L-82-215, Responds to Discussing Operator Action During Postulated Main Steam Line Break.Submittal Justifies Time at Which Credit Taken for Operator Action in Analysis for IE Bulletin 82-04
| ML17341B177 | |
| Person / Time | |
|---|---|
| Site: | Turkey Point |
| Issue date: | 05/21/1982 |
| From: | Robert E. Uhrig FLORIDA POWER & LIGHT CO. |
| To: | Varga S Office of Nuclear Reactor Regulation |
| References | |
| REF-SSINS-6820 IEB-82-04, IEB-82-4, L-82-215, NUDOCS 8205250015 | |
| Download: ML17341B177 (6) | |
Text
RESULATORYQIPORNATION DISTRIBUTION S,EN (RIOR)
AOCESSION NBR:8205250015 DOC ~ DATE: 82/05/21 NOTARIZED:
NO DOCKET FACIL:50-250 Turkey Point Planti 'Unit 3E Florida tPower and Light C
05000250 50"251 Turkey Point Planti Unit 4P Florida Power and Li'ght C
05000251 AUTH'AME AUTHOR AFFILIATION UHRIGP R ~ E ~
Flor ida Power 8 Light Co.
>R EIC IP ~ NAME RECIPIENT AFFILIATION VARGAgS ~ AD Operating Reactors Branch 1
SUBJECT:
Respo postu cr edi 82 04 DISTRIBUTION C
TITLE: General NOTES:
nds to 820426 ltr discussing operator action during lated main steam line break, Justifies time out which t taken for operator action in analysis for IE Bulletin ODE:
A001S COPIES 'RECEIVED:LTR J ENCL Q SIZEA.~
Distribution for af ter Issuance of Operating License RECIPIENT ID CODE/NAME ORB ¹1 BC 01 INTiERNAL: ELD/HOSE NRR/DL DIR NRR/DSI/RAB RGN2 COPIES LTTR ENCL RECIPIENT ID CODE/NAKE NRR/DHFS DEPY08 NRR/DL/DRAB 04 COPIES LTTR ENCL EXTERNAL: ACRS 09 NRC PDR 02 NTIS 10 1
1 1
LPDR NSIC 03
-05 TOTAL NUMBER OF COPIES REQUIRED:
LTTR 28 ENCL
II l
g
\\
P.O. BOX 529100 MIAMI,FL33152 FLORIDAPOWER & LIGHTCOMPANY May 21, 1982 L-82-215 Office of Nuclear Reactor Regulation Attention:
Mr. Steven A. Varga, Chief Operating Reactors Branch gl Division of Licensing U.S.
Nuclear Regulatory Commission Washington, D.C. 20555
Dear Mr. Varga:
'e:
Turkey Point Units 3 8 4 Docket No. 50-250, 50-251 IE Bulletin 80-04 Florida Power 8 Light has reviewed your letter dated April 26, 1982 concerning operator action during a postulated main steam line break event.
That letter requested that we discuss the operator actions necessary to prevent exceeding containment design pressure.
As we discussed in our letter (L-81-211) dated May 19, 1981, the operator determines the faulted steam generator by comparing steam line pressure after the Main Steamline Isolation Valves are closed.
A low steam line pressure compared to the other loops denotes a faulted loop.
The operator then closes the valves in the auxiliary feedwater line supplying the damaged steam generator.
The operator actions are further described in Emergency Operating Procedure 20002.2 (Loss of Secondary Coolant) which is attached.
Your letter also asked for justification for the time at which credit was taken for operator action in our analysis for IE Bulletin 80-04.
In the description of our analysis, we stated that credit was taken for operator action at 10 minutes to isolate auxiliary feed flow to the faulted steam generator.
This assumption was made for the analysis with both the existing steam generators and those to be used in the repair project.
It has been our experience that at simulator exercises, when operators have been given a main steam line break event, they have routinely performed the necessary isolation of auxiliary feedwater well within the assumed 10 minutes.
We credit this performance to the training emphasis that has been placed on this isolation action during the main steam line break event.
Based on our simulator experience, we are confident that the assumed time limit for operator action in the analysis is a conservative assumption.
8205250015 820521 PDR, ADOCK'5000250 8 '" ',-
P.DR =
o(
Li y PEOPLE... SERVING PEOPLE
4l
~I
Re:
Turkey Point Units 3 5 4 Docket No. 50-250, 50-251 IE Bulletin 80-04 The second question in your letter was to provide information based on an analysis with the assumption that the operator would take no action to isolate the auxiliary feedwater flow to the faulted steam generator.
Again, based on our simulator experience we are confident that the operators would take the necessary action.
Me, therefore, do not see the necessity to conduct an analysis with the invalid assumption that the operator would take no action.
I Should you have further questions on the operator's actions in this event, please call us.
Very truly yours, R
E; Uhrig Vice President Advanced Systems 5 Technology REU/JEtk/mbd.
cc:
J.P. O'Reilly, Region II Harold F.
Rei s, Esquire
0 w>ll I
f' p K I
IL~
m I
1 1
I
~ II g
k l<l, It t
I C.
1'h
/
II II ol a
%II l
I II 1,
I ill',
~e.'l e
hl I
li II e
I'