L-02-104, September 2002 Monthly Operating Report for Beaver Valley

From kanterella
(Redirected from L-02-104)
Jump to navigation Jump to search
September 2002 Monthly Operating Report for Beaver Valley
ML022900474
Person / Time
Site: Beaver Valley
Issue date: 10/07/2002
From: Bezilla M
FirstEnergy Nuclear Operating Co
To:
Document Control Desk, Office of Nuclear Reactor Regulation
References
GL-97-002, L-02-104
Download: ML022900474 (5)


Text

FENOC FRrs*Et'er*"NiclarCean C a."

Beaver Valley Power Station P. 0. Box 4 Shippingport, PA 15077 L-02-104 October 7, 2002 Beaver Valley Power Station Unit 1 - Docket No. 50-334, License No. DPR-66 Unit 2 - Docket No. 50-412, License No. NPF-73 Monthly Operating Report U. S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 Gentlemen:

In accordance with NRC Generic Letter 97-02, "Revised Contents of the Monthly Operating Report", and Unit 1 and 2 Technical Specification 6.9.4, the "Monthly Operating Report" is submitted for Unit 1 and Unit 2 for the month of September 2002.

Respectfully, M. B. Bezilla Vice-President DTJ/cmg Enclosures cc: NRC Regional Office King of Prussia, PA

UNIT SHUTDOWNS DOCKET NO. 50-334 UNIT NAME BVPS Unit #1 DATE October 2, 2002 COMPLETED BY David T. Jones TELEPHONE (724) 682-4962 REPORTING PERIOD: September 2002 No. Date Type Duration Reason Method of Cause / Corrective Actions (Y/M/D) F: Forced (Hours) (1) Shutting S: Scheduled Down (2) Comments NONE (1) Reason (2) Method A - Equipment Failure (Explain) 1 - Manual B - Maintenance or Test 2 - Manual Trip I Scram C - Refueling 3 - Automatic Trip / Scram D - Regulatory Restriction 4 - Continuation E - Operator Training / License Examination 5 - Other (Explain)

F - Administratve G - Operational Error (Explain)

H - Other (Explain)

SUMMARY

The Unit operated at a nominal value of 100% output for the entire report period.

OPERATING DATA REPORT DOCKET NO.: 50-334 UNIT NAME: BVPS UNIT #1 REPORT DATE: 10/01/02 COMPLETED BY: DAVID T. JONES TELEPHONE: (724) 682-4962

  • Notes: Rated thermal power at
  • la. REPORTING PERIOD: SEPTEMBER 2002
  • BVPS-l was uprated from 2652 MWt*
  • to 2689 MWt on 10/20/01. Net *
1. DESIGN ELECTRICAL RATING (Net MWe): 835
  • MDC was also uprated from *
  • 810 MWe to 821 MWe. *
2. MAX. DEPENDABLE CAPACITY (Net MWe): 821 THIS MONTH YEAR TO DATE CUMULATIVE 720.0 6551.0 231575.0 3a. HOURS IN REPORTING PERIOD:

720.0 6551.0 158633.4

3. NO. OF HRS. REACTOR WAS CRITICAL:

720.0 6551.0 156172.9

4. SERVICE HOURS GENERATOR ON LINE:

0.0 0.0 0.0

5. UNIT RESERVE SHUTDOWN HOURS:

593210.0 5388950.0 117055093.0

6. NET ELECTRICAL ENERGY GEN. (MWH):

628400.0 5705720.0 124972506.0

7. GROSS ELECT. ENERGY GEN. (MWH):

1933446.0 17479611.0 385114416.5

8. GROSS THERMAL ENERGY GEN. (MWH):

100.0 100.0 68.9

9. UNIT AVAILABILITY FACTOR (M6):

100.4 100.2 64.2

10. UNIT CAPACITY FACTOR (MDC) (M):

0.0 0.0 15.8 II. UNIT FORCED OUTAGE RATE (M):

UNIT SHUTDOWNS DOCKET NO. 50-412 UNIT NAME BVPS Unit #2 DATE October 2, 2002 COMPLETED BY David T. Jones TELEPHONE (724) 682-4962 REPORTING PERIOD: September 2002 (1) Reason (2) Method A - Equipment Failure (Explain) 1 - Manual B - Maintenance or Test 2 - Manual Trip / Scram C - Refueling 3 - Automatic Trip / Scram D - Regulatory Restriction 4 - Continuation E - Operator Training / License Examination 5 - Other (Explain)

F - Administratve G - Operational Error (Explain)

H - Other (Explain)

SUMMARY

The Unit began the report period operating at a nominal value of 100% output. On 9/20102 with the Main Unit Condenser parameters degrading due to suspected macro fouling, the Unit began to make incremental load reductions beginning at 0829 hours0.00959 days <br />0.23 hours <br />0.00137 weeks <br />3.154345e-4 months <br /> in order to prevent exceeding Condenser operating limits. With load incrementally reduced approximately 19% throughout the day, the Unit began to reduce output an additional 13% at approximately 2100 hours0.0243 days <br />0.583 hours <br />0.00347 weeks <br />7.9905e-4 months <br /> on 9/20/02 in order to clean the Main Unit Condenser. An output of approximately 68% was achieved at 0018 hours2.083333e-4 days <br />0.005 hours <br />2.97619e-5 weeks <br />6.849e-6 months <br /> on 9/21/02. All four waterboxes of the Main Condenser were required to be cleaned due to the presence of Cooling Tower fill material which had migrated through a damaged basin screen and into the inlet side of the Condenser. While Condenser cleaning continued, the Unit raised output approximately 6% at 1520 hours0.0176 days <br />0.422 hours <br />0.00251 weeks <br />5.7836e-4 months <br /> on 9/24/02 in an effort to reduce Turbine vibrations being experienced at the #3 Turbine Trip/Governor Valve. Upon completion of cleaning all four Condenser waterboxes, the Unit commenced to return to full power at 0539 hours0.00624 days <br />0.15 hours <br />8.912037e-4 weeks <br />2.050895e-4 months <br /> on 9/25/02. A nominal value of 100% output was achieved at 0423 hours0.0049 days <br />0.118 hours <br />6.994048e-4 weeks <br />1.609515e-4 months <br /> on 9/26/02. The Unit continued to operate at a nominal value of 100% output for the remainder of the report period.

OPERATING DATA REPORT DOCKET NO.: 50-412 UNIT NAME: BVPS UNIT #2 REPORT DATE: 10/01/02 COMPLETED BY: DAVID T. JONES TELEPHONE: (724) 682-4962

  • Notes: Rated thermal power at
  • la. REPORTING PERIOD: SEPTEMBER 2002
  • BVPS-2 was uprated from 2652 MWt*
  • to 2689 Mw1t on 10/30/01. Net *
1. DESIGN ELECTRICAL RATING (Net MWe): 836
  • MDC was also uprated from *
  • 820 MWe to 831 MWe. *
2. MAX. DEPENDABLE CAPACITY (Net MWe): 831 THIS MONTH YEAR TO DATE CUMULATIVE 720.0 6551.0 130358.0 3a. HOURS IN REPORTING PERIOD:

REACTOR WAS CRITICAL: 720.0 5991.6 107346.1

3. NO. OF HRS.

720.0 5924.9 106617.5

4. SERVICE HOURS GENERATOR ON LINE:

0.0 0.0 0.0

5. UNIT RESERVE SHUTDOWN HOURS:

(MWH): 561323.0 4747484.0 83325576.0

6. NET ELECTRICAL ENERGY GEN.

ENERGY GEN. (MWH): 592063.0 5009033.0 88083776.0

7. GROSS ELECT.

1823375.0 15295737.0 268703318.0

8. GROSS THERMAL ENERGY GEN. (MWH):

100.0 90.4 81.8

9. UNIT AVAILABILITY FACTOR (M}:

93.8 87.2 77.2

10. UNIT CAPACITY FACTOR (MDC) (M):

0.0 0.3 9.9

11. UNIT FORCED OUTAGE RATE (M):

Text

FENOC FRrs*Et'er*"NiclarCean C a."

Beaver Valley Power Station P. 0. Box 4 Shippingport, PA 15077 L-02-104 October 7, 2002 Beaver Valley Power Station Unit 1 - Docket No. 50-334, License No. DPR-66 Unit 2 - Docket No. 50-412, License No. NPF-73 Monthly Operating Report U. S. Nuclear Regulatory Commission Document Control Desk Washington, DC 20555 Gentlemen:

In accordance with NRC Generic Letter 97-02, "Revised Contents of the Monthly Operating Report", and Unit 1 and 2 Technical Specification 6.9.4, the "Monthly Operating Report" is submitted for Unit 1 and Unit 2 for the month of September 2002.

Respectfully, M. B. Bezilla Vice-President DTJ/cmg Enclosures cc: NRC Regional Office King of Prussia, PA

UNIT SHUTDOWNS DOCKET NO. 50-334 UNIT NAME BVPS Unit #1 DATE October 2, 2002 COMPLETED BY David T. Jones TELEPHONE (724) 682-4962 REPORTING PERIOD: September 2002 No. Date Type Duration Reason Method of Cause / Corrective Actions (Y/M/D) F: Forced (Hours) (1) Shutting S: Scheduled Down (2) Comments NONE (1) Reason (2) Method A - Equipment Failure (Explain) 1 - Manual B - Maintenance or Test 2 - Manual Trip I Scram C - Refueling 3 - Automatic Trip / Scram D - Regulatory Restriction 4 - Continuation E - Operator Training / License Examination 5 - Other (Explain)

F - Administratve G - Operational Error (Explain)

H - Other (Explain)

SUMMARY

The Unit operated at a nominal value of 100% output for the entire report period.

OPERATING DATA REPORT DOCKET NO.: 50-334 UNIT NAME: BVPS UNIT #1 REPORT DATE: 10/01/02 COMPLETED BY: DAVID T. JONES TELEPHONE: (724) 682-4962

  • Notes: Rated thermal power at
  • la. REPORTING PERIOD: SEPTEMBER 2002
  • BVPS-l was uprated from 2652 MWt*
  • to 2689 MWt on 10/20/01. Net *
1. DESIGN ELECTRICAL RATING (Net MWe): 835
  • MDC was also uprated from *
  • 810 MWe to 821 MWe. *
2. MAX. DEPENDABLE CAPACITY (Net MWe): 821 THIS MONTH YEAR TO DATE CUMULATIVE 720.0 6551.0 231575.0 3a. HOURS IN REPORTING PERIOD:

720.0 6551.0 158633.4

3. NO. OF HRS. REACTOR WAS CRITICAL:

720.0 6551.0 156172.9

4. SERVICE HOURS GENERATOR ON LINE:

0.0 0.0 0.0

5. UNIT RESERVE SHUTDOWN HOURS:

593210.0 5388950.0 117055093.0

6. NET ELECTRICAL ENERGY GEN. (MWH):

628400.0 5705720.0 124972506.0

7. GROSS ELECT. ENERGY GEN. (MWH):

1933446.0 17479611.0 385114416.5

8. GROSS THERMAL ENERGY GEN. (MWH):

100.0 100.0 68.9

9. UNIT AVAILABILITY FACTOR (M6):

100.4 100.2 64.2

10. UNIT CAPACITY FACTOR (MDC) (M):

0.0 0.0 15.8 II. UNIT FORCED OUTAGE RATE (M):

UNIT SHUTDOWNS DOCKET NO. 50-412 UNIT NAME BVPS Unit #2 DATE October 2, 2002 COMPLETED BY David T. Jones TELEPHONE (724) 682-4962 REPORTING PERIOD: September 2002 (1) Reason (2) Method A - Equipment Failure (Explain) 1 - Manual B - Maintenance or Test 2 - Manual Trip / Scram C - Refueling 3 - Automatic Trip / Scram D - Regulatory Restriction 4 - Continuation E - Operator Training / License Examination 5 - Other (Explain)

F - Administratve G - Operational Error (Explain)

H - Other (Explain)

SUMMARY

The Unit began the report period operating at a nominal value of 100% output. On 9/20102 with the Main Unit Condenser parameters degrading due to suspected macro fouling, the Unit began to make incremental load reductions beginning at 0829 hours0.00959 days <br />0.23 hours <br />0.00137 weeks <br />3.154345e-4 months <br /> in order to prevent exceeding Condenser operating limits. With load incrementally reduced approximately 19% throughout the day, the Unit began to reduce output an additional 13% at approximately 2100 hours0.0243 days <br />0.583 hours <br />0.00347 weeks <br />7.9905e-4 months <br /> on 9/20/02 in order to clean the Main Unit Condenser. An output of approximately 68% was achieved at 0018 hours2.083333e-4 days <br />0.005 hours <br />2.97619e-5 weeks <br />6.849e-6 months <br /> on 9/21/02. All four waterboxes of the Main Condenser were required to be cleaned due to the presence of Cooling Tower fill material which had migrated through a damaged basin screen and into the inlet side of the Condenser. While Condenser cleaning continued, the Unit raised output approximately 6% at 1520 hours0.0176 days <br />0.422 hours <br />0.00251 weeks <br />5.7836e-4 months <br /> on 9/24/02 in an effort to reduce Turbine vibrations being experienced at the #3 Turbine Trip/Governor Valve. Upon completion of cleaning all four Condenser waterboxes, the Unit commenced to return to full power at 0539 hours0.00624 days <br />0.15 hours <br />8.912037e-4 weeks <br />2.050895e-4 months <br /> on 9/25/02. A nominal value of 100% output was achieved at 0423 hours0.0049 days <br />0.118 hours <br />6.994048e-4 weeks <br />1.609515e-4 months <br /> on 9/26/02. The Unit continued to operate at a nominal value of 100% output for the remainder of the report period.

OPERATING DATA REPORT DOCKET NO.: 50-412 UNIT NAME: BVPS UNIT #2 REPORT DATE: 10/01/02 COMPLETED BY: DAVID T. JONES TELEPHONE: (724) 682-4962

  • Notes: Rated thermal power at
  • la. REPORTING PERIOD: SEPTEMBER 2002
  • BVPS-2 was uprated from 2652 MWt*
  • to 2689 Mw1t on 10/30/01. Net *
1. DESIGN ELECTRICAL RATING (Net MWe): 836
  • MDC was also uprated from *
  • 820 MWe to 831 MWe. *
2. MAX. DEPENDABLE CAPACITY (Net MWe): 831 THIS MONTH YEAR TO DATE CUMULATIVE 720.0 6551.0 130358.0 3a. HOURS IN REPORTING PERIOD:

REACTOR WAS CRITICAL: 720.0 5991.6 107346.1

3. NO. OF HRS.

720.0 5924.9 106617.5

4. SERVICE HOURS GENERATOR ON LINE:

0.0 0.0 0.0

5. UNIT RESERVE SHUTDOWN HOURS:

(MWH): 561323.0 4747484.0 83325576.0

6. NET ELECTRICAL ENERGY GEN.

ENERGY GEN. (MWH): 592063.0 5009033.0 88083776.0

7. GROSS ELECT.

1823375.0 15295737.0 268703318.0

8. GROSS THERMAL ENERGY GEN. (MWH):

100.0 90.4 81.8

9. UNIT AVAILABILITY FACTOR (M}:

93.8 87.2 77.2

10. UNIT CAPACITY FACTOR (MDC) (M):

0.0 0.3 9.9

11. UNIT FORCED OUTAGE RATE (M):