L-2012-135, Environmental Protection Plan Report Request for Minor Revision to Iww Permit No. FL0002208
ML12097A280 | |
Person / Time | |
---|---|
Site: | Saint Lucie |
Issue date: | 03/23/2012 |
From: | Katzman E Florida Power & Light Co |
To: | Document Control Desk, Office of Nuclear Reactor Regulation |
References | |
FL0002208, L-2012-135 | |
Download: ML12097A280 (24) | |
Text
0 Florida Power & Light Company, 6501 S. Ocean Drive, Jensen Beach, FL 34957 FPL March 23, 2012 L-2012-135 10 CFR 50.4 EPP 3.2.4 U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington, DC 20555 Re: St. Lucie Units 1 and 2 Docket Nos. 50-335 and 50-389 Environmental Protection Plan Report Request for Minor Revision to IWW Permit No. FL0002208 Pursuant to Section 3.2.4 of the St. Lucie Environmental Protection Plan, Florida Power &
Light Company (FPL) is hereby providing the enclosed copy of the requested revision to the Industrial Wastewater Facility Permit (Permit Number FL0002208) at the same time that it is being submitted to the State of Florida Department of Environmental Protection.
Please contact Vince Munnd (772) 263-2847 should you have any questions on this matter.
Sincerely, Eric S. Katzman Licensing Manager St. Lucie Plant ESK/kdr Enclosure an FPL Group company
Florida Power & Light Company, 6501 S. Ocean Drive, Jensen Beach, FL 34957 L March 16, 2012 FPL Marc Harris, P.E. CERTIFIED MAIL Florida Department of Environmental Protection RETURN REC[PT REQUESTED Industrial Wastewater Section 7006 3450 0003 0174 4752 2600 Blair Stone Road, MS 3545 Tallahassee, Florida 32399-2400 RE: Florida Power & Light Company St. Lucie Power Plants Units 1 and 2 IWW Permit No. FL0002208 Request for Minor Revision
Dear Mr. Harris:
St. Lucie is requesting a Minor Revision to our NPDES Permit that addresses a change in discharge pumping methodology from the Outfall 1-008.
The following enclosures are included herein:
I) Three (3) signed and sealed copies of FDEP Form 62-620,910(9), Application for a Minor Revision to Wastewater Facility or Activity Permit (Enclosure 1),
- 2) Three (3) signed and sealed copies of FPL - St. Lucie Nuclear Steam Power Plant FDEP IWW Permit # FL0002208 - Attachment 1 - Evaporation / Percolation Basin -
Emergency Discharge Structure (Enclosure 2),
- 3) Three signed and sealed drawings of the proposed 1-008 Discharge Structure, DRAWING NO. PSL-C-275630-001 (Enclosure 3),
- 4) FPL check payable to the State of Florida, Department of Environmental Protection in the amount of $250.00 for application fee (Enclosure 4).
If you have any questions or need additional information, please contact Vince Munnr at (772) 263-2847.
Sincerely, Richard L. Anderson Site Vice President St. Lucie Plant Enclosures VPPSL006 cc: Siting Office VPPSL006 an FPL Group company
VPPSL006 ENCLOSURE 1 Three (3) signed and sealed copies of FDEP Form 62-620.910(9)
Application for a Minor Revision to Wastewater Facility or Activity Permit (Cover + 6 pages)
APPLICATION FOR A MINOR REVISION TO A WASTEWATER FACILITY OR ACTIVITY "tao FLOA _PERMIT
- 1. Instructions
- a. In accordance with Rule 62-620.325, F.A.C., this form must be submitted to the appropriate Department district office or approved local program when requests for minor revisions to a permit or minor modifications to a facility are made by a permittee, except for transfer of a permit to a new permittee and addition of a major user of reclaimed water to a Part III reuse system. Application for transfer of a permit to a new permittee shall be made on DEP Form 62-620.910(11). Application for addition of a major user of reclaimed water shall be made on DEP Form 62-610.300(4)(a)1.
- b. Each applicable item must be completed in full in order to avoid delay in processing of this form. Where attached sheets or other technical documentation are provided, indicate appropriate cross-references.
- c. Three (3) copies of this application with supporting documentation shall be submitted with this form.
- d. All infonnation is to be typed or printed in ink. Dates are to be entered in MM/DD/YR format.
- e. This application and attachments shall be signed in accordance with Rule 62-620.305, F.A.C. Also, as applicable, this application and all attachments shall be signed and sealed by a professional engineer registered in Florida in accordance with Rule 62-620.310, F.A.C.
- 2. Facility Information
- a. Permit Number FL0002208 b. Facility Identification Number; FL0002208
- c. Project/Facility Name: FPL - St Lucie Nuclear Steam Power Plant
- d. Contact Name: Vince Munne Number and Street: 6501 South Ocean Drive City/State/Zip Code: Jensen Beach/FL/34957 Telephone 772-263-2847
- 3. Type of Revision LI Correct Typographical Errors' - Submit one copy of each page of the permit showing revisions being requested.
[] Change Improvement Schedule' - Provide a description of the improvement, a list of the dates to be revised, and a reason for the proposed change in each date.
[]Change Expiration Date of Permit' - Provide the current and proposed expiration dates for the permit and the reasons for the proposed change.
[1 Change Staffing Requirements 2 - Describe the proposed change and submit justification for the change in accordance with Chapter 62-699, F.A.C.
[A prccessiag fee is not required. DI.P Form 62-620,910(9)
)A procereng fee is required with theapplication Effective October 23, 2000 in accordance with Rule 62-4.050, F. C.
El Change Monitoring and Reporting Requirements' - Describe the proposed change and submit justification for the change in accordance with Chapter 62-601, F.A.C.
El Modify Approved Pretreatment Program' - Describe the proposed modification and provide the information required by Rule 62-625.540, F.A.C.
El Delete Point Source Outfall' - Identify the outfall and explain why the outfall is being eliminated.
EL Modify or Expand Approved Residuals Land Application Sites2 - Attach a new or updated Agricultural Use or Dedicated Site Plan as required by Chapter 62-640, F.A.C.
[ Minor Modification to the Facility2 - Provide a description of the proposed modification. If applicable, attach any reports, plans, and specifications which have been developed to implement this modification.
Li Other 2 - Provide appropriate documentation. Describe.
- 4. Certifications
- a. Applicant or Authorized Representative I certify under penalty of law that I have personally examined and am familiar with the information submitted in this application and all attachments and that, based on my inquiry of persons immediately responsible for obtaining the information contained in the application, I believe that the information is true, accurate and complete. I am aware that there are significant penalties for submitting false information, including the possibility of fine and i urisonment.
(Signatureof4A cat Authorized Representative) (Date)
Name (please type) Richard L. Anderson Company Name FPL St Lucie Plant Title Site Vice President Company Address: 6501 South Ocean Drive Phone: 772-467-7100 City/State/Zip Code: Jensen Beach/FL/34957
- b. Professional Engineer Registered in Florida I certify that the engineering features of this project have been (designed) (examined) by me and found to conform to engineering principles applicable to such projects. In my professional judgement, this facility, when properly constructed, operated, and maintained, will comply with all applicable statutes of the State of Florida and rules of the Department.
Name (please type): Glenn M. Andrews Florida Registration Number: 65772 Company Name: Absolute Consulting, Inc.
Company Address: 7552 Navarre Parkway, Suite 63 City/State/Zip Code: Navarre/FL/32566 Phone Number: 772-361-5865 (Seal, Signature, Date, and Registration Number)
'If signed by the authorized representative, 2 DEP Form 62-620.910(9) attach a letter ofaulhorization in accordance Effweti-e October 23, 2000 Rule 62-620.305, F.A.C.
APPLICATION FOR A MINOR REVISION TO FA WASTEWATER FACILITY OR ACTIVITY SFLOR A PERMIT
- 1. Instructions
- a. In accordance with Rule 62-620.325, F.A.C., this form must be submitted to the appropriate Department district office or approved local program when requests for minor revisions to a permit or minor modifications to a facility are made by a permittee, except for transfer of a permit to a new perrnittee and addition of a major user of reclaimed water to a Part Ill reuse system. Application for transfer of a permit to a new permittee shall be made on DEP Form 62-620.910(11). Application for addition of a major user of reclaimed water shall be made on DEP Form 62-610.300(4)(a)1.
- b. Each applicable item must be completed in fall in order to avoid delay in processing of this form. Where attached sheets or other technical documentation are provided, indicate appropriate cross-references.
- c. Three (3) copies of this application with supporting documentation shall be submitted with this form.
- d. All information is to be typed or printed in ink. Dates are to be entered in MMv/DD/YR format.
- e. This application and attachments shall be signed in accordance with Rule 62-620.305, F.A.C. Also, as applicable, this application and all attachments shall be signed and sealed by a professional engineer registered in Florida in accordance with Rule 62-620.310, F.A.C.
- 2. Facility Information
- a. Permit Number: FL0002208 b. Facility Identification Number: FL0002208
- c. Project/Facility Name: FPL - St Lucie Nuclear Steam Power Plant
- d. Contact Name: Vince Munne Number and Street: 6501 South Ocean Drive City/State/Zip Code: Jensen Beach/FL/34957 Telephone 772-263-2847
- 3. Type of Revision LI Correct Typographical Errors' - Submit one copy of each page of the permit showing revisions being requested.
El Change Improvement Schedule' - Provide a description of the improvement, a list of the dates to be revised, and a reason for the proposed change in each date.
LI Change Expiration Date of Permit' - Provide the current and proposed expiration dates for the permit and the reasons for the proposed change.
El Change Staffing Requirements 2 - Describe the proposed change and submit justification for the change in accordance with Chapter 62-699, F.A.C.
'A procesing fmeis "ot required. . DEP Form 62-620.910(9)
A processing fee is required with the applimtion Effeutive October 23, 2000 in accordance wit Rule 62-4.050, F. AC.
El Change Monitoring and Reporting Requirements2 - Describe the proposed change and submit justification for the change in accordance with Chapter 62-601, F.A.C.
[] Modify Approved Pretreatment Program' - Describe the proposed modification and provide the information required by Rule 62-625.540, F.A.C.
El Delete Point Source Outfall' - Identify the outfall and explain why the outfall is being eliminated.
[i Modify or Expand Approved Residuals Land Application Sites2 - Attach a new or updated Agricultural Use or Dedicated Site Plan as required by Chapter 62-640, F.A.C.
[ Minor Modification to the Facility2 - Provide a description of the proposed modification. If applicable, attach any reports, plans, and specifications which have been developed to implement this modification.
[ Other' - Provide appropriate documentation. Describe.
- 4. Certifications
- a. Applicant or Authorized Representative I certify under penalty of law that I have personally examined and am familiar with the information submitted in this application and all attachments and that, based on my inquiry of persons immediately responsible for obtaining the information contained in the application, I believe that the information is true, accurate and complete. I am aware that there are significant penalties for submitting false information, including the poss ty of fine and rsonment.
T (Signature of Applicant or )Cothorized Representative7) (Date)
Name (please type) Richard L. Anderson Company Name FPL St Lucie Plant Title Site Vice President Company Address: 6501 South Ocean Drive Phone: 772-467-7100 City/State/Zip Code: Jensen Beach/FL/34957
- b. Professional Engineer Registered in Florida I certify that the engineering features of this project have been (designed) (examined) by me and found to conform to engineering principles applicable to such projects. In my professional judgement, this facility, when properly constructed, operated, and maintained, will comply with all applicable statutes of the State of Florida and rules of the Department.
Name (please type): Glenn M. Andrews Florida Registration Number: 65772 Company Name: Absolute Consulting, Inc.
Company Address: 7552 Navarre Parkway, Suite 63 City/State/Zip Code: Navarre/FL!32566 Phone Number: 772-361-5865 (Seal, Signature, Date, and Registration Number)
'If sigped by the authorized repreentative, 2 DEP Form 62-620 910(9) attach a letter ofauttorization in accordance FffertCvM OCtober23, 2000 Rule62-620.305, F.AC.
APPLICATION FOR A MINOR REVISION TO A WASTEWATER FACILITY OR ACTIVITY
_PERMIT
- 1. instructions
- a. In accordance with Rule 62-620;325, F.A.C., this form must be submitted to the appropriate Department district office or approved local program when requests for minor revisions to a permit or minor modifications to a facility are made by a permittee, except for transfer of a permit to a new permittee and addition of a major user of reclaimed water to a Part IIl reuse system. Application for transfer of a permit to a new permittee shall be made on DEP Form 62-620.910(11). Application for addition of a major user of reclaimed water shall be made on DEP Form 62-610.300(4)(a)1.
- b. Each applicable item must be completed in full in order to avoid delay in processing of this form. Where attached sheets or other technical documentation are provided, indicate appropriate cross-references.
- c. Three (3) copies of this application with supporting documentation shall be submitted with this form.
- d. All information is to be typed or printed in ink. Dates are to be entered in MM/DD/YR format.
- e. This application and attachments shall be signed in accordance with Rule 62-620.305, F.A.C. Also, as applicable, this application and all attachments shall be signed and sealed by a professional engineer registered in Florida in accordance with Rule 62-620.310, F.A.C.
- 2. Facility Information a- Permit Number: FL0002208 b. Facility Identification Number: FL0002208
- c. Project/Facility Name: FPL - St Lucie Nuclear Steam Power Plant
- d. Contact Name: Vince Munne Number and Street: 6501 South Ocean Drive City/State/Zip Code: Jensen Beacb/FL/34957 Telephone 772-263-2847
- 3. Type of Revision
[E Correct Typographical Errors' - Submit one copy of each page of the permit showing revisions being requested.
[]Change Improvement Schedule' - Provide a description of the improvement, a list of the dates to be revised, and a reason for the proposed change in each date.
[I Change Expiration Date of Permit' - Provide the current and proposed expiration dates for the permit and the reasons for the proposed change.
El Change Staffing Requirements2 - Describe the proposed change and submit justification for the change in accordance with Chapter 62-699, F.A.C.
A procesing fee is not required. DEP Form 62-620.910(9)
'A processing fee is required with the application Effective October 23, 2000 in accordance with Rule 62-4.050, F.A.C.
[] Change Monitoring and Reporting Requirements2 - Describe the proposed change and submit justification for the change in accordance with Chapter 62-601, F.A.C.
[] Modify Approved Pretreatment Program' - Describe the proposed modification and provide the information required by Rule 62-625.540, F.A.C.
F- Delete Point Source Outfall' - Identify the outfall and explain why the outfall is being eliminated.
[ Modify or Expand Approved Residuals Land Application Sites2 - Attach a new or updated Agricultural Use or Dedicated Site Plan as required by Chapter 62-640, F.A.C.
[ Minor Modification to the Facility7 - Provide a description of the proposed modification. If applicable, attach any reports, plans, and specifications which have been developed to implement this modification.
El Other 2 - Provide appropriate documentation. Describe.
- 4. Certifications
- a. Applicant or Authorized Representative I certify under penalty of law that I have personally examined and am familiar with the information submitted in this application and all attachments and that, based on my inquiry of persons immediately responsible for obtaining the information contained in the application, I believe that the information is true, accurate and complete. I am aware that there are significant penalties for submitting false information, including the possibility of fine and imprisonment.
(Signature of Applicant or\ uthorized Representative3) (Date)
Name (please type) Richard L. Anderson Company Name FPL St Lucie Plant Title Site Vice President Company Address: 6501 South Ocean Drive Phone: 772-467-7100 City/State/Zip Code: Jensen Beach/FL/34957
- b. Professional Engineer Registered in Florida I certify that the engineering features of this project have been (designed) (examined) by me and found to conform to engineering principles applicable to such projects. In my professional judgement, this facility, when properly constructed, operated, and maintained, will comply with all applicable statutes of the State of Florida and rules of the Department.
Name (please type): Glenn M. Andrews Florida Registration Number: 65772 Company Name: Absolute Consulting, Inc.
Company Address: 7552 Navarre Parkway, Suite 63 City/State/Zip Code: Navarre/FL/32566 Phone Number: 772-361-5865 (Seal, Signature, Date, and Registration Number)
'if signed by the authodzcd reprsentative, 2 DEP Forem62-620.910(9) atuch a letter of authorization in accordance Fffective October 23, 2000 Role62-620,305, F.AC
VPPSL006 ENCLOSURE 2
FPL - St.
Lucie FDEP IWWNuclear Steam Power Permit #
Evaporation FL0002208 Plant
/ Percolation Attachment Basin - I (Cover + Emergency Discharge 3 pages) Structure
FPL - St Lucie Nuclear Steam Power Plant FDEP IWW Permit # FL0002208 Attachment I Evaporation/ Percolation Basin Emergency Discharge Structure Project Narrative Discharges from the existing onsite Stormwater Management Evaporation/Percolation Basin are allowed and governed by existing Industrial Wastewater Permit FL0002208 dated September 29, 2011. Specifically, permit condition I.B.8 states, "...permittee is authorized to discharge stormwater from Internal Outfall 1-008 to the intake canal." In preparation for forecast extreme inclement weather (hurricane warning issued) commonly experienced at the plant, plant procedures dictate that the level in the basin be drawn down to 3.5' NGVD29. In times of unexpected extreme weather (i.e. Tropical Storm Faye 15" rainfall instead of forecast 3"), plant procedures dictate that if the water level reaches 5.5' NGVD29, the basin is drawn down to elevation 3.5' NGVD29. Failure to control the basin water level as described can result in the forced shutdown of the plant (i.e.
Tropical Storm Faye). The current method of drawing down the water level is by the use of portable pumps. These pumps must be monitored and refueled during operation in the midst of the storm, which introduces safety and environmental risks. High winds have prevented the successful placement of the portable pumps. In accordance to the permit conditions, the volume of water discharged is monitored, recorded, and reported to FDEP when the discharge becomes necessary.
The proposed alternative draw down method is to construct a permanent discharge structure that is normally closed, but can be manually opened to drain the basin. The attached sketches show a precast concrete structure that has a control weir cast into the face of the structure. A manually activated sluice gate is mounted on the inside of the structure to control the flow into the structure.
The invert of the control weir will be set at the elevation described by the existing procedures. The existing procedures will be revised accordingly. Discharge pipe(s) will be installed between the discharge structure and the intake canal. The number and size of the pipe(s) is dependent upon the construction method chosen. The discharge pipe(s) will protrude through the existing intake canal revetment system slightly above normal operating level taking advantage of the energy dissipating characteristics of water. The discharge pipe(s) will be equipped with flap gates to prevent backflow from the canal. The flow through the structure is automatically metered and recorded per the permit conditions. Since the proposed system is a passive system once activated and can be monitored by existing plant surveillance systems, the safety and environmental hazards are greatly reduced.
Applicant's Signature: ý:- 3 /)JI.2/, I-Richard L. Ande on Date Engineer's Signature: & , - 03/06/12 Glenn M. Andrews, PE #65772 Date
FPL - St Lucie Nuclear Steam Power Plant FDEP IWW Permit # FL0002208 Attachment 1 Evaporation/Percolation Basin Emergency Discharge Structure Project Narrative Discharges from the existing onsite Stormwater Management Evaporation/Percolation Basin are allowed and governed by existing Industrial Wastewater Permit FL0002208 dated September 29, 2011. Specifically, permit condition I.B.8 states, "...permittee is authorized to discharge stormwater from Internal Outfall 1-008 to the intake canal." In preparation for forecast extreme inclement weather (hurricane warning issued) commonly experienced at the plant, plant procedures dictate that the level in the basin be drawn down to 3.5' NGVD29. In times of unexpected extreme weather (i.e. Tropical Storm Faye 15" rainfall instead of forecast 3"), plant procedures dictate that if the water level reaches 5.5' NGVD29, the basin is drawn down to elevation 3.5' NGVD29. Failure to control the basin water level as described can result in the forced shutdown of the plant (i.e.
Tropical Storm Faye). The current method of drawing down the water level is by the use of portable pumps. These pumps must be monitored and refueled during operation in the midst of the storm, which introduces safety and environmental risks. High winds have prevented the successful placement of the portable pumps. In accordance to the permit conditions, the volume of water discharged is monitored, recorded, and reported to FDEP when the discharge becomes necessary.
The proposed alternative draw down method is to construct a permanent discharge structure that is normally closed, but can be manually opened to drain the basin. The attached sketches show a precast concrete structure that has a control weir cast into the face of the structure. A manually activated sluice gate is mounted on the inside of the structure to control the flow into the structure.
The invert of the control weir will be set at the elevation described by the existing procedures. The existing procedures will be revised accordingly. Discharge pipe(s) will be installed between the discharge structure and the intake canal. The number and size of the pipe(s) is dependent upon the construction method chosen. The discharge pipe(s) will protrude through the existing intake canal revetment system slightly above normal operating level taking advantage of the energy dissipating characteristics of water. The discharge pipe(s) will be equipped with flap gates to prevent backflow from the canal. The flow through the structure is automatically metered and recorded per the permit conditions. Since the proposed system is a passive system once activated and can be monitored by existing plant surveillance systems, the safety and environmental hazards are greatly reduced.
Applicant's Signature: _______RiharL._____,___D___
- Richard L. An ,rson Date Engineer's Signature: 03/06/12 Glenn M. Andrews, PE #65772 Date
FPL - St Lucie Nuclear Steam Power Plant FDEP LWW Permit # FL0002208 Attachment 1 Evaporation/Percolation Basin Emergency Discharge Structure Project Narrative Discharges from the existing onsite Stormwater Management Evaporation/Percolation Basin are allowed and governed by existing Industrial Wastewater Permit FL0002208 dated September 29, 2011. Specifically, permit condition I.B.8 states, ".. permittee is authorized to discharge stormwater from Internal Outfall 1-008 to the intake canal." In preparation for forecast extreme inclement weather (hurricane warning issued) commonly experienced at the plant, plant procedures dictate that the level in the basin be drawn down to 3.5' NGVD29. In times of unexpected extreme weather (i.e. Tropical Storm Faye 15" rainfall instead of forecast 3'", plant procedures dictate that if the water level reaches 5.5' NGV-D29, the basin is drawn down to elevation 3.5' NGVD29. Failure to control the basin water level as described can result in the forced shutdown of the plant (i.e.
Tropical Storm Faye). The current method of drawing down the watcr level is by the use of portable pumps. These pumps must be monitored and refueled during operation in the midst of the storm, which introduces safety and environmental risks. High winds have prevented the successful placement of the portable pumps. In accordance to the permit conditions, the volume of water discharged is monitored, recorded, and reported to FDEP when the discharge becomes necessary.
The proposed alternative draw down method is to construct a permanent discharge structure that is normally closed, but can be manually opened to drain the basin. The attached sketches show a precast concrete structure that has a control weir cast into the face of the structure. A manually activated sluice gate is mounted on the inside of the structure to control the flow into the structure.
'The invert of the control weir will be set at the elevation described by the existing procedures. The existing procedures will be revised accordingly. Discharge pipe(s) will be installed between the discharge structure and the intake canal. The number and size of the pipe(s) is dependent upon the construction method chosen. The discharge pipe(s) will protrude through the existing intake canal revetment system slightly above normal operating level taking advantage of the energy dissipating characteristics of water. The discharge pipe(s) will be equipped with flap gates to prevent backflow from the canal. The flow through the structure is automatically metered and recorded per the permit conditions. Since the proposed system is a passive system once activated and can be monitored by existing plant surveillance systems, the safety and environmental hazards are greatly reduced.
Applicant's Signature: ?d ncL/ ... O/.a Engineer's Signature: - 03/06/12 Glenn M. Andrews, PE #65772 Date
VPPSL006 ENCLOSURE 3 Three signed and sealed drawings of the proposed 1-008 Discharge Structure DRAWING NO, PSL-C-275630-001 (Cover + 9 pages)
FDEP IWVW Permit # FL0002208 Attachment 2 ATLANTIC OCEAN HERMAN BAY Glenn M.Andrews, P.E.
~1AR R~ 6 2612 KEY MAP Lic. No. 65772 NPE DIV: CIVIL OR: JCG CH: OMA DATE: 3/1/12 CAD fLE: PSL-C-275630-001
FDEP IWW Permit # FL0002208 Attachment 2
ýix S .R.A I A , r-x x-x
/1 ~
"N 0
'N W.E. 5.2 A1 PROPOSED Nd CONTROL STRUCTURE PIPE x
- N
/
- VERTICAL DATUM = NGVD 29 DRAWING NO.
DIV: CIVIL DR: JCG PSL-C-275630-001 CH: GMA SHEET DATE: 3/1/12 2 OF 3
FIDEP (WW Permit # FL0002208 Attachment 2 EXIS77NG DRAINAGE POND EXIS77NG INTAKE CANAL WHEEL ACTIVATED SLUICE GATE EQUIPPED WITH FLOW METERING
& RECORDING DEVICE (SEE NOTE)-
I I ,-EXISI7NG GROUND INTAKE CANAL SURFACE EL -FLAP GATE V7 - 3.20' NCVD 29 ZPRECAST CONCRETE CONTROL STRUCTURE RIM EL. = 6.25 NOTCH EL - 3.50 INV. EL. = 0.50 BOTTOM EL. - 0.00 NOTE.' /
PROCEDURALLY ACTIVATE SLUICE GATE WHEN WATER SURFACE CONCRET7 BLOCK (f ELEVATION REACHES 5.50' NGVD 29 AND IN PREPARATION TO SEVERE WEATHER AFTER ACCEPTABLE WATER QUALITY TESTiNG RESULTS.
SECTION A-A Glenn M.Andrews, RE MAR 0 6 2012 Lic. No. 65772 NPE DRAWING NO.
DIV: CIVIL DR: JC( APPROVAL UNIT 1 & 2 PSL-C-275630-001 <
CH: GMA TYPICAL CROSS SECTION SHEET DATE: 3/1/12 SECTION A-A 3 OF 3 0-CADFILE:PSL-C-275630-001 SH2
FDEP JWV Permit # FL0002208 Attachment 2 ATLANTIC OCEAN
-PROJECT LOCATION HERMAN BAY KEY MAP NPE DIV: CIVIL DR: JCG CH: GMA DATE: 3/1/12 CAD MLE:PSL-C-275630-O01
FDEP IWV Permit # FL0002208 Attachment 2 X x x
-~ ~
x* *-S.R. A1A Nx ix xtN A~
I \
~
A
/N '~.
-7 x I
/ WE. 5.2 N
PROPOSED
/ CONTROL STRUCTURE PIPE
~ x
\x *
./ /,-
PLAN DIV: CIVIL DR: JCG CH: GMA DATE: 3/1/12 CAD FILE:PSL-C-275630-OO1 SH 2
FOEP IWVVN Permit # FL0002208 Attachment 2 EXlS1"NG DRAINAGE POND I XISTINC INTAKE CANA4L WHEEL ACTIVATED SLUICE GATE r INTAKE CANAL EQUIPPED WITH FLOW METERING {-EXISTING GROUND
& RECORDING DEVICE (SEE NOTE)
SURFACE EL. F-FLAP GATE V_ =J.20' NGV 29 VD 29 PFRECAST CONCRETE CONTROL STRUCTURE RIM EL. - 6.25 NOTCH EL - 3.50 1 L
,00741 INV. EL. = 0.50 BOTTOM EL. = 0.00 PROCEDURALLY ACTIVATE SLUICE GATE WHEN WATER SURFACE CONCRETE BLOCK (
ELEVATION REACHES 5.50' NGVD 29 AND IN PREPARATION TO SEVERE WEATHER AFTER ACCEPTABLE WATER QUALrY TESTING RESULTS.
SECTION A-A
~4~~nM n~rew, R__
MA 2062M Li. o.69-77?2 NPE FLORIDA POWER & LIGHT COMPANY DRAWING NO. i ST. LUCIE PLANT DIV: CML DR JCG APPROVAL UNIT 1 & 2 PSL-C-275630-O01 CH: GMA TYPICAL CROSS SECTION SHEET DATE: 3//12 T PL SECTION A-A 3 OF 3 0 CAD FLE PSL-C-275630-O01 SH2
FDEP IWWN Permit # FL0002208 Attachment 2 ATLANTIC OCEAN HERMAN BAY KEY MAP NPE DIV: CIVIL DR: JCG CH: GMA DATE: 3/1/12
FDEP 'WW Permit # FL0002208 Attachment 2 x x
- x. x .. . - S.R. AlA Nx
/1?
f/4'ý
/
I x W.E. 5.2 AA PROPOSED -PROPOSED CONTROL S DISCHARGE PIPE x
to Cd
-I PLAN NPE DIV: CIVIL DR: JCG CH: OMA DATE: 3/1/12 CADFILE:PSL-C-275630-00l SH 2
FODEP IWI Permit # FL0002208 Attachment 2
[
EXISTING DRAINAGE POND £XIT77NO INTAKE CANAL WHEEL ACTIVATED SLUICE GATE INTAKE CANAL EQUIPPED WITH FLOW METERING EXIS77NG GROUND
& RECORDING DEVICE (SEE NOTE)
SURFACE ELN rFLAP GATE V-3.20' NGIýV 29 ZPRECAST CONCRETE CONTROL STRUCTURE NV,. ESL 0.DD RIM EL = 6.25 NOTCH EL = 3.50 INV. EL - 0.50 BOT'rOM EL = 0.00 /
"ISING ARTnCUL4-TNG i PROCEDURALLY ACTIVATE SLUICE GATE WHEN WATER SURFACE CONCRETE BLOCK (rYP)
ELEVATION REACHES 5.50' NGVD 29 AND IN PREPARATION TO SEVERE WEATHER AFTER ACCEPTABLE WATER QUALITY TESTING RESULTS.
SECTION A-A Glenn M.Andrews, P.E.
Li-ýR.[,', 62 2012 Lic. No. G5772 A
NPE DRAWING NO.
DIV: CIVIL DR: JCG APPROVAL CH: GMA TYPICAL CROSS SECTION SHEET DATE: 3/1/12 SECTION A-A 3 OF 3 CADFILE' PSL-C-275630-O01 SH2
VPPSL006 ENCLOSURE 4 FPL check payable to the State of Florida, Department of Environmental Protection in the amount of $250.00 for application fee (Cover + 1 page)