SPEC Date //Z 7 ,20 -06 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period W--* 0 to 1-2-9 -01 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. U A (Y, " Commissions NC 978 Inspector's Signature Date 7-__,20__) Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. owner DUKE POWER COMPANY la Date 11/29/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit --] 1 E 32 [--] 3 [1] Shared (specify UnitsD-] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 982:54178-58 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class C RN NUCLEAR SERVICE WATER SYSTEM
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Replacement Stamped Number (yes or no)
A Bolting Bolt-SA193,SA325 HexNut-SA194, REPLACEM] A for Manway Covers M-7-1 M-6-1 -M-8-+/ B A/ REPAIRED C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Restore Manway Covers_
- 8. Test Conducted: Hydrostatic [-D Pneumatic F] Nominal Operating Pressure D Other ["] Exempt 0 Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed AAI*
- TECH SPEC Date ZcŽ ,20 -&
Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period &/0-00 to I -Z9-6 I and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. _ _ _ _ _ _ __A_ Commissions NC 978 Inspector's Signature Date l,? __ ,20_0 1 Page 2 of 2 Revision 6
C Section E Exhibit A ASME Section XI Manual FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 12/06/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit F-- 1 Z2 R 3 1- Shared (specify Units- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order# 98272154-39 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class C RN NUCLEAR SERVICE WATER SYSTEM
- 5. (a) Applicable Construction Code 1I1 1974 Edition, S'75 Addenda, N-416-1 Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Serial Number Built Replaced. or Code Component Manufacturer Replacement Stamped Number (yes or no)
A Pipe Welds Duke Power C-2RN 160 2RN10-40,41 )98S REPLACEM] \)CS I _ _ __ _ _ Co. _ _ _ _ _ B REPAIRED _____ liblox REPAIRED DC D REPAIRED F REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A '-J NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x II in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work R/R Section of RN Piping_
- 8. Test Conducted: Hydrostatic "l- Pneumatic [] Nominal Operating Pressure Other El Exempt E Pressure 68 psig Test Temp. 64 deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed 14 -a__ ! TECH SPEC Date (ZI ,20O0 Title Owner or Owner's Designee, CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 1c*- 1 --c, to I -. 3 k- c-i and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions NC 978 Inspector's Signature Date _3_,200C __ Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 01/29/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit E- 1 N2 -' 3 - Shared (specify Units- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98332745-06 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System SM MAIN STEAM SYSTEM Class B
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE Identification of Cornonents Renaired or Renlacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 6 8 4
Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Manufacturer Serial Number Built Replaced. or Code Component Replacement Stamped Number _(yes or no) A Bolting Threaded Rod-SA193, Nuts-SA194 for REPLACEM] A! 2SM-FE-5790 _ _ 0 B REPAIRED "7"WP" C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 l/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work R/R Bolting Material for 2SM-FE-5790_
- 8. Test Conducted: Hydrostatic 0] Pneumatic L-- Nominal Operating Pressure I' Other [ Exempt E Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed TECH SPEC Date 20e/
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period "-I0l - i to ) '3 j- '1 -and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. I Ua. Inspector's Signature Commissions NC 978 Date _J120 _ Page 2 of 2 Revision 6
( Section E Exhibit A ASME Section XI Manual FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 01/02/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Piant CATAWBA NUCLEAR STATION 2a Unit t--
1 I *2 -E13 E' Shared (specify Units[-' ) Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 982:56048-02 98262706-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of SystemVG DG Starting Air System Class C
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, N-416-1 Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE T *nti-firtifn of Com nonents Renaired or Replacement Comtonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 6 8 4
Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Serial Number Built Replaced. or Code Component Manufacturer Replacement Stamped Number (yes or no) A Endcap Process F1578 5317 DG Engine Starting Air Aftercooler 1979 REPLACEM' 1. Engineering "2A2" /_ - B Flange Duke Power C-2VG 161 Welding Neck Flange-SA105 REPLACEM Co. YE,: ii C Plate Duke Power C-2VG 161 1/2" Thk. SA515 REPLACEM , (_____ Co. D Welds Duke Power C-2VG 161 1212.03-003.001-2A2-13,14,15 REPLACEM] Co. / E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 1/2in. x 11 in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replace Endcap_
- 8. Test Conducted: Hydrostatic ' Pneumatic 'ii Nominal Operating Pressure Other [-] Exempt []
Pressure 75 psig Test Temp. 45 deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed ", Zý TECH SPEC Date / ,20 D_ Owner or Owner's Designee, Title
/
CERTIFICATE OF INSERVICE INSPECTION 1,the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 5 -/ )- LC, to i - 3P ', / and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. _ _ _ . _ _ _ Commissions NC 978 Inspector's Signature Date _ -S:iI ,20_0 1_ Page 2 of 2 Revision 6
( ( Section E Exhibit A ASME Section XI Manual FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 02/14/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Piant CATAWBA NUCLEAR STATION 2a Unit i--1 [ *2 [-- 3 [" Shared (specify UnitsD] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 982 56051-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System VG-Diesel Generator Starting Air Sys Class C
- 5. (a) Applicable Construction Code 11I 1974 Edition, S'75 Addenda, N-416-1 Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE i TrAnt~flr,*t;n rneffnmi,,n~nfnt. P~nnirM~ nr Renlacement Cornnonents Column 2 Column 3 Column Column 5 Column Column 7 Column Column 1 8 1 4 6 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Serial Number Built Replaced. or Code stamped Component Manufacturer Replacement Number (yes or no)
A Endbell Process Eng. F-01878 5320 Flange-SA105, Plate-SA515 for VG REPLACEM. Aftercooler "2B2" "0 B Welds Duke power C-2VG 161 1212-03.003.001-2B2-13,14,15 REPLACEM] Company C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section X1 Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replace Endcap_
- 8. Test Conducted: Hydrostatic [ Pneumatic [- Nominal Operating Pressure Other D Exempt E]
Pressure 73 psig Test Temp. 48 deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed jj*zý TECHSPEC Date /" ,20_51 Owner or Owner's Designee, Title
/
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period , otC to 2-- 19 -01 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. (2 0 *ei$ V'c4 1 Commissions NC 978 Inspector's Signature Date _ 2-"i ' 200 _ Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 02/14/01 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit -' 1 ]2 [- 3 F-- Shared (specify Units-] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 983 42587-06 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System SM MAIN STEAM SYSTEM Class B
- 5. (a) Applicable Construction Code I1l 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Replacement Stamped Number (yes or no)
A Bolting Studs-SA- 193 Nuts-SA 194 for REPLACEM 2SMFE5760 A_/_0 B REPAIRED C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work IR Steam Leak at Flange_
- 8. Test Conducted: Hydrostatic E] Pneumatic -- Nominal Operating Pressure I Other [I] Exempt 0 Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed/ TECH SPEC Date 20 0 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 12-0?- to 2.-/9-0) and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions NC 978 Inse or- Signtfu Date 2.--M_,20_0 1 Page 2 of 2 Revision 6
( ( Section E Exhibit A ASME Section XI Manual FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 12/06/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit -] 1 ]2 E] 3 E-] Shared (specify Units- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 982 72153-37/49 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class C RN NUCLEAR SERVICE WATER SYSTEM
- 5. (a) Applicable Construction Code 1II 1974 Edition, S'75 Addenda, N-416-1 Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE A Melntification of"Co* onents Renaired or Renlacement Comvonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Serial Number Built Replaced. or Code Component Manufacturer Replacement Stamped Number (yes or no)
A Pipe Welds Duke Power C-2RN 160 2RN9-37,36 REPLACEM]/ Co. Y6-s B REPAIRED 7"P5,' C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work R/R Section of RN Piping_
- 8. Test Conducted: Hydrostatic 1L Pneumatic [-- Nominal Operating Pressure Z Other L- Exempt LI Pressure 72 psig Test Temp. 68 deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Sia-ned & - , I TECH SPEC Date ,20 ae
-7 Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period I i- 4-~o to L- Z--I-o0) and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. UnA YV U\A-jvt Commissions NC 978 Inspector's Signature Date _t-2A 20_-b _ Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 11/16/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit -i 1 32 [- 3 [ Shared (specify Units- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 982 72153-40 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System Class C RN NUCLEAR SERVICE WATER SYSTEM
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Cop onents Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 1 _ 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Replacement Stamped Number, (yes or no)
A Bolting Studs-SA193 HexNuts-SA194for REPLACEM] A valve 2RN287A B REPAIRED C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Refurbished Valve 2RN287A_
- 8. Test Conducted: Hydrostatic E] Pneumatic []Nominal Operating Pressure nI Other i] Exempt [
Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed ITC SC TECH SPEC t Date 11fJ,1 ,0 0 0
,20 -/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period tOAj -& 0 to t "2S--oj and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Y N d Commissions NC 978 Inspector s Signature Date_ i__ ,20 , _ Page 2 of 2 Revision 6
( Section E Exhibit A ASME Section XI Manual FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI la Date 04/26/00 Sheet 1 of 1
- 1. Owner DUKE POWER COMPANY Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit 1 I' 12 -- 3 El Shared (specify Units[-] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981 74833-06 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A 4 Identification of System Class B NV CNEMICAL VOLUME CONTROL SYSTEM
- 5. (a) Applicable Construction Code 11I 1974 Edition, S'75 Addenda, N-416-1 Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE Sr ,T÷+';*o;^* ,¢~~ *~nnnte Pan~ir*d nr Ranlheement Comnonents Column 2 Column 3 Column Column 5 Column Column 7 Column Column 1 8 4 6 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Number Built Replaced. or Code Component Manufacturer Serial Replacement Stamped Number (yes or no)
A Valve Kerotest 310453SN- For valve tag 2NV-269 1994 REPLACED A! 16 B Valve Kerotest SN/TACI-18 35394 For valve tag 2NV-269 1983 REPLACEM . C Pipe Duke Power C-2NV 170 2"Pipe- SA376, Pipe Welds- 2NV405- REPLACEM DREPADCo. 1,2,3 D REPAIRED F REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replace Valve 2NV269_
- 8. Test Conducted: Hydrostatic [-] Pneumatic [-] Nominal Operating Pressure Other [l] Exempt El Pressure 27.5 psig Test Temp. 78.2 deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Si2.- Z-/- TECH SPEC Date ,20 0 t Owner o"Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period to -i3- to 4 -D- 4-and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. ____w__ Commissions NC 978 Inspedt~r's Signature Date _,2_ ,20_ -00 - Page 2 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x II in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replace Endcap_
- 8. Test Conducted: Hydrostatic ["] Pneumatic E Nominal Operating Pressure E- Other Eli Exempt L1 Pressure 75 psig Test Temp. 75 deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed TECH SPEC Date //6 ~ ,20 Co Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period g-- i0- *o to tIo- Ib- oi3 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. inspection. _ ' "_ _ _ _ _ _ Commissions NC 978 ector's Signature Date _ JV- 1.__,20_O Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 09/25/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit F-1 1 E12 [: 3 - Shared (specify Units- )
Address 4800 CONCORD RD. YORK, S.C. 29745 F8 560749 -0/
- 3. Work Performed By Duke Power Company 3a Work Order # 982: 56049-02 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/Ak Expiration Date N/A 4 Identification of SystemVG DG Starting Air System Class C
- 5. (a) Applicable Construction Code I1 1974 Edition, S'75 Addenda, N-416-1 Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE A TIntificatinn AfConnonents Renaired or Renlacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Manufacturer Serial Number NumerReplacement Built Replaced. or Code Stamped Component Number _(yes or no)
A End Bell Process F01778 5319 For DG Aftercooler 2B 1 1979 REPLACEM] Engineering B 6" Flange and Duke Power C-lVG 161 Flange- SA105 WN Sch 40, Weld # REPLACEM. y weld Co. 1212.03-003.001-2B1-13 __ C Plate Duke Power C-1VG 161 Plate - 1/2"CS SA515 REPLACEM' Co.DEPAIRE D REPAIRED E REPAIRED F REPAIRED Page 1 of2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x II in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replace End Bell_
- 8. Test Conducted: Hydrostatic El Pneumatic L' Nominal Operating Pressure [ Other FL Exempt El Pressure 76 psig Test Temp. 74 deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Sinned /. TECH SPEC Date 9 _,20 0 Signed Owner or Owner's Designee, Title
/
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period S-/1.0) to 9 -TS- 4? and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. ______,_ _ _ VCommissions _, NC 978 Inspector's Signature Date - 'IS 20_ 41QV' Page 2 of 2 Revision 6
/
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 09/14/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit 1 I"l 32 E-] 3 [] Shared (specify Units[:] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 982,47648-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A 4 Identification of System VN Diesel Generator Starting Air Class C
- 5. (a) Applicable Construction Code 11I 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE 4 ý TA,,+ p;nrn ' Pennirad Ar Renlhcement Comnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 1
Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Serial Number Built Replaced. or Code Component Manufacturer Replacement Stamped Number (yes or no) A Snubber Pacific 6040 2-R-VN-0051 1979 REPLACED / Scientific B Snubber PSA 40122 2-R-VN-0051 1998 REPLACEMI A/V'//,pi C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replace Snubber 2-R-VN-005 1_
- 8. Test Conducted: Hydrostatic " Pneumatic EI] Nominal Operating Pressure [l Other E- Exempt Z Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A SigneddTJ* TECH SPEC Date V I _,20 owner or Owner's Designee, Title / CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 8 "2-') to q - f' 00 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. _ _ _ _ _ _ _ _ _ _ _ Commissions NC 978 Inspector's Signature Date _ __ ,20_00 Page 2 of 2 Revision 6
( ( Section E Exhibit A ASME Section XI Manual FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. owner DUKE POWER COMPANY la Date 08/23/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit E- i E *2 F] 3 F Shared (specify UnitsD )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 982,15857-04 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A 4 Identification of System SM MAIN STEAM SYSTEM Class B
- 5. (a) Applicable Construction Code III 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE Tdefntification of Con onents Renaired or Replacement Components Id Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 __6 8
Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Serial Number Built Replaced. or Code Component Manufacturer Number Replacement Stamped Number(yes or no) A Bolting Hex Nut-SA 193, Rod - SA193 for REPLACEM] l flange connection. REPAIRED B //zbo B REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x II in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work I/R Flange Leak 2-SM-FE-5780_
- 8. Test Conducted: Hydrostatic 11 Pneumatic Rii Nominal Operating Pressure El] Other --' Exempt DU Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed TECH SPEC Date _,20 aO or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period S o. to 8 -21c, a and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. __'__ _ _ Commissions NC 978 Inspector's Signature Date ,20_(QtU L_2-_ Page 2 of 2 Revision 6
/
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. owner DUKE POWER COMPANY la Date 08/07/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit 1 E]2 l-] [-] 3 I-] Shared (specify Units-- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 980 88748-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # NA Expiration Date N/A 4 Identification of System KC COMPONENT COOLING SYSTEM Class C
- 5. (a) Applicable Construction Code 1I1 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE A TAi titfntatinn nf rnonnts Rtenaired or Renlacement Comnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Manufacturer Serial Number Built Replaced. or Code Component Replacement Stamped
______________(yes or no) REPLACEM] (e -r-p SA193 Gr. B7 for valve 2KC356 A Rod SA-194 Gr. 2H for valve 2KC356 REPAIRE IATb B Nut C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work I/R Valve 2KC356_
- 8. Test Conducted: Hydrostatic E] Pneumatic -]Nominal Operating Pressure DI Other E"-Exempt [
Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of uthorization No. N/A Signed TECHTECZ7 SPEC Date *" 7 ,20 2)o
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 3- n- oo to B" 2ý1- at and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Qo , XV"$4A Commissions NC 978 Inspector's Signature Date _b-2A ,20_ C Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 08/07/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit El I *E]2 F-' 3 -' Shared (specify Units["] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981 57451-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A 4 Identification of System Class B NV CNEMICAL VOLUME CONTROL SYSTEM
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE t; TIj.nfpqoitin nf" nrm nnn~nt* R enaired or Renlacement Comnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Manufacturer Serial Number Built Replaced. or Code Component Replacement Stamped (yes or no)
A Studs Threaded Rod- SA193 for valve 2NV- REPLACEM] 205 B REPAIRED 7/- r" C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work I/R Inlet flange leak @ 2NV205_
- 8. Test Conducted: Hydrostatic L] Pneumatic - Nominal Operating Pressure L"] Other EL Exempt []
Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed TECH SPEC Date ?/7 _,20 _ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 3-23,300 to -V - (- and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. _ __ _ __ _ __ _ Commissions NC 978 Inspe~tor's Signature Date _ 20_ CA.
,-2 Page 2 of 2 Revision 6
ASME Sectioni, Aeanual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 07/03/00 Sheet I of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit E] 1 E *2 0] 3 [-- Shared (specify Units[] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981138215-09 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A 4 Identification of System NM NUCLEAR SAMPLING SYSTEM Class B
- 5. (a) Applicable Construction Code III 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Manufacturer Serial Number Built Replaced. or Code Component Number Replacement Stamped (yes or no)
A Pivot Pin Grinnell For Snubber 2-R-NM-1379 REPLACED B Pivot Pin Grinnell For Snubber 2-R-NM-1379 REPLACEM A /Ai' SREPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section, 4anual Section E Exhibit A / FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR ixEPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 07/03/00 Sheet I of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit E-- 1 F 2 E--] 3 -] Shared (specify Units[] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981 37690-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A 4 Identification of System KC COMPONENT COOLING SYSTEM Class B
- 5. (a) Applicable Construction Code III 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE 6 Identification of Comnonents Renaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Manufacturer Serial Number Built Replaced. or Code Component Number Replacement Stamped Number(yes or no)
A Bolting Ror-SA193, Hex Nuts-SA194 for flange REPLACEM Al connections at 2KC-848&2KC-823 _ _ _ B13 REPAIRED 7om IC REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la D*ate 06/19/00 Sheet of Address 526 S. CHURCH STREET. CHARLOTTE NC 28201-1006
. iantI CATAWBA NUCLEAR STATION
- 2. 2a Ut it [-] 1 Z2 [] 3 ["7 Shared (specify Units "Address 4800 CONCORD RD. YORK, SC 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 98188262-02 Address 526 S. Church St. Charlotte, NC 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b N SM or MN # N/A Expiration Date N/A 4 Identification of System NC REACTOR COOLANT SYSTEM Class A
- 5. (a) Applicable Construction Code III 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column I Column 2 Column 3 Column 4 Column 5 Col 6 Column 7 Column 8 Name of Component Name of Mfg. Mfg. Serial No. National Board Other Identification Year Repaired. ASME (Size) Built Replaced. or Code No. Stamped Replacement (yes or no)
A Safety Relief Valve Dresser BS-2865 N/A 1NC-001 1979 Lj B Safety Relief Valve Dresser BS-2866 N/A 1NC-UU2 IY/Y -rtr []YES Dresser BS-2867 N/A 1NC-003 1979 ** El NO C Safety Relief Valve E]YES Dresser BS-2868 N/A SPARE 1979 ** E] NO D Safety Relief Valve (:]YES E Safety Relief Valve Dresser BS-2869 N/A 2NC-001 1980 ** Dresser BS-2870 N/A 2-NC-002 1980 ** - ENo i F Safety Relief Valve ___E]YES Dresser BS-2871 N/A 2-NC-003 1980 ** E] NO G Safety Relief Valve _ ___-E]YES Dresser BS-2872 N/A SPARE 1979 ** El NO H Safety Relief Valve [:]YES lrl
- 1 *,"'
rage i oi 6 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (I) size is 81/2in. x II in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work: Replace safety relief valve 2NC-00 1 with existing spare.
- 8. Test Conducted: Hydrostatic [I] Pneumatic [- Nominal Operating Pressure [ Other E-i Exempt El Pressure 2235 psig Test Temp. 648 deg.F.
- 9. Remarks ** These valves are interchangeable and can be used in any of the valve applications / locations listed.
(Applicable Manufacturers Data Records to be attached) CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Sinned c& Date _ __ Owner or Owner's Designee, Title
/
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Providence of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period *-I - to 6-"Lo ,Go ; and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. __-__ _ _ __ _ _Commissions NC 978 Inspector's Signature Date _Lo- Cu Page 2 of 2 Revision 6
Section E Exhibit A ASME Section XI Manual FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI la Date 06/20/00 Sheet 1 of 1
- 1. owner DUKE POWER COMPANY
- 2. Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006 Plant CATAWBA NUCLEAR STATION 2a Unit [' 1 2 *2 ['-I 3 - Shared (specify Units-] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981 95978-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 10213 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # CE Expiration Date N/A 4 Identification of System Class C KD DIESEL GENERATOR COOLING WATER SYSTEM
- 5. (a) Applicable Construction Code III 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Name of Replaced. or Code Serial Number Built Component Manufacturer Replacement Stamped Number (yes or no)
Valve BIF N-59032-3 356 For valve tag # 2KD13 1979 REPLACED -/ Fisher 8263C-01A 382 For valve tag # 2KD13 2000 REPLACEM B Valve C REPAIRED
.. REPAIRED D
REPAIRED E REPAIRED F Page 1 of 2 "Revision6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replace Valve 2KD 13_
- 8. Test Conducted: Hydrostatic nL Pneumatic "- Nominal Operating Pressure Z Other [-- Exempt El Pressure 12 psig Test Temp. 161 deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed . "L i TECH SPEC Date C4z,* ,2000
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 3- I 14-00 to _ Zd-2-9 -Oiand state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions NC 978 Inspector's Signature Date_(6",Qý ,20_V __ Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 06/22/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit -J 1 232 E] 3 "- Shared (specify Units[] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981 88128-14 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A 4 Identification of System KC COMPONENT COOLING SYSTEM Class C
- 5. (a) Applicable Construction Code III 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Comnonents Repaired or Replacement Components Column I Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Manufacturer Serial Number Built Replaced. or Code Component Replacement Stamped (yes or no)
A Bolts Bolts-SA325 for s/r 2-R-KC-1858, 2-R- REPLACEM AD KC-1873 .-/ B Welds 2-R-KC-1848-6,5,3 2-R-KC-1873-7,8, REPLACEM A! / 9,20,21 iv) C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 8 l/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replace NC Pump Motor_
- 8. Test Conducted: Hydrostatic [1 Pneumatic I] Nominal Operating Pressure [] Other [] Exempt [
Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed AgJe TECH SPEC Date 4/z _., ,20 tco
/ Owner or--wner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period -c7v to _!ý,'L -uo and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. X;k\ VY& lnspe-etor's signature Commissions NC 978 Date - LL6 ,20_ co _ Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. owner DUKE POWER COMPANY la Date 05/25/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. P*ant CATAWBA NUCLEAR STATION 2a Unit [i 1 2 E-] 3 E] Shared (specify Units-] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981 85391-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A 4 Identification of System NI SAFETY INJECTION SYSTEM Class A
- 5. (a) Applicable Construction Code I1 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Cop onents Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 6 8 4
Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Manufacturer Serial Number Built Replaced. or Code Component Number Replacement Stamped Number _(yes or no) A Disc Westinghous For valve tag #2NI-71 REPLACED A/ e _/O,-, B Disc Westinghous 1977 For valve tag#2NI-71 REPLACEM IM//b e _/l/o C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work R/R Valve 2NI-7 1_
- 8. Test Conducted: Hydrostatic D Pneumatic F Nominal Operating Pressure EIl Other [ Exempt 0 Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed TECH SPEC Date 6&5 ,20 0
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period S - I- 'O to 1-- I - o,0 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. _ _*.__ _ __ _ _ _ _Commissions NC 978 Inspect'6r's Signature Date _Lý- I _,20 ()-u __ Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 05/22/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit "i 1 32 E- 3 E] Shared (specify Units[-- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981:88027-07 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A 4 Identification of System Class B NV CNEMICAL VOLUME CONTROL SYSTEM
- 5. (a) Applicable Construction Code 11I 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Cop onents Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 1 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped Number _(yes or no)
A Snubber Pacific 15806 For hanger #2-R-NV-0243 1982 REPLACED / Scientific t.,
*z,-
B Snubber Pacific 17609 For hanger #2-R-NV-0243 1983 REPLACEM '///N Scientific _/0 C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of2 Revision 6
ASME Section XI Manual Form NIS-2 ( Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work R/R Snubber for Testing_
- 8. Test Conducted: Hydrostatic 1- Pneumatic ] Nominal Operating Pressure l Other [] Exempt E Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed TECH SPEC Date Z/- --- ,20_C
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 3 -/ , -ov to S -2Z -'00 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. PI2& mtv4 J Commissions NC 978 Inspector's Signature Date _5-L ,20_- Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 05/09/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit E] i ]2 E] 3 F-1 Shared (specify Units[:] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981 86573-09 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A 4 Identification of System CF MAIN FEEDWATER SYSTEM Class B
- 5. (a) Applicable Construction Code II 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE A Ti*fntifiecntinn of C* nonents Renaired or Renlacement Comnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 6 8 4
Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped Number _(yes or no) A Base Metal Duke Power C-2CF 158 Valve disc with serial #H532 REPAIRED /
'4-Repair Co. ____
B REPAIRED C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Repair Valve Disc_
- 8. Test Conducted: Hydrostatic [- Pneumatic -- Nominal Operating Pressure E Other [ Exempt 0 Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed 1 ceo TECH SPEC Date 5- ,20 t 0 Owner or Owner's Designee, Title
/
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 3-2-V to S- 1(4-oV and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. _Commissions ___av*a_ NC 978 Insleltor's Signature Date _S- \ k_, 2 0 _ v __ Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 05/16/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit -1 1 F 2 [-] 3 E] Shared (specify Units-] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981 27441-01/03 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A 4 Identification of System SA MAIN STEAM SUPPLY TO AUX EQUP Class B
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE 1; Ttdpntif'nthv, nfC mnrn*mnt.* Ro~nired or Renlacement Cornnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped Number (yes or no)
A Bonnet Studs and For valve tag #2SA-4 REPLACEM !' Nuts ___ _____________ ____A 40X__ B Bonnet For valve tag 2SA-4 REPLACEM' A /o__ C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x I1 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work hR Valve 2SA-4_
- 8. Test Conducted: Hydrostatic [-] Pneumatic [] Nominal Operating Pressure [* Other [] Exempt El Pressure 1080 psig Test Temp. 557.8 deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of uthorization No. N/A Signed TECH SPEC Date 5-- ,200P6 S Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period3-?A- Lo to -I ,- cv and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions NC 978 Inspector's Signature Date _!&-\- _20_o-3 Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 05/15/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit '] I F 12 E] 3 [] Shared (specify Units" )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981t 38260-04 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A 4 Identification of System NC REACTOR COOLANT SYSTEM Class A
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Cop onents Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 6 8 1
Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Replacement Stamped Number _(yes or no) A Bolts Hex Nut- SA194 for snubber 2-R-NC- REPLACEM] 1675 _ A_ REPAIRED -i-. C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Restore Snubber 2-R-NC-1675_
- 8. Test Conducted: Hydrostatic n- Pneumatic [- Nominal Operating Pressure [l Other -- Exempt E Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/.A Expiration Date N/A Certificate of Authorization No. N/A Signed j IzIIý(f TECH SPEC Date * ,20 o c)
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 4-2-0--) to S &-,"-)and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. ___ f a Commissions NC 978 InDS'p _ ,0_ ture Date _-Jg - 20_-0 , _ Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. Owner DUKE POWER COMPANY la Date 05/09/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit El 1 E 32 [- 3 n Shared (specify Units-] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981 75630-04/07 Address 526 S. Church St. Charlotte, N.C. 28201-1006 L Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/1A Expiration Date N/A 4 Identification of System Class ,ki5' ,
NV CNEMICAL VOLUME CONTROL SYSTEM
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, N-416-1 Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE A TAdntffitinn nfCrnronent. Renaired or Renlacement Comnonents Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 6 8 4
Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Manufacturer Serial Number Built Replaced. or Code Component Number Replacement Stamped (yes or no) A Valve Kerotest CA0142 31146 For Valve tag #2NV1 86A 1980 REPLACED B Valve BW/IP 330437SN5 For Valve tag #2NV186A 1997 REPLACEM' 11 International 4/0t C Pipe Duke Power C-2NV 170 2" pipe-SA312, Pipe welds-2NV297-4,3 . ce_ REPLACEM \ Co. 2NV298 D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replace Valve Body 2NV 186A_
- 8. Test Conducted: Hydrostatic [ Pneumatic lii] Nominal Operating Pressure Other [-1 Exempt El Pressure 33.9 psig Test Temp. 78.2 deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A SignedA TECH SPEC Date 2 "L' ,2040 0 Owner or Owner's Designee, Title
/
CERTIFICATE OF INSERVICE INSPECTION 1, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 1 LOb to S 00 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions NC 978 Inspector's Signature DateS?- IZ ,20_ol) Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. owner DUKE POWER COMPANY la Date 05/09/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit -i 1 *2 [- 3 E] Shared (specify Units- )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981 86572-07 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A 4 Identification of System CF MAIN FEEDWATER SYSTEM Class B
- 5. (a) Applicable Construction Code 1I1 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE A Identification of Corn onents Renaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 1 4 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Manufacturer Serial Number NumerReplacement Built Replaced. or Code Stamped Component Number _(yes or no)
A Base Metal Duke Power C-2CF 158 Valve disc with serial #H533 REPAIRED Repair Co._(S B REPAIRED IWO 1l14l6 7.. C 'REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items I through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Weld Repair Valve Disc_
- 8. Test Conducted: Hydrostatic El Pneumatic E] Nominal Operating Pressure [] Other [-] Exempt [
Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed o<I-Ze Z TECH SPEC Date ,, 2000C)
/ Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period A-LLtto S2P0ýw and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions NC 978 Ia pet or's SgAture Date _rý -iVA,20-c u Page 2 of 2 Revision 6
ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI
- 1. owner DUKE POWER COMPANY la Date 05/09/00 Sheet 1 of 1 Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit E- 1 F2 E-] 3 [] Shared (specify Units[ )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981186573-09 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A 4 Identification of System CF MAIN FEEDWATER SYSTEM Class B
- 5. (a) Applicable Construction Code I1I 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE
- 6. Identification of Components Repaired or Replacement Components Column 1 Column 2 Column 3 Column Column 5 Column Column 7 Column 4 1 6 8 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Component Manufacturer Serial Number Built Replaced. or Code Number Replacement Stamped Number_ (yes or no)
A Base Metal Duke Power C-2CF 158 Valve disc with serial #H532 REPAIRED -/ Repair Co. _ _ _ __ ___ _ _ B REPAIRED C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x 11 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Repair Valve Disc_
- 8. Test Conducted: Hydrostatic El Pneumatic -] Nominal Operating Pressure r Other - Exempt [
Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed TECH SPEC Date,_L/ , 2046* Owner or Owner's Designee, Title
/
CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 3 .LP-CV to S- i1 wo and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI. By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.
.* JqflKW Commissions NC 978 Inspector's Signature Date_S -1 _, 20_ oLb Page 2 of 2 Revision 6
( ASME Section XI Manual Section E Exhibit A FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI la Date 05/10/00 Sheet 1 of 1
- 1. Owner DUKE POWER COMPANY Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit F 1 *2 Shared (specify Units-] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 982 60092-01 Address 526 S. Church St. Charlotte, N.C. 28201-1006 Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A Class *g*
ZSR of System CF MAIN FEEDWATER SYSTEM 4 Identification
- 5. (a) Applicable Construction Code I1I 1974 Edition, S'75 Addenda, NONE Code Cases (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Addenda NONE STrlpintfinntinn nf C.mnnnents Renaired or Renlacement Components Column 2 Column 3 Column Column 5 Column Column 7 Column Column 1 8 4 6 1
Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Serial Number Built Replaced. or Code Component Manufacturer Replacement Stamped Number (yes or no) A Snubber Pacific 8471 Hanger #2-R-CF-10 11 1979 REPLACED , Scientific ._______"_ B Snubber Pacific 8596 Hanger #2-R-CF-1011 1979 REPLACEM] //I Scientific C REPAIRED D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x I1 in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work Replace Snubber_
- 8. Test Conducted: Hydrostatic El Pneumatic Eli Nominal Operating Pressure [] Other 0 Exempt [
Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed 14&z, TECH SPEC Date 2 -00
,20 / Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period to and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. Commissions NC 978 Inspector's Signature Date _ __ ,20_ - Page 2 of 2 Revision 6
Section E Exhibit A ASME Section XI Manual FORM NIS-2 OWNER'S REPORT FOR REPAIRS OR REPLACEMENTS As Required By The Provisions Of The ASME Code Section XI la Date 05/10/00 Sheet 1 of 1
- 1. Owner DUKE POWER COMPANY Address 526 S. CHURCH STREET. CHARLOTTE N.C. 28201-1006
- 2. Plant CATAWBA NUCLEAR STATION 2a Unit E- 1 32 E-1 3 E] Shared (specify Units-] )
Address 4800 CONCORD RD. YORK, S.C. 29745
- 3. Work Performed By Duke Power Company 3a Work Order # 981:88027-06 Address 526 S. Church St. Charlotte, N.C. 28201-1006 L Type Code Symbol Stamp N/A Authorization No. N/A 3b NSM or MN # N/A Expiration Date N/A 4 Identification of System NS CONTAINMENT SPRAY SYSTEM Class B
- 5. (a) Applicable Construction Code 111 1974 Edition, S'75 Addenda, NONE Code Cases Edition of Section XI Utilized (b) Applicable d-dnm for Repairs or Replacements 1989 Addenda NONE trrlTA;*iit~otn w~n~nt*z Pennired nr Renlacement Conmonents Column 2 Column 3 Column Column 5 Column Column 7 Column Column 1 8 4 6 Name of Name of Manufacturer N B Other Identification (Size) Year Repaired. ASME Serial Number Built Replaced. or Code Component Manufacturer Replacement Stamped Number (yes or no)
A Bolts Studs- SA193, Nuts- SA194 for snubber REPLACEM A/
#2-R-NS-0096 A"0 B REPAIRED REPAIRED C
D REPAIRED E REPAIRED F REPAIRED Page 1 of 2 Revision 6
ASME Section XI Manual Form NIS-2 (Back) Section E Exibit A NOTE: Supplemental sheets in form of lists, sketches, or drawings may be used, provided (1) size is 81/2in. x II in. (2) information in items 1 through 6 on this reports included on each sheet, and (3) each sheet is numbered and the number of sheets is recorded at the top of this form.
- 7. Description of Work R/R Snubber
- 8. Test Conducted: Hydrostatic [] Pneumatic [] Nominal Operating Pressure ["] Other 7" Exempt M Pressure psig Test Temp. deg.F.
- 9. Remarks (Applicable Manufacturers Data Records to be attached)
CERTIFICATE OF COMPLIANCE We certify that the statements made in the report are correct and this repair or replacement conforms to the rules of the rules of the ASME Code, Section XI. Type Code Symbol Stamp N/A Expiration Date N/A Certificate of Authorization No. N/A Signed l&g TECH SPEC Date 6-/ ,200 0
/ Owfier or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of NORTH CAROLINA and employed by HSB I AND I Company of Hartford Connecticut have inspected the components described in this Owners Report during the period 1-1 b-vo to -' I and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owner's Report in accordance with the requirements of the ASME Code, Section XI.
By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measure described in this Owners Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. UntA VyxcA Commissions NC 978 insj~ector's Signature Date _0.A _,20-0 u _ Page 2 of 2 Revision 6
11.0 PressureTesting This section shows a compilation of Pressure Tests conducted from refueling outage EOC-1 0 through refueling outage EOC-1 1. Outage Summary Total Examinations Examination Test Requirement Credited For This Outage Category B-E System Hydrostatic Test (IWB-5222) 0 B-P System Leakage Test (IWB-5221) 1 B-P System Hydrostatic Test (IWB-5222) 0 C-H System Inservice/Functional Test (IWC-5221) 16 C-H System Hydrostatic Test (IWC-5222) 0 A detailed description of each Examination Category listed above is located in subsection 11.1 of this report. Results of each Examination Category are located in subsection 11.2 of this report. Refueling Outage Report EOC1 1 Page 1 of 5 Revision 0 Catawba Unit 2 November 1, 2001 Section 11
This section shows a complete status of Pressure Tests conducted during the second period. PeriodSummary Total Total (%) Examination Test Requirement Examinations Examinations Examinations Category Required For CreditedFor Complete For This Period This Period This Period B-E System Hydrostatic 0 0 0% Test (IWB-5222) B-P System Leakage Test 3 2 66.67% (IWB-5221) B-P System Hydrostatic 0 0 0% Test (IWB-5222) C-H System 21 16 76.19% Inservice/Functional Test (IWC-5221) C-H System Hydrostatic 0 0 0% Test (IWC-5222) Refueling Outage Report EOC1 1 Page 2 of 5 Catawba Unit 2 Revision 0 Section 11 November 1,2001
11.1 Required Examinations This Outage: A listing of each pressure test and associated VT-2 Visual Examination conducted from EOC-1 0 through EOC-1 1 is included in this section. The information shown below is a field description for the listing format included in this section of the report: Zone Number = The unique number assigned to track certain systems or portions of systems that make up a pressure test. Boundary Drawing = Detail drawing of pressure test boundary. Required Test L/I/F/H = A column of information that shows an "X" indicating the required tests for the examination zone. L = "Leakage Test, I = "Inservice Test", F =
"Functional Test", and H = "Hydrostatic Test".
System Name = Name of pressure retaining component system Required Inspection = Type of visual examination required. Required Procedure = Required inspection procedure. ASME Item Number(s) = ASME Section XI Tables IWB-2500-1 (Class 1) and IWC-2500-1 (Class 2) Comments = General and/or Detail Description Refueling Outage Report EOC1 1 Page 3 of 5 Revision 0 Catawba Unit 2 November 1, 2001 Section 11
This Report Was Generated On: 10/30/2001 Duke Power Company - Catawba Unit 2 Pressure Testing Zone Number Listing Int = 2 Outage 11 Period = 2 Boundary Required Test Required Required ASME Item I Lone Numner mm m ra naL Il I"IIrI System Name Inspection Procedure I U I l WI
;I J .. I II .1..... 1 i. ,
Z..........n a Ina L /IIV/- 2NC-001 L-A CN-2553-1.0 x Reactor Coolant (NC) VT-2 QAL-1 5 B1 5.10 N/A B15.30 B15.50 B15.60 B15.70 CN-2553-1.1 X Reactor Coolant (NC) VT-2 QAL-1 5 B135.20 N/A B15.50 B15.70 CN-2554-1.0 X Reactor Coolant (NC) VT-2 QAL-1 5 B135.50 N/A B15.70 CN-2554-1.5 X Reactor Coolant (NC) VT-2 QAL-1 5 B135.50 N/A B15.70 CN-2561 -1.0 X Reactor Coolant (NC) VT-2 QAL-1 5 B135.50 N/A B15.70 CN-2561 -1.1 X Reactor Coolant (NC) VT-2 QAL-15 B15.50 N/A B15.70 CN-2562-1.0 X Reactor Coolant (NC) VT-2 QAL-1 5 B135.50 N/A B135.70 CN-2562-1.1 X Reactor Coolant (NC) VT-2 QAL-15 B15.50 N/A B15.70 CN-2562-1.2 X Reactor Coolant (NC) VT-2 QAL-1 5 B135.50 N/A B15.70 CN-2562-1.3 X Reactor Coolant (NC) VT-2 QAL-1 5 B135.50 N/A B15.70
This Report Was Generated On: 10/30/2001 Duke Power Company - Catawba Unit 2 Pressure Testing Zone Number Listing Int = 2 Outage 11 Period = 2 Boundary Required Test Required Required ASME Item I1* A* I IIIlIl Qkm*n IMlewma Inenrtinn DrnrrImmr N. ,mhArh ('nmmontf zUone I'iUIl LIl .IavvIII I I I I II Y0I ; Ull I*gI*l* I 2BB-OO1 L-B CN-2565-2.6 X Steam Generator Blowdown VT-2 QAL-15 C7.30 N/A C7.70 CN-2572-1.4 X Steam Generator Blowdown VT-2 QAL-1 5 C7.30 N/A C7.70 CN-2580-1.0 X Steam Generator Blowdown VT-2 QAL-1 5 C7.30 N/A C7.70 2CA-001 L-B CN-2584-1.0 X Auxiliary Feedwater (CA) VT-2 QAL-1 5 C7.30 N/A C7.70 CN-2591 -1.1 X Auxiliary Feedwater (CA) VT-2 QAL-15 C7.10 N/A C7.30 C7.70 CN-2592-1.1 X Auxiliary Feedwater (CA) VT-2 QAL-15 C7.30 N/A C7.70 CN-2593-1.0 X Auxiliary Feedwater (CA) VT-2 QAL-15 C7.30 N/A C7.70 CN-2593-1.1 X Auxiliary Feedwater (CA) VT-2 QAL-15 C7.30 N/A C7.70 CN-2593-1.7 X Auxiliary Feedwater (CA) VT-2 QAL-1 5 C7.30 N/A C7.70 2FW-001 L-B CN-2554-1.2 X Refueling Water (FW) VT-2 QAL-15 C7.30 N/A C7.70 CN-2554-1.7 X Refueling Water (FW) VT-2 QAL-1 5 C7.30 N/A C7.70 CN-2561 -1.0 X Refueling Water (FW) VT-2 QAL-1 5 C7.30 N/A C7.70 CN-2562-1.2 X Refueling Water (FW) VT-2 QAL-1 5 C7.30 N/A
This Report Was Generated On: 10/30/2001 Duke Power Company - Catawba Unit 2 Pressure Testing Zone Number Listing Int = 2 Outage 11 Period = 2 Boundary Required Test Required Required ASME Item I II I"u SMama Incnl*r~finn D~PnedI'IrA Nuimh~r(/ Crmments Lonie iumIIU l- iJndW ilI ,. i El r / I I 1yo1l~ l U.. ii . . u ..... .. 2FW-001 L-B C7.70 CN-2563-1.0 X Refueling Water (FW) VT-2 QAL-1 5 C7.30 N/A C7.70 CN-2570-1.0 X Refueling Water (FW) VT-2 QAL-1 5 C7.30 N/A C7.70 CN-2571 -1.0 X Refueling Water (FW) VT-2 QAL-1 5 C7.30 N/A C7.70 2FW-002L-B CN-2571 -1.0 X Refueling Water (FW) VT-2 QAL-1 5 C7.30 N/A C7.70 2ND-001L-B CN-2561 -1.0 x Residual Heat Removal (ND) VT-2 QAL-15 C7.10 N/A C7.30 C7.50 C7.70 CN-2561-1.1 X Residual Heat Removal (ND) VT-2 QAL-15 C7.10 N/A C7.30 C7.50 C7.70 CN-2562-1.2 X Residual Heat Removal (ND) VT-2 QAL-15 C7.30 N/A C7.70 CN-2562-1.3 X Residual Heat Removal (ND) VT-2 QAL-15 C7.30 N/A C7.70 CN-2563-1.0 X Residual Heat Removal (ND) VT-2 QAL-15 C7.10 N/A C7.30 C7.50 C7.70 CN-2571 -1.0 X Residual Heat Removal (ND) VT-2 QAL-15 C7.30 N/A C7.70
This Report Was Generated On: 10/30/2001 Duke Power Company - Catawba Unit 2 Pressure Testing Zone Number Listing Int = 2 Outage 11 Period = 2 Boundary Required Test Required Required ASME Item Inenai-fnn Dmrneehdir* Nllmh#_rt_* S.... ILl .... L----
,I IIl* U O~e*n Ie na C'rnmmentr 4 o ne N umD er u ra w il g i I rl I I V0 .a . .M ,v . . . .. . . . - .- --..
CN-2572-1.0 X Residual Heat Removal (ND) VT-2 QAL-15 C7.30 N/A C7.70 2ND-002L-B CN-2561 -1.0 X Residual Heat Removal (ND) VT-2 QAL-15 C7.30 N/A C7.70 CN-2561 -1.1 X Residual Heat Removal (ND) VT-2 QAL-1 5 C7.30 N/A C7.70 CN-2562-1.2 X Residual Heat Removal (ND) VT-2 QAL-1 5 C7.30 N/A C7.70 CN-2562-1.3 X Residual Heat Removal (ND) VT-2 QAL-15 C7.30 N/A C7.70 CN-2563-1.0 X Residual Heat Removal (ND) VT-2 QAL-15 C7.30 N/A C7.50 C7.70 CN-2571 -1.0 X Residual Heat Removal (ND) VT-2 QAL-1 5 C7.30 N/A C7.70 CN-2572-1.0 X Residual Heat Removal (ND) VT-2 QAL-15 C7.30 N/A C7.70 CN-2561 -1.0 X Residual Heat Removal (ND) VT-2 QAL-15 C7.30 N/A 2ND-003L-B C7.70 CN-2561 -1.1 X Residual Heat Removal (ND) VT-2 QAL-1 5 C7.30 N/A 2ND-004L-B C7.70 2ND-007L-B CN-2562-1.3 X Residual Heat Removal (ND) VT-2 QAL-15 C7.30 N/A C7.70 2ND-008L-B CN-2562-1.3 X Residual Heat Removal (ND) VT-2 QAL-15 C7.30 N/A C7.70 2NI-002L-B CN-2562-1.1 x Safety Injection (NI) VT-2 QAL-1 5 C7.30 N/A
/
This Report Was Generated On: 10/30/2001 Duke Power Company - Catawba Unit 2 Pressure Testing Zone Number Listing Outage 11 Int = 2 Period = 2 Boundary Required Test Required Required ASME Item Zone Number Drawina L IIIFIH System Name Insoection Procedure Number(s) Comments 2NI-002L-B C7.70 CN-2572-1.1 X Safety Injection (NI) VT-2 QAL-15 C7.30 N/A C7.70 2NI-004L-B CN-2562-1.2 X Safety Injection (NI) VT-2 QAL-15 C7.30 N/A C7.70 2NI-006L-B CN-2562-1.2 X Safety Injection (NI) VT-2 QAL-15 C7.30 N/A C7.70 2NS-001L-B CN-2563-1.0 X Containment Spray (NS) VT-2 QAL-15 C7.30 N/A C7.70 2NS-002L-B CN-2563-1.0 X Containment Spray (NS) VT-2 QAL-15 C7.30 N/A C7.70 2NV-001L-B CN-2554-1.0 X Chemical & Volume Control (NV) VT-2 QAL-15 C7.30 N/A C7.70 CN-2554-1.5 X Chemical & Volume Control (NV) VT-2 QAL-15 C7.30 N/A C7.70 CN-2554-1.8 X Chemical & Volume Control (NV) VT-2 QAL-15 C7.30 N/A C7.70 2NV-002L-B CN-2554-1.7 X Chemical & Volume Control (NV) VT-2 QAL-1 5 C7.30 N/A C7.70 2NV-003L-B CN-2554-1.7 X Chemical & Volume Control (NV) VT-2 QAL-1 5 C7.30 N/A C7.70 2NV-004L-B CN-2554-1.2 X Chemical & Volume Control (NV) VT-2 QAL-1 5 C7.30 N/A C7.70 2NV-005L-B CN-2554-1.2 X Chemical & Volume Control (NV) VT-2 QAL-1 5 C7.30 N/A C7.70 2NV-006L-B CN-1554-1.4 x Chemical & Volume Control (NV) VT-2 QAL-1 5 C7.30 N/A
This Report Was Generated On: 10/30/2001 Duke Power Company - Catawba Unit 2 Pressure Testing Zone Number Listing Int = 2 Outage 11 Period = 2 Boundary Required Test Required Required ASME Item I IlI~l' l- Q,e*m tJam Incnrtinn PrnrcwI.iri NMimharic! Comments zoneI N'umbe ail~ar Id1 LIE ~~III ~ ~ ~ ~ ~ ~ awimn ~ IP ~ n -____________ r n-... 2NV-006L-B C7.70 CN-1 556-1.0 X Chemical & Volume Control (NV) VT-2 QAL-1 5 C7.30 N/A C7.70 CN-2554-1.0 X Chemical & Volume Control (NV) VT-2 QAL-1 5 C7.30 N/A C7.70 CN-2554-1.1 X Chemical & Volume Control (NV) VT-2 QAL-15 C7.30 N/A C7.70 CN-2554-1.2 X Chemical & Volume Control (NV) VT-2 QAL-1 5 C7.30 N/A C7.50 C7.70 CN-2554-1.5 X Chemical & Volume Control (NV) VT-2 QAL-1 5 C7.30 N/A C7.70 CN-2554-1.6 X Chemical & Volume Control (NV) VT-2 QAL-1 5 C7.30 N/A C7.70 CN-2554-1.7 X Chemical & Volume Control (NV) VT-2 QAL-1 5 C7.30 N/A C7.70 CN-2562-1.0 X Chemical & Volume Control (NV) VT-2 QAL-1 5 C7.30 N/A C7.70 CN-2562-1.2 x Chemical & Volume Control (NV) VT-2 QAL-15 C7.30 N/A C7.70 I I-4-I-4-l F j 2BB-001 L-B CN-2584-1.0 x Steam Generator Blowdown VT-2 QAL-15 C7.10 N/A C7.30 _________________________ _____________________________________________ L
11.2 Examination Results For This Outage: The results of each pressure test and associated VT-2 Visual Examination conducted from EOC-10 through EOC-1 1 are included in this section. The information shown below is a field description for the Class 1 and Class 2 listing format included in this section of the report: Zone Number = The unique number assigned to track certain extremity valves that make up a test Boundary Drawing = Detail drawing of pressure test boundary Outage - The number for the refueling outage cycle of this report Test Status = Complete or Partial Test Result = Clear (No Evidence Of Leakage), Reportable (Evidence Of Leakage - Not Through Wall such as packing leak), Reportable (Evidence Of Through Wall Leakage) VT-2 Examiner = The name of the Level II Visual examiner VT-2 Date = Date that VT-2 visual examination was performed Refueling Outage Report EOC1 1 Page 4 of 5 Catawba Unit 2 Revision 0 Section 11 November 1,2001
Current Interval = 2 Current Period = 2 Duke Power Company - Catawba Unit 2 Class = A Pressure Testing VT-2 Examination Results Boundary Zone Number Drawing Outage Test Status Test Result VT-2 Examiner VT-2 Date CN-2553-1.0 11 Complete Recordable J. Brown 10/20/2001 2NC-001 L-A C. Mathews T. Murray J. Faris J. Persinger 11 Complete Clear T. Murray 10/20/2001 CN-2553-1.1 CN-2554-1.0 11 Complete Recordable J. Faris 10/20/2001 CN-2554-1.5 11 Complete Clear J. Faris 10/20/2001 11 Complete Clear T. Murray 10/20/2001 CN-2561 -1.0 CN-2561 -1.1 11 Complete Clear J. Brown 10/20/2001 CN-2562-1.0 11 Complete Clear J. Brown 10/20/2001 CN-2562-1.1 11 Complete Clear J. Faris 10/20/2001 CN-2562-1.2 11 Complete Clear J. Brown 10/20/2001 C. Mathews T. Murray J. Faris J. Persinger CN-2562-1.3 11 Complete Clear J. Brown 10/20/2001 C. Mathews T. Murray J. Faris J. Persinger
-- - -.1-- ^-. 1r)1,W)1OnO1
Current Interval = 2 Current Period = 2 Duke Power Company - Catawba Unit 2 Class = B Pressure Testing VT-2 Examination Results Boundary Zone Number frsriwinn Outnae Test Status Test Result VT-2 Examiner VT-2 Date Zone Number Drawin a Test Status 2BB-001 L-B CN-2565-2.6 11 Complete Clear J. Brown 10/20/2001 C. Mathews T. Murray J. Fars J. Persinger CN-2572-1.4 11 Complete Clear J. Brown 10/20/2001 C. Mathews T. Murray J. Faris J. Persinger 11 Complete Clear J. Brown 10/20/2001 CN-2580-1.0 C. Mathews T. Murray J. Fars J. Persinger 11 Complete Clear J. Brown 10/20/2001 CN-2584-1.0 C. Mathews T. Murray J. Faris J. Persinger 2CA-001 L-B CN-2584-1.0 11 Complete Clear J. Brown 10/20/2001 C. Mathews T. Murray J. Faris J. Persinger CN-2591-1.1 11 Complete Recordable J. Brown 10/20/2001 C. Mathews T. Murray J. Faris J. Persinger CN-2592-1.1 11 Complete Recordable J. Brown 10/20/2001 C. Mathews
I Current Interval = 2 Current Period = 2 Duke Power Company - Catawba Unit 2 Class = B Pressure Testing VT-2 Examination Results Boundary 7 flnl* Nimimh~r rlrnlAtinf A. T*=t .*tnh L* Te__*t Re__*HIt MT-2 IExnminer VT-2 Date 7rnin Kliimhar T-2 Examiner T. Murray VT-2 ate 2CA-001 L-B J. Faris J. Persinger CN-2593-1.0 11 Complete Clear J. Brown 10/20/2001 C. Mathews T. Murray J. Fars J. Persinger 11 Complete Clear J. Brown 10/20/2001 CN-2593-1.1 C. Mathews T. Murray J. Faris J. Persinger CN-2593-1.7 11 Complete Recordable J. Brown 10/20/2001 C. Mathews T. Murray J. Faris J. Persinger 2FW-001 L-B CN-2554-1.2 11 Complete Clear J. Brown 07/25/2001 G. Graft CN-2554-1.7 11 Complete Clear J. Brown 07/25/2001 G. Graft CN-2561 -1.0 11 Complete Recordable J. Brown 07/25/2001 G. Graft 11 Complete Clear J. Brown 07/25/2001 CN-2562-1.2 G. Graft 11 Complete Clear J. Brown 07/25/2001 CN-2563-1.0 G. Graft CN-2570-1.0 11 Complete Clear J. Brown 07/25/2001 G. Graft
- -. 1. 4n/OnlOnn.
( Current Interval = 2 Current Period = 2 Duke Power Company - Catawba Unit 2 Class = B Pressure Testing VT-2 Examination Results Boundary Zone Number Drawing Outage Test Status Test Result VT-2 Examiner VT-2 Date Zone Number CN-2571 -1.0 11 Complete Clear J. Brown 07/25/2001 G. Graff 2FW-002L-B CN-2571-1.0 11 Complete Recordable J. Fars 07/25/2001 T. Murray 2ND-002L-B CN-2561 -1.0 11 Complete Clear J. Persinger 05/30/2001 C. MATHEWS CN-2561-1 .1 11 Complete Recordable J. Persinger 05/30/2001 C. Mathews CN-2562-1.2 11 Complete Clear J. Persinger 05/30/2001 C. Mathews CN-2562-1.3 11 Complete Clear J. Persinger 05/30/2001 C. Mathews CN-2563-1.0 11 Complete Clear J. Persinger 05/30/2001 C. Mathews CN-2571 -1.0 11 Complete Clear J. Persinger 05/30/2001 C. Mathews CN-2572-1.0 11 Complete Clear J. Persinger 05/30/2001 C. Mathews 2ND-003L-B CN-2561 -1.0 11 Complete Recordable J. Brown 09/19/2001 E. Adamson M. Sharpe 2ND-004L-B CN-2561 -1.1 11 Complete Recordable J. Brown 09/19/2001 E. Adamson M.Sharpe 2ND-007L-B CN-2562-1.3 11 Complete Clear J. Brown 09/19/2001 E. Adamson M. Sharpe 2ND-008L-B CN-2562-1.3 11 Complete Clear J. Brown 09/19/2001 E. Adamson
( ( Current Interval = 2 Current Period = 2 Duke Power Company - Catawba Unit 2 Class = B Pressure Testing VT-2 Examination Results Boundary "7 ^ ,*, ^ one I*l i, rbt Iq^
- T--e* I*-eem si VT-2 Examiner VT-2 Date um er Drawng Ouage es Stt Test Result M.Sharpe 2ND-008L-B 2NI-002L-B CN-2562-1.1 11 Complete Clear J. Persinger 10/20/2001 11 Complete Clear J. Persinger 10/20/2001 CN-2572-1.1 11 Complete Recordable J. Faris 08/02/2001 2NI-004L-B CN-2562-1.2 CN-2563-1.0 11 Complete Recordable C. Mathews 09/06/2001 2NS-001 L-B T. Murray 2NV-001 L-B CN-2554-1.0 11 Complete Recordable J. Brown 10/20/2001 C. Mathews T. Murray J. Fans J. Persinger CN-2554-1.5 11 Complete Recordable J. Brown 10/20/2001 C. Mathews T. Murray J. Fans J. Persinger CN-2554-1.8 11 Complete Clear J. Brown 10/20/2001 C. Mathews T. Murray J. Fans J. Persinger 2NV-002L-B CN-2554-1.7 11 Complete Clear J. Brown 07/10/2001 11 Complete Clear C. Mathews 08/15/2001 2NV-003L-B CN-2554-1.7 11 Complete Clear J. Brown 08/21/2001 2NV-005L-B CN-2554-1.2
- .1.1-- -..- - - --,--. 4npýnf,)A^ I
11.3 Reportable Indications: None Refueling Outage Report EOC1 1 Page 5 of 5 Revision 0 Catawba Unit 2 November 1, 2001 Section 11}}