Tennessee Valley Authority, Post Office Box 2000, Soddy-Daisy, Tennessee 37384-2000 October 5, 2001 U.S. Nuclear Regulatory Commission ATTN:

Document Control Desk Washington, D.C.

20555 Gentlemen:

In the Matter of Tennessee Valley Authority Docket Nos. 50-327 50-328 SEQUOYAH NUCLEAR PLANT -

UNITS 1 AND 2 -

EMERGENCY PLAN IMPLEMENTING PROCEDURE (EPIP) REVISIONS In accordance with the requirements of 10 CFR 50, Appendix E, Section V, the enclosure provides the following EPIP:

Revision 34 20 2

17 22 Title Activation and Operation of the Technical Support Center Activation and Operation of the Operations Support Center (OSC)

Dose Assessment Radiological Control Response Emergency Equipment and Supplies This letter is being sent in accordance with RIS 2001-05.

If you have any questions concerning this matter, please telephone me at (423) 843-7170 or J.

D. Smith at (423) 843-6672.

Licensing and Industry Affairs Manager Enclosures Printed on recycled piper EPIP EPIP-6 EPIP-7 EPIP-13 EPIP-14 EPIP-17

) )

TENNESSEE VALLEY AUTHORITY SEQUOYAH NUCLEAR PLANT EMERGENCY PLAN IMPLEMENTING PROCEDURE EPIP - 6 ACTIVATION AND OPERATION OF THE TECHNICAL SUPPORT CENTER Revision 34 QUALITY RELATED PREPARED BY:

RESPONSIBLE ORGANIZATION:

APPROVED BY:

EFFECTIVE DATE:

10/01/2001 Level of Use:

Reference W. C. Pegaram Emercqency Preparedness J. Randy Ford I

ACTIVATION AND OPERATION OF THE EPIP - 6 SQN TECHNICAL SUPPORT CENTER Rev. 34 Page 2 of 51 Revision History Rev Date Reason for Revision 32 03/30/2001 Clarified inter-relation of Appendix U and B. Reformatted TSC minimum staffing to more clearly define necessary staff. Added TAT actions concerning Aux Air Dryers from DCN D20393A. Revised PAR chart in accordance with REP revision. Removed iodine channels from 101, 106, and 112 rad monitors. Added Area monitor RM-90-61.

Corrected instrument IDs.

33 05/31/2001 Reformatted index and cover page. Added Revision history. Revised header to smaller format. Added evaluation of Control Building Ventilation isolation as part of actions of PER 01-002674-000.

Added Shift turnover verification EP Manager and added necessary forms as Appendices BB and CC.

34 10/01/2001 Revised Appendix L to instruct the clerks to disable "Memory Fax" option (PER 01-006615-000). Deleted Appendix Y (PER 01-008461 000). Revised Title for Appendix Z due to no longer having equipment listed in Appendix. Minor formatting changes.

ACTIVATION AND OPERATION OF THE EPIP - 6 SQN TECHNICAL SUPPORT CENTER Rev. 34 Page 3 of 51 TABLE OF CONTENTS Section Title Page Table of Contents............................................................................

2 1.0 P U R P O S E............................................................................................

5

2.0 REFERENCES

5 2.1 Interface Documents...................................

5 2.2 Developmental Documents..............................................................

5 3.0 INSTRUCTIONS............................................................................

5 3.1 Declaration of the Event.................................................................

5 3.2 Activation of TSC...........................................................................

6 3.2.1 Shift Manager..................................................................................

6 3.2.2 C a ll L ist.........................................................................................

.. 6 3.2.3 R esponse.......................................................................................

.. 6 3.2.4 TSC Operations.............................................................................

7 3.2.5 Site Vice President..........................................................................

7 3.2.6 Site Emergency Director (SED)........................................................

8 3.2.7 Operations Manager.......................................................................

8 3.2.8 Technical Assessment Manager (TAM).......................................... 8 3.2.9 Technical Assessment Team (TAT).................................................

8 3.2.10 Operations Advisor, TAT.............................

.--... 8 3.2.11 Site Security Manager.....................................................................

9 3.2.12 Radiological Control Manager........................................................

9 3.2.13 Chemistry Manager..........................................................................

9 3.2.14 NRC Coordinator............................................................................

9 3.2.15 Control Room Communicator..........................................................

9 3.2.16 EP Manager..................................................................................

10 3.2.17 TSC Clerical/Logkeeper Staff........................................................

10 3.2.18 Maintenance Manager..................................................................

10 3.2.19 Operations Communicator............................................................

10 3.3 Termination and Deactivation.......................................................

10 4.0 RECORDS....................................................................................

11 4.1 Q A R ecords.................................................................................

11 4.2 Non-QA Records............................................................................

11 APPENDICES (index on next page)

SOURCE NOTES..........................................................................

51

ACTIVATION AND OPERATION OF THE TECHNICAL SUPPORT CENTER SQN EPIP -6 EPIP - 6 Rev. 34 Page 4 of 51 Appendix Appendix A Appendix B Appendix C Appendix D Appendix E Appendix F Appendix G Appendix H Appendix I Appendix J Appendix K Appendix L Appendix M Appendix N Appendix 0 Appendix P Appendix Q Appendix R Appendix S Appendix T Appendix U Appendix V Appendix W Appendix Y Appendix Z Appendix AA Appendix BB Appendix CC TABLE OF CONTENTS (Continued)

Page Site Vice President Checklist................................ 11 Site Emergency Director Checklist........................ 12 Operations Manager Checklist.............................. 16 Technical Assessment Manager Checklist........... 17 Operations Advisor, TAT Checklist........................ 18 Site Security Manager Checklist............................ 19 RADCON Manager Checklist................................ 20 Chemistry Manager Checklist.................................

21 NRC Coordinator Checklist..................................

22 Control Room Communicator Checklist.............

24 EP Manager Checklist.........................................

25 TSC Clerical/Logkeeper Staff Checklist................ 26 Maintenance Manager Checklist...........................

27 Technical Assessment Team Checklist................. 28 Plant Parameter Data Sheets................................ 30 Predictive Release Data Sheet.............................

35 TSC Accident Assessment Sheet..................

36 Protective Action Recommendation Guidance.....

37 Containment Sump Operation and Level G uidance...............................................................

38 ERCW Concerns for Technical Assessment Team... 39 SED Turnover Data Sheet.................................... 42 Control Building Battery Room Exhaust Fan Failure..................................

44 Contingencies for Control and Processing...

Large Volumes of Secondary Side Contaminated W ater.............................................

45 C ancelled...........................................................

.. 46 Reference Materials List......................................

47 Operations Communicator Checklist.....................

48 TSC Roster..........................................................

49 Emergency Responder Notification Form............. 50

ACTIVATION AND OPERATION OF THE EPIP - 6 SQN TECHNICAL SUPPORT CENTER Rev. 34 Page 5 of 51 1.0 PURPOSE The purpose of this procedure is to describe activation of the Technical Support Center (TSC), describe the TSC organization, and provide for TSC operation once it has been staffed. The TSC is activated during an Alert, Site Area Emergency, and General Emergency.

2.0 REFERENCES

2.1 Interface Documents A. EPIP-15, "Emergency Exposure Guidelines" B. EPIP-16, "Termination and Recovery" C. 0-SO-67-3, "ERCW Strainers and Traveling Screens" D. EPIP-7 "Activation and Operation of the Operations Support Center" E. EPIP-14 "Radiological Control Response" 2.2 Developmental Documents A. Memorandum from J. B. Hosmer to R. J. Johnson dated 1/15/88, Implementing PRDCS and Operation Training (RIMS-B25880115028)

B. EPIP-7, "Activation and Operation of the Operations Support Center (OSC) 3.0 INSTRUCTIONS 3.1 Declaration of the Event The Shift Manager (SM) upon detection of an emergency condition becomes the Site Emergency Director (SED), classifies the emergency, and declares the event. Upon arrival of the Plant Manager or alternate defined in the Duty Roster or Call List, the SM will be relieved of the SED duties.

Appendix U may be used to ensure a complete turnover. The SED activates and operates the TSC (Appendix B) and oversees the operations of the Operations Support Center (OSC).

3.1.1 Procedure Usage During declared radiological emergencies follow procedures to the extent practical. Regardless of the use of procedures, system configuration will be maintained.

ACTIVATION AND OPERATION OF THE EPIP - 6 SQN TECHNICAL SUPPORT CENTER Rev. 34 Page 6 of 51 S3.2 Activation of the TSC 3.2.1 Shift Manager (SM)

The SM will activate the TSC and OSC by announcing the emergency condition by one or more of the following methods.

A. Plant Public Address (PA) announcement.

B. The SM or Operations Clerk will normally activate the Emergency Paging System (EPS) or, contact the persons designated on the call list. If the EPS cannot be activated from the site, contact the Operations Duty Specialist (ODS) on the ringdown line or 5-751-1700 and have the EPS activated from the CECC.

C. The SM may activate the onsite emergency sirens at an "Alert" and shall activate the sirens at a "Site Area Emergency" or "General Emergency."

3.2.2 Call List The Emergency Preparedness Manager (EPM) shall maintain a call list listing all TSC personnel by name, plant and home telephone numbers. The REP Call List will be updated at least quarterly by the EPM or designee with input by the appropriate section/group supervisors. The list will be provided to the SM and placed in the TSC.

3.2.3 Response Personnel performing the following REP functions should report to the TSC, or the assigned TSC support locations (see NP-REP Appendix B Figure B-3 for TSC Layout), upon announcement of an "ALERT" or higher emergency classification or at the direction of the SED.

A. Site Vice President B. Site Emergency Director C. Operations Manager D. Technical Assessment Manager E. Operations Advisor, TAT F. Site Security Manager G. Radiological Control Manager (RCM)

H. Chemistry Manager I. NRC Coordinator J. Control Room Communicator (affected Unit Control Room)

K. EP Manager L. TSC Clerical/Logkeeper Staff (Clerical will be called)

M. Maintenance Manager N. Technical Assessment Team

0. Operations Communicator P. Other Plant staff the SED determines to be necessary to support TSC functions will be called.

ACTIVATION AND OPERATION OF THE EPIP - 6 SQN TECHNICAL SUPPORT CENTER Rev. 34 Page 7 of 51 3.2.4 TSC Operations The TSC shall operate to ensure the following:

A. Provide plant management and technical support to plant operations personnel during emergency conditions.

B. Perform CECC functions for the Alert Emergency class, the Site Area Emergency class, and General Emergency class until the CECC is functional.

C. Help the reactor operators determine the plant safety status.

D. Relieve the reactor operators of peripheral duties and communications not directly related to reactor system manipulations.

E. Prevent congestion in the control room.

F. Provide assistance to the operators by technical personnel who have comprehensive plant data at their disposal.

G. Provide a coordinated emergency response by both technical and management personnel.

H. Provide reliable communications between onsite and offsite emergency response personnel.

1. Provide a focal point for development of recommendations for offsite actions.

J. Provide relevant plant data to the NRC for its analysis of abnormal plant operating conditions.

3.2.5 Site Vice President The Site Vice President serves as a corporate interface for the SED, relieving him from duties which could distract from the SED's primary purpose of plant operations and accident mitigating activities. The Site Vice President shall provide assistance in the areas of TVA Policy, site resources, direct interface with the CECC, onsite media, NRC, FEMA, or other federal organizations responding to the site. The Site Vice President may assist the SED as requested. Appendix A, Site Vice President Checklist, shall be used to ensure required actions are completed.

SACTIVATION AND OPERATION OF THE EPIP - 6 SQN TECHNICAL SUPPORT CENTER Rev. 34 Page 8 of 51 3.2.6 Site Emergency Director (SED)

The SED directs activities of the onsite emergency organization; determines the emergency classification; initiates protective actions onsite; prior to the CECC being staffed, makes notification of escalated emergency classification to the State and recommendations for protective actions to State and local agencies in accordance with Appendix R, Protective Action Recommendation Guidance or EPIP-5; coordinates emergency actions with onsite NRC; and approves or authorizes emergency doses that will exceed occupational dose limits. May be relieved by the Operations Manager as needed. Appendix B, Site Emergency Director Checklist, shall be used to ensure required actions are completed.

3.2.7 Operations Manager The Operations Manager directs operational activities; informs SED of plant status and operational problems; provides input to the SED for emergency classification declaration; performs damage assessment as necessary; and recommends solutions and mitigating action for operational problems. The Operations Manager may relieve the SED when the SED must leave the TSC. Appendix C, Operations Manager Checklist, shall be used to ensure required actions are completed.

3.2.8 Technical Assessment Manager (TAM)

The TAM directs onsite effluent assessment; directs activities of Technical Assessment Team (TAT); provides information, evaluations, and projections to the SED; provides input to the SED for emergency classification declaration; coordinates assessment activities with the CECC plant assessment team; and establishes and maintains a status of significant plant problems. Appendix D, Technical Assessment Manager Checklist, shall be used to ensure required actions are completed.

3.2.9 Technical Assessment Team (TAT)

The TAT prepares and provides periodic current assessment on plant conditions and provides this information to the CECC Plant Assessment Team on Appendix Q when requested; monitors and trends key plant parameters against EAL criteria and provides technical assessment; projects future plant status based on present plant conditions; provides technical support to plant operations on mitigating actions. Appendix N, Technical Assessment Team Checklist, shall be used to ensure required actions are completed.

3.2.10 Operations Advisor, TAT The Operations Advisor, TAT operates the ICS to obtain plant status and parameters; completes plant parameter data sheets, as needed, and provides information from the Control Room to the Technical Assessment Manager and Technical Assessment Team. Appendix E, Operations Advisor, TAT Checklist, shall be used to ensure required actions are completed.

ACTIVATION AND OPERATION OF THE EPIP - 6 SQN TECHNICAL SUPPORT CENTER Rev. 34 Page 9 of 51 S3.2.11 Site Security Manager The Site Security Manager directs activities of Site Security; controls access to site and control room; and reports on site accountability/evacuation.

Appendix F, Site Security Checklist, shall be used to ensure required actions are completed.

3.2.12 Radiological Control Manager The TSC RCM directs assessment of inplant and onsite radiological conditions; coordinates additional RADCON support with CECC; recommends protective actions for onsite personnel to the SED; after notifying the SED authorizes KI issue; coordinates assessment of radiological conditions offsite with CECC; and provides RADCON surveillance/support to MET station personnel ensuring the Maintenance Manager is tracking those off-site personnel on the Team Tracking Board.

Provides input to the SED for emergency classification declaration and PARs. Appendix G, RADCON Manager Checklist, shall be used to ensure required actions are completed.

3.2.13 Chemistry Manager The Chemistry Manager coordinates assessment of radioactive effluents with the CECC; directs post accident sampling system (PASS) activities; directs the initiation of onsite/off-site dose assessment if needed prior to the CECC being staffed; and determines impact of the incident on radwaste and various effluent treatment systems; and provides input to the SED for emergency classification and PARs. Appendix H, Chemistry Manager Checklist, shall be used to ensure required actions are completed.

3.2.14 NRC Coordinator The NRC Coordinator acts as primary liaison with onsite NRC personnel; updates NRC personnel on plant status; and obtains information from TSC personnel as requested by the NRC; and may be assigned communication duties on the ENS line to the NRC. Appendix I, NRC Coordinator Checklist, shall be used to ensure required actions are completed.

3.2.15 Control Room Communicator The Control Room Communicator serves in the control room as the communications interface with the Operations Communicator in the TSC and OSC Operations Advisor; provides advice regarding Technical Specifications, system response, safety limits, etc.; communicates status of plant systems and major equipment, automatic and manual initiation of ESF equipment, important system parameters, procedure transitions, and communicates messages between the Shift Manager and the TSC; assists in development of recommended solutions to developing problems; informs the Operations Communicator and OSC Ops. Advisor of Ops.

personnel/teams dispatched by the SM. Appendix J, Control Room Communicator Checklist, should be used to ensure required actions are completed.

ACTIVATION AND OPERATION OF THE EPIP - 6 SQN TECHNICAL SUPPORT CENTER Rev. 34 Page 10 of 51 3.2.16 EP Manager The EP Manager advises the SED regarding the overall radiological emergency plan, use of implementing procedures, emergency equipment availability, and coordination with CECC; and confirms TSC and OSC are operating properly. He will keep the plant staff informed, by P/A system, of current plant conditions as directed by the SED. He will be responsible for the call in of Clerks (action may be delegated). He will provide assistance to the OSC Manager as requested. Appendix K, EP Planning Manager Checklist, shall be used to ensure required actions are completed.

3.2.17 TSC Clerical/Logkeeper Staff The TSC clerks provide logistics support to the TSC. The designated TSC logkeeper will maintain a chronological log of the SED and TSC activities.

The log should include entries such as decisions made by the SED, content of SED discussions, time of classification upgrades and PARs and the level of each, status of repair and damage control teams, briefing times and any other entry as directed by the SED. The logkeeper may prepare briefing notes for the SED. The notes should include activities since the last briefing and include team status, changes in classification and PARs, and current plant conditions. The TSC logkeeper should have some technical writing ability. Appendix L, TSC Clerical Staff Checklist, shall be used to ensure required actions are completed.

3.2.18 Maintenance Manager The Maintenance Manager maintains communications between the OSC and TSC, maintains cognizance of dispatched teams and status, and assists the SED and OSC Manager in establishing OSC work priorities.

Appendix M, Maintenance Manager checklist, shall be used to ensure required actions are completed.

3.2.19 Operations Communicator The Operations Communicator monitors the Control Room Operations Bridge, provides information from the MCR to the TSC, and maintains a current log of major operational events for the Operations Manager's use.

Appendix AA shall be used to ensure required actions are completed.

3.3 Termination and Deactivation A. The TSC will be deactivated when the indicated plant conditions are such that in accordance with EPIP-16 "Termination and Recovery" the emergency has been terminated, and the OSC has been deactivated.

B. All records generated during the operation of the TSC and OSC have been reviewed and forwarded to the Emergency Preparedness Manager.

C. All equipment and usable supplies have been returned to their storage locations.

ACTIVATION AND OPERATION OF THE EPIP - 6 SQN TECHNICAL SUPPORT CENTER Rev. 34 Page 11 of 51 4.0 RECORDS 4.1 QA Records The following appendices and checklists necessary to demonstrate key actions during an emergency are considered QA records. These records shall be forwarded to the EP Manager who shall submit QA records and any other records deemed necessary to corporate Emergency Preparedness for maintenance.

A.

TSC Checklists B.

Plant Parameter Data Sheets C.

Predictive Release Data Sheets D.

TSC Accident Assessment Sheets E.

TSC Log Book 4.2 Non-QA Records The appendices and checklists in this instruction necessary to demonstrate key actions during NRC evaluated exercises will be retained by the SON EP Manager for at least two years.

ACTIVATION AND OPERATION OF THE EPIP - 6 SQN TECHNICAL SUPPORT CENTER Rev. 34 Page 12 of 51 APPENDIX A Page 1 of 1 SITE VICE PRESIDENT INITIAL ACTIVATION OF THE TECHNICAL SUPPORT CENTER INT/TIME

1.

Fill out the Organizational/Staffing Chart.

2.

Establish log of communications/events.

3.

Establish contact with the Media Relations Specialist.

4.

Check the status of emergency actions already in effect such as accountability or site evacuation.

OPERATIONAL RESPONSIBILITIES

"* Provides TVA policy direction to the Site Emergency Director.

"° Directs the site resources to support the SED in the accident mitigation activities.

"" Provides direct interface on overall site response activities with NRC, FEMA, Federal organizations, the CECC Director, and onsite media.

" At your discretion, may provide interface at the appropriate offsite location on the overall site response activities with State and Local agencies, NRC region/corporate, and the Joint Information Center.

Provides support to other emergency operation centers as necessary. As applicable, designates an alternate to provide direction and/or support for the overall site response and support to the SED.

Will assure that following all changes in emergency classification that the State has been notified in accordance with established procedures. Will appoint an alternate to complete this function if absent from the TSC.

SACTIVATION AND OPERATION OF THE EPIP - 6 SQN TECHNICAL SUPPORT CENTER Rev. 34 Page 13 of 51 APPENDIX B Page 1 of 3 SITE EMERGENCY DIRECTOR INITIAL ACTIVATION OF THE TECHNICAL SUPPORT CENTER INT/TIME

1.

Obtain turnover briefing from SM/SED in accordance with Appendix U (may be done concurrent with this Appendix).

Note: Transfer of responsibilities does not take place until Step 8 below has been confirmed.

2.

Fill out the Organizational/Staffing Chart.

3.

Establish log of communications/events.

4.

Establish contact with the CECC Director and determine if the Director has assumed responsibility for primary contact with the site and state. (NOTE: the ODS has this responsibility until the CECC Director assumes the function.)

5.

Note that if the emergency classification is escalated, and the CECC has not assumed responsibility for communications with the State, ensure the State is notified within 15 minutes by implementing EPIP-3, EPIP-4 or EPIP-5, as appropriate.

6.

Check the status of emergency actions already in effect such as accountability or site evacuation.

7.

Review checklist with key positions (Operations, Technical Assessment Manager, RADCON, Maintenance Manager, etc.).

8.

Ensure minimum staffing is present for TSC operability. The following individuals must be present:

"* SED

"* RADCON Manager

"* Operations Mgr or Ops Communicator TAM or TATL or (Reactor & Mech & Elec Engineers)

9.

Assume role of SED from SM/SED and SNotify CECC that TSC is operational.

E Notify OSC that TSC is operational.

0 Announce on plant PA system TSC is operational.

II

10. Clearly announce the time of activation of the TSC and OSC to the TSC and OSC staffs.

ACTIVATION AND OPERATION OF THE EPIP - 6 SQN TECHNICAL SUPPORT CENTER Rev. 34 Page 14 of 51 J

APPENDIX B Page 2 of 3 SITE EMERGENCY DIRECTOR OPERATIONAL RESPONSIBILITIES

"* Periodically briefs the TSC/OSC staff on the current situation.

"* Periodically direct key TSC positions to provide status summary to TSC staff.

"* Periodically updates the plant staff on plant status and emergency conditions.

"* Periodically reviews operation of the OSC with the OSC Manager.

"* Directs activities of onsite emergency organizations.

"* Consults with the CECC Director and Site VP on important decisions.

"* Initiates onsite protective actions.

"* When necessary, establish a RADCON checkpoint for site evacuation.

"" Coordinates emergency actions with onsite NRC.

"* Initiates long-term 24 Hour/day operation.

"* Approves or authorizes, in accordance with EPIP-15, emergency doses that may exceed occupational dose limits. This responsibility cannot be delegated.

Prior to the CECC being staffed, in accordance with Appendix R or EPIP-5 makes recommendations for protective actions to State and Local agencies through the Operations Duty Specialist within about five minutes of the determination. This responsibility cannot be delegated except to the CECC Director.

Determines the emergency classification and periodically reevaluates the classification. Changes to the classification will be reported to the CECC Director within about five minutes and the NRC. The classification of the event cannot be delegated.

Evaluates conditions and determines if additional emergency procedures should be implemented.

a. CECC EPIP-9 "Emergency Environmental Radiological Monitoring Procedures"
b. SQN EPIP-10 "Medical Emergency Response"
c. PHYSI-32 "Security Instructions to Members of the Security Force"
d. SQN EPIP-8 "Personnel Accountability and Evacuation"
e. SQN EPIP-13 "Dose Assessment"
f. SQN EPIP-14 "Radiological Control Response"

ACTIVATION AND OPERATION OF THE TECHNICAL SUPPORT CENTER SQN EPIP - 6 Rev. 34 Page 15 of 51 APPENDIX B Page 3 of 3 SITE EMERGENCY DIRECTOR OPERATIONAL RESPONSIBILITIES CONTINUED Assumes responsibility for Severe Accident Management when directed by the MCR and the TSC is functional and the SAMG evaluators are monitoring the Diagnostic Flow Chart. The TSC must have Three evaluators monitoring SAMGs to assume the accident responsibility.

DEACTIVATION RESPONSIBILITIES

"* Declare the event to be terminated in accordance with EPIP-16 "Termination and Recovery."

"* Activate recovery personnel.

"* Declare the OSC is deactivated.

Declare. the TSC deactivated I

ACTIVATION AND OPERATION OF THE EPIP - 6 SQN TECHNICAL SUPPORT CENTER Rev. 34 Page 16 of 51 APPENDIX C Page 1 of 1 OPERATIONS MANAGER INITIAL ACTIVATION OF THE TECHNICAL SUPPORT CENTER INT/TIME

1.

Fill out the Organizational/Staffing Chart.

2.

Establish log of communications/events.

3.

Log on to ICS.

4.

Check the status of emergency actions already in effect such as Accountability or Site Evacuation.

5.

Verify notification of the NRC has been accomplished.

6.

Designates an operationally competent person to establish and maintain communications with the NRC via the NRC emergency communication phones.

OPERATIONAL RESPONSIBILITIES

"* Directs operational activities.

"* Provide input to the SED for emergency classification.

"* Informs the SED of plant status and operational problems.

"* Recommends solutions and mitigating action for operational problems.

"* Periodically reviews the emergency status with the control room. Reviews trended parameters, time history information, and status boards with the control room staff.

"* Assures the control room is aware of the TSC accident assessment.

"* Discuss with the control room the OSC activities such as repair and response priorities and, status of damage control and repair teams.

" During long term accident operating conditions, evaluate routine activities which would be performed under normal plant operating conditions, e.g., AUO rounds, equipment inspections, surveillance instructions, compensatory measures, or other similar activities. Determine if any of these actions should be performed on a normal or reduced frequency.

" Assume SED responsibilities if the SED must leave the TSC

ACTIVATION AND OPERATION OF THE EPIP - 6 SQN TECHNICAL SUPPORT CENTER Rev. 34 Page 17 of 51 APPENDIX D Page 1 of 1 TECHNICAL ASSESSMENT MANAGER INITIAL ACTIVATION OF THE TECHNICAL SUPPORT CENTER INT/TIME

1.

Fill out the Organizational/Staffing Chart.

2.

Establish log of communications/events.

3.

Check the status of emergency actions already in effect such as Accountability or Site Evacuation.

4.

Check status of staff members (TATL, Rx Engr, Mech Engr, Elec Engr, TAT Ops Advisor and Westinghouse Rep).

OPERATIONAL RESPONSIBILITIES o Directs onsite effluent assessment.

"" Directs activities of the Technical Assessment Team.

o Projects future plant status based on present plant conditions.

o Keeps assessment team informed of plant status.

o Provides information, evaluations, and projections to the SED.

  • Coordinates assessment activities with the CECC Plant Assessment team.

o Establishes and maintains a status of significant plant problems.

  • Assures information on EPIP-6, Appendix P,.is sent to the CECC to be used in the predictive release rate model.

o If the need for post accident sampling is anticipated, alert TSC Chemistry Manager so that they can prepare RWP and support.

o Assures Post Accident sampling in accordance with 1,(2)-TI-CEM-043-066.0 is initiated as required.

"* Provides for trending of significant parameters.

"* Designates personnel to maintain Plant Status and Trending Boards.

- Provide input to the SED for emergency classification.

ACTIVATION AND OPERATION OF THE EPIP - 6 SQN TECHNICAL SUPPORT CENTER Rev. 34 Page 18 of 51 APPENDIX E Page 1 of 1 OPERATIONS ADVISOR, TAT INITIAL ACTIVATION OF THE TECHNICAL SUPPORT CENTER INT/TIME

1.

Fill out the Organizational/Staffing Chart.

2.

Log on to ICS.

3.

Establish contact with the Control Room. (Dial x1 01)

4.

Check the status of emergency actions already in effect such as Accountability or Site Evacuation.

OPERATIONAL RESPONSIBILITIES

"* Operates ICS to obtain plant status and parameters.

"* Monitors procedure direction taken by the main control room operators and keeps TATL informed of potential future problems and status of safety related "equipment.

" Provides information from the Control Room to the Technical Assessment Manager and Technical Assessment Team.

" Completes portions of plant parameters data sheets (Appendix 0 and Appendix P) as needed.

"* Plots/trends as designated by TAM.

"* Obtains supplemental data as needed by the TSC, OSC, or CECC.

SACTIVATION AND OPERATION OF THE EPIP - 6 SQN TECHNICAL SUPPORT CENTER Rev. 34 Page 19 of 51 APPENDIX F Page 1 of 1 SITE SECURITY MANAGER INITIAL ACTIVATION OF THE TECHNICAL SUPPORT CENTER INT/TIME

1.

Fill out the Organizational/Staffing Chart.

2.

Establish log of communications/events.

3.

Establish contact with the CAS and the SAS.

4.

Check the status of emergency actions already in effect such as Accountability or Site Evacuation and report status to the SED.

OPERATIONAL RESPONSIBILITIES

  • Directs activities of Site Security personnel.

& Controls access to Site and control room.

  • Reports on site accountability/evacuation as defined in EPIPs.
  • Assures an officer is dispatched to areas outside the protected area such as the STC, Old Visitor Center, Livewell, and Design Services Complex during accountability / evacuation.
  • Advises incoming emergency response personnel at the gate house of any radiological hazards in route to the TSC or OSC.

& Assists in establishing search teams, as required.

e Provides status updates to Site Security personnel.

ACTIVATION AND OPERATION OF THE EPIP - 6 SQN TECHNICAL SUPPORT CENTER Rev. 34 Page 20 of 51 APPENDIX G Page 1 of 1 RADCON Manaaer INITIAL ACTIVATION OF THE TECHNICAL SUPPORT CENTER INT/TIME

1.

Fill out the Organizational/Staffing Chart.

2.

Establish log of communications/events.

3.

Establish contact with the OSC RADCON Supervisor (Bridge x1 03),

the radiological monitoring van (if dispatched), and the CECC Radiological Assessment Coordinator (RAC) or Radiological Assessment Manager if the RAC is not available.

4.

Log on to ICS.

5.

Check the status of emergency actions already in effect such as Accountability or Site Evacuation.

OPERATIONAL RESPONSIBILITIES 9 Remains cognizant of assessments of inplant and onsite radiological conditions from the "OSC RADCON Manager.

e Keeps the CECC Radiological Assessment Coordinator informed of site radiological conditions.

  • Coordinates supplemental RADCON support with the CECC Radiological Assessment Coordinator e Makes recommendations for protective actions for onsite personnel to the SED.
  • Authorizes issue of KI to onsite personnel, after informing SED.
  • Coordinates assessment of radiological conditions offsite with CECC Radiological Assessment Coordinator.
  • Maintains status maps of offsite radiological conditions and inplant radiation status board.
  • Provides RADCON surveillance through the OSC for off-site personnel assigned to the SQN Training Center, MET station, Communication Node Building, etc. if required by environmental releases. Ensure these off-site personnel are tracked through the Maintenance Manager on the Team Tracking Board.

Assures the RADCON Laboratory Supervisor has designated a qualified/

knowledgeable person to provide inplant radiological data to the NRC HP Network (HPN) upon request.

  • Provides periodic status reports to the SED on radiological conditions and input on the emergency classification and PARs.

I ACTIVATION AND OPERATION OF THE EPIP - 6 SQN TECHNICAL SUPPORT CENTER Rev. 34 SQPage 21 of 51 APPENDIX H Page 1 of I CHEMISTRY MANAGER INTITIME 1.

Fill out the Organizational/Staffing Chart.

2.

Establish log of communications/events.

3.

Establish contact with the Chemistry Supervisor in the lab and the CECC Radiological Assessment Coordinator.

Obtain assessment of any radiological release in progress and provide to the SED.

4.

Log on to ICS.

5.

Check the status of emergency actions already in effect such as Accountability or Site Evacuation.

OPERATIONAL RESPONSIBILITIES

"* Directs the Chem. Lab Supervisor to implement the applicable portions of EPIP-14 and EPIP-13 to initiate onsite/off-site dose assessment if needed prior to the CECC being staffed.

"* Coordinates the assessment of radioactive effluents with the CECC Radiological Assessment Coordinator.

"* Remains cognizant of Chemistry lab Post Accident Sampling Activities.

"* Determines the impact of the incident on radwaste and various effluent treatment systems.

"* Performs release rate calculations and dose projections in accordance with EPIP-13 when required.

"* Completes portions of plant parameter data sheets (Appendix 0 and P) as needed.

"* Provides all plant chemistry data to the Technical Assessment Team.

"* Completes Predictive Release Data sheet (Appendix P) and transmits it to the CECC PAT.

"* Provide input to the SED for emergency classification and PARs.

ACTIVATION AND OPERATION OF THE EPIP - 6 SQN TECHNICAL SUPPORT CENTER Rev. 34 Page 22 of 51 APPENDIX I Page 1 of 2 NRC COORDINATOR INITIAL ACTIVATION OF THE TECHNICAL SUPPORT CENTER INT/TIME

1.

Fill out the Organizational/Staffing Chart.

2.

Establish log of communications/events.

3.

Check the status of emergency actions already in effect such as Accountability or Site Evacuation.

4.

Contact the Operations Manager to determine if the ENS line requires continuous communications.

OPERATIONAL RESPONSIBILITIES Acts as primary liaison with onsite NRC personnel.

0 Updates NRC personnel on plant status.

0 Provides information requests from NRC to TSC personnel.

"* Maintain contact with the NRC on ENS line, if requested and coordinate the transfer of responsibility for ENS continuous communications with the MCR..

"* Obtain copy of Appendix Q from the TATL and report data to NRC in the event ERDS fails.

If necessary establish NRC communication at 9-1-301-816-5100 (see below).

If requested to maintain contact with the NRC, coordinate the turnover of responsibilities with the MCR. It is recommended that the NRCC use the cordless phone and get on the NRC bridge by dialing 9-1-301-816-5100. The NRCC should listen long enough to determine the status of questions and when ready, instruct the existing MCR ENS communicator that you are assuming responsibility and identify yourself as the TSC NRCC. The next page provides information on expected questions and sources of information.

I ACTIVATION AND OPERATION OF THE EPIP - 6 SQN TECHNICAL SUPPORT CENTER Rev. 34 Page 23 of 51 APPENDIX I Page 2 of 2 Typical questions and sources of information:

1. Classification change and reason - This information is available thru SED briefings.
2. Ongoinglimminent damage to the facility, including affected equipment and safety features - This information should be available thru SED briefings and by discussions at the SED table.
3. Toxic or radiological release current or projected, both onsite and offsite and what is the basis - This information should be provided by the Chemistry Manager.
4. What are the health effects onsite and offsite and how many people are affected Same as item 3 only the RadCon Mgr will provide the input.
5. What is being done to bring the event under control - this information should be available thru the SED briefings and the OSC tracking board (NRCC will probably need to know why we are doing these items).
6. Onsite protective measures - Available by SED briefing.
7. Offsite protective measures - Available by SED briefing.
8. Status of Statellocal/Federal agencies if known - This information should be provided by the Site VP through CECC..
9. Status of public information activities such as alarms, broadcast press releases and status of JIC - same as 8.

ACTIVATION AND OPERATION OF THE EPIP - 6 SQN TECHNICAL SUPPORT CENTER Rev. 34 Page 24 of 51 "APPENDIX J Page 1 of 1 CONTROL ROOM COMMUNICATOR INITIAL ACTIVATION OF THE TECHNICAL SUPPORT CENTER INT/TIME

1.

Fill out the Organizational/Staffing Chart.

_ 2.

Pick up headset report to the Control Room (phone is already in MCR).

3.

Establish log of communications/events.

4.

Establish contact with the TSC Operations Communicator and OSC Operations Advisor. (Dial x101).

5.

Check the status of emergency actions already in effect such as Accountability or Site Evacuation.

6.

Locate all Operations personnel/teams currently or previously tasked and ensure each is tracked on the OSC Ops. Team board.

OPERATIONAL RESPONSIBILITIES

"* Serves as the control room - TSC and OSC communications link.

"* Provides operational knowledge for status evaluation of plant systems.

"* Provides advice regarding Technical Specifications, system response, safety limits, etc.

"* Assists in development of recommended solutions to developing problems.

"* May use ICS to trend parameters.

"* Assures the control room staff is aware of the TSC accident assessments and OSC activities Ensures the OSC Ops. Advisor and TSC Ops. Communicator are informed of the status of all Ops. personnel/teams dispatched by the SM.

"* Communicate operational status of plant systems and major equipment, automatic and manual initiation of ESF equipment, important system parameters associated with EALs, and procedure transitions by the MCR.

Communicate messages between the Shift Manager and the TSC.

I ACTIVATION AND OPERATION OF THE EPIP - 6 SQN TECHNICAL SUPPORT CENTER Rev. 34 Page 25 of 51 APPENDIX K Page 1 of 1 EP MANAGER INITIAL ACTIVATION OF THE TECHNICAL SUPPORT CENTER INT/TIME

1.

Fill out the Organizational/Staffing Chart.

2.

Establish log of communications/events.

3.

Check the status of emergency actions already in effect such as Accountability or Site Evacuation.

4.

Verifies checklists are distributed and are being completed.

5.

Verifies all essential positions are filled.

6.

Verifies all activation activities (TSC and OSC) are proceeding normally.

7.

Call in Clerical Support and other personnel as necessary.

OPERATIONAL RESPONSIBILITIES

  • Advises the SED regarding overall REP, use of EPIPs, emergency equipment availability, and coordination with the CECC.
  • Confirms TSC and OSC are operating properly.
  • Provides assistance to the SED and OSC Manager as requested.
  • Makes P/A announcements to update plant personnel of emergency status.
  • Ensures Clerks prepare for Shift Turnover using Appendices BB and CC.
  • Tracks entry into EAL's and PAR's.

DEACTIVATION RESPONSIBILITIES

  • Collect all logs and information from all TSC and OSC staff.
  • Return the TSC and OSC to "stand by" condition.

ACTIVATION AND OPERATION OF THE EPIP - 6 SQN TECHNICAL SUPPORT CENTER Rev. 34 Page 26 of 51 APPENDIX L Page 1 of 1 TSC CLERICAL/LOGKEEPER STAFF INITIAL ACTIVATION OF THE TECHNICAL SUPPORT CENTER INT/TIME

1.

Fill out the Organizational/Staffing Chart.

2.

Establish a log of activities.

3.

Notify the EP Manager of arrival (if called in by phone to support otherwise N/A).

OPERATIONAL RESPONSIBILITIES

"* Assists in setup and activation of the TSC.

"* Maintains accountability of TSC personnel.

"* Answers telephones.

"* Distributes plant parameter data sheets.

"" Uses REP Call List to obtain staff for unfilled positions or replacement staff for shift turnover.

"* Operates fax machines. (Note; deactivate memory fax if so equipped, light must be off)

Provides faxes of AUO status from the OSC to the Operations Manager and TAT Leader.

"* Operates the TSC classification clock.

"* Logkeeper maintains a chronological log of the SED and TSC activities to include classification changes, PARs, changes in plant conditions, briefings, team status, content of discussions, and decisions made by the SED.

"* Logkeeper assists the SED in preparing briefing notes.

" Obtain TSC checklist if requested:

11 SED El Ops Mgr E RADCON Mgr El Site VP El Chemistry Mgr El TATL

[I Ops Communicator El TAT Ops Advisor El EP Mgr El TAM El Maint Mgr El NRCC El Security El Control Room Communicator (on deactivation)

DEACTIVATION OF THE TECHNICAL SUPPORT CENTER

  • Transfers all logs, notes, and other materials to the EP Planning Manager for documentation and storage.

a Deactivates the TSC by returning all equipment, reference materials and supplies to the TSC storage cabinets.

ACTIVATION AND OPERATION OF THE EPIP - 6 SQN TECHNICAL SUPPORT CENTER Rev. 34 Page 27 of 51 APPENDIX M Page 1 of 1 MAINTENANCE MANAGER INITIAL ACTIVATION OF THE TECHNICAL SUPPORT CENTER INT/TIME

1.

Fill out the Organizational/Staffing Chart.

2.

Establish log of communications/events.

3.

Establish contact with the Assistant OSC Manager or Maintenance Shift Supervisor in the OSC.

(Bridge X1 04).

4.

Check the status of emergency actions already in effect such as Accountability or Site Evacuation.

5.

Check status of deployed emergency response teams.

OPERATIONAL RESPONSIBILITIES

"* Makes task assignments tasks to the OSC.

"* Maintains cognizance of deployed OSC emergency response teams purpose and status.

"* Assists the SED and the OSC Manager in determining the relative priorities of activities.

"* Monitors the emergency response team tracking.

ACTIVATION AND OPERATION OF THE EPIP - 6 SQN TECHNICAL SUPPORT CENTER Rev. 34 Page 28 of 51 APPENDIX N Page 1 of 2 TECHNICAL ASSESSMENT TEAM INITIAL ACTIVATION OF THE TECHNICAL SUPPORT CENTER INT/TIME

1.

Fill out the Organizational/Staffing Chart.

2.

Establish log of communications/events.

3.

Establish contact with the Technical Assessment Manager.

4.

Establish contact with the CECC Plant Assessment Team (751-1629).

5.

Check the status of emergency actions already in effect such as Accountability or Site Evacuation.

OPERATIONAL RESPONSIBILITIES

"* Prepares and provides current assessment on plant conditions and provides this information to the CECC Plant Assessment Team.

"" Project future status based on present plant conditions.

"* Provide technical support to plant operations on mitigating actions.

"* Monitor containment sump level per Appendix S.

"* Provides direction for environmental qualification operating concerns for containment cooling following a non-LOCA event inside containment (i.e., loss of secondary side coolant) per Appendix T.

"* Determines the condition of the reactor and nuclear fuel.

"* Prepares TSC accident assessment sheet Appendix Q and transmits to the CECC when requested.

"* Performs trending of key plant parameters against EAL criteria and provides technical assessment.

"* Provides Technical Assessment to TAM on Appendix Q when requested.

"* Team leader may designate a TSC log keeper and board writer.

ACTIVATION AND OPERATION OF THE EPIP - 6 SQN TECHNICAL SUPPORT CENTER Rev. 34 Page 29 of 51 APPENDIX N Page 2 of 2

" Verifies that all ABSCE doors are closed (call Fire Ops at 7447 or OSC Fire Ops Advisor at 6407).

" Identifies and tracks the status of current ABSCE breaches (call Fire Ops at 7447 or OSC Fire Ops Advisor at 6407).

"* Verifies that all Control Room Emergency Ventilation Pressure Boundary (CREVS) doors are closed (call Fire Ops at 7447 or OSC Fire Ops Advisor at 6407).

" Identifies and tracks the status of current CREVS breaches (call Fire Ops at 7447 or OSC Fire Ops Advisor at 6407).

" If all control building battery room exhaust fans are off, then refer to Appendix V.

" Monitor the temperature of the 6.9kv shutdown board rooms in accordance with Appendix V.

" Refer to Appendix W, for contingency plan for control and processing of large volumes of contaminated water in the plant secondary side.

  • Interface with Nuclear Engineering onsite and in the CECC (751-1634) for specific technical assistance and support as needed.

& In the event of a high energy line break (HELB) in the Auxiliary Building, evaluate the need to restore the environmental condition of-the Auxiliary Building back to a normal condition within 6 to 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. If environmental conditions are adverse, make recommendations to the Technical Assessment Manager to mitigate the condition.

  • Auxiliary Air Dryers should be turned on within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> after an accident and, if one or more trains of dryers are inoperable and the outside ambient air temperature is at or below freezing, then monitor the rooms listed below for freezing temperatures at least once every 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. If necessary, actions such as turning off ventilation fans and instituting freeze protection shall be taken until both trains are operable.

(DCN D20393A)

"* 480V Transformer Rooms (Rooms 749-A6, -A7, Al 0, and -Al1)

"* Mechanical Equipment Rooms (Rooms 763-A3, and -A4)

  • In the event of a radiological, chemical, or smoke release that may impact the air intake at the north or south end of the Control Building, evaluate stopping the Control Bldg Emergency Pressurization Fan from the affected intake. (Note: Train A takes suction from north end and Train B takes suction from the south end.

Reference:

FSAR 11.4.2.2.5 and 47W866-4).

ACTIVATION AND UOPEA I Iu I UOF I HE.

TECHNICAL SUPPORT CENTER SQN

-Mi c Rev. 34 Page 30 of 51 APPENDIX 0 Page 1 of 5 PLANT PARAMETER DATA SHEETS DATE:

TIME:

UNIT:

1.
2.
3.

4.

GENERAL INFORMATION CST LEVEL:

(LI-2-230A).

GAL (LI-2-233A)

GAL SG HEAT SINK:

CONDENSER ATMOSPHERE AFW PUMPS RUNNING: MD-A MD-B TD_

SG LEVELS: NR: (1)

(2)

(3)

(4)

(LI-3-39)

(LI-3-52)

(LI-3-94)

(LI-3-107)

WR: (1)

(2)

(3)

(4)

(LR-3-43)

(LR-3-98)

5.

SG PRESSURES: (1)

(2)

(3)

(4)

PSIG (PI-1-2A)

(PI-1-9A)

(PI-1-20A)

(PI-1-27A)

6.

RVLIS: (LOWER RANGE)

(WIDE RANGE)

(PLENUM)

(LI-68-367)

(LI-68-368)

(LI-68-369)

(LI-68-370)

(LI-68-371)

(LI-68-372)

7.

PZR LEVEL: (LI-68-335)

(LI-68-320)

8.

PZR PRESSURE: (PI-68-342A).

(PI-68-340A)

PSIG

9.

RCS PRESSURE: WR: (LOOP I HOT LEG)

(PI-68-69)

PSIG

10. RCS HL TEMP: WR: (1)

(2)

(3)

(4)

OF (TR-68-1)

(TR-68-24)

(TR-68-43)

(TR-68-65)

11.

RCS CL TEMP: WR: (1)

(2)

(3)

(4)

OF (TR-68-1)

(TR-68-24)

(TR-68-43)

(TR-68-65)

12.

RCS FLOW: RUNNING RCPs NATURAL CIRCULATION

13.

ECCS STATUS: STANDBY INJECT RECIRC SPRAY

14.

RWST LEVEL: (LI-63-50)

(LI-63-51)

15.

CONTAINMENT SUMP LEVEL: WR: (LI-63-176)

16.

CHARGING SI FLOW RATE: (FI-62-93).

(FI-63-170)

GPM "17. CONTAINMENT PRESSURE: NR: (PI-30-44)

(PI-30-45)

PSID

ACTIVA1 IUN ANU Ul*VlA I ulI %jr I nHE TECHNICAL SUPPORT CENTER SQN

=DI

-n A*

I Rev. 34 Page 31 of 51 APPENDIX 0 Page 2 of 5 PLANT PARAMETER DATA SHEETS DATE:

TIME:

UNIT:

GENERAL INFORMATION (Continued)

18.

INCORE THERMOCOUPLES:

(Exo-Sensor)

19.

NIS SOURCE RANGE:

QUAD 1 - (1 of #41,28,24,56,55,29,6)

°F QUAD 2 - (1 of #44,22,58,21,16,63,64)

OF QUAD 3 - (1 of #54,12,8,40,4,3,7)

OF QUAD 4 - (1 of #60,9,45,6,46,42,36)

OF (N31)

(N32)

CPS DATA BY:

ACTIV SQN TE



Fr "rR*

I ATION AND UPIRA I Iu0 ur I HE CHNICAL SUPPORT CENTER Rev. 34 Page 32 of 51 APPENDIX 0 APPENDIX 0 Page 3 of 5 PLANT PARAMETER DATA SHEETS DATE:

TIME:

UNIT:

RADIATION MONITORS

1.

LOWER CONTAINMENT (RM-90-106)

ISOLATED BLOCKED 0-M-12

2.

UPPER CONTAINMENT (RM-90-112)

ISOL BLOCKED TO LOWER.

0-M-12

3.

SHIELD BLDG VENT (RM-90-400) M-30

4.

AUXILIARY BLDG VENT (RM-90-101)

ISOLATED BLOCKED 0-M-12 (A) PARTICULATE CPM (B) TOTAL GAS CPM (A) PARTICULATE _CPM (B) TOTAL GAS CPM Eff. Level p.Ci/sec (A) PARTICULATE CPM (B) TOTAL GAS CPM

5.

SG BLOWDOWN:

(RM-90-120A)

(RM-90-121A)

CPM 0-M-12 0-M-12

6.

CONDENSER EXHAUST:(LR) or (LR)

CPM RM-90-99 RM-90-119 0-M-12 0-M-12

7.

ERCW DISCHARGE:

HEADER A:

RM-90-133A RM-90-140A 0-M-12 0-M-12 CPM HEADER B:

CPM RM-90-134A RM-90-141A 0-M-12 0-M-12 DATA BY:

I I

ACTIVATION AND OPERATION OF THE EPIP -6 SQN TECHNICAL SUPPORT CENTER Rev. 34 Page 33 of 51 "APPENDIX 0 Page 4 of 5 PLANT PARAMETER DATA SHEETS DATE:

TIME:

UNIT:

POST ACCIDENT AND AREA RADIATION MONITORS

1.

UPPER CONTAINMENT:

(TOP OF #2 & #3 SG)

RM-90-271:

R/HR (TOP OF #1 & #4 SG)

RM-90-272:

R/HR

2.

LOWER CONTAINMENT:

(BETWEEN #2 & #3 SG)

RM-90-273:

R/HR (BETWEEN #1 & #4 SG)

RM-90-274:

R/HR

3.

SHIELD BLDG VENT (LR/RM-90-260) Ul U2 MR/HR (HR/RM-90-261) Ul U2 MR/HR (FLOW/FE-90-400) Ul U2 CFM

4.

RCDT PUMP DISCH: (RM-90-277)

(RM-90-278)

MR/HR

5.

RX FLOOR/EQ SUMP DISCHARGE HEADER: (RM-90-275)

(RM-90-276)

MR/HR

6.

RHR PUMP A-A: (LR/RM-90-290)

(HR/RM-90-291)

MR/HR ROOMS: B-B:

(LR/RM-90-292)

(HR/RM-90-293)

MR/HR

7.

COND VAC EXHAUST: (MR/RM-90-255)

(HR/RM-90-256)

MR/HR

8.

AREA MONITORS: (RM-90-59)

MR/HR (RM-90-60)

MR/HR (RM-90-61)

MR/HR

9.

ERCW DISCH A: (RM-90-133A)

(RM-90-140A)

CPM HEADERS:

B: (RM-90-134A)

(RM-90-141A)

CPM

10.

MN STM LINES:(RM-90-421)

(RM-90-422)

ýtCi/cc (RM-90-423)

(RM-90-424)

VtCi/cc DATA BY:

ACTIVATION AND OPERATION OF THE SQN TECHNICAL SUPPORT CENTER I

EPIP

-6 EPIP - 6 Rev. 34 Page 34 of 51 DATE:

TIME:

UNIT:

APPENDIX 0 Page 5 of 5 PLANT PARAMETER DATA SHEETS RADIOLOGICAL RELEASE DATA

1.

RELEASE POINT:

2.

RELEASE RATES: 13DECREASING USTABLE L3INCREASING QUNKNOWN AIRBORNE LIQUID RELEASE_______

I ISO-CONCENTRATION FLOW RATE TOTAL RELEASE GROSS RELEASES FLCi/SEC I TOPE VALUE UNITS VALUE UNITS VALUE UNITS NOBLE GAS IODINES PARTICULATE ISOTOPE RELEASE RATE

3.

RELEASE BEGAN EXPECTED TO END EST/EDT. DURATION HR RELEASE POTENTIAL:

Ci, IN VOLUME OF (CU FT OR GAL)

4.

METEOROLOGICAL CONDITIONS: (IF REQUESTED DUE TO MET DATA LINK INOPERABLE)

DATE TEMPERATURE DIFFERENTIAL TIME WINDSPEED (METER/S)

FROM (DEGREES)

ELEVATION (METERS)

5.

REMARKS/COMMENTS:

DATA COLLECTED BY:

II

APPENDIX P Page 1 of 1 PREDICTIVE RELEASE DATA SHEET TO: CECC PAT DATE:

TIME:

UNIT:

DATA NEEDED FOR CECC TO PERFORM PREDICTIVE RELEASE METHODOLOGY 1

PRIMARY COOLANT CONCENTRATION IN GAS IN LIQ ISOTOPE PCi/cc PCi/ml 1-131 1-132 1-133 1-134 1-135 CS-1 37 CS-1 38 KR-85m KR-85 KR-87 KR-88 XE-133 XE-1 35 SAMPLE DATA DATE:

TIME LOCATION:

TEMPERATURE:

DEG F PRESSURE PSIA GAS VOLUME:

CC WATER MASS:

GRAMS WATER LEVEL:

2.

CONCENTRATION OF HYDROGEN IN CONTAINMENT ATMOSPHERE H CONC (MOLE %):

DATE:

CNTMT TEMP:

DEGREES F TIME:

CNTMT PRESS PSID LOCATION:

3.

OPERATING POWER HISTORY (IF ICS DATA LINK INOPERABLE)

DATE/TIME OF SHUTDOWN:

END AVG POWER PERIOD IN MWt START END AVG POWER PERIOD PERIOD IN MWt

4.

EXO-SENSOR CORE EXIT THERMOCOUPLE READINGS (IF ICS DATA LINK INOPERABLE)

THERMOCOUPLE DATE TIME READING NOTES:

NUMBER (F)

5.

Rx WATER LEVEL HISTORY (IF ICS DATA LINK INOP)

  • See TI-28, Appendix B, Page 5 TIME RVLIS %

RCS COOLANT RCS GALS.*

RCS VOL.

ELEVATION (FT)

BY VOL.

BY CUFT.

START PERIOD

APPENDIX Q To: Technical Assessment Manager (cc: CECC PAT & NRC Coordinator)

From: SQN Technical Assessment Team (To be filled out when ICS is not operable or as requested)

1. HEAT REMOVAL CAPABILITY (FR-H and FR-C; S/G Level, RCP Flow, ECCS Flow, Subcooling RCS):
2. FUEL INTEGRITY: (Rad Monitors, Core Exit T/Cs, RCS Chemistry, RVLIS, H2 Concentration):
3. RADIOACTIVITY IN CONTAINMENT: (Rad Monitors, Rad Surveys, Fuel Integrity):
4. CONTAINMENT INTEGRITY: (FR-Z; CNTMT Pressure, CNTMT Breeches, Releases Outside CNTMT):
5. SUBCRITICALITY: (FR-S; Rods all inserted, NIS SR + IR Decreasing):
6. RCS INVENTORY: (FR-1; PZR Level, RVLIS, RCS Subcooling, Core Exit T/Cs):
7. OVERALL ASSESSMENT:
8. RECOMMENDATIONS:

Time:

Date:

TAT Leader:

ACTIVATION AND OPERATION OF THE SQN TECHNICAL SUPPORT CENTER EPIP -6 EPIP - 6 Rev. 34 Page 37 of 51 APPENDIX R Page 1 of 1 PROTECTIVE ACTION RECOMMENDATION LOGIC DIAGRAM G en eral Em erg en Declared CONTIP

  • Modify p on availal "I"monitorir
  • Locate an hot spots.

or beyond 5 miles is the Projected NO or Measured Dose Greater than PAG Table 1 Limits YES II

  • UE ASSESSMENT rotective actions based ble plant and field ig information.

id evaluate localized F

A A

Table 1 Radioactivity Release Dose Note: Unknown conditions are assumed less than listed conditions TYPE I

Protective Action Guide (PAG) Limits 3.9E-6 microCurie/cc loaine -13 1 1 Rem/hr External Dose 1 Rem TEDE 5 Rem Thyroid CDE Measured Projected RECOMMENDATION 1 EVACUATE 2 miles radius and 10 miles downwind AND SHELTER remainder of 10 mile EPZ RECOMMENDATION 2 EVACUATE 2 mile radius and 5 miles downwind AND SHELTER remainder of 10 mile EPZ I

I I

Ap

ACTIVATION ANU UrM'M-I 'lu mr IJIL-I 34 TECHNICAL SUPPORT CENTER Page 38 of 51 APPENDIX S Page 1 of I CONTAINMENT SUMP OPERATION AND LEVEL GUIDANCE

1. The 11 percent containment level set point for switch over was specified to prevent an inappropriate automatic switch over to the containment sump for steam line breaks in the yard that could damage the RWST.

Switch over, as required for a LOCA, is based on change in RWST level (i.e., volume of water injected). Based upon RWST Technical Specification limits and switch over setpoints, the actual sump level will be at least 63.5 percent (el. 693) at the time of switch over.

2.

During the injection phase following a LOCA, the only function of the containment sump level instrumentation is to provide a permissive input for the switch over.

3.

Until the inflow into the containment sump and the leakage out of it through the crane wall reaches equilibrium, the actual transient sump level could approach 90 percent. When instrumentation errors are considered, the sump level indication could go high off scale for a short period of time.

4.

Actual equilibrium level in the containment sump is expected to be 63.5 percent (i.e., crane wall penetrations are sealed up to 63.5 percent, and more than enough water will be injected to reach this level; surplus water will flow into the area outside the crane wall). However, due to instrument inaccuracies, the indicated level could vary between 50 percent and 78 percent.

5.

After the sump has reached equilibrium and temperature effects on instrumentation have stabilized, the indicated sump level should remain constant. Because the sump volume is large and will tend to mask small leaks, any significant trend showing an increase or decrease in level, however slow, should be investigated.

6.

The containment sump is subject to vortexing, which could damage the pumps if the sump is operated at too low level. As long as the indicated level stays above 37 percent, the sump will operate as designed with full ECCS flow.

7.

The limiting set point for sump operation at full flow (37 percent level) is based upon vortex prevention requirements.

8.

If recirculation from the sump is required with a low sump level (less than 37 percent) following a large break LOCA, then the operator should be aware that vortex-free sump operation is no longer assured. If operation under these conditions is required, the probability of effective ECCS operation will improve if flow from the sump is reduced. Also, other system indicators (e.g., pump amps, pressure, and flow) should be monitored for signs of vortexing.

9.

For near normal conditions (i.e., containment spray is no longer required and total flow from the sump is less than 11,000 gal/min, the instrument inaccuracies are less than +/- 8 percent and a minimum indicated level of 18 percent will ensure vortex free sump operation.

10 Utilize the "External Leakage Rates" notebook, in the affected unit Control Room, to anticipate areas of potentially high dose rates when sump recirculation is initiated.

APPENDIX T Page 1 of 3 ERCW CONCERNS FOR TECHNICAL ASSESSMENT TEAM 1

Provide direction for environmental qualification operating concerns for containment cooling following a non-LOCA event (e.g. loss of secondary coolant) inside containment. Items which should be addressed are listed below:

a.

Cooldown the RCS to less than 350°F within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and continue as conditions allow.

b.

In case of failure of the normal RHR suction valve FCV-74-1 to open, continue cooldown using the steam generators.

CAUTION: Prior to initiating ERCW flow to the LCC coils, the potential for water hammer must be considered. Parameters to consider are containment temperature which can cause boiling in the coils, available system pressure to prevent boiling, and maintenance of system inventory after initiating ERCW flow.

c.

Within one to four hours after event initiation, place at least two lower containment coolers in service. Ensure ERCW is aligned before placing coolers in service. This action will require entry into the annulus to manually open the ERCW valve if one train of power is lost. Preferably, all lower containment coolers should be placed in service.

(1) If A-train power is lost, A-train valves FCV-67-104, FCV-67-112, FCV-67-83 and FCV-67-91, located in the annulus (approx. el. 690) will have to be manually operated in order to place the B-train ERCW header to the B-train lower compartment coolers in service. See Appendix T, page 3, for the specific location of these valves.

(2) If B-train power is lost, B-train valves FCV-67-88, and FCV-67-96, FCV-67-99 and FCV-67-107, located in the annulus (approx. el. 690) will have to be manually operated in order to place the A-train ERCW header to the A-train lower compartment coolers in service. See Appendix T, page 3, for the specific location of these valves.

(3) The Temperature Control Valves (TCV's) for each Lower Compartment Cooler must be opened to obtain ERCW flow. The TCV's are operated from panel M-9 for Units 1 & 2 or can also be failed open from the Auxiliary Control Room via transfer switches.

d.

Evaluate containment heat loads. If a reactor coolant pump is running, then at least three lower containment coolers should be in service.

e.

ERCW gages are located in the 669 Penetration Room. Expect that each string of ERCW entering containment would require >400 gpm if all coolers in that string are receiving flow. Evaluate the ERCW flow to the lower compartment coolers and consider reducing flow to other equipment such as the containment spray heat exchangers if the required flow is not available. (The system flow balance assumes that containment spray flow will be removed if the lower compartment coolers are used.)

ACTIVATION AND OPERATION OF THE EPIP - 6 SQN TECHNICAL SUPPORT CENTER Rev. 34 Page 40 of 51 APPENDIX T Page 2 of 3 ERCW CONCERNS FOR TECHNICAL ASSESSMENT TEAM

f.

In case of failure of both the CVCS letdown and excess letdown flow paths, then evaluate use of the reactor vessel head vent system or pressurizer PORV.

2.

Monitor ERCW screens and strainers. Within 3 hours3.472222e-5 days <br />8.333333e-4 hours <br />4.960317e-6 weeks <br />1.1415e-6 months <br /> after an operating [C.2]

basis earthquake (1/2 SSE), a loss of downstream dam, a stage I flood, a tornado warning or within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> following a LOCA, then perform the following actions

a.

Isolate chlorination to ERCW.

b.

Inspect ERCW traveling screens and place screens into continuous backwash.

c.

Inspect ERCW strainers differential pressure and place into continuous backwash.

3.

For events other than those listed in previous step, then maintain the normal monitoring and cleaning frequency of the ERCW screens and strainers per O-SO-67-3.

Appendix T Page 3 of 3 ANNULUS ENTRANCE EL 690'67-107 (9 Train) 67-88 (B Train)67-112 (ATrain) 6"-83 (A Train)

R 67-83 (A Train) 67-1 T(ATrain) 6 7-8 8BTran 67-107 JB Trm)n ANNULUS K* ENTRANCE EL. 690' I

APPENDIX U Page 1 of 2 SED TURNOVER DATASHEET

1.

Current Emergency Classification:

[3UE

[3ALERT

[3SAE

[3GE EAL(s)

Time Declared Time ODS Notified State Notified Time NRC Notified

2.

Event

Description:

3.

Equipment Problems:

4.

Rad Release: I1 Yes U No Onsite Dose Assessment Initiated: [3 Yes [3 No

"[3 Filtered U3 Unfiltered "I3 Monitored U3 Unmonitored 1U Controlled U1 Uncontrolled Projected Duration (Hours/Minutes)

Wind Speed mi/hr Wind Direction From Degrees Projected TEDE mrem @

miles Projected Thyroid CDE mrem @

miles

5.

Protective Action Recommendations to Offsite Officials (General Emergency Only)

U3 None U31 U2 U3 U34

ACTIVATION AND OPERATION OF THE TECHNICAL SUPPORT CENTER SQN

EPIP -6 EPIP - 6 Rev. 34 Page 43 of 51 APPENDIX U APPENDIX U Page 2 of 2

6.

Onsite Protective Actions Taken:

Field Monitoring Vans Activated: U3 Yes U3 No Emergency Facilities Activated: U3 TSC U OSC U3 CECC Personnel/Actions Dispatched by the SM:

10.

Ensure minimum staffing of the TSC has completed (see App B Step #8)

11.

Review this turnover Appendix with SM for any changes.

12.

Ensure Appendix B complete through step 8.

13.

SED Responsibility Transferred:

From SED Time Date_

To SED

7.
8.

9.

ACTIVA I IUN/

-l r-riml-1 mJ',,

STECHNICAL SUPPORT CENTER Rev. 34 IPage 44 of 51 APPENDIX V Page 1 of 1 CONTROL BUILDING BATTERY ROOM EXHAUST FAN FAILURE AND 6.9KV SHUTDOWN BOARD ROOMS TEMPERATURE MONITOR With all control building battery room exhaust fans off there is a potential for Hydrogen buildup in the battery rooms. Calculations (EEB 800723 901 and EEB 800723 902) show that it will take approximately 11 days to reach potentially explosive limits of hydrogen in the room. The TSC staff shall monitor the time frame that the battery room exhaust fans are off. The TSC staff shall determine how and when the fans are to be returned to service prior to the explosive limits being reached.

Monitor the temperature of the 6900V shutdown board rooms within the first hour and then every 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> in accordance with 0-PI-OPS-000-606.0 to ensure that the temperature remains below 800F. If the temperature of a Board Room exceeds 80 0F, actions must be taken (as determined by the TSC) to reduce the temperature below 80°F and the temperature of the affected Board Room(s) must be monitored at an increased frequency as determined by the TSC.

ACTIVATION AND OPERATION OF THE EPIP -6 SQN TECHNICAL SUPPORT CENTER Rev. 34 SPage 45 of 51 "APPENDIX W Page 1 of 1 CONTINGENCIES FOR CONTROL AND PROCESSING LARGE VOLUMES OF SECONDARY SIDE CONTAMINATED WATER The method of processing large amounts of contaminated water in the secondary side of the plant due to a steam generator tube rupture will be determined by the Chemistry Lab, based on condensate samples for activity.

The preferred method is to process the water through the condensate D.I. Waste Regeneration System to the High Crud Tanks (HCT). The water can then be released to the release header using O-SI-CEM-077-400.1 or 0-SI-CEM-077-400.2.

Reference flow diagrams 1,2-47W838-1 and 4.

If the contamination levels of the condensate are almost within limits for release, consideration should be given to using one of the condensate D.I. beds to reduce the activity level to a point that release using method one is possible. This will depend on the age and condition of the resins. Contact the WWPG manager or Technical Support Engineer for guidance.

If the contamination levels are high enough to prevent release, consider processing the water through a Demineralizer System similar to the Rad Waste D.I. being supplied by Chem Nuclear, under agreement contract #93N7B-79294A-000.

Two methods of D.I. operation are discussed here. The first being the best method.

METHOD 1 (PREFERRED)

Process the water through the condensate D.I. Waste Regeneration System. This will provide a flow path from the condensate system through a vendor supplied demineralizer system back to the unit hotwell through an open manway (vacuum will have to be broken). This will allow recirculation of water from the condensate system of up to 200 gpm back to the hotwell until the activity levels are at a point that the water can be released to the HCT's, or after Chem Lab analysis indicates that it can be saved as condensate.

METHOD 2 (ALTERNATE)

Process water through a vendor supplied D.I. System to the HCT's and then release the HCT's to the release header, using 0-SI-CEM-077-400.1 or 0-SI-CEM-077 400.2, as clean D.I. water. As this water is being removed additional make-up water will be required to maintain inventory in the unit hotwell.

1 A#

I' I A

^-P!'r noID:

ATI(

IM nl: TWi:

EPIP - 6 1

TECHNICAL SUPPORT CENTER SQN Rev. 34 Page 46 of 51 I.

APPENDIX Y Page 1 of 1 This appendix has been intentionally deleted.

Telephone numbers are available in the Radiological Emergency Notification Directory (REND).

ACTIVATION AND OPERATION OF THE EPIP-6 SQN TECHNICAL SUPPORT CENTER Rev. 34 Page 47 of 51 APPENDIX Z Reference Materials List Page 1 of I The following reference materials are provided in the TSC:

1. Sequoyah Nuclear Plant FSAR.
2. Sequoyah Nuclear Plant Technical Specifications (Unit 1).
3. Sequoyah Nuclear Plant Technical Specifications (Unit 2).
4. Surveillance Instructions (Selected).1
5. Technical Instructions (Selected).1
6. Radiological Control Instructions.
7. Site Health and Safety Manual.
8. System Operating Instructions.
9. General Operating Instructions.
10. REP and SQN and CECC Emergency Plan Implementing Procedures
11. Plant Functional Drawings.
12. Abnormal Operating Procedures.
13. Emergency Operating Instructions.

I Selection to be made by Technical Support Manager.

APPENDIX AA OPERATIONS COMMUNICATOR Page 1 of 1 INITIAL ACTIVATION OF THE TECHNICAL SUPPORT CENTER INT/TIME

1. Fill out the Organization/Staffing Chart.
2. Obtain headset connect to the Control Room Operations Bridge(dial X 101).
3. Provide the completed checklist to the TSC log keeper.

OPERATIONAL RESPONSIBILITIES Monitors the Control Room Operations Bridge.

Provides information from the MCR and OSC to TSC personnel including information on AUO activities.

Monitors plant status boards and ICS.

Obtains supplemental data as needed by the TSC, OSC, or CECC.

Makes inquiries to the Control Room Communicator to obtain specific information as necessary.

Maintains a current log of major operational events for the Operations Manager's use.

APPENDIX BB TSC ROSTER r

I NOTIFIED NAME (Print)

SIGNAT URE SSN ERO POSITION REPLACEMENT ANDFFD YES NO I

+

I__

i I

i -

I I

I I

iI

_I__

1-1 I

4 1-t-

j.
  • 1.

4

  • I*

tT 4

I

  • I t-t-I I

_______________________ I I

t-T



1 4-I-I-

__I_

I I

I-I i

___I__I I

I

_I II I

I Ir I

4 1

.1.

11*

I ______________________

I t

I

.1 1 _______________

EP Records Coordinator:

Date of TSC Activation:

IJ I

I I

I_

i I

Appendix CC EMERGENCY RESPONDER NOTIFICATION FORM Fitness for Duty Person Calling Date Consumed Alcohol 5 Hrs.

Prior to Report YES NO Name

~.

~

~

~i~

PDIP - AI ATECIVA I SUN/ANU UPPOrT ICuEN rn TECHNICAL SUPPORT CENTER r-__

SQN I

I Rev. 34 Page 51 of 51 SOURCE NOTES REQUIREMENTS STATEMENT To address emergency classification by the Site Emergency Director SED) in the TSC.

Operation of ERCW screens/

strainers to be consistent with DNE USQD (RIMS-B25871008558).

IMPLEMENTING SOURCE DOCUMENT STATEMENT NRC Exercise Weakness 50/327, 328/86-64-08 NRC-IE-87-52-02 Weakness No. 1 NCO-870324038 NP Radiological Emergency Plan (NP-REP)

NUREG-0696 C.1 C.2

TENNESSEE VALLEY AUTHORITY SEQUOYAH NUCLEAR PLANT EMERGENCY PLAN IMPLEMENTING PROCEDURE EPIP-7 ACTIVATION AND OPERATION OF THE OPERATIONS SUPPORT CENTER (OSC)

Revision 20 QUALITY RELATED PREPARED/PROOFREAD BY:

Bill Peparam RESPONSIBLE ORGANIZATION:

Emergency Preparedness APPROVED BY Randy Ford EFFECTIVE DATE:

10/01/2001 LEVEL OF USE:

REFERENCE

I ACTIVATION AND OPERATION OF THE EPIP-7 I

SQN OPERATIONS SUPPORT CENTER Rev. 20 Paae 2 of 37

._VISION HISTORY:

19 04/26/2001 RadCon Supervisor in the OSC to reactivate the Emergency Response RWPs that are kept in a deactivated status as a corrective action of PER 01-000449-000. Conditions requiring Habitability surveys were clarified to allow professional discretion in determining when an air sample is necessary. OSC Clerical no longer faxes Maintenance Team status if ERN is functional as this is now available on the web page and now also sends AUO team status. Corrected Procedure Number for Radio Sensitivity Procedure. Changed the reference in Section 3.2.13 from EPIP-14 to EPIP-1 3. Revised App. 0 to match current REND. Corrected Title of App. B in Table of Contents.

Removed the "yes" or "no" from the RWP line in the RADCON Requirements section of the App.D, OSC Team Briefing/Debriefing Form.

20 10/01/2001 Corrected pagination references on Table of Contents. Corrected title of Materials Coordinator in Table of Contents. Removed Appendix Q - REND section references, removed reference to Section G of the REND from App H. Reworded announcement to dispatch team and added Emergency Tool Kit Numbers and Tools Needed items to Appendix D. Added Secunty to examples of outlying groups in App. E. Corrected erroneous Appendix E reference to "SITE AREA EMERGENCY declaration" Moved staffing verification to higher on Appendix E checklist. (PER 008641-000) Revised format of staffing checks in Appendix E to match Maintenance Briefers. Re-worded reminder to check teams radiological protection status after major changes in Appendix E. Added statements in Appendices A, H and M after major changes, OSC Manager, OSC Safety and Fire Ops Advisor to reassess the status of teams. Reformatted Appendix S to be like EPIP-6 Appendixes BB and CC.

Added note to Appendix J for Clerical staff to turn off memory fax mode before faxing.

TABLE OF CONTENTS Section Title Page T a ble of C o ntents............................................................................................

1.0 2.0 3.0 3.1 3.2 3.2.1 3.2.2 3.2.3 3.2.4 3.2.5 3.2.6 3.2.7 3.2.8 3.2.9 3.2.10 3.2.11 3.2.12 3.2.13 3.2.14 3.2.15 3.2.16 3.2.17 3.2.18 3.2.19 3.2.20 3.3 4.0 4.1 4.2 PURPOSE...................................................................................................

REFERENCES.................................................................................................

4 INSTRUCTIONS........................................................................................

4 An Alert or Higher Classification................................................................

4 Activation of OSC......................................................................................

4 Shift Manager Actions......................................................................................

4 Call List.....................................................................................................

5 Response...................................................................................................

5 Maintenance Shift Supervisor (MSS)..........................................................

6 OSC Operation

...................................... 6 OSC Manager.......................................................................................

Assistant OSC Manager..............................................................................

8 OSC RADCON Supervisor..........................................................................

8 OSC RADCON Briefer................................................................................

8 OSC Operations Advisor......................................................................

8 Personnel Pool Manager....................................................................

8 Fire Operations Advisor.............................................................................

9 Chemistry Shift Supervisor..........................................................................

9 OSC Log Keeper........................................

......................................... 9 OSC Clerk...................................................................................................

OSC Site Security Advisor.........................................................................

9 OSC Briefers..............................................................................................

9 OSC Industrial Safety Advisor..........................................................................

9 DCRM Coordinator.......................................................................................

10 I OSC Materials Coordinator..............................................................................

10 Deactivation...............................................................................................

10 RECORDS.................................................................................................

10 QA Records..............................................................................................

10 Non-QA Records.........................................................................................

10 APPENDICES Appendix A, OSC Manager Checklist..........................................................

11 Appendix B, OSC Manager Briefing Outline...............................................

12 Appendix C, Assistant OSC Manager Checklist.........................................

15 Appendix D, OSC Team Tracking/Briefing/Debriefing Forms..................... 17 Appendix E, OSC RADCON Supervisor Checklist...................................... 19 Appendix F, OSC RADCON Briefer Checklist.............................................

21 Appendix G, OSC Operations Advisor Checklist.........................................

23 Appendix H, Fire Operations Advisor Checklist.......................................... 23 Appendix I, OSC Log Keeper Checklist.....................................................

24 Appendix J, OSC Clerical Staff Checklist....................................................

25 Appendix K, OSC Site Security Advisor......................................................

26 Appendix L, OSC Briefer Checklist............................................................

27 Appendix M, OSC Industrial Safety Checklist..........................................

29 Appendix N, Personnel Pool Manager Checklist.........................................

30 Appendix 0, DCRM Coordinator Checklist..................................................

31 Appendix P, OSC Materials Coordinator Checklist....................................

32 Appendix Q, Canceled................................................................................

33 Appendix R, Personnel Pool Manager Log.................................................

34 Appendix S, OSC Roster and Emergency Responder Notification Form......... 35 SOURCE NOTES......................................................................................

37 I

A N

-nD OPERATION OF THE EPIP-7J SQN OPERATIONS SUPPORT CENTER Rev. 20 II Page 4of 37 1.0 PURPOSE The purpose of this procedure is to describe the activation of the Operations Support Center (OSC), describe the OSC organization, and provide for OSC operation once it has been staffed. The OSC is activated during an "Alert,"

"Site Area Emergency," or "General Emergency."

2.0 REFERENCES

Developmental Documents A.

EPIP-6, "Activation and Operation of the Technical Support Center" B.

EPIP-8, "Personnel Accountability and Evacuation" C.

EPIP-14, "Radiological Control Response" D.

EPIP-16, "Termination and Recovery" 3.0 INSTRUCTIONS 3.1 An Alert or higher Emergency Classification At an Alert or higher Emergency Classification, the OSC Manager will report directly to the OSC and shall be responsible for implementing this procedure and coordinating OSC personnel and activities.

3.2 Activation of OSC 3.2.1 Shift Manager (SM) Actions The SM will activate the OSC by announcing the emergency condition by one or more of the following methods:

A.

Plant Public Address (PA) announcement.

B.

The Shift Manager or operations clerk will normally activate the Emergency Paging System (EPS) or contact the persons designated on the REP Duty Roster and/or Call Lis--t. If the EPS cannot be activated from the site, the SM will contact the Operations Duty Specialist (ODS) and have the EPS activated from the CECC.

C.

The SM may activate the onsite emergency sirens at an "Alert" and shall activate the sirens at a "Site Area Emergency" or "General Emergency".

3.2.2 Call List The Emergency Preparedness Manager (EPM) shall maintain a REP Duty Roster and Call List book listing key OSC personnel by name, plant and home telephone numbers. The REP Call List and Duty Roster book will be updated at least quarterly by the EPM or designee with input by the appropriate section/group supervisors. This book will be provided to the SM and will also be maintained in the TSC and OSC.

3.2.3

Response

The following personnel should report to the OSC or the assigned OSC support location upon announcement of an "ALERT" or higher emergency classification, or at the direction of the SED:

A. OSC Manager B. Assistant OSC Manager C. Maintenance Shift Supervisor D. OSC RADCON Supervisor E. Fire Operations Advisor F. OSC Operations Advisor G. Two Instrument Maintenance Briefers H. Two Mechanical Maintenance Briefers I. Two Electrical Maintenance Briefers J. RADCON Briefer K. Chemistry Shift Supervisor L. OSC Personnel Pool Manager M. Two Duty Damage Control Teams - one team will dress-out and standby for assignment N. RADCON Lab Supervisor

0. Other plant staff the OSC Manager determines to be necessary to support OSC functions will be called:
1. OSC Clerks
2. OSC Log Keeper
3. HIS-20 Operator
4. Maintenance Personnel needed for support
5. Operations Personnel needed for support
6. Transmission and Customer Service
7. Technical Support Personnel needed for support
8. DCRM support
9. Materials support
10. Industrial Safety support
11. Security Advisor

I ACTIVATION AND OPERATION OF THE EPIP-7 SQN OPERATIONS SUPPORT CENTER Page 6 of 37 3.2.4 Maintenance Shift Supervisor (MSS)

The Maintenance Shift Supervisor (MSS) shall ensure that the OSC and Tool Room are unlocked and open for access when required.

The MSS maintains responsibility as single point maintenance contact for the Shift Manager until the OSC Manager is in place. The MSS initiates OSC setup and may sign designated actions on the Assistant OSC Manager's Checklist.

The MSS may assist in the activation of the Emergency Response Organization to ensure adequate personnel are available. The MSS will provide a briefing to the OSC Manager when he arrives and then becomes the second Assistant OSC Manager.

3.2.5 OSC Operation The OSC shall operate to ensure the following actions are taken:

A.

All personnel or teams previously tasked by the Control Room or Site Emergency Director prior to OSC staffing and activation shall be located and assigned a Team Tracking Letter designation for tracking and debriefing purposes.

B.

All teams shall be briefed and/or coordinated with the OSC prior to dispatch and debriefed by the OSC upon task completion. The exceptions are:

"* AUO teams responding to procedure driven missions or are otherwise under the direction of the SM. These teams shall be tracked on the OSC Ops tracking board via communication between the Control Room Communicator and the OSC Operations Advisor.

"* The Fire Brigade or Medical Emergency Response Team may be briefed in route by radio when response time is critical. These teams will be tracked by the OSC.

"* If an Emergency Response Team is responding or near the task area prior to OSC staffing the team may be briefed by radio or telephone and shall be tracked by the OSC.

"* RADCON Survey Teams and Chemistry Teams may be dispatched directly from their respective labs provided they are coordinated through the OSC RADCON Supervisor and tracked on the RADCON/CHEM board C.

Each potential damage control and repair team member shall have qualifications verified and dosimetry issued prior to assignment to a response team.

D.

RADCON and Operations should be members of each response team.

E.

Each team should have a radio for communications with the OSC. The Operations or RADCON member of each team should be the radio talker. Muted radios are available for use in radio-sensitive areas of the plant.

F.

RADCON shall maintain sufficient respiratory protection equipment available for issue in a manner that will not delay teams response.

AC-TIVATION AND OPERATION OF THE I EPIP-7 SQN OPERATIONS SUPPORT CENTER Rev. 20 Page 7 of 37 3.2.5 OSC Operation (Continued)

G.

Teams should respond with damage control tool kits to the assigned task.

H.

If a person/team is unable to complete a mission or is reassigned a task after briefing, the OSC shall be immediately notified by the team leader.

I.

At least one Emergency Response Team is on standby at all times.

3.2.6 OSC Manager The OSC Manager is responsible for directing repairs and corrective actions; performing damage assessment; coordinating repair activities with the TSC; coordinating maintenance teams and ensuring proper briefings and accompaniment by RADCON; activating the Fire Brigade, Search and Rescue, and Medical Emergency Response Teams as necessary; relocation of the OSC in accordance with 3.2.6.A; deactivating the OSC. Appendix A, OSC Manager Checklist, shall be used to ensure required actions are completed.

A.

Relocate OSC personnel and equipment to an alternate OSC location when conditions require:

1.

Direct OSC RADCON Supervisor to make habitability survey for the OSC if a release has occurred. Surveys are to include direct radiation readings, area swipes, and air activity monitoring as appropriate for the existing conditions and based on good radiological practices.

2.

Inform the SED if conditions exceed habitability criteria.

3.

Relocate the OSC (upon direction from the SED) to the backup OSC in the O&PS building if it meets habitability requirements.

4.

If the backup OSC does not meet habitability criteria, then an alternate location must be selected based on the following criteria:

a.

Location has adequate access to the plant (preferably is within the Protected Area), has a current radiological survey, is upwind from plant, and has adequate ventilation control.

b.

Location has adequate communications capabilities (including three telephone circuits).

c.

Physical size: space for at least 25 persons.

d.

Provides access to appropriate reference materials, tools, safety equipment, etc.

ACTIVATION AND OPERATION OF THE I EPIP-7 I SQN OPERATIONS SUPPORT CENTER Rev. 20 Page 8 of 37 Assistant OSC Manager The Assistant OSC Manager maintains continuous communication with the Maintenance Manager in the TSC, ensuring that OSC tasks are entered on the team tracking board/system; initiates an OSC Team Briefing/Debriefing Form, (Appendix D) for each task; assigns tasks to briefing teams; coordinates and directs damage control and repair activities as directed by the OSC Manager; ensures RADCON support for each team; ensures all teams (except as indicated in 3.2.5.B) are briefed before dispatch in accordance with Appendix D; ensures all teams are debriefed upon return to the OSC in accordance with Appendix D. When available, a qualified individual may assume communications and/or boardwriting responsibilities as delegated by the Assistant OSC Manager. Appendix C, Assistant OSC Manager Checklist, shall be used to ensure required actions are completed.

3.2.8 OSC RADCON Supervisor The OSC RADCON Supervisor provides and coordinates RADCON resources; assigns a HIS-20 Operator and calls in additional support as needed; directs the RADCON Lab through the Lab Supervisor; informs the TSC RADCON Manager, OSC Manager and OSC RADCON briefer of current radiological conditions; enters data on the Radcon/Chem tracking board; provides RADCON support for emergency response teams as warranted.

Appendix E, OSC RADCON Supervisor Checklist, shall be used to ensure required actions are completed.

3.2.9 OSC RADCON Briefer The OSC RADCON briefer remains informed of the site radiological conditions; provides technical assistance for radiological concerns; assist in technical briefings of OSC teams; ensures each team has a RADCON member present during briefing or may be dispatched with the team; completes applicable portions of Appendix D. Appendix F, OSC RADCON Briefer Checklist, shall be used to ensure required actions are completed.

3.2.10 OSC Operations Advisor The OSC Operations Advisor provides operational advice, plant status, and important system parameters to support the operation; provides Operations personnel as part of OSC response teams as warranted; maintains the Operations tracking board in the OSC. Provide Operations personnel, advice, and plant status to support the entire OSC including briefing emergency response teams as needed. Keeps the TSC Operations Communicator and Control Room Communicator informed of OSC team activities. May provide briefing/debriefing to AUOs as requested by the Control Room Crew and/or SED. Appendix G, OSC Operations Advisor Checklist, shall be used to ensure required actions are completed.

3.2.11 Personnel Pool Manager The OSC Personnel Pool Manager provides and coordinates a pool of qualified maintenance personnel to staff damage control and repair teams.

He also tracks individual team members and assesses their future availability for other assignments. Appendix N, Personnel Pool Manager Checklist, shall be used to ensure required actions are complete. The Personnel Pool Manager Log (Appendix R) should be used to manage information regarding individual qualifications and OSC assignments.

Fire Operations Advisor The Fire Operations Advisor initiates fire response, medical emergency response, hazardous material containment; provides personnel to support Nuclear Security in searches of hazardous areas. Provides evaluations of the plant environment and recommendations to OSC management on safety aspects of the response team tasks. Contacts the site and/or corporate Safety Specialist as necessary.

Maintain status of Fire Ops personnel.

Appendix H, Fire Operations Advisor Checklist, shall be used to ensure required actions are completed.

3.2.13 Chemistry Shift Supervisor The Chemistry Shift Supervisor in the CHEM lab provides first-line direction of Chemistry support personnel; calls in additional support as required; briefs Chemistry personnel on emergency events and status; initiates onsite/off-site dose assessment, per EPIP-1 3, as directed by the TSC or the Ops. SM; provides Chemistry support to the OSC as needed.

3.2.14 OSC Log Keeper The OSC Log Keeper ensures status boards are continuously updated to reflect current plant conditions and collects/maintain all original copies of generated documents. Appendix I, OSC Log Keeper, shall be used to ensure required actions are completed.

3.2.15 OSC Clerk The OSC Clerk provides logistics support to the OSC. Appendix J, OSC Clerical Staff, shall be used to ensure required actions are completed.

3.2.16 OSC Site Security Advisor The OSC Site Security Advisor coordinates Nuclear Security activities from the OSC when requested by the TSC Security Mgr or OSC Mgr; supports response to fire, medical emergencies, or other security responses; conducts search and rescue operations. Appendix K, OSC Nuclear Security Advisor, shall be used to ensure required actions are completed.

3.2.17 OSC Briefer The OSC Briefer provides and coordinates resources to support the OSC Manager; provide damage and repair assessments; remain informed of the site conditions; assist in technical briefings of OSC emergency response teams; and complete applicable portions of Appendix D. Appendix L, OSC Briefer Checklist, shall be used to ensure required actions are completed.

3.2.18 OSC Industrial Safety Advisor Industrial Safety issues are normally handled by the team briefer and/or assistance from Fire Ops when needed. If necessary, Fire Ops will contact site/corp Safety Specialist. When requested, Appendix M, Industrial Safety Advisor Checklist shall be used to ensure required actions are completed.

3.2.12

DCRM Coordinator The DCRM Coordinator provides support to OSC personnel by providing drawings, documents, vendor manuals and provides other support as requested. When requested, Appendix 0, DCRM Coordinator Checklist, shall be used to ensure required actions are completed.

3.2.20 OSC Materials Coordinator The Materials Coordinator provides support to the OSC by determining materials availability, coordinating between Power Stores and the OSC and by expediting materials needed. When requested, Appendix P, OSC Materials Coordinator Checklist shall be used to ensure required actions are completed 3.3 Deactivation The OSC will be deactivated when directed by the SED. Appendix A, OSC Manager Checklist, may be used to ensure required actions are completed.

4.0 RECORDS 4.1 QA Records The following records generated during real emergency events are considered QA Records. These shall be forwarded to the EP Manager who shall submit QA Records and any other records deemed necessary to corporate Emergency Preparedness for maintenance.

A.

Appendix B, Emergency Conditions Data Sheets B.

Appendix D, OSC Team Briefing/Debriefing Forms C.

Appendices for OSC Position Checklists D.

OSC Log Sheets 4.2 Non-QA Records The appendices and checklists to this procedure necessary to demonstrate key actions during NRC evaluated exercises, drills, or used to establish/support NRC Performance Indicators will be retained by the SQN EP Manager for at least 2 years.

3.2.19

APPENDIX A Page 1 of 2 OSC MANAGER CHECKLIST INITIAL ACTIVATION OF THE OPERATIONS SUPPORT CENTER Time/

Initials

1.

Swipe Accountability Reader.

2.

Ensure OSC set-up using materials in OSC Storage closet.

3.

Establish a log of activities and communications.

4.

Ensure OSC Briefing Area set-up using materials in OSC storage closet.

5.

Obtain briefing from the MSS.

6.

Establish communications with the TSC and obtain an update of the emergency conditions. Appendix B should be used as a guideline.

7.

Determine location and function of persons/teams currently and previously tasked by the TSC or Control Room and ensure assignment of Team Tracking Letter designation.

8.

Ensure Activation of OSC.

a.

Ensure minimum staffing in OSC. (See note below)

b.

Ensure OSC set-up complete.

c.

Ensure OSC habitability OR relocate OSC in accordance with 3.2.6.A.

d.

Ensure OSC support personnel are notified of activation, if needed.

9.

Brief OSC Personnel on Plant Conditions, unless SED has provided briefing.

10.

Announce to the OSC and notify the SED the time that OSC is operational and activated.

11.

Establish necessary emergency teams.

NOTE: Minimum staffing requirements are one representative from Mechanical Maintenance, Electrical Maintenance and Instrument Maintenance.

Continued Next Page

I ACTIVATION AND OPERATION OF THE I EPIP-7 SQN OPERATIONS SUPPORT CENTER Rev. 20 SQN Page 12 of 37 APPENDIX A "Page 2 of 2 OSC MANAGER CHECKLIST OPERATIONAL RESPONSIBILITIES

"* Demonstrate command and control of the OSC throughout the emergency.

"* Direct Asst. OSC Manager to form teams for accident assessment and repair and Announce the intent to form OSC teams.

"* Approve and Announce the dispatching of teams from the OSC.

"* Provide supplemental staffing for the OSC if needed.

"* Periodically direct key OSC positions to provide status summary to OSC staff or perform briefing yourself.

"* Update the SED and TSC Maintenance Manager as needed.

"* Ensure that team activities are prioritized and synchronized with the TSC.

"* Announce results of OSC teams following debriefing.

"" If event duration expected to exceed 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />, then establish relief rotations using Appendix S.

"* Request habitability survey by RADCON if a release has occurred.

  • Reassess each team's radiological and safety protection status after accountability, after major changes in plant conditions and at emergency classification upgrades.

Relocate the OSC as habitability conditions dictate.

Maintain a log of communications and activities.

Informs TSC of as-found plant conditions and status of emergency conditions.

Ensure the Emergency Response Teams Tracking Boards/System, Radiological Status Boards and other visual displays are kept current.

DEACTIVATION RESPONSIBILITIES

  • Ensure all assigned tasks and assignments are completed.

Ensure all emergency response teams have been debriefed.

Ensure all emergency equipment and supplies have been returned to their specified storage locations.

Review all records for completeness and forward all records to the Emergency Preparedness Manager.

KACTIVATION AND OPERATION OF THE SQN OPERATIONS SUPPORT CENTER APPENDIX B Page 1 of 2 OSC MANAGER BRIEFING OUTLINE Emergency Classification: (check one)

I-1 UNUSUAL EVENT nI ALERT L1 SITE AREA EMERGENCY I

EPI P -7 r

EPIP-7 Rev. 20 Pag 13 of 37 E] GENERAL EMERGENCY Affected Unit:

[

Event

Description:

] UNIT I I-UNIT 2

[I BOTH UNITS 1 & 2 UNIT STATUS: rI UNIT I

[I UNIT 2 Time Emergency Classified:

Primary Plant Condition:

UNIT 1 Mode:

L-1, EL 2, [] 3, 1 4, [] 5, or El 6 UNIT2 Mode:

L]1, E]2, 1113, [14, [15, or El6 Electrical Lineup:

Diesel Generators:

Offsite Power Avail DESCRIPTION OF ANY ABNORMAL LINEUP DG I Operating

-I.Yes/ E-] No DG 2 Operating LI Yes / LI No able:

I Yes / INo Major Mechanical Problems:

Major Electrical Problems:

Continued Next Page LI I

ACTIVATION AND OPERATION OF THE SQN OPERATIONS SUPPORT CENTER r

.r-rl Ir- -I ReRev. 20 Paae 14 of 37 II APPENDIX B Page 2 of 2 OSC MANAGER BRIEFING OUTLINE Major Instrument and Control Problems:

Environmental Problems High Rad Levels:

Toxic Gas:

High Press. Steam Releases:

Other:

Recorded by:

Time:

Date:

I LUIU I

I I

APPENDIX C Page 1 of 2

^O*trAktlT flf'.

MANJA(IFR Cl.HI=FKLIST INITIAL ACTIVATION OF THE OSC Time/

Initials

1.

Swipe Accountability Reader - Assistant OSC Manager.

Swipe Accountability Reader - Maintenance Shift Supervisor.

2.

Obtain keys at Work Coordination Center and open cafeteria (if locked), the OSC, and OSC storage room. (May be signed off by MSS)

3.

Ensure the minimum maintenance personnel are staffed or have been called in as necessary, (May be signed off by MSS)

S Mechanical Craft Electrical Craft Instrumentation Craft ONSITE LI 1 on shift LI I on shift CALL-IN I] onsite within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> Lii I onsite within 30 minutes III 1 onsite within 30 minutes CALL-IN I 1 onsite within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> LI 1 onsite within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> TOTAL TOTAL:

2 Available onsite within 30 TOTAL 2 onsite within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> minutes and 2 onsite within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> TOTAL 3 onsite within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />

4.

Open the Tool Room if it is not staffed. (May be signed off by MSS)

5.

Establish a log of activities and communications.

6.

Establish contact with Maintenance Manager in the TSC (Bridge x1 04 or 6478).

7.

Obtain initial briefing and status of Operations and Maintenance tasks related to the emergencies that are underway from MSS, OSC Manager, or SM.

8.

Ensure all emergency response teams previously tasked are assigned team tracking letter designation and entered on the Emergency Response Team Tracking Board/System.

9.

Assign a team briefer to any teams previously dispatched.

10. Ensure that two emergency response teams are pre-staged in the OSC staging area of the cafeteria.
11. Notify Power Stores (X 7155) and the Tool Room (X 7755) (if staffed), advise them to remain staffed during the emergency unless released by the Site Emergency Director.

Continued Next Page I

APPENDIX C Page 2 of 2 ASSISTANT OSC MANAGER INITIAL ACTIVATION OF THE OSC Continued

12. Verify the priorities of teams dispatched from the OSC, or being formed, with the TSC.

1 3. Review the OSC Team Tracking Board/System and reconcile any discrepancies with information obtained from briefing sources.

OPERATIONAL RESPONSIBILITIES

"* Assist the OSC Manager in providing direction and control to the OSC areas.

"* Open OSC, and OSC storage room.

"* Receive direction from SM/SED until OSC Manager arrives.

"* Oversee the operations of the OSC Teams and coordinate the supporting activities using Appendix D, "OSC Team Briefing/Debriefing Form".

"* Maintains continuous communication with Maintenance Manager in the TSC.

"* Receives TSC-assigned tasks, enters them on the Team Tracking Board/System, informs the OSC Manager, and assigns the task to a specific OSC Team Briefer.

"* Keeps the OSC Manager informed of important communications from the TSC.

"* Coordinate with OSC RADCON Supervisor and Operations Advisor as needed regarding OSC Team activities (determines if teams need RADCON and/or Operations support).

"* Maintain log of communications and activities.

DEACTIVATION RESPONSIBILITIES Ensure all assigned tasks and assignments are completed.

"* Ensure all emergency response teams have been accounted for and debriefed.

"* Ensure all emergency equipment and supplies have been returned to their specified storage locations.

"* Ensure all log and team briefing forms are completed and signed.

APPENDIX D Page 1 of 2 OSC TEAM BRIEFING/DEBRIEFING FORM ASST. MGR.

Init/Time Date

.- rr^Ama "rA~ev. m I p,--tirnn LTrnihle Sohnnting F

Reoair TASK LOCATION: (Bldg, EL., Rm. Name, etc) r-ASSIGN Team next Letter designator (A, B, C etc.):

El ENTER on Team Tracking Board.

Dl INFORM OSC Mgr. of task and make PA Announcement in OSC.

El ASSIGN task to Lead Briefer Name:

Heads-up to Briefer: E-1 Ops E] R/C El Safety El Other I _______________________________________________________________________

RAD SUPV.

I/

I nit/Ti me 3RIEFER

/I Init/Ti-me (Use Page 2 to conduct briefing)

I.

RADCON REQUIREMENTS: RWP:

RWP #

E] SCBA E] Respirator

[] Dressout El Other Emergency Exposure Approved by SED: ElYes (REM

.)

(Ref: EPIP-15)

RNo KI ISSUE Approved by TSC Radcon Mar.: Res rlNo (Ref:_EPIp-14)

Team Members Names Team Leader Name:.

- Discipline (MM, EM, IM, etc.)

AUO RADCON Tech Briefing conducted by:

Communication Method: [] Phone#

El Pager#

El Messenger E] OSC Hotline (x6406)

Yes El Radio Ch#

Radio Sensitive Area (O-TI-OPS-000-061.0) El Yes r-i r...÷*.

ct Rri~for

,=r'J Minutes

[I No L

_J a,,

U "II C *.4m U,.

-*, p.

A M./

l t. '

.. v ** *.

OSC MGR.

FINAL APPROVAL TO RELEASE TEAM I

Team Necessary? [] Yes L1 No Initfrime Radiological Condition Change Since Briefing? [] Yes E] No

--Announce to OSC: "Is there any reason that we should not dispatch (Use Team Designator) team at this time?".

TEAM LEADER DEBRIEFING (Use Page 2 to conduct debriefing) or BRIEFER Debriefing conducted by:

Init/Time Hl PROVIDE Summary to the OSC Manager.

EL UPDATE the OSC Team Tracking Board.

S- =.,.=,* *~

n"* a E

t"..

  • .1... H.-

+-k*

(AQC JI:/A *~~

OSC MGR.

/_1 El ENSURE TSC is informed of Team results.

TEAM I

I I

I Inif/ I ime 1 r'-m llV I

6l* L--J

";tl.

J

,,.,l.il i

C.on3t.inued INiXL rayu

APPENDIX D Page 2 of 2 EMERGENCY RESPONSE TEAM BRIEFING/DEBRIEFING CHECKLIST BRIEFING Description of problems -Team Priority El Plant system status E]

Plant radiological status Route to/from work area El Hazards between OSC and work location E-Radiation Work Permit (RWP)

-7 RADCON support El OPS support E-l Procedures to be used r-ii Tools Kits needed: (See tool pouch number and description in O-PI-REM-OOO-001.Q, "Quarterly Tool Kit Inventory".)

Emergency Tool Kit to be obtained from the Tool Room in MMG Shop: 10, 2--, 3E], 401, 50-, 601, 7[E], 8[-'

El]

Other Tools needed:

El Equipment needed El Clearance required/Hold Order #

El Safety evaluation of job El Communication with OSC Fl Copy of Briefing Form (Appendix D) and clipboard given to team with phone number(s).

E-l Key(s) needed for task.

DEBRIEFING El Was assignment completed?

El Observations from the Field El Equipment El Hazards El1 Radiological conditions El Unusual sounds, etc.

El Other information El Team directed to Personnel Pool Manager NOTES: (Observations/Damage Assessment/Recommendations, etc.)

APPENDIX E Page 1 of 2 OSC RADCON SUPERVISOR CHECKLIST INITIAL ACTIVATION OF THE OSC Time/

Initials

1.

Swipe Accountability Reader.

2.

Fill out the Organizational/Staffing Chart and obtain OSC badge.

3.

Establish a log of activities and communications.

4.

Verify the minimum number of ANSI qualified RADCON personnel currently onsite. The RADCON Lab Supervisor is counted as a 60 minute responder when relieved qualified OSC RadCon Supervisor.

SANSI Qualified RadCon Technicians ONSITE

_ 2 on shift CALL-IN 6 additional (8 total onsite) within 30 minutes CALL-IN 6 additional (14 total onsite) within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />

5.

Ensure a) that a current HIS-20 printout is available in the OSC; b) a HIS-20 Computer Operator is assigned to provide computer access or use the printout for RADCON qualification checks of Emergency Response Team members; c) any Emergency Response Team members already assigned tasks in the field have acceptable RAD and qualifications (Contact MSS to for names and assigned task of individuals);

d) the Personnel Pool Manager is notified when the HIS-20 operator is assigned and given the name of the HIS-20 operator.

e) Emergency related RWPs are active.

6.

Establish communications with the TSC RADCON Manager and the RADCON I Lab Supervisor. (Bridge 103, mute telephone when not speaking. or X 6472/6463 TSC and X 6417 Lab).

7.

Ensure adequate RADCON staffing available for OSC support. (Dosimetry support, boardwriters, RWP support, HIS-20 operators)

8.

Locate all RADCON/CHEM personnel/teams currently and previously tasked arid ensure that teams are identified on RADCON/CHEM Team Tracking Board for tracking and debriefing.

9.

Control eating and drinking in the OSC until habitability has been established. I

10. Ensure habitability surveys have been initiated for the of OSC, TSC, and Control Room, if a release has occurred. Surveys are to include direct radiation readings, area swipes, and air activity monitoring as appropriate for the existing conditions and based on good radiological practices.

Continued Next Page

APPENDIX E Page 2 of 2 OSC RADCON SUPERVISOR CHECKLIST OPERATIONAL RESPONSIBILITIES

"* Brief Emergency response Teams.

"* Provide and coordinate RADCON resources as necessary

"* Direct RADCON personnel in the RADCON Lab.

"* Ensure all RADCON Teams are coordinated and tracked through the OSC.

"* Ensure all Chemistry Teams are tracked through the OSC.

"* Ensure Emergency Response Teams have adequate RADCON/dosimetry coverage present during briefings and field support.

Brief the OSC Manager regularly on radiological conditions status (especially when radiological conditions are changing rapidly).

"* Brief the TSC RADCON Manager on radiological conditions status.

"* Provide assistance to the OSC Manager as needed.

"* Periodically verify habitability of TSC, OSC, and Control Room (especially during changing radiological conditions and at each emergency classification upgrade).

"* Conduct habitability surveys for the TSC, OSC and Control Room if a release has occurred. Surveys are to include direct radiation readings, area swipes, and air activity monitoring as appropriate for the existing conditions and based on good radiological practices.

" Reassess each team's radiological protection status after accountability, after major changes in plant conditions and at emergency classification upgrades.

"* Log on to the Integrated Computer System (ICS).

"* Periodically brief the RADCON and CHEM Lab personnel on plant status.

"* Administer KI to emergency response teams according to EPIP-14 and inform the OSC manager. (Forward EPIP-14 KI Issue Report to the TSC RADCON Manager.)

Ensure outlying teams/groups (i. e., line crews, warehouse, security) have dosimetry anc are being protected throughout the emergency.

Ensure emergency responders' exposures are maintained As Low As Reasonably Achievable (ALARA).

DEACTIVATION RESPONSIBILITY

"* Ensure all teams are accounted for and properly debriefed.

"* Ensure all logs and team briefing forms are completed and signed.

APPENDIX F Page 1 of 1 OSC RADCON BRIEFER CHECKLIST INITIAL ACTIVATION OF THE OSC Time/

Initials

1. Swipe Accountability Reader.
2. Fill out the Organizational/Staffing Chart and obtain OSC badge.
3. Notify the OSC RADCON Supervisor of arrival.
4. Establish a log of activities and communications.
5. Locate all RADCON persons/teams currently and previously tasked and ensure assignment of Team Tracking Letter designator (AA, BB, etc.) for tracking and debriefing.
6.

Establish communications on the RADCON Bridge (x103). Mute telephone when not speaking.

OPERATIONAL RESPONSIBILITIES

"* Provide radiological technical assistance to the Briefing Teams.

"* Provide radiological conditions for inclusion in the analysis of the job performed by the OSC Briefing Team.

"* Assist with portions of the OSC Team briefings and debriefings including a debriefing from the team RADCON member.

Ensure each OSC team has a RADCON member present during briefings and field support as needed. (Dispatch with team if necessary)

"* Complete applicable portions of Appendix D.

"* Inform the OSC RADCON Supervisor of any unexpected radiological conditions encountered.

"* Write on the RADCON status boards, RADCON Team Tracking Board and ensure wind direction arrow is kept current.

"* Post radiological status information in the OSC Teams Staging Area.

"* Ensure emergency responders exposures are maintained ALARA.

APPENDIX G Page 1 of 1 OSC OPERATIONS ADVISOR CHECKLIST INITIAL ACTIVATION OF THE OSC Time/

Initials

1. Swipe Accountability Reader.
2. Fill out the Organizational/Staffing Chart and obtain OSC badge.
3. Establish a log of activities and communications.
4. Establish communications with the TSC Operations Communicator and the Control Room Communicator for updates and to obtain Operations support (Dial 101 on telephone).
5. Locate all Operations personnel/teams currently and previously tasked and ensure each is tracked on the Operations tracking board.
6. Activate the ICS terminal to the affected unit.
7. Announce on the portable radio OPS channel "OSC AUOs Report to the OSC" (Repeat).
8. Ensure AUOs Swipe Accountability Reader at cafeteria entrance.

OPERATIONAL RESPONSIBILITIES Provide Operations personnel, advice, and plant status to support the entire OSC including briefing emergency response teams as needed (additional Operations personnel including AUOs can be used to assist).

  • Operate the ICS and provide plant operations advice to support the OSC.

Provide personnel for any operations actions that may be required while in the field.

Provide Operations personnel for damage control and repair teams.

Call-in additional AUOs/Operations personnel from offshift to support OSC activities, if requested.

Keep the TSC Operations Communicator and the Control Room Communicator appraised of the OSC Team priorities, assignments and activities while in the field.

Provide assistance to the OSC Manager as needed.

"* Maintain the OSC Operations Tracking Board.

"* Direct AUOs to maintain a log, and listen to the Operations Bridge (X102) to maintain a current awareness on plant status as needed.

Ensure OSC AUOs maintain accountability by swiping reader at cafeteria entrance.

APPENDIX H Page 1 of 1 OSC FIRE OPERATIONS ADVISOR CHECKLIST INITIAL ACTIVATION OF THE OSC Time/Initials

1. Swipe Accountability Reader.
2. Fill out the Organizational/Staffing Chart and obtain OSC badge.
3. Establish a log of activities and communications.
4. Establish communications with the Fire Operations Unit or the Fire Station.
5. Verify that Fire Operations, if not responding to a fire or medical emergency, has reported to the designated assembly area. (see Note below)
6. Ensure that Fire Operations if responding to a fire or medical emergency is assigned a Team Tracking Letter designator for tracking and debriefing and team has been entered on tracking board.
7. Ensure sufficient SCBA equipment and air bottles for response teams are available at established entry points.

Note:

If Fire Operations is not involved in the emergency response, dispatch a Fire Operator to the MCR to operate panel 0-M-29. This operator will be tracked on a tracking board and will be recalled at the discretion of the Fire Brigade Leader.

OPERATIONAL RESPONSIBILITIES

"* Monitor plant status and initiate fire response.

"* Initiate medical emergency response as needed.

"* Reassess each team's safety protection status after major changes in plant conditions and at emergency classification upgrades.

"* Initiate and provide first response for Hazardous Material Containment.

"* Support Nuclear Security in searches of hazardous areas.

"* Provide assistance to the OSC Manager as needed.

"* Periodically brief Fire Operations Unit personnel of plant status.

"* Brief the team in the field by telephone/radio (if necessary) in order to decrease response time.

"* Request the SM to sound the fire alarm when needed to form the fire brigade or MERT.

Provide evaluations of the plant environment, recommendations to OSC Management on safety aspects of response team task.

Contact or call in the site/corporate Safety Specialist as necessary (see REND).

APPENDIX I Page 1 of 1 OSC LOG KEEPER CHECKLIST Time/

Initials

2.
2.
3.
4.
5.
6.

7.

Swipe Accountability Reader.

Fill out the Organizational/Staffing Chart and obtain OSC badge.

Notify the OSC Manager of arrival.

Establish a log of OSC activities and communications.

Notify Boardwriter to report to the OSC if requested.

Notify OSC Clerks to report to the OSC if requested.

Notify other staff as determined by the OSC Manager if requested.

OPERATIONAL RESPONSIBILITIES

"* Ensure the OSC Status Boards are continuously updated to reflect current plant conditions.

"* Ensure a log is maintained of all important OSC activities.

"* Collect and maintain all original copies of generated documents.

"* Following OSC deactivation forward all records to the Emergency Preparedness Manager.

"* Retain completed original of OSC team briefing/debriefing form, Appendix D.

I ATIVATION AND OPERATION OF THE I EPIP-7 OPERATIONS SUPPORT CENTER KRev. 20 SNPae 25 of 37 APPENDIX J Page 1 of I OSC CLERICAL STAFF CHECKLIST Time/

Initials

1. Swipe Accountability Reader.
2. Fill out the Organizational/Staffing Chart and obtain OSC badge.
3. Notify the OSC Manager of arrival.
4. Establish a log of activities and communications.
5. Ensure FAX is operable.

OPERATIONAL RESPONSIBILITIES

"* Uses call list to obtain staff for unfilled positions or replacement staff for shift turnovers as directed by the OSC Manager.

"" Assist in set-up and activation of the OSC.

"* Answer telephones.

"* Distribute forms.

"* Ensure OSC responders have signed the OSC Roster, Appendix S when requested.

Establish OSC Shift change (Use Appendix S page 2 of 2 and ask appropriate Fitness For Duty Questions).

"* Operates FAX machine. (Turn off "Memory Fax" mode before faxing)

"* FAX AUO Teams summary to Main Control Room (FAX# 6208) and TSC (FAX# 6461) on a routine basis.

"* If Emergency Response Network (ERN) is inoperable, then FAX Maintenance Repair Teams summary to Main Control Room (FAX# 6208) and TSC (FAX# 6461) on a routine basis.

DEACTIVATION OF THE OSC

"* Transfers all log notes and other materials to the OSC Log Keeper.

"* Deactivate the OSC by returning all equipment, materials, and supplies to designated storage areas.

SON s

TIVATION AND OPERATION OF THE PERATIONS SUPPORT CENTER I E PI-7*..

E PIP-7 Rev. 20 Paae 26 of 37 APPENDIX K APPENDIX K Page 1 of 1 OSC SITE SECURITY ADVISOR CHECKLIST Time/

Initials

2.
3.
4.
5.
6.

7.

Swipe Accountability Reader.

Fill out the Organizational/Staffing Chart and obtain OSC badge.

Notify the OSC Manager of arrival.

Establish communications with Site Security Manager in the TSC (X 6469).

Establish a log of activities and communications.

Establish contact with the CAS.

Check status of emergency actions already in effect such as Accountability or Site Evacuation.

OPERATIONAL RESPONSIBILITIES

"* Coordinate activities of Site Security personnel in support of OSC activities.

"* Provide personnel to support Fire Operations in response to fire, medical emergency, or hazardous material containment.

"* Forms, briefs and dispatches search and rescue teams with Fire Operations support.

"* Provide assistance to the OSC (including briefing teams) as needed.

"* Ensure the OSC Manager/OSC Staff are aware of security hazards that could affect emergency response activities.

"* Ensure onsite Security personnel are apprised of radiological and plant conditions and associated hazards.

"* Ensure OSC Manager is aware of Security personnel locations and activities.

1I I

ACTIVATION AND OPERATION OF THE SQN OPERATIONS SUPPORT CENTER APPENDIX L Page 1 of 2 OSC BRIEFER CHECKLIST INITIAL ACTIVATION OF THE OSC

EPIP-7 E PIP-7 Rev. 20 Pane 27 of 37 Time/

Initials

1.
2.
3.
4.
5.
6.

7.

Swipe Accountability Reader.

Fill out the Organizational/Staffing Chart and obtain OSC badge.

Establish the "OSC Team Hotline" on position speaker phone by dialing X6406.

Establish a log of OSC activities and communications.

Establish contact with emergency team leaders.

Establish contact with Personnel Pool Manager.

If assigned a team that is already working in the field, establish contact with the team leader and ensure that they are fully briefed on their task and obtain status (report results to the OSC Manager).

8.

Verify and/or ensure the minimum (for the briefer's discipline) maintenance personnel have been called in as necessary,

.r R

(rrat I Electrical Craft Instrumentation Craft

Iri ONSITE CALL-IN CALL-IN TOTAL I1VIS l,,.;I I'"II!=U cIl V II oshft111 on shift 1 onsite within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> 1 onsite within 30 minutes 1 onsite within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> 1 onsite within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> TOTAL:

2 Available onsite within 30 TOTAL 2 onsite within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> minutes and 2 onsite within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br /> TOTAL 3 onsite within 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />

9. Verify that Maintenance Call List is available. As necessary call in additional maintenance personnel for your discipline.

OPERATIONAL RESPONSIBILITIES Provide Mechanical, Electrical, and Instrument technical expertise.

Evaluate job conditions (including RADCON, Fire Operations, and Operational aspects of the task) and analyze the necessary precautions and methods best suited to safe performance of the task.

When possible combine Damage Assessment and Repair Teams.

Continued Next Page I

I i

I I

IAACTIVAT ION AND OPERATION OF THE SQN OPERATIONS SUPPORT CENTER APPENDIX L Page 2 of 2 OSC BRIEFER CHECKLIST OPERATIONAL RESPONSIBILITIES Continued

"* Brief the OSC Teams based on the analysis of the job.

"* Track the OSC Teams while in the field.

"* Debrief the OSC Teams after completion of the Task.

"* Complete applicable portions of the OSC Team Briefing/Tracking and Debriefing Forms (Appendix D) and forward to OSC Manager.

I EPI P -7 Rev. 20 Page 28 of 37 I

I I

l I

APPENDIX M Page 1 of 1 OSC INDUSTRIAL SAFETY ADVISOR CHECKLIST Time/

Initials S1. Swipe Accountability Reader.

2.

Fill out the Organizational/Staffing chart and obtain OSC badge.

3. Notify the OSC Manager of arrival.
4. Establish a log of activities and communications.
5. Notify the Assistant OSC Manager of arrival.
6. Notify Fire Ops Advisor of arrival.

OPERATIONAL RESPONSIBILITIES

"* Provide and coordinate Industrial Safety personnel needed to support the OSC.

Reassess each team's radiological protection status after accountability, after major changes in plant conditions and at emergency classification upgrades

"* Evaluate plant environment.

"* Provide recommendations to OSC management concerning the safety aspects of Emergency Response team tasks.

ACTIVATION AND OPERATION OF THE SQN OPERATIONS SUPPORT CENTER 1

EPIP-7 E PIP-7 Rev. 20 Pacie 30 of 37 APPENDIX N Page 1 of 1 PERSONNEL POOL MANAGER CHECKLIST INITIAL ACTIVATION OF THE OSC Time/

Initials

1.
2.
4.
5.

6.

Swipe Accountability Reader.

Fill out the organization/Staffing Chart and obtain OSC badge.

Establish a log of communications and activities.

Establish communications with the Assistant OSC Manager and/or Briefer.

Locate all teams previously tasked and ensure assignment of Team Tracking Letter designation for tracking and debriefing.

Ensure at least two teams are fully staged outside OSC in the cafeteria.

OPERATIONAL RESPONSIBILITIES

"* Form teams as requested by the OSC.

"* Manage personnel in the OSC Staging Area by:

1. Directing personnel to enter keycards into the Accountability Card Reader (at cafeteria entrance).
2. Directing responders (potential OSC teams) to check-in with the HIS-20 Operator.
3. Requiring potential/actual OSC Team members to dress out.
4. Maintain command and control (quiet/orderly) in OSC Staging Area.

"* Recover personnel for future members.

"* Ensure at least one team on standby at all times.

"* Validate qualifications of team members by completing the information on Appendix R, including remaining allowable dose (RAD) il m

I I

ACTIVATION AND OPERATION OF THE SQN OPERATIONS SUPPORT CENTER APPENDIX 0 Page 1 of 1 DCRM Coordinator Time/

Initials 1,

2.
3.
4.
5.

6.

Swipe Accountability Reader.

Fill out the Organizational/Staffing chart and obtain OSC badge.

Notify the OSC Manager of arrival.

Establish a log of activities.

Log in on computer.

Notify the Assistant OSC Manager and/or Briefing Teams DCRM information is available on request.

OPERATIONAL RESPONSIBILITIES

"* Provide DCRM expertise as needed.

"* Provide drawings, documents, vendor manuals as requested.

"* Assist in OSC logistics as requested.

1 EPIP-7 SEPIP-7 Rev. 20 Paqe 31 of 37 I

!1 I

APPENDIX P Page 1 of 1 OSC Materials Coordinator Time/

Initials

1.
2.
3.
4.
5.
6.

7.

Swipe Accountability Reader.

Fill out the Organizational/Staffing chart and obtain OSC badge.

Notify the OSC Manager of arrival.

Establish a log of activities.

Log in on computer.

Establish contact Power Stores Personnel at X-7155.

Notify the Assistant OSC Manager or Briefing Teams material expediting information is available on request.

OPERATIONAL RESPONSIBILITIES

"* Provide coordination between Power Stores and OSC.

"* Provide materials as expeditiously as possible for emergency response.

"* Operate computer to determine materials availability.

"* Coordinate safety of warehouse personnel with the OSC Manager and RADCON Supervisor.

V II

APPENDIX Q Page 1 of 1 This Appendix has been canceled The information is available in the REND

APPENDIX R Page 1 of I PERSONNEL POOL MGR. LOG CRAFTSMAN SECTION NAME SSN CRAFT HIS-20 OPERATOR SECTION HIS-20 OPERATOR:

TLD#

  • RAD SCBA RESP REP mRem QUAL QUAL TRAINED 0 YES 11 YES D YES D NO LINO 11 NO PERSONNEL POOL MGR SECTION CRAFT:

RAD ASSIGNED TO BRIEFER COMMENTS mRem*

TEAM #

(Same as above)

  • RAD mRem can change depending on assigned Team task. RAD will need to be verified after completion of Assigned Team task before assignment to another team.

Appendix S Page 1 of 2 OSC Roster NOTIFIED NAME (Print)

SIGNATURE SSN ERO POSITION REPLACEMENT AND FFD NAME (Print)_

YES NO I__

- i I-t t i I

I

+

I It I

4 4

1 t1 I __________________

I I.

1-1 -1



I __________________

I

+

t 1-t-L I

+

t TT I

I 4

I I

4 I

I

_________4I I

i I

I~

I I

I 1 1 1

1

-4 t

t I~

I__

I i

i i

I_

I i

F -t

-i 4 _________________

1 4

tt EP Records Coordinator:

Date of OSC Activation:

1 4

F TT I

--F I -

I

EMERGENCY RESPONDER NOTIFICATION FORM Fitness for Duty Person Calling Date rTT t.i..

1 1 Cnmment

Time Time Needed to Reoort nava yFUI Consumed Alcohol 5 Hrs.

Prior to Report Time?

YES NO Are you Fit for Duty?

YES NO Called__

4 r

F f

4 I

1-1-4

______________ I I

I I-i-t I

I l-*l-t I.

1 1-1 I

1 1

4.

4 4 1

+

t 4

4-4 t

4

4.

F 1

4 1

1-1 1

1 4

I I-I-i

_______________ I F

I

-L I____

i i

F-

-i Name 1

4

4.

4 1-4-1 I _____

.11 4

h i I____

1 1

4 I

I I

+

1 1

4 I

______________ I I

i-I-I

.1

  • 1 I

i-I-I

__I J

L==

=

a L ____

14 Comments...

SOURCE NOTES REQUIREMENTS STATEMENT SOURCE DOCUMENT NP Radiological Emergency Plan (NP-REP)

IMPLEMENTING STATEMENT

TENNESSEE VALLEY AUTHORITY SEQUOYAH NUCLEAR PLANT EMERGENCY PLAN IMPLEMENTING PROCEDURE EPIP - 13 DOSE ASSESSMENT Revision 2 QUALITY RELATED PREPARED BY:

W. C. Pegaram.

RESPONSIBLE ORGANIZATION:

Emer-qency Preparedness APPROVED BY:

J. Randy Ford.

EFFECTIVE DATE:

10/01/2001 Level of Use:

Reference

SQN DOSE ASSESSMENT EPIP-1 3 E PIP-1 3 Rev. 2 Page 2 of 14 Revision History Rev Date Reason for Revision 0

12/19/2000 Initial Issuance 1

6/11/2001 Revised Appendices A, B and C to utilize the new source term and methodology from CECC-EPIP-8 2

10/01/2001 Corrected typographical errors in Appendix B. (PER 01-008641-000)

TABLE OF CONTENTS Section Title.........................................................

Page T a b le of C o nte nts.............................................................................................................

1.0 PURPOSE.............................................................

4

2.0 REFERENCES

4 2.1 Interface Documents................................................................

4 3.0 INSTRUCTIONS..........................................................................

4 3.1 C hem istry R esponse.............................................................................................

4 3.2 Request for Dose Assessm ents........................................................................ 4 3.3 Dose A ssessm ent Process.................................................................................

5 4.0 R E C O R D S............................................................................................................

5 4.1 Q A Records.................................................................................

5 4.2 Non-QA Records................................................

5 4.3 T raining R e co rd s...................................................................................................

APPENDIXES Appendix A, ICS Dose Assessment................................................................

6 Appendix B, Manual Dose Assessment............................................................

7 Appendix C, TEDE Factor (Rem/hr per 1iCi/s).....................................................

10 Appendix D, Plant Total Gaseous Rad Release Rate...................................... 11 Appendix E, Steam Generator Release Rate Adjustment................................

12 Appendix F, Calculation of Plant Total Gaseous Rad Release Rate............. 13 SOURCE NOTES....................................................................

14

1.0 PURPOSE This procedure describes the initial dose assessment methodology to be used in the event of a radiological emergency until the Central Emergency Control Center (CEOC) dose assessment staff starts performing this function. Additionally, the procedure provides Chemistry a manual method to determine the site noble gas release rate for determination of emergency classification in accordance with EPIP-1. The procedure can be performed in any mode and is a best estimate of the release rates for comparison with the limits contained in the Emergency Plan Implementing Procedures (EPIPs).

The Integrated Computer System (ICS) dose assessment must be used in conjunction with this instruction if a release is occurring through the main steam safety valves or atmospheric relief valves (PORVs) of the main steam system (the ICS code RAD025 does not include this release pathway).

2.0 REFERENCES

2.1 INTERFACE DOCUMENTS A.

EPIP-14, "Radiological Control Response" B.

CECC-EPIP-9, "Emergency Environmental Radiological Monitoring Procedures" C.

0-TI-CEM-030-030.0, "Manual Calculation of Plant Gas, Iodine, and Particulate Release Rates for Offsite Dose Calculation Manual (ODCM) Compliance" D.

TI-18, "Radiation Monitors" E.

EPIP-1, "Emergency Plan Classification Matrix" 3.0 INSTRUCTIONS 3.1 Chemistry Response The designated Chemistry personnel are responsible for managing the activities of the Chemistry Lab.

A. Upon request of the Shift Manager (SM) or Site Emergency Director (SED), Chemistry personnel shall determine the plant total gas release rate (source term) using Appendix D.

B. Upon request of the SM or SED, Chemistry personnel shall determine the doses associated with the plant total gas release rate calculated in section A above.

C. In the event of a CECC activation, any source term assessments and associated dose assessments should be reported to the CECC dose assessment staff when the CECC is staffed and further dose assessments using this procedure should cease.

3.2 Requests for Dose Assessments The performance of these assessments may be initiated by request of the SM if (1) ICS point "RAD025" is not available or (2) the "dose assessment' feature on ICS is not functional or (3) if a release is occurring through the main steam safeties or atmospheric relief valves (PORVs) or (4) at the discretion of the SM.

3.3 Dose Assessment Process NOTE: Emergency Classification may be required based on this data. If data cannot be independently QV&V, then immediately carry to the Main Control Room.

3.3.1 If ICS is available and not excluded by Section 3.3.2, then conduct a dose assessment using Appendix A.

3.3.2 If ICS is unavailable or this is a Special Case - Steam Generator Release Through Safeties or PORVs, then conduct the dose assessment using Appendix B with support from Appendices C and D as appropriate.

4.0 RECORDS 4.1 QA Records None 4.2 Non-QA Records The materials generated in support key actions during an actual emergency are considered Lifetime retention Non-QA records. Materials shall be forwarded to the EP Manager who shall submit any records deemed necessary to demonstrate performance for lifetime storage.

The materials generated in support key actions during drills and exercises are considered Non-QA records. These records shall be forwarded to the EP Manager who shall retain records deemed necessary to demonstrate six-year plan performance for six years and shall retain records from other required drills for two years.

4.3 Training Records Materials generated as part of training need not be retained.

Appendix A ICS Dose Assessment Release Point(s) -

Shield Bldg, Aux Bldg, Service Bldg, Turbine Bldg, Condenser, (SG via PORV/Safety use Appendix B)

If."nklnnwn or unsure. use 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> A2 Lxpecteu uuuauv, -

WIN A3 Accident Release Type Assumption SG = Tube Rupture/Leak, Release via Steam Generator ShId Bldg = LOCA, Shield Building Release - Filter Systems Normal Other = Fuel Handing, WGDT, LOCA with Containment Bypass, or Unfiltered A4 Core Exit - Hottest Thermocouple - from ICS Screen NSITCMAP A5 Core Damage Level Assumption Peak Thermocouple since start of event.

Gap = Peak Thermocouples (A4) <700F Overtemp = Peak Thermocouples (A4) 700F-1200F Melt = Peak Thermocouples (A4) >1200°F A6 TIEDE Multiplier - select based on determinations from A3 and A5 (A3 4, A5 -)

Ga OverTemp Core Melt Shield Bld 1.0 1.1 1.4 SG >33% Level 9.1 16 49 SG <33% Level 48 29 75 Unfiltered/Byass 13 17 52 B. Dose Assessment B1 Go to ICS Screen REP Menu (REP) then select DOSE ASSESSMENT.

Press RECALCULATE button. Enter the information from that screen in the first blank of each line below.

Site Boundary TEDE Hourly Dose 2.00 Mile TEDE Hourly Dose 5.00 Mile I

Hiourly uuD ___

TEDE Hrs (A2) iyroid Committed Dose Equivalent (CDE) calculatio CDE Multiplier - select based on determinations from A3 and A5 (A3)'4' A5 Gap OverTemp Shield Bldg 0.11 0.043 SG >33% Level 2.6 0.64 SG <33% Level 13 8.3 Unfiltered/Bypass 6.2 2.0 Calculate Iodine CDE Doses.

Obtain the TEDE Dose from Block B1 and CDE Multiplier from Block C1.

Site Boundary CDE Dose 2.00-4.99 mi CDE Dose (circle all that apply)

(circle all that apply) hours SG - Narrow Level >33%

SG - Narrow Level <33%

Shield Bldg - Filtered Other - Unfiltered or Bypass degrees F Gap Overtemp TEDE Multiplier Site Boundary _

Rem 2.00 Mi

'Rem 5.00 Mi Rem I

Thyroid CDE Dose Site Boundary _

Rem 2.00 Mi Rem 5.00 Mi Rem 5.00-1U.U mi C, Uu-I TEDE Dose (B1)

CDE Multiplier (Cl)

"-ýOTE: Emergency Classification may be required based on this data. If necessary, hand carry to the Main Control Room.

Report Release Rates and Dose Values obtained in Blocks B1 and C2 to SM and/or SED Performed/Reported By:

Initials Date / Time Li C. T r c1 C2 I

Rfi W

liar A

.v.uup,.*,

y /

Appendix B Page 1 of 3 Manual Dose Assessment A. Key Information

[ Al I Release Point(s) -

Shield Bldg, Aux Bldg, Service Bldg, Turbine Bldg, A2 A3 (circle all that apply)

Condenser, or SG via PORV/Safety Expected Duration - If unknown or unsure, use 4 hours4.62963e-5 days <br />0.00111 hours <br />6.613757e-6 weeks <br />1.522e-6 months <br /> hours Accident Release Type Assumption SG - Narrow Level >33%

SG = Tube Rupture/Leak, Release via Steam Generator SG - Narrow Level <33%

ShId Bldg = LOCA, Shield Building Release - Filter Systems Normal Other = Fuel Handing, WGDT, LOCA with Containment Bypass, or Unfiltered Shield Bldg - Filtered O3ther - Unfiltered or Bypass A4 Core Exit - Hottest Thermocouple - from ICS Screen NSITCMAP A5 Core Damage Level Assumption Peak Thermocouple since start of event Gap = Peak Thermocouples (A4) <700F Overtemp = Peak Thermocouples (A4) 700F-1200F Melt = Peak Thermocouples (A4) >1200°F A6

-,TEDE Multiplier - slect based on determinations from A3 and A5 (A3)4, AS 5-Ga OverTemp Core Melt Shield Bld 1.0 1.1 1.4 SG >33% Level 9.1 16 49 "SG <33% Level 48 29 75 Unfiltered/Byass 13 17 52 B. Dose Assessment Determine Plant Total Gaseous Rad Release Rate in uCi/sec.

I Use Appendix D.

B2 B3 r4 Determine 46 meter 15 min avg windspeed in mph by using the preferred list below. (See page 3 of 3 of this Appendix for additional instructions)

(1) ICS Screen METDATA then press DOSE CALC MET DATA button, OR (2) TSC Met Data (convert using mph = m/s

  • 2.2), OR (3) =m/s *2.2 WBN Met Tower (call WBN), OR (4) National Weather Service (423) 586-8400, OR (5) Default - use 1 m/s (2.2mph)

Determine 46-10 meter Stability Class (A-F) by using the preferred list below.

(See page 3 of 3 of this Appendix for additional instructions)

(1) ICS Screen METDATA then press DOSE CALC MET DATA button, OR (2) ICS Screen MTDATA6 to get delta-T and use Appendix B Table 1, OR (3) ICS Screen METDATA to get temperatures and use Appendix B Table 1, OR (4) WBN Met Tower (call WBN), OR (5) Default - Use Stability Class E Calculate TEDE Doses. (See page 3 of 3 of this Appendix for instructions)

Obtain TEDE Factor (rem/hr per uCi/s) from Appendix C and calculate.

Site Boundary TEDE 2.00-4.99 mi TEDE 5.00-10.0 mi TEDE TEDE Factor (Apdx C) rem/hr per uCi/s Hrs (A2)

Multiplier (A6) uCi/s (B1)

Continued Next Page degrees F Gap Overtemp TEDE Multiplier uCi/sec mph I1 Stability Class Site Boundary Rem 2.00 Mi Rem 5.00 Mi Rem I

Appendix B Page 2 of 3 Manual Dose Assessment C. Thyroid Committed Dose Cl C2 CDE Multiplier - select based on determinations trom Xý ana Ao (A3)4, (A5)--)

Gap OverTemp Core Shield Bldg 0.11 0.043 0.0 SG >33% Level 2.6 0.64 0.'

SG <33% Level 13 8.3

6.

Unfiltered/Bypass 6.2 2.0

1.

Calculate Iodine CDE Doses.

Obtain the TEDE Dose from Block B4 and CDE Multiplier from Block C1.

Site Boundary CDE Dose 2.00-4.99 mi CDE Dose 5.00-10.0 mi CDE Dose 1 -U U~e**'

  • ,L*

~lu~a**

CDE Multiplier Thyroid CDE Dose Site Boundary _

Rem 2.00 Mi Rem 5.00 Mi Rem NOTE: Emergency Classification may be required based on this data. If necessary, hand carry to the Main Control Room.

Report Release Rates and Dose Values obtained in Blocks B4 and C2 to SM and/or SED

-jrformed/Reported By:

Initials Date / Time Table 1 Stability Class Manual Calculation Worksheet Stability Class b 46-10 m Delta-T Delta-T OF < minus 1.3 OF A

For raw temperatures, use 15 min. average Delta-T OF > minus 1.3 < minus 1.2 F B

if available, otherwise use Instantaneous.

Delta-T OF > minus 1.2 < minus 1.0 OF C

Delta-T OF > minus 1.0 < minus 0.4 'F D

Temp at 46 meters =

F Delta-T OF > minus 0.4 < 0.9 OF E

Temp at 10 meters =

F Delta-T OF > 0.9 < 2.6 F F

Delta-T (46m -10m) -

=

F Delta-T °F > 2.6 F G

Stability Class from Table 1 =

TEDE Dose tD-t) u F

nr-KA Ri li-ffýl I "A"

Appendix B Page 3 of 3 Manual Dose Assessment Expanded instructions for performing calculations.

B2.

Option 1: On the affected Unit ICS Main Menu click on "SECONDARY MIMICS" button. On the Secondary Mimics page click on "MET DATA" button. From the "MET-TOWER LINK" page or the "DOSE CALC MET DATA" page record the 46 Meter Ave. Wind Speed (15 Min) in mph.

Option 2: From the TSC Data System obtain the latest weather data printout (see TSC Users Manual). Remember you must multiply 15 min average wind speed in m/s by 2.2 to obtain mph.

Option 3: Call the National Weather Service in Morristown, Tn. for wind speed in mph.

Option 4: If no other data is available, use a default value of 2.2 mph (1.0 m/s).

B3.

Option 1: On the affected Unit ICS Main Menu click on "SECONDARY MIMICS" button. On the Secondary Mimics page click on "MET DATA" button. From the "MET-TOWER LINK" page click the "DOSE CALC MET DATA" and record the 46-10 Meter Stability Class PID 0Y2319A (A-F).

Option 2: From the "MET-TOWER LINK" page click on the "STABILITY DELTA-T's" button note the

[VERTICAL AIR TEMP DELTA-T 46-10 METERS (INSTANTANEOUS)] and refer to Table

1.

Option 3: From the "MET-TOWER LINK" page obtain the [10 METER AIR TEMP] value and the [46 METER AIR TEMP] value and refer to Table 1.

Option 4: If no other data is available, use a default value of Stability Class E.

B4. From Appendix C, find the appropriate stability class. Then, find the desired distance range in miles on the vertical scale and the wind speed on the horizontal scale. Record the corresponding TEDE FACTOR the appropriate section B4 blank. For wind speeds that fall between the values in the table, default to the lower wind speed. This is the more conservative value.

DOSE ASSESSMENT EPIP-1 3 Rev. 2 Page 10 of 14 APPENDIX C TEDE FACTOR (rem/hr per iCCi/s)

Stability A

miles 2.2 mph 4.4 mph 6.6 mph Site Bdn/

1.6E-09 8.0E-10 6.4E-10 2 mi 5.5E-10 2.8E-10 2.2E-10 5 mi 7.5E-1 1 5.2E-1 1 5.2E-1 1 Stability B

miles 2.2 mph 4.4 mph 6.6 mph Site Bdr 7.5-09 3.7E-09 3.IE-09 2

7.2E-1 0 3.6E-1 0 2.9E-1 0 5

T.9E-1 1 6.8E-11 6.7E-11 Stabilit miles Site Bdr 2

5*

Stabili

v r

wind speed I



I



I 44 

4'') 'nnh IS A mflh 1 lb mon i.o mon LL 011.11' I 0.0 p

i

'I14n I





I 4 OIA I

198 mDh 1 22 mph 8.8 mph mp 2 Mh 4.8E-10 3.2E-10

.l~f

.2E--l 010l

1.

. Of-1 78" E-11 fE 11 9

1=1 3OF1 1 2

5.1 E-1 1

5.

6E11 OE-11 1

35-wind speed 11 mnh 7 mon 1 t4 mon

(.0 mpo 4 1mh I

mFJ1 15 mphW 1 U-~

0~-I

-E09 311-09 1 2E-09 1OE-09 104 3E1 2E- 0 1 19 71-Zmph~I I

.66E-1 I

OE-1 1 S 3E-1 I wind speed ry 2.2E-08 11.1 E-0 9.05-09 6.7E-09 4.3E-09 I3.9E-09 3.5E-09 I3.0tE-09 I2.6E--09

.E ty D

wind speed miles 2.2 mph 4.4 mph 6.6 mph Site Bdr 6.3E-08 3.2E-08 2.6E-08 2

1.0E-08 5.4E-09 4.3E-09 S

8.3E-10 5.8E-10 5.7E-10 Stability E

miles 2.2 mph 4.4 m h 6.6 mph Site Bdrn 1.1 E-07 5.5E-08 4.4E-08 2

2.1E-08 1.0E-08 8.3E-09 5

1.8E-09 1.2E-09 1.2E-09 Stability F

miles 2.2 mph 4.4 mph 6.6 mph Site BdrI 2.2E-07 1.0E-07 8.3E-08 2

4.9E-08 2.5E-08 1 2.OE-08 5

4.6E-09 3.2E-09 3.1 E-09 8.8 mph 11 mphI12mh 1

5*zmp

.,4 mph 17.6 mpH

,198,,h"

72. r" 1.9E-08 1.2E-08 1.1 E-08 1 OE-08 8.8E-09 7.5E-09 6.3E-09 3.2E-09 2.2E-09 1.9E-09 1.7E-09 1.5E-09 1.3E-09 1.0E-09 5.6E-10 5.6E-10 5.0E-10 4.SE-10 3.9E-10 3.4E-10 2.8E-10 wind speed 00,I, 44.,.,h V49mnh I

11.0 mon

.L IIIFJt I 1 O

IIJI II11 13' mpht' 4..

.. mp E.~U I 1

A-.

~noI~~10 3EC 09 3 8E-09O 3AE.fQ I

0--09I.~

wind speed 132mh 154 mph mp h

22 Mh 3OI0 O

A OA

-L-00 0 F.O XW-O "71:-n Ii t-UI 24-O 1

3OE09

- J 21E-092L SQN

1 Stability G

wind speed miles 2.2 mph 4.4 mph 6.6 mph 8.8 mph 11 mph 13.2 Mh 15.4 mph 17.6 mph 19.8 mp 7h 2 Mph Site Bdry 4.8E-07 2.3E-07 1.8E-07 1.4E-07 9.OE-08 8.1 E-08 7.2E-08 6.3E-08 5.4E-08 4.6E-08 2

1.1 E-07 5.1 E-08 4.OE-08 3.OE-08 2.0E-08 1.8E-08 1.6E-08 1.4E-08 1.2E-08 1.OE-08 5

1.1 E-08 7.5E-09 7.3E-09 7.2E-09 7.OE-09 6.3E-09 5.6E-09 4.9E-09 4.1 E-09 3.4E-09 3,

E,:-

j 1 1 mnh 4 AI= _r*Q 4 A[* 4rm 13

  • mDh 1 *I:; -r'l*

'1 ",(I,--1 I 1 u.rL-i i v.vb-i i

wind speed I b.4 mDn 1 ?F-09 "1 ]p_'l l ]

SR mnh S71:_1 1 17.6 mph f DE--U[]

2.9E-09t 8l[l 6-10U 19.8 mTp[h I.

  • L--IJIJ 2_.Eo--

7.or' I mph.llJI

.1 E-08 21 E09 A OF-1 0 1:* 9 mnh

")

[ I1.._1 IX 3 BI--O9 1 1 I=.ri*

15 4 toDD "1 PIl'.l It'*

3.4h_-U*l g BE-IO 0 Q *h SqCRQ 4 '*E t3(*

11 rnnh A 91=_t'1Cl 10 I::: J3Q 2E-08

.49E09 15E-09 "1 "i /J. mnn

-<*L*-[I*

/.*1- -U*

? 4F-Og II ID [IIUII

.5 [ I r--ut"J 6.8E--09

.IF n--U p*gIIII L J3 E--U{;*

5.8E--09 1.R'-o O 71:: _£*Q S/31:::_*Q R RF-Og 9 71=.£1Q 2E09 E-n9 8E-1 0 l*.U mDn z* fllpll lO. 9 mnh 1 i31::.113

  • 1 *;I---1 I 1K
  • mnh "2 *'*1..---1 I I

.q OE-1 1

& I I1--- I I 1* [* mDrl

/

/if--It!

(.*l---] 1

.'1 31-- I I

  • - Ar-44 t 1 l:::_lr*

S4E 41 5

1 1

.5E-1 1 I *E-IU 6.7Er-11 1 1.o mpn 1.UI--U*

I [JE-- LU 4.6El-1 1 19.8 lmpJI

  • .*1-- IU U. l F--.-- I I

'.OI'-II

/.Or--IU

.2E-1 I

APPENDIX D Plant Total Gaseous Rad Release Rate IF RAD025 Functional Monitored Release Rate from ICS "SHOW RAD025" command

=

uCi/s Steam Generator Release Rate Adjustment using Appendix E

=

uCi/s Total Release = summation of the above values

=

uCi/s Performed By:

Initials Date / Time IF RAD025 Not Functional but Effluent Rad Monitors Functional Unit 1 Shield Bldg 1-RE-90-400 OR UNID 1R9102A (pCifsec)

=

uCi/s Unit 2 Shield Bldg 2-RE-90-400 OR UNID 2R9102A (pCi/sec)

=

uCi/s Aux. Bldg.

x x 8.7E-6 =_uCi/s 0-RM-90-1 01 B OR OR0020A (cpm) 0-FE-30-174 OR 0F2704A (cfm) unit conversions Service Bldg.

x x 8.7E-6 =_uCi/s 0-RM-90-132B OR OR0011A (cpm) 0-FE-90-132 OR 0F2702A (cfm) unit conversions Ul Condenser_

x x 26.55 =

uCi/s 1-RM-90-255 or 256 OR 1-FT-2-256 OR 1F2700A (cfm) unit conversions 1 R9022A OR 1 R9023A (mR/h)

U2 Condenser x

x 26.55

=_uCi/s 2-RM-90-255 or 256 OR 2-FT-2-256 OR 2F2700A (cfm) unit conversions 2R9022A OR 2R9023A (mR/h)

Steam Generator Release Rate (if necessary - use appendix E)

=

uCi/s Total Release = Summation of releases through rad monitors above

=

uCi/s Performed By:

Iiilae/Tm Initials Date / Time

APPENDIX E Steam Generator Release Rate Adjustment Adjustment of Plant Total Gaseous Rad Release Rate for Steam Generator Releases This calculates the release from a Steam Generator (SG) with release to environs.

Steam Lines Flowrates (Ibm/hr) are considered zero below unless the SM/US has confirmed both:

(1) a tube leak/rupture exists on the specified loop and (2) a release is potentially on-going through the main steam safety valves or PORV's on the specified loop.

INCLUDE DATA for SGs that meet both I and 2 above; Otherwise NIA.

UNIT 1:

SG#1, (pCi/cc) x MLB/HR (1-RM-90-421) OR 1R9027A (1-FE-1-3) OR 1F0405A OR 1F0406A SG#2, (pCi/cc) x MLB/HR (1-RM-90-422) OR1R9028A (1-FE-1-10) OR 1F0425A OR 1F0426A SG#3, _(pCi/cc) x MLB/HR (1-RM-90-423) OR 1R9029A (1-FE-1-21) OR 1F0445A OR 1F0446A SG#4, __

(PCi/cc) x MLB/HR (1-RM-90-424) OR 1R9030A (1-FE-1-28) OR 1F0465A OR 1F0466A x 106 x 4.24 =

uCi/s unit conversions X 10 6 x 4.24 =

unit conversions x 106 x 4.24 =_

unit conversions X 106 x 4.24 =

unit conversions UNIT 2:

SG#1, _(pCi/cc) x MLB/HR x 106x 4.24 =_uCi/s (2-RM-90-421) OR 2R9027A (2-FE-1-3) OR 2F0405A OR 2F0406A unit conversions SG#2, (pCi/cc) x MLB/HR x 106 x 4.24 = _

uCi/s (2-RM-90-422) OR 2R9028A (2-FE-1 -10) OR 2F0425A OR 2F0426A unit conversions SG#3, (pCi/cc) x MLB/HR x 106 x 4.24 = _

uCi/s (2-RM-90-423) OR 2R9029A (2-FE-1-21) OR 2F0445A OR 2F0446A unit conversions SG#4, (pCi/cc) x MLB/HR x 106 x 4.24 = _

uCi/s (2-RM-90-424) OR 2R9030A (2-FE-1-28) OR 2F0465A OR 2F0466A unit conversions L

Additional Releases from Steam Generators (sum above releases)

=

uCi/s (Record results in appropriate blank from Appendix D)

Unit conversions based on 3600 s/hr, 28317 cc/ft3, 0.53916 ft3/Ibm for steam at 524F.

Performed By:

Initials Date / Time uCi/s uCi/s uCi/s

APPENDIX F BASIS: Calculation of Plant Total Gaseous Rad Release Rate Unit conversion factor 26.55 is based on radiation monitor efficiency of 0.05625 uCi/cc per mR/h (from energy calculation SQNAPS3-1 00) and 472 cc/sec per cfm (see REP basis 7.1 SAE)

Units conversions factor of 8.7E-6 = 5.42E+7 CPM per uCi/cc (from table below)

  • 28317 cc/ft3
  • 0.016 min/sec KR-85 KR-85M KR-87 KR-88 XE-131M XE-1 33 XE-133M XE-1 35 XE-138 To

rwi Conversion uCilcc to PM Nuclide GAP Release Mix llmmg' ='L 4A C

6.82E+04 6.82E+04 3.16E+06 6.42E+06 9.23E+06 6.43E+04 7.41 E+06 5.84E+05 4.41 E+06 2.29E+07

.11 1.1 E-03 4.6E-02 9.2E-02 1.3E-01 1.9E-03

1. 1E-02 6.3E-02 3.3E-01 6.26E+07 6.90E+07 7.OOE+07 7.OOE+07 3.40E+07 2.27E+07
5. 10E+07 7.00E+07 7.00E+07



-'-I 401

 A9F.bflJ I!IJF II I I I UI (based on NUREG 1465 Gap Release Mix and TI -18 factors) tals 1

u---uu.............

t A Ali=+nl TYf.JHI I I-I O

  • 11 d't it" J. irlllr*

N mr-%j 1 &*0 NU Kr'l.1 i*og Conversion uCi/cc to CP Lei..Vl

SOURCE NOTES REQUIREMENTS STATEMENT NP Radiological Emergency Plan (NP-REP)

Appendix A - C.1 Appendix B - C.1 SOURCE DOCUMENT 99-002929-000 99-002929-000 IMPLEMENTING STATEMENT Manual calculation for Thyroid CDE to match ICS.

Manual calculation for Thyroid CDE to match ICS.

TENNESSEE VALLEY AUTHORITY SEQUOYAH NUCLEAR PLANT EMERGENCY PLAN IMPLEMENTING PROCEDURE EPIP-14 RADIOLOGICAL CONTROL RESPONSE Revision 17 QUALITY RELATED PREPARED/PROOFREAD BY:

Bill Peapra RESPONSIBLE ORGANIZATION: Emergency Preparedness APPROVED BY:

J. Randy Ford EFFECTIVE DATE:

10/01/2001 Level Of Use:

Reference

REVISION DESCRIPTION:

Rev Date D

tion 12/19/2000 10/01/2001 Intent Change Removed Dose Assessment from EPIP-14 to new EPIP-13. Updated KI issuance to allow tablet by tablet issuance versus 10 day course. Deleted specific KI information sheet due to change of vendor and FDA information sheet is now part of packaging. Added record retention information. Required manual Radiation Monitor data collection only if ICS is non-functional. Clarified that spraying water is treated same by RADCON as standing water from a personnel protection standpoint. Modified directions associated with assembly siren to be consistent with EPIP-7. Revisions are not shown due to extent of the changes.

Corrected section 3.1.A from Appendix E to Appendix D. (PER 01-008641-000) 1 16 17

C01 4DDA I

RADIOLOGICAL CONTROL RESPONSE Rev. 17 Paae 3 of 16 Page Table of Contents............................................................................................

.3 1.0 PURPOSE.................................................................................

4

2.0 REFERENCES

4 2.1 Developm ental Docum ents.....................................................................................

4 3.0 3.1 3.2 3.3 3.3.1 3.4 3.4.1 3.5 3.5.1 3.6 3.6.1 3.7 3.8 3.9 4.0 4.1 4.2 4.3 INSTRUCTIONS..........................................................................................................

4 Initiation of an Alert or Higher Declaration..............................................................

4 TSC RADCON Manager Responsibilities..............................................................

5 Activation of the Operations Support Center..........................................................

6 OSC RADCON Supervisor....................................................................................

6 RADCON Lab Responsibilities................................................................................

7 Designated RADCON Shift Supervisor...................................................................

7 Chemistry Response................................................................................................

8 Designated Chemistry Personnel................................................................ 8 General Response...................................................................................................

8 All RADCON Personnel...........................................................................................

8 Issuance of Potassium Iodide (KI).........................................................................

10 Use of Silver Zeolite Cartridges..............................................................................

10 Personnel Decontamination and Facilities...............................................................

10 R E C O R D S...................................................................................................................

1 1 Q A R e co rd s.................................................................................................................

1 1 Non-QA Records....................................................................................................

11 Other Records............................................................................................... 11 APPENDIXES Appendix A Inplant Radiation Monitors..............................................................

12 Appendix B Potassium Iodide Issue Report........................................................

12 Appendix C Occupational Thyroid Dose From Inhalation of Iodine-131............. 14 Appendix D Fitness For Duty Program Admin Call-In Sheet............................... 15 SOURCE NOTES....................................................................................................

16 SQN

`i-!LE OF CONTENTS Section Title I

I

SEPIP-14 SQN I

RADIOLOGICAL CONTROL RESPONSE Rev. 17

-Page 4 of 16 1.0 PURPOSE To describe the actions and responsibilities of Sequoyah's Radiological Control (RADCON) and Chemistry Sections in the event of a radiological emergency.

2.0 REFERENCES

A.

EPIP-7, "Activation and Operation of the Operations Support Center (OSC)"

B.

EPIP-8, "Personnel Accountability and Evacuation" C.

EPIP-13, "Initial Dose Assessment" D.

CECC-EPIP-9, "Emergency Environmental Radiological Monitoring Procedures" E.

RCI-20, "Radioiodine Monitoring During Accident Conditions" 2.1 Developmental Documents A.

EPIP-6, "Activation and Operation of the Technical Support Center B.

EPIP-1 0, "Medical Emergency Response" 3.0 INSTRUCTIONS 3.1 Initiation of an Alert or Higher Declaration Upon initiation of an Alert, Site Area Emergency, or General Emergency, the RADCON and Chemistry Sections shall assemble a specific number of personnel as described below.

A. RADCON: During normal and off-shifts a Radiological Emergency Plan (REP) activation will be announced over the public address system or the emergency sirens may be activated and the Emergency Paging System (EPS) will be activated. The RADCON Lab will be contacted by the Shift Manager or designee. RADCON Shift Supervisor (RCSS) will determine the number of ANSI qualified RADCON personnel currently onsite. He shall ensure that at least a total of eight (8) (not counting him/herself) are available onsite within approximately 30 minutes and a total of least fourteen (14) (counting him/herself if qualified) are available onsite within one hour [six (6) additional ANSI qualified RADCON personnel within 30 minutes]. Call ins shall be in accordance with Appendix D ensuring that Fitness For Duty questions are asked and response documented. Additional RADCON support personnel may need to be called in using Appendix D.

B.

CHEMISTRY: The Chemistry Lab will be contacted by the Shift Manager or designee. Chemistry Shift Supervisor (CSS) will determine the number of chemistry technicians currently (counting the CSS if qualified) onsite and shall ensure that at least a total of two (2) chemistry technicians are available onsite within approximately 30 minutes and at least a total of three (3) are available onsite within one hour if the Dose Assessment function has not been assumed by other staff. Additional (above the minimum required staffing) Chemistry support personnel may need to be called in, use Appendix D to document.

I EPIP-14 SQN RADIOLOGICAL CONTROL RESPONSE Rev. 17 Page 5 of 16 3.1 Initiation of an Alert (Continued)

C.

Chemistry Shift Supervisor (CSS) shall perform Dose Assessment in accordance with EPIP-13, "Initial Dose Assessment" when notified by the Shift Manager or Site Emergency Director.

D.

When the OSC is staffed by the OSC RADCON Supervisor (OSC RCS), the RCSS shall assemble two survey teams and dispatch them to the OSC for briefings and dressout.

E. The TSC and OSC are activated during Alert, Site Area Emergency, or General Emergency or as deemed necessary by the SED.

F. All response teams, except as listed in EPIP-7, will be dispatched from the OSC and should have a RADCON representative as a member. If the Fire Brigade, Medical Emergency Response Team or Damage Control Team is already responding they are not required to return to the OSC to be dispatched, but shall be tracked, briefed, and de-briefed by the OSC in accordance with EPIP-7, Section 3.2.5. RADCON survey teams may be dispatched from the lab but shall be tracked by the OSC.

G. Response teams will be debriefed by the OSC after completing their team assignment.

3.2 TSC RADCON Manager (RCM) Responsibilities The responsibilities and duties of the TSC RADCON representative are detailed in EPIP-6. A summary of the details associated with these responsibilities are provided below.

A. The primary responsibilities of the TSC RCM are to direct onsite radiological surveillance activities, assess inplant and onsite radiological conditions and to make this information available to the Site Emergency Director (SED), the Central Emergency Control Center (CECC) and other TSC personnel as necessary, to support and coordinate protective actions.

B. To facilitate the evaluation of in-plant radiological conditions and to establish trends. Appendix A lists the radiation monitors [i.e., Area Radiation Monitors (ARMs) and Continuous Air Monitors (CAMs)] that may be used.

C. The TSC RCM, together with other TSC personnel, evaluates plant conditions to anticipate future developments and formulates corrective action plans to address actual or postulated conditions. The TSC RCM renders recommendations and advises the SED on radiological issues.

D. The TSC RCM communicates with the CECC RADCON Manager, providing pertinent in-plant radiological data so that appropriate offsite protective actions can be implemented in a timely manner.

E. The TSC RCM maintains communications with the OSC RADCON Supervisor (RCS), constantly evaluating inplant radiological conditions, recommending and identifying the need for radiological surveys.

I EPIP-14 SQN RADIOLOGICAL CONTROL RESPONSE Rev. 17 Page 6 of 16 3.2 TSC RADCON Manager (RCM) Responsibilities (Continued)

F. When directed by the Site Emergency Director, establishes a contamination checkpoint for personnel and vehicles leaving the site.

G. Determines when to issue and to whom to issue Potassium Iodide in accordance with section 3.7.

3.3 Activation of the Operations Support Center 3.3.1 OSC RADCON Supervisor (RCS)

The OSC RADCON Supervisor is a trained and qualified individual designated by the RADCON Manager. The approved alternates are listed in the Call List.

The responsibilities and duties of the OSC RADCON Supervisor are detailed in EPIP-7. A summary of the details associated with these responsibilities are provided below:

A. The primary responsibilities of the OSC RADCON Supervisor are to ensure that, when required, a RADCON tech accompanies each team; detailed radiological briefings are provided to OSC team members; and the OSC Manager, and OSC Staff are knowledgeable of in-plant radiological conditions.

He also serves as the interface between the TSC and the RADCON Lab.

B. Maintains awareness of in-plant radiological conditions and related parameters and reports those conditions to the TSC RCM.

C. Communicates directly with the TSC to coordinate inplant response activities.

Assists in the development of briefing notes, and radiological condition updates.

D. In conjunction with the TSC, identifies the need, location, and extent of radiological surveillance activities required to assess or mitigate the consequences of the accident.

E. All teams are dispatched from the OSC except as described in section 3.1.F.

The OSC RADCON Supervisor is responsible for ensuring that personnel making entries into the plant, including survey teams, are aware of any special precautions, plant conditions, or requirements and are assigned team tracking numbers.

F. Ensure that OSC Team members are instructed to note their Remaining Allowable Dose (RAD) upon exiting the RCA and to provide their current RAD to the Personnel Pool Manager when they return to the OSC. The Personnel Pool Manager will update their RAD in his log. Repetitive exposures of workers should be restricted by substituting other qualified personnel for team members, on reentry, to distribute exposures.

G. Report all survey results as soon as possible to the TSC so they can make recommendations to the proper agencies to initiate any required protective actions.

I EPIP-14 SQN I

RADIOLOGICAL CONTROL RESPONSE Rev. 17 Page 7 of 16 3.4 RADCON Lab Responsibilities 3.4.1 Designated RCSS The designated RCSS is responsible for managing the activities of the RADCON lab.

A. In the event of an Alert, Site Area Emergency, or General Emergency the OSC may become the staging area for entries into affected plant areas.

B. A RADCON Representative should accompany all emergency response teams when initial entries are made into affected plant areas.

C. The RCSS is responsible for ensuring that adequate numbers of RADCON representatives are available, in accordance with paragraph 3.1.A, to support emergency activities and that two (2) survey teams are dressed out and ready for briefing.

D. The RCSS is responsible for preparing and designating an onsite RADCON environmental monitoring team. Team members will prepare and operate the monitoring van in accordance with CECC-EPIP-9. Record all survey results. If results indicate offsite contamination, the survey areas may need to be expanded. Obtain further instructions and perform required surveillance.

E. Until relieved by the OSC RADCON Supervisor, if directed by the TSC, SED, or deemed necessary by the RCSS based on plant conditions, the RCSS will dispatch survey teams to assembly areas, the OSC and TSC to evaluate radiological conditions, monitor radiation levels as conditions dictate and ensure updated habitability surveys are performed. These survey teams will monitor contamination levels as needed both on personnel and floor/equipment areas and implement corrective actions (e.g., decontamination or zoning) as necessary.

F. The RCSS will monitor the RADCON lab for habitability and will coordinate evacuation activities to the alternate RADCON lab location if warranted.

G. The RCSS will ensure all survey teams are tracked by the OSC.

H. The RCSS will ensure DAC-hour exposure when available and RAD calculations are completed and reported to the OSC RADCON Supervisor.

I. The RCSS will ensure respiratory protection is issued as needed.

J. Ensure that HIS-20 entries are properly made and that all dosimetery is properly issued, collected and identified for each worker. Make arrangements to have TLD badges read, as soon as possible.

3.5 Chemistry Response 3

Noble gas concentrations

> 1 x 10-3 pCi/cc Iodine concentrations

> 10 DAC Particulate concentrations

> 10 DAC Standing water >

Precaution: If fuel damage has occurred or is suspected, respirators should be worn due to potentially rapid changes in conditions (ensuring TEDE is ALARA).

SCBA Particulate mask or SCBA (SCBA recommended if >

50 DAC).

Rain suits, rubber boots, Extremity dosimetry F....

3.5.1 Designated Chemistry Personnel The designated Chemistry personnel are responsible for managing the activities of the Chem Lab.

A. Upon request of the Shift Manager (SM), Chemistry personnel shall determine the plant source term that shall be reported to the SM for classification purposes and protective action recommendations to the state.

B. The CSS is responsible for ensuring that adequate numbers of chemistry personnel are available in accordance with paragraph 3.1.B.

C. In the event of an Alert, Site Area Emergency, or a General Emergency, due to a radiological release, a plant total gas release rate (source term) may need to be determined in accordance with EPIP-1 3.

D. The source term shall be reported to the CECC dose assessment staff, when the CECC is manned, for input into a preliminary dose assessment.

E. Projected dose at the site boundary, 2 miles and 5 miles may be determined in accordance with EPIP-1 3.

3.6 General Response 3.6.1 All RADCON Personnel All RADCON personnel should comply with the following:

A. The following precautions should be considered during emergency incidents.

Anticipated Conditions Protective Considerations

EPIP-14 SON RADIOLOGICAL CONTROL RESPONSE Rev. 17 Page 9 of 16 3.6.1 All RADCON Personnel (Continued)

B. If it is necessary to evacuate the RADCON lab, then the personnel stationed in the lab will secure the equipment listed in EPIP-17, Appendix C. This equipment will be brought to the alternate lab by RADCON. This list is a minimum and if time permits and manpower allows, then efforts should be made to transport additional equipment and supplies to the alternate lab. The SED shall be informed when it becomes necessary to evacuate the 690' RADCON lab. If this situation develops, a RADCON Lab will be established adjacent to the TSC. This alternate lab should be set-up in the switchgear room, El 732' or other suitable area, as emergency conditions allow (the TSC RCM is responsible for making this determination). This lab will be equipped with necessary supplies and instrumentation needed to perform minimum radiological surveys and analysis required during an emergency.

C. If severe radiological conditions are suspected, the "Buddy System" shall be utilized.

D. If not already covered under a standing RWP and if time is available, an RWP should be issued to cover entry teams; if not, suitable protective measures should be taken in accordance with established procedures.

E. When accountability is initiated, if not previously accounted for, RADCON personnel shall secure work in a safe manner and proceed to the 690' RADCON Lab and/or other designated assembly areas and swipe into the accountability reader in accordance with EPIP-8. If previously accounted for, contact the RCSS or OSC RADCON Supervisor for directions.

F. RADCON representatives may be sent to the assembly areas to determine if any workers were in the affected plant areas at the time of the event. These people shall be separated from other plant workers and personnel contamination surveys should be initiated for all personnel.

G. If ICS is not functional, radiation monitor readings may be obtained from Control Room personnel or an individual may be sent to the Control Room to record the necessary values. Readings are obtained from panels 0-M-12 and 1/2-M-30 and recorded on Appendix A.

H. As radiation monitor readings are updated, the OSC RADCON Supervisor ensures labs will be contacted to ensure that their status boards are made current.

I. As reports become available regarding the details of the emergency, RADCON personnel shall prepare all necessary equipment needed during recovery and report to the OSC as needed to ready survey or damage control team(s) for entry into the affected area(s).

J. Upon notification from the OSC RADCON Supervisor, the survey team(s) may proceed to the specified area. It should be noted that depending on the type of accident, this initial survey may not be performed until hours or perhaps even days after the event. In this case, procedures may be developed describing the reentry steps to be followed. Other essential personnel may be required to assist in reentry activities.

EPIP-14 SQN RADIOLOGICAL CONTROL RESPONSE Rev. 17 Page 10 of 16 3.7 Issuance of Potassium Iodide (KI)

A. Projected cumulative doses to the thyroid from inhalation of radioactive iodine can be estimated using Appendix C "Occupational Thyroid Dose from Inhalation of I 131."

B. If a person's projected cumulative dose to the thyroid from inhalation of radioactive iodine might exceed 10 rem, the exposed person should be started immediately on KI. Authorization to issue KI is the responsibility of the TSC RCM.

He shall inform the SED prior to issuance.

C. The initial dose of KI should not be delayed and those who begin therapy should continue the KI unless their thyroid dose is determined not to have exceeded 10 rem. A copy of the Food and Drug Administration approved instructions shall accompany issue of KI Dosage schedules and other pertinent information are outlined on the package and should be followed closely.

D. Potassium iodide is stored in the OSC. KI has an approved shelf-life with the expiration date listed. To ensure that the KI supply is valid, these dates will be inspected and the KI replaced as necessary.

E. The issuing agent shall complete the Potassium Iodide Issue Report (Appendix B) for KI issued. A copy of this report will be routed to the TSC RCM in a timely manner.

3.8 Use of Silver Zeolite Cartridges A. During accident conditions noble gas concentrations may be present in significant quantities both inplant and offsite. The collection of these noble gases on charcoal cartridges during iodine sampling will interfere with subsequent iodine analysis.

B. Silver zeolite cartridges are provided for use during periods of high noble gas concentrations. RCI-20 describes the utilization of and lists hazards associated with Silver Zeolite cartridge use.

3.9 Personnel Decontamination and Facilities A. RADCON will use established procedures for personnel decontamination.

Decontamination facilities are available for use by Sequoyah personnel.

B. Contaminated personnel are normally decontaminated at the 690' elevation decon facility. This facility is equipped with a wash sink, shower, and all necessary supplies. These supplies include various decontamination agents and soaps, towels, clean clothing, and other miscellaneous supplies.

C. EPIP-10 contains guidelines for RADCON assistance during a medical emergency or hospital treatment. Contaminated personnel requiring offsite medical attention are treated at the agreement hospital where the staff that has been trained in the handling and care of contaminated patients. Emergency Preparedness maintains a supply cabinet at the hospital's Emergency Room which contains posting materials and various other supplies.

EPIP-14 SQN RADIOLOGICAL CONTROL RESPONSE Rev. 17 Page 11 of 16 4.0 RECORDS 4.1 QA Records 4.2 Non-QA Records The Appendices A, B, or D generated in support of key actions during an actual emergency are considered Non-QA records. These records shall be forwarded to the EP Manager who shall submit any records deemed necessary to demonstrate performance for lifetime storage.

The Appendices A, B, or D generated in support of key actions during a drills and exercises are considered Non-QA records. These records shall be forwarded to the EP Manager who shall retain records deemed necessary to demonstrate six-year plan performance for six years and shall retain records from other required drills for two years.

4.3 Other Records Materials generated as part of training need not be retained.

I SQN RADIOLOGICA LL CONTROL RESPONSE I

EPIP-1 4

SEPIP-14 Rev. 17 Page 12 of 16 APPENDIX A Page 1 of I DATE

  • _IN PLANT RADIATION MONITORS Affected Unit INITIAL UPDATED READINGS DESCRIPTION IDENTIFIER READING TIME:

TIME:

TIME:

PANEL 6-M-12 SPENT FUEL PIT AREA RADMON 1/2-RM-90-1 mR/hr SFP AREA RADMON O-RM-90-5 mR/hr CCS HXS AREA RADMON 1/2-RM-90-6 mR/hr HOT SAMPLE ROOM AREA 1/2-RM-90-7 mR/hr RADMON AFW PUMPS AREA RADMON 1/2-RM-90-8 mR/hr

)S WASTE TKS AREA O-RM-90-9 mR/hr

"-ADMON CVCS BD AREA RADMON 1/2-RM-90-10 mR/hr CNTMT SPRAY AND RHR PUMPS O-RM-90-11 mR/hr RADMON CNTMT UPPER COMPT RADMON TOTAL GAS CNTMT LOWER COMPT RADMON-TOTAL GAS PANEL 112-M-30 SHIELD BLDG VENT MON RAD INDICATOR SAMPLE ROOM POST ACCIDENT AREA MONITOR RHR POST ACCIDENT AREA MONITOR -LO RNGE

-HI RNGE

-LO RNGE

-HI RNGE 1/2-RM-90 112B 1/2-RM-90 106B 1/2-RI-90-400 Low Range Mid Range High Range Effluent 1/2-RM-90-280 1/2-RM-90-290 I1/2-RM-90-291 I1/2-RM-90-292 I1/2-RM-9Q-293 Route to EP Manager Data Taker Signature Time Date CPM CPM pCi/cc LCi/cc jtCi/cc i*Ci/cc 1iCi/sec mR/hr mR/hr mR/hr mR/hr mR/hr I

SQN APPENDIX B Page 1 of 1 POTASSIUM IODIDE ISSUE REPORT NAME SS NUMBER EXPOSURE PERIOD TIME OF NUMBER OF INFORMATION ISSUED BY INITIAL I

DOSES INSTRUCTIONS DOSE ISSUED ISSUED I

I I

I I

4 1

t I

I__

1.

+ -

i 1-i

_ 4.

I A-I1 1*

i t i I

  • +

I t

I I

4 I

t I

I.

I I

I I.

I I

I 4

1 i

I t

1 4

I I

I

________________________________ I 4

1 1

1 r~~~UU ~

~

riac LU~n arIII~iL~*

RADIOLOGICAL CONTROL RESPONSE

("PIP-14

.ev.

17 IPage 13 of 16

(

r UUte

o. r-lleilvulby lgl,=-,'

v u'=~*

(sjnoq) ewujL ajnsodx3 OOL I

(

4 Wei' L-Ba we.'* ~---

we.' 0j -.-l waj 09 0

ML I,

I I

I.O czn-:fnnl' L 900*1O LO-300" 1

.1...

I..........

.1....

1 0

0 C,, 0 CD 90-300*

=

0 0

90-3001 0

0

-9 I.............

I...............

LO-300"l

)

ýc Vi jo uonelequi Wojj asoa p!oJALLL leuopednoDO L J0 L abed o XIGN3ddV 9 IJO 14 I abed I LI "A9UI LL, I..Jl l

NOS 3SNOdS3HU "0QU1NOD IVOIOO7OIUVU CN I

k SJ

-f Iv1.o a, I~C3 I

I I

I to-90oo" I

I....

I....

-1.....

I..........

l....-............

I.........................

I FDID..IA I

RADIOLOGICAL CONTROL RESPONSE Rev. 17 Pace 15 of 16 APPENDIX D Page 1 of I FITNESS FOR DUTY PROGRAM ADMINISTRATION CALL-IN SHEET Person Calling Date_

Give this message: "This is (caller's name) at Sequoyah Nuclear Plant. An emergency has been declared, or a REP drill is being conducted (as appropriate). Have you consumed any alcohol within the last five hours?

Are you fit for duty? If you are fit for duty, please report to the RADCON Lab or Chemistry Lab (as applicable) and the duty Shift Supervisor immediately."

  • SPP-1.2, "Fitness For Duty", Section 3.14, Call-in-for Unscheduled Work, 3.14.1.A.4, If the answer to the alcohol consumption question is "yes" and the employee is told to report to work then Nuclear Security on site should be notified and be requested to administer a saliva test or hand held breathalyzer to the employee. This must be administered as soon as the person arrives on site.

ALCOHOL 5 HRS.

mJ.

m-mI TIME NEEDED TO REPORT ALCOHOL 5 HRS.

PRIOR TO REPORT?

(Y/N)*

I 1-DUTY (Y/N)

I

+

_ I.

I NAME COUMIM ErrNSL I SQN TIME CALLED J

I TIME CALLED 1

r I

1 r

I EPIP-14 SQN RADIOLOGICAL CONTROL RESPONSE Rev. 17 Pag~e 16 of 16 SOURCE NOTES REQUIREMENTS STATEMENT SOURCE DOCUMENT IMPLEMENTING STATEMENT NP Radiological Emergency Plan (NP-REP)

Paragraph 3.1.A SQ963213PER Revise EPIP-14 to indicate fitness for duty questions are required for call-ins.

TENNESSEE VALLEY AUTHORITY SEQUOYAH NUCLEAR PLANT EMERGENCY PLAN IMPLEMENTING PROCEDURE EPIP-17 Emergency Equipment and Supplies Revision 22 QUALITY RELATED PREPARED/PROOFREAD BY:

Bill Peparam RESPONSIBLE ORGANIZATION: Emergency Preparedness APPROVED BY Randy Ford EFFECTIVE DATE: 10/01/2001

  • .Level Of Use:

Reference

EPIP-17 SQN EMERGENCY EQUIPMENT AND SUPPLIES Revision 22 Page 2 of 20 REVISION DESCRIPTION:

Rev Date Description 21 03/30/01 Intent Change. This change moves equipment functional tests for TSC and OSC from 0-PI-REM-244 001.0 to this procedure. This procedure now performs Emergency Center inventories and equipment functional tests in a common procedure consistent with peer recommendations. 0-PI-REM-244-001.0 and 0-PI-REQ 244-001.0 specify monthly and quarterly functional tests requiring site coordination.

Removed the INPO Emergency Resources Manual from TSC Inventory, current INPO document is now available "on-line".

Added I & C Tool Kit to App. K. Renumbered Appendices.

22 10/01/2001 Update OSC Radio functional check requirements.

Remove Polaroid Camera and Film and add digital camera. Realigned or added Column headings.

EPIP-17 SQN EMERGENCY EQUIPMENT AND SUPPLIES Revision 22 Page 3 of 20 TABLE OF CONTENTS Section Title Page T able of C ontents............................................................................................

3 1.0 P U R P O S E.......................................................................................................

4 2.0 R E F E R E N C E S................................................................................................

4 3.0 IN S T R U C T IO N S..............................................................................................

4 3.1 General Instructions.................................................................................

4 3.2 Detailed Instructions...................................................................................

5 3.3 Completion of Appendices.........................................................................

6 4.0 R EC O R D S.................................................................................................

6 4.1 Q A R ecords...............................................................................................

6 4.2 Non Q A R ecords........................................................................................

6 APPENDICES Appendix A Emergency Equipment - Main Control Room (MCR).................. 7 Appendix B Emergency Equipment - Communication Room......................... 8 Appendix C Emergency Equipment - RADCON Lab...................................... 9 Appendix D OSC Response Team Equipment.............................................

10 Appendix E Emergency Equipment-480V Reactor MOV Board Room......

11 Appendix F Decon Facility - Service Building.............................................. 12 Appendix G Hospital Cabinet Inventory.......................................................

13 Appendix H Technical Support Center (TSC).............................................. 14 Appendix I Operations Support Center (OSC)..........................................

16 Appendix J Local Recovery Center (LRC)...................................................

18 Appendix K Inventories Performed in Other Procedures............................. 19 SO UR C E NO TES.................................................................................................

20

I EPIP-17 SQN I

EMERGENCY EQUIPMENT AND SUPPLIES Revision 22 Page 4 of 20 1.0 PURPOSE "This instruction is used to comply with the requirements of the Radiological Emergency Plan for periodic inspection and maintenance of equipment and supplies.

2.0 REFERENCES

A. CECC EPIP-9 B. O-PI-FPU-317-301.M C. O-PI-FPU-049-401.M D. O-PI-REM-000.001.Q E. O-PI-REM-244.001.M F. O-PI-REM-244.002.Q 3.0 INSTRUCTIONS 3.1 General Instructions 3.1.1 Responsible Organizations (as designated below) shall conduct inventory at the specified frequencies For the purposes of these inventories, monthly is defined as once per calendar month, quarterly is defined as once per calendar quarter, and annual is defined as once per calendar year.

Appendix Frequency Description Responsible Org.

A Annual Main Control Room - Corridor Cabinet - Table A RadCon A

Quarterly Main Control Room - Corridor Cabinet - Table B RadCon B

Annual Communications Room - Control Building - Table A RadCon B

Quarterly Communications Room - Control Building - Table B RadCon C

Quarterly Radiological Control Lab RadCon D

Quarterly OSC Response Team Storage RadCon E

Quarterly 480V Rx MOV Board Room EL 734 RadCon F

Quarterly Decon Facility - Service Building EL 690 RadCon G

Quarterly Agreement Hospital Emergency Room Corporate EP H

Quarterly Technical Support Center EP Manager I

Quarterly Operations Support Center EP Manager J

Quarterly Local Recovery Center EP Manager K

Quarterly Inventories Performed in other Procedures EP Manager 3.1.2 The individuals performing the inspection shall complete the appendices and the Emergency Preparedness Manager shall review the results as indicated and make arrangements to correct deficiencies.

3.1.3 List any deviations and the disposition on the appropriate Appendix Data Sheet.

Deficient, outdated or missing items shall be replaced.

3.1.4 Special checks of certain material in the cabinets shall be performed. The following checks shall be made where applicable:

A. The protective clothing shall be checked for deterioration.

B. The smoke tubes and aspirator bulbs shall be checked for deterioration and that the tubes have not been broken or used.

C. Replace all flashlight batteries at the end of shelf-life with fresh batteries. (Do not discard batteries. Return them to the tool room.)

D. Check to determine that flashlights are operable.

E. Rezero all emergency dosimeters to assure proper operation.

EPIP-17 SQN EMERGENCY EQUIPMENT AND SUPPLIES Revision 22 Page 5 of 20 3.2 Detailed Instructions 3.2.1 The emergency equipment, listed in Appendices A and B, are stored in cabinets provided with a lock or plastic seal. This provides a means of controlling access or determining that the cabinet has not been opened. An inventory list of the equipment may be posted on the outside of the cabinet. The two cabinets are located in the Main Control Room corddor, and Communications Room.

3.2.2 Each cabinet and storage location, including the medical treatment area, shall be inventoried and required equipment inspected and checked for operation and/or condition. Equipment in certain cabinets is separated into Table A and Table B.

Table A is a list of all non-perishable items stored in a small metal box equipped with a security seal within the cabinet itself. These items will be inventoried annually (preferably in January) and whenever a security seal has been found to be violated.

Those items listed in Table B of these attachments are inventoried on a quarterly basis.

3.2.3 The radiation monitoring instruments, which are in normal plant use, are located in the RADCON laboratory as listed in Appendix C.

3.2.4 Protective clothing for use by the OSC response teams is located in the Operations Support Center storage room and is listed in Appendix D.

3.2.5 Protective clothing for use in contamination controls from affected plant areas in the Control Building are listed in Appendix E and is located in the 480 V Reactor MOV Board Room, Elevation 734.

3.2.6 Supplies for decontamination of personnel are stored in the E1.690' Decon. Room near the RadCon lab and are listed in Appendix F.

3.2.7 The emergency room supplies furnished by TVA for use of the agreement hospital(s) in case of injury involving radioactive materials are listed in Appendix G.

3.2.8 References and supplies for use during an emergency stored in the Technical Support Center (TSC) are listed in Appendix H.

3.2.9 References and supplies for use during an emergency stored in the Operations Support Center (OSC) are listed in Appendices I and D.

3.2.10 References and supplies for use during an emergency stored in the Local Recovery Center (LRC) are listed in Appendix J.

3.2.11 The emergency equipment referenced in Appendix K is inventoried by other procedures and reviewed by the Emergency Preparedness Manager for acceptability.

3.2.12 TSC/OSC position notebooks and work areas shall be scanned during the quarterly inventory for uncontrolled or outdated materials; not just outdated forms.

EPIP-17 SQN EMERGENCY EQUIPMENT AND SUPPLIES Revision 22 Page 6 of 20 3.3 Completion of Appendices 3.3.1 If the particular items are present and in sufficient quantities and, when applicable, in good working condition, then check the "Yes" column.

3.3.2 If a deficiency is noted, then check the "No" column and replace deficient items. All deficiencies must be corrected as soon as possible. If circumstances do not allow deficiencies to be corrected, then the appropriate supervisor shall be notified.

3.3.3 Under the "Remarks" column, explain the corrective actions taken.

3.3.4 All comments in the "Remarks" column should be detailed enough to leave no doubt as to the actions taken. Comments to the effect - "batteries missing" will not suffice.

A simple check in the "No" column will represent that a deficiency exists. Such comments do not allow a person to determine what, if any, action has been taken.

Comments should read for example: "Batteries missing, replaced on March 5.

2001".

4.0 RECORDS 4.1 QA Records None 4.2 Non-QA Records The Appendices/Checklists in this Instruction are NON-QA documents and will be retained by the SQN Emergency Planning (EP) Manager for at least two years.

EPIP-17 SQN EMERGENCY EQUIPMENT AND SUPPLIES Revision 22 Page 7 of 20 APPENDIX A MAIN CONTROL ROOM CORRIDOR CABINET - CONTROL BUILDING "Page 1 of 1 TABLE A Quantity Description Yes No Remarks S ecurity seal intact:.....................................................................

NOTE: Table A will be inventoried annually (preferably in January) and whenever a security seal has been found to be violated.

12 pr.

Rubber overshoes - Various sizes.

6 pr.

Canvas gloves...........................

12 pr.

Rubber gloves-Various sizes................................

6 Hoods.......................................

2 P e n cils....................................................................

2 Clipboards w ith paper.............................................

2 Boxes smoke tubes...........................................

2 Aspirator bulbs....................................................

1 Log B ook................................................................

4 rolls Duct tape and/or masking tape..............................

S ecurity seal replaced................................................................

TABLE B Quantity Description Yes No Remarks 12 Pairs of paper overalls - Various sizes...................

2 H ardhats.................................................................-

2 F la shlig hts..............................................................-

12 Spare flashlight batteries Expires:

2 Spare flashlight bulbs....

1 F irst-a id kit..............................................................

12 Face G oggles.........................................................

1 Radiation Survey M eter..........................................

Cabinet Relocked or Resealed.............................................

Inspection performed by:

RADCON Representative Date Review and Approval:

Emergency Preparedness Manager Date EP Manager shall retain the completed form as a Non-QA Record for at least 2 years.

EPIP-17 SQN EMERGENCY EQUIPMENT AND SUPPLIES Revision 22 Page 8 of 20 APPENDIX B COMMUNICATIONS ROOM - CONTROL BUILDING Page 1 of I TABLE A Description Yes No Remarks S ecurity seal intact:.....................................................................

NOTE: Table A will be inventoried annually (preferably in January) and whenever a security seal has been found to be violated.

6 Pairs of rubber overshoes...................................

6 Pairs canvas gloves......................................

6 Pairs rubber gloves..........

6 Hoods.......................................

2 P e n cils....................................................................

2 Clipboards with paper....................

2 Boxes sm oke tubes................................................

2 A spirator bulbs.......................................................

1 Lo g B o o k................................................................

S ecurity seal replaced................................................................

TABLE B Quantity 6

2 2

12 2

1 Description Ye,,

No Remarks Pairs of coveralls - various sizes............................

Hardhats.................................................................

Flashlights..............................................................

Spare flashlight batteries Expires:

Spare flashlight bulbs.............................................

First-aid kit..............................................................

Cabinet Relocked or Resealed.............................................

Inspection performed by:

RADCON Representative Date Review and Approval:

Emergency Preparedness Manager Date EP Manager shall retain the completed form as a Non-QA Record for at least 2 years.

Quantity

I EPIP-17 SQN I

EMERGENCY EQUIPMENT AND SUPPLIES Revision 22 Page 9 of 20 APPENDIX C RADIOLOGICAL CONTROL LABORATORY - SERVICE BUILDING Page 1 of 1 Quantity I

2 6

1 5

10 5

1 5

2 5

10 5

1 Description Yes Alpha Survey Meter (500,000 cpm).............................

Neutron dose rate survey meter

(.025 eV - 10 MeV/5,000 mR/hr).................................

High Range Survey Instrument (1,000 R/hr with extendible probe)..............................

ION Chamber Survey Meter (50 R/h)

ION Chamber Survey Meter (20,000 R/h)...................

High volume Air Samplers (and support equipment)...

Frisker Type Survey Meters (0-50,000 cpm)...............

Low-volume air samplers (and support equipment)....

P ortable S caler...........................................................

C alcu lato rs..................................................................

Cal/Response Ck Sources..........................................

Noble Gas Sampling Syringes....................................

Silver Zeolite Cartridges..............................................

M arinelli B eakers.........................................................

S hielded D etector.......................................................

Inspection performed by:

RADCON Representative Review and Approval:

Emergency Preparedness Manager No Remarks Date Date EP Manager shall retain the completed form as a Non-QA Record for at least 2 years.

EPIP-17 SQN EMERGENCY EQUIPMENT AND SUPPLIES Revision 22 Page 10 of 20 APPENDIX D OSC RESPONSE TEAM EQUIPMENT CAFETERIA OSC EQUIPMENT STORAGE ROOM Page 1 of 1 Quantity Description Yes 40 pr.

Cotton liners..........................................................................

40 pr.

Rubber gloves - Various sizes...............................................

40 pr.

Plastic booties.......................................................................

40 pr.

Rubber overshoes - Various sizes.........................................

30 pr.

Coveralls - Various sizes.......................................................

30 Surgeon caps........................................................................

30 Hoods....................................................................................

4 rolls Duct Tape and/or Masking Tape...........................................

2 Hardhats................................................................................

6 pr.

Canvas gloves.......................................................................

2 Spare flashlight bulbs............................................................

2000 doses KI (Expires

.)

(#Pkgs * #Tablets/pkg = #doses).....

Door Relocked...........................................................................

No Remarks inspection performed by:

RADCON Representative Date Review and Approval:

Emergency Preparedness Manager Date EP Manager shall retain the completed form as a Non-QA Record for at least 2 years.

SQN EMERGENCY EQUIPMENT AND SUPPLIES E-PIP-17 Revision 22 Page 11 of 20 APPENDIX E 480V REACTOR BOARD ROOM - AUXILIARY BUILDING (EL. 734)

Page 1 of 1 Quantity Description.......................................e 40 Dr.

C otton liners.........................................................

40 pr.

40 pr.

40 pr.

30 pr.

30 1

4 rolls 6 pr.

2 2

12

--

kI.

S I'4U Remarks Rubber gloves - Various sizes...........................

Plastic booties.........................

Rubber overshoes - Various sizes.............................

Paper coveralls..........................................................

Surgeon caps...................................................

Box of vinyl gloves...............................................

Duct Tape and/or Masking Tape...............................

Canvas gloves...........................................................

Flashlights.................................................................

Spare flashlight bulbs............................................

Spare flashlight batteries Expires_______

Cabinet Relocked or Resealed.............................................

Inspection performed by:

RADCON Representative Date Review and Approval:

Emergency Preparedness Manager Date EP Manager shall retain the completed form as a Non-QA Record for at least 2 years.

LNI*U-

EPIP-17 SQN EMERGENCY EQUIPMENT AND SUPPLIES Revision 22 Page 12 of 20 APPENDIX F EL. 690' DECONTAMINATION ROOM Page 1 of 1 Inspection Performed By:

RADCON Representative:

Reviewed By:

RADCON Shift Supervisor:

Date:

Date:

Reviewed By:

EP Manager:

Date:

EP Manager shall retain the completed form as a Non-QA Record for at least 2 years.

MIN SUGGESTED QUANITY ITEM QUANITY QUANITY ON HAND REMARKS Disposable Gloves 1 box 2 boxes Gauze Pads 1 box 2 boxes Cotton Swabs 1 pkg 1 pkg Saline Solution 1 bottle 2 bottles Surgical Brushes 1 each 12 each Shampoo 1 bottle 2 bottles Soap 2 bars 5 bars Laundry detergent none 1 box Soap (liquid abrasive) none 1 bottle Mechanic's Hand Cleaner none 2 can Shaving Cream 1 can 1can Razors 2 each 5 each Paper Bath Towels none 1 box Towels 5 each 25 each Scissors 1 pair 1 pair Petri Dishes 3 each 5 each Duct Tape none 2 rolls Paper Coveralls 5 pair 10 pair Tennis Shoes (Sizes 7-none one pair half sizes are OK

12) each

APPENDIX G HOSPITAL CABINET INVENTORY Page 1 of 1 r-i North Park SATI Quantity I Description Remarks Protective Clothinlg 10 pair Shoe covers 10 pkg Dress out packages (coveralls, booties, gloves) 3 Surgical gowns 2 boxes Surgical gloves 4 rolls Surgical tape for dressout - 2 inch Facility Preparation set Floor coverings (hospital specific) 1 roll Heavy duty paper (3 foot wide) 2 rolls 2 inch ducttape 1 roll Radiation Warning symbol tape 12 inch) 2 Step off pads 8

Radiological barrier posting signs I Spool Radiological barrier rope or ribbon 5

Traffic cones 10 Large rad waste plastic bags (trash can size) 10 Medium rad waste plastic bags (x-ray cassette size) 2 copies Hospital specific booklet (1 at desk, 1 in cabinet)

Last Update:

i Radioactive material label tape Decontamination Supplies

-iDecontamination table, backboard and bottles (min. total capacity of 10 gallons) 1 Flexible funnel with drain hose - optional 1

Decontamination media /soap product 1

NCRP # 65 Reference Handbook 12 Cotton swabs 20 Zip lock bags for sample collection 10 Labels for sample bags 2

Scissors 1

Wall poster with decontamination steps Health Physics Supplies (Serial # and cal due) 1 Bicron ISM (RSO-5 or 50) 2 Bicron Surveyor 50 1

Wound probe with cable 10 TLDs 10 Electronic dosimeters and tray 200 1Smears 12 Radioactive Material tags 1

Masslin mop and 20 cloths Inspection Performed By:

Review and Approval:

Emergency Preparedness Manager Date Date I--'1 I-- rl,.-j *,.*

  • r.

APPENDIX H TECHNICAL SUPPORT CENTER Paaqe I of 2 Qtv Description Yes No Remarks Assorted Dryboard Supplies (Erasers, markers, etc.).................................

Assorted Desktop Supplies (Stapler, Tape, Logbooks).................................... _

Assorted Office Supplies (Pen, Pencils, Staples, Etc.)................................-... _

1 Spare Roll of thermal Paper for Tracking Board................................-

2 AS M E Steam Tables.........................................................................

4 Com munications Head Sets.............................................................-

4 Sequoyah Phone Directories (latest edition)................................ _

3 Chattanooga Phone Directories (latest edition).............................. _

2 TVA Phone Directories (latest edition)......................................

5 Electronic Display Projectors............................................................

1 each TSC Position Notebooks.........................................................................

(Scan/Check for uncontrolled/out-of-date materials in Position notebooks & seating areas.)

Verify wall maps are latest revision (see CECC EPIP-9) 1 2 M ile M ap......................

Latest Rev.

1 10 Mile Evac Map........... Latest Rev.

2 50 Mile Sample Map....... Latest Rev.

1 50 M ile M ap....................

Latest Rev.

(NOTE: Retain marked up REND pages or pnntouts as documentation)

Verify Key Phones for TSC are functional by calling each number listed in the REND and checking on a copy of the REND page...................................

Verify Fixed Satellite Phone is functional by calling known good phone........

Verify CECC Terminal/Printer is functional by printing current Met Data.............

Verify copier is functional by copying a page..........................................................

Verify clocks are functional by checking current time............................................

Verify signs are functional by changing to all classifications and observing.......

Verify all ICS/Wide Area Network Terminals are functional..................................

"Position q

Position

-I Position V

Ops Mgr.

Ops Comm. #1 TAT 1 ICS Chem Mgr Ops Comm. #2 TAT 2 ICS TAT 3 ICS RadCon ICS I

Main. Mgr TAT 4 ICS RadCon WAN SVP TAT TEC ICS NRC Room Logkeeper TAT DSPL Check Unit 1 and Unit 2 ICS or WAN access to P vveusite as appruIP1IaLU Verify CECC ring-down is functional by calling CECC Director Position..............

(Continued on Next Page)

APPENDIX H TECHNICAL SUPPORT CENTER Pa-qe 2 of 2 Qty Description Yes No Remarks Verify presence only (DCU controls contents) 4 REP (Radiological Emergency Plan)............................................

2 REND (Radiological Emergency Notification Directory)................ __

2 Central Emergency Control Center EPIP (CECC EPIP)................ _

4 S Q N E P IP..................................................................................

4 Severe Accident Management Guidance (SAMG)............................

1 U pdated SQ N FSA R.........................................................................

2 Unit 1 Technical Specifications........................................................

2 Unit 2 Technical Specifications.........................................................

1 Site Health and Safety Manual.........................................................

1 State of Tennessee Multijurisdictional REP Response Plan.............

1 System Operating Manual/System Operating Instructions (SO/SO l).

1 Annunciator Response Manuals (AR)...............................................

1 P eriodic Instructions (P I)...................................................................

2 Abnormal Operating Procedures (AOP)............................................

1 Technical Instructions (TI)....................................................

I General Operating Instructions (GO).................................................

1 SQN Offsite Dose Calculation Manual (ODCM)................................

1 SQN Process Control Program (PCP)...............................................

1 Radiological Control Instructions (RCI)..............................................

1 Radwaste Handling/Shipping Index (RHSI).......................................

2 Functional Restoration Guidelines...................................................

2 Emergency Instructions..................................................................

2 Emergency Abnormal Procedures (EAPs).............

2 Emergency Contingency Actions......................................................

2 Users Manual - Meteorological Data Print Program..........................

2 Users M anual - FR ED.......................................................................

1 Users Manual - Meteorological Data Display..................................

1 Users Manual - CECC Information System.......................................

1 U sers M anual - IC S..................................................................

Inspection Performed By:

Date Review and Approval:

Emergency Preparedness Manager Date

APPENDIX I OPERATIONS SUPPORT CENTER (OSC)

Page 1 of 2 Quantity Description Assorted Desktop Supplies (stapler, tape, logbook).................................

Assorted Office Supplies (pens, pencils)..................................................

Assorted Dryboard Supplies (eraser, markers, etc.)..................................

2 Spare Roll of thermal Paper for Tracking Board........................

1 S Q N E P IP s...............................................................................

2 SQN Telephone Book (latest edition).........................................

2 TVA Telephone Book (latest edition)....................................

1 User M anual - IC S..................................................................

4 Communication Headsets.....................................................-.

1 Digital C am era.......................................................................

2 Team Tracking Status Boards........................

1 Ops Tracking Status Boards......................................................

1 RadCon/Chem Tracking Status Boards................................

12 Spare flashlight batteries Expires 6

Spare Pager Batteries Expires 2

Electronic Display Projectors...................................................

1 each OSC Position Notebooks......................................................

(Scan/Check for uncontrolled/out-of-date materials in Position Notebooks & seating areas.)

Verify wall maps are latest revision (see CECC EPIP-9 for latest map revision levels) 1 2 Mile Map Latest Rev.

1 10 Mile Evac Sector Map Latest Rev.

1 10 Mile Sampling Point Map Latest Rev.

(NOTE: Retain marked up REND pages or printouts as documentation)

Verify Key Phones for OSC are functional by calling each number listed in the REND and checking on a copy of the REND page................................... _

Verify Portable Satellite Phone is functional by calling known good phone........

Verify copier is functional by copying a page..........................................................

Verify clocks are functional by checking current time....................

Verify signs are functional by changing to all classes and observing........-

Verify Plant Drawing Racks are present (Contents controlled by DCU)...............

Verify HIS-20 Terminal functional and HIS-20 loads..........................................

Verify all ICS/W ide Area Network Terminals are functional..................................

Position Position Position Ops Advisor #1 DCRM Fire Ops Ops Advisor #2 Materials Coordinator MSS NOMS RadCon Check Unit 1 and Unit 2 ICS or WAN access to EP Website as appropriate (Continued on Next Page)

KI Dnrnnritc I

"APPENDIX I OPERATIONS SUPPORT CENTER (OSC)

Paaqe 2 of 2 Yes No Remarks Verify all conference Bridges are functional............................................................

Bridge Number Ops Bride-Talk 101 Ops Bridge - Listen 102 RadCon Bridge 103 Maintenance Bridge 104 OSC Teams Hotline-6406 (must dial and wait)

OSC Radios:

A. Rotate batteries from radios to the battery conditioner ensuring that batteries moved on to the radios from the conditioner are fully charged.

B. Reset conditioner to "Auto-recondition" and place batteries from radios in receptacles.

C. After charging cycle is complete (8-24 hours), analyze each battery in the conditioner by ensuring that both "Service Display" lights are flashing simultaneously.

D. Remove all batteries from the conditioner and reset conditioner to "Standby" Replace the batteries in the conditioner.

E. Perform functional check of each radio by keying each radio on Daily Work channel and ensuring that signal is transmitted (if not marked as non-transmitting) or will not transmit (if marked as non transmitting).

Inspection Performed By:

Date Review and Approval:

Emergency Preparedness Manager Date

EPIP-17 SQN EMERGENCY EQUIPMENT AND SUPPLIES Revision 22 Page 18 of 20 APPENDIX J Local Recovery Center Page 1 of 1 (NOTE: Retain printouts as documentation)

Verify CECC Terminal/Printer is functional by printing current Met Data........

Verify Key Phones for LRC are functional by calling each number listed in the REND and checking on a copy of the REND page..................................

Inspection Performed By:

Date Review and Approval:

Emergency Preparedness Manager Date

APPENDIX K Page 1 of 1 Review of Inventories Performed by other Procedures Ambulance Medical Supplies: (Fire Operations) 0-PI-FPU-317-301.M performed on Date SCBA Inventories: (Fire Operations) 0-PI-FPU-049-401.M performed on Date Review 0-PI-FPU-049-401.M to ensure the following equipment is available:

RELAY ROOM OUTSIDE TECHNICAL SUPPORT CENTER (EL 732):

12 Self-contained breathing apparatus 12 Additional air cylinders 2

Small MSA face pieces 2

Large MSA face pieces SERVICE BUILDING EL 690 (PASF Units):

8 Dual Purpose self-contained breathing apparatus 4

Dual Purpose Airline Hoses 3

Small MSA face pieces 3

Large MSA face pieces SERVICE BUILDING EL 690 (RADCON AND RADCHEM LABS):

16 Self-contained breathing apparatus SERVICE BUILDING (EL. 706) FIRE EQUIPMENT CAGE 6

Self-contained breathing apparatus 12 Additional cylinders Emergency Van Supplies: (Radcon) at least one per van per quarter CECC-EPIP Appendix J based inventory performed Date Date Quarterly Tool Room Tool Kits: (Tool Room) 0-PI-REM-000.001.Q Date:

Mechanical tool kit

  1. 1, #2, #4, #5, #6 Electrical tool kit
  1. 3, #7 I & C tool kit
  1. 8 Monthly NRC Communications Equipment: (EP Manager) 0-PI-REM-244-001.0 based inventory last performed on Date Quarterly Communications Equipment: (EP Manager) 0-PI-REM-244-002.Q based inventory performed on Date Diesel Generator Operating Guidelines At least one per quarter Date Emergency Preparedness Review of Results:

Date Emergency Preparedness Manager

EPIP-17 SQN EMERGENCY EQUIPMENT AND SUPPLIES Revision 22 Page 20 of 20 SOURCE NOTES REQUIREMENTS STATEMENT H-10 Appendix E, Section E Section 8.0 SOURCE DOCUMENT NUREG 0654 10 CFR 50 NP REP NUREG 0696 IMPLEMENTING STATEMENT "Emergency Equipment Inspections" "Emergency Response Facilities, Equipment, and Supplies" "Functional Criteria For Emergency Response Facilities"