l k.
JAMES A. FITZPATRICK NUCLEAR POWER PLANT OPERATING DATA REPORT DOCKET NO: 50-333 UNIT NAME FITZPATRICK DATE JUNE 1987 COMPLETED BY JOHN COOK TELEPHONE (315) 349-6569 OPERATING STATUS 1:
UNIT NAME:
FITZPATRICK
- NOTES 2:
REPORTING PERIOD: 870501 - 870531 3:
LICENSED THERMAL POWER (MWT):
2436 4:
NAMEPLATE RATING (GROSS MWE):
883 5:
DESIGN ELECTRICAL RATING (NET MWE):
816 6:
MAXIMUM DEPENDABLE CAPACITY (GROSS MWE):
823 7:
MAXIMUM DEPENDABLE CAPACITY (NET MWE):
794 8:
IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS 3 - 7) SINCE LAST REPORT, GIVE REASONS:
NONE 9:
POWER LEVEL TO WHICH RESTRICTED, IF ANY (NET MWE):
NONE 10:
REASONS FOR RESTRICTIONS, IF ANY:
THIS MONTH YR-TO-DATE CUMULATIVE 11.
HOURS IN REPORTING PERIOD.
744 3624 103825 12.
NUMBER OF HOURS REACTOR WAS CRITICAL.
744 1305.5 74796.9 13.
REACTOR RESERVE SHUTDOWN HOURS.
0 0
0 14 HOURS GENERATOR ON-LINE.
744 1106.9 72565.2 15.
UNIT RESERVE SHUTDOWN HOURS.
0 0
0 16.
GROSS THERMAL ENERGY GENERATED (MWH).
1703136 2405952 156539074 17.
GROSS ELECTRICAL ENERGY GENERATED (MWH).
574590 795860 53618820 18.
NET ELECTRICAL ENERGY GENERATED (MWH).
554860 766870 51347000 19.
UNIT SERVICE FACTOR.
100%
30.5%
69.9%
20.
UNIT AVAILABILITY FACTOR.
100%
30.5%
69.9%
21.
UNIT CAPACITY FACTOR (USING MDC NET).
93.9%
26.7%
63.8%
22.
UNIT CAPACITY FACTOR (USING DER NET).
91.4%
25.9%
60.6%
23.
UNIT FORCED OUTAGE RATE.
0 0
12.0%
24.
SHUTDOWNS SCHEDULED OVER NEXT 6 MONTHS (TYPE, DATE AND DURATION OF EACH):
NONE 25.
IF SHUT DOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP:
26.
UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION):
FORECAST ACHIEVED INITIAL CRITICALITY INITIAL ELECTRICITY
~
COMMERCIAL OPERATION 8706150051 B70531 PDR ADOCK 050 33 I&%
2' JAMES A. FITZPATRICK NUCLEAR POWER PLANT
-AVERAGE DAILY UNIT POWER LEVEL DOCKET NO: 50-333 UNIT: FITZPATRICK DATE: MAY 1987 COMPLETED BY: John Cook j
TELEPHONE: (315)349-6569 MONTH APRIL 1987 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL MWe NET MWe NET 1
227 17 804 2
280 18 803 3
439 19 803 4
672 20 803 5
703 21 803 6
790 22 801 7
795 23 801 8
778 24 802 9
795 25 802 10 801 26 801 11 800 27 803 12 803 28 802 13 802 29 799 14 802 30 800 15 801 31 799 16 803
SUMMARY
- The FitzPatrick Plant returned to full power operation this reporting period.
-.,,, _ _._. _ -_ ~.-_ - _ -._ - _
JAMES A. FITZPATRICK NUCLEAR POWER PLAhT UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO: 50-333 UNIT NAME: FITZPATRICK
.DATE: JUNE 1987 REPORT MONTH MAY 1987 COMPLETED BY: John Cook TELEPHONE: (315)349-6569 D
C UH R
METHOD S
O RO E
OF YC MC CAUSE AND CORRECTIVE ACTION AU A
SHUTTING LICENSEE SO PO TO NO.
DATE TYPE TR S
DOWN EVEhT TD OD PREVEhT RECURRENCE IS O
THE REPORT EE NE O
N REACTOR M
E N
N T
NONE I
2 3
4 F: FORCED REASON:
METHOD:
EXHIBIT G.- INSTRUCTIONS S: SCHEDULED A. EQUIPMENT FAILURE (EXPLAIN) 1-MANUAL FOR PREPARATION OF DATA B. MAIhTENANCE OR TEST 2-MANUAL SCRAM ENTRY SHEETS FOR LICENSEE C. REFUELING 3-AUTOMATIC SCRAM EVENT REPORT (LER) FILE D. REGULATORY RESTRICTION 4-0THER (EXPLAIN)
E. OPERATOR TRAINING AND LICENSE EXAMINATION F. ADMINISTRATIVE G. OPERATIONAL ERROR (EXPLAIN)
H. OTHER (EXPLAIN)
NARRATIVE
SUMMARY
OF OPERATING EXPERIENCE MAY 1987 The FitzPatrick plant returned to full power operation this reporting period.
At the end of the month, the unit is operating at approximately 800 MWe.
4 i
d i
1 i
i l
J
-_m-NEW YORK POWER AUTHORITY JAMES A. FITZPATRICK NUCLEAR POWER PLANT MAYNTENANCE
SUMMARY
DOCKET NO:
50-333 UNIT NAME:
FITZPATRIC" DATE:
JUNE 1987 COMPLETED BY:
JOHN COOK FOR THE MONTH OF: MAY 1987 TELEPHONE:
(315) 349-6569 WORK REQUEST NO.
HOW CAUSE OF RESULTS OF ACTION TAKEN TO REPAIR DATE SYSTEM COMPONENT NO.
DETECTED MALFUNCTION MALFUNCTION PRECLUDE RECURRENCE TIME HOURS 870508 02-3 054441 OPS LEADS TERMINATED OUTPUT FOUND MOVE TO CORRECT 8
SLM-75D INCORRECTLY READING LOW TERMINALS 870421 03 054164 OPS PCV-204A NEEDS RV-7A,B LIFTING ADJUSTED TO CLOSE 14 PCV-204A ADJUSTMENT ON CRD AT 20 PSI l
870427 07 050667 JIC BAD COMPONENT SPARE SUPPLY CHANGE VR1 IN -20V 16 PVR SUPP'S FOUND DEFECTIVE SUPPLY 870503 07 054266 JIC INCORRECT CORE REPAIR "B" DRIVE CORRECT VALUES PER 2
NM-131-4B TOP CH2 CONTROL UNIT IMP-7.26 l
870505 07 054410 0FS RETRACTION SPEED "A" PROBE COUNTS ADJUST SPEED 12 NM-131-4A TOO SLOW OUT TOO LOW j
870529 07 054429 OPS BAD APRM AUX CARD REF SIGNAL FAILED REPLACE FROM STOCK, 37 NM-80C UPSCALE IMP-7.6 870512 07 054747 OPS CALIBRATION READS 55 WHEN AT IMP-7.22, ADJUSTED 14 NM-20-37 CURRENT LOW POWER CALIBRATION CURRENT l
l l
7 _.
NEW YORK POWER AUTHORITY JAMES A. FITZPATRICK NUCLEAR POWER PLANT MAINTENANCE
SUMMARY
DOCKET NO:
50-333 UNIT NAME:
FITZPATRICK l
DATE:
JUNE 1987 l
COMPLETED BY:
JOHN COOK FOR THE MONTH OF: MAY 1987 TELEPHONE:
(315) 349-6569 WORK REQUEST NO.
HOW CAUSE OF RESULTS OF ACTION TAKEN TO REPAIR DATE SYSTEM COMPONENT NO.
DETECTED MALFUNCTION MALFUNCTION PRECLUDE RECURRENCE TIME HOURS 870501 07 054757 OPS DIRTY ROTARY "A" TIP INDEXER CLEAN WITH CRC; 6
NM-131-4A SWITCH HANGS UP VERIFY OPERATION 870501 07 054768 OPS SLIP CLUTCH TIP "C" MOVES ADJUST TORQUE PER 8
NM-101C VERY SLOWLY IMP-7.26 870501 07 054769 OPS LOOSE CONNECTION LIGHT INDICATION SOLDER LOOSE 2
NM-131-4B IS MISSING DIGITS CONNECTIONS 870503 07 054783 OPS BAD TRANSISTOR ON "B" DRIVE CONTROL REPLACE BOARD FROM 7
NM-131-4B PROGRAM BOARD UNIT WON'T SEE STOCK CORE TOP 870521 07 055249 OPS K2 RELAY BAD "D" TIP DETECTOR REPLACE K2 RELAY 10 NM-131-4D FAILED TO DRIVE ON TIP DRIVE 870514 17 050559 JIC DUAL TRIP UNIT HI VOLT INOP REPLACE Z16 Ah"0 19 RM-50B MODULE Z16 APPEARS TO DRIFT PERFORM ISP-27-3 e
NEW YORK POWER AUTHORITY JAMES A. FITZPATRICK NUCLEAR POWER PLAhT MAINTENANCE SU}D'ARY
~
DOCKET NO:
50-333 UNIT NAME:
FITZPATRICK DATE:
JUNE 1987 COMFLETED BY:
JOHN COOK FOR THE MONTH OF: MAY 1987 TELEPHONE:
(315) 349-6569 WORK REQUEST NO.
HOW CAUSE OF RESULTS OF ACTION TAK13 TO REPAIR DATE SYSTEM COMPONENT NO.
DETECTED MALFUNCTION MALFUNCTION PRECLUDE RECURRENCE TIME HOURS 870228 17 051428 OPS MOD F1-84-038 INSTALL RAD ITE-INSTALLATION TEST, 218 RAD MONITORS MONITORS AND INSTALL, CHECK ASSOCIATED DETECTORS 870506 17 052731 OPS IMPROPER LIGHT CHECK SOURCE REPLACE; VERIFY 64 RIS-458A BULB WON'T INSERT "A" OPERATION 870424 17 054225 JIC BAD METER COULDN'T ADJUST REPLACE; CALIBRATE 10 RIS-432 METER WITHIN ISP-25 SPECS 870423 17 054259 JIC WRONG TYPE FUSES FUSES BLEW DURING REPLACE; ISP-27-1 OK 4
RM-350 ISP-27-1 870429 23 051197 OPS N/A NO FAILURE; INSTALL 0-RING PER 2
LS-90 INSTALL COVER VENDOR MANUAL 0-RINGS 870428 23 054078 OPS NEEDS REPLACEMENT HPCI TURBINE INSTALL AND CALIBRATE 13 PRESS GAGE EXHAUST LINE PER IMP-G1 GAGE
NEW YORK POWER AUTHORITY JAMES A. FITZPATRICK NUCLEAR POWER PLANT MAINTENANCE
SUMMARY
DOCKET NO:
50-333 UNIT NAME:
FITZPATRICK DATE:
JUNE 1987 COMPLETED BY:
JOHN COOK FOR THE MONTH OF: MAY 1987 TELEPHONE:
(315) 349-6569 WORK REQUEST NO.
HOW CAUSE OF RESULTS OF ACTION TAKEN TO REPAIR DATE SYSTEM COMPONENT NO.
DETECTED MALFUNCTION MALFUNCTION PRECLUDE RECURRENCE TIME HOURS 870424 23 054226 OPS AIR IN SENSING READS 700 GPM FT-82, VENT 7
FI-108-1 LINES WITH NO FLOW 870425 23 054263 JIC AIR TRAPPED IN FALSE 180 GPM VENT INSTRUMENT 2
FT-82 SENSING LINES INDICATION 870527 27 050442 OPS BURNED CONTACT, DOES NOT REGULATE REPAIR LEAKS; REPAIR 48 FIS-103B LEAKS FLOW RELAY 870418 27 050637 JIC MAINTAIN MOISTURE NO FAILURE; INSTALL / ATTACH #1; 44 PCA-101A,B TO CELL MEMBRANES INSTALL TEMP CAL /ISP-30-1 N2 BUBBLER 870505 27 054189 OPS WEAR WIRE BROKEN OFF CHECK PRINTS, 26 RM-104A TERMINAL BB-68 RETERMINATE WIRE 870504 27 054780 JIC NEEDED CALIBRATION POWER SUPPLY REPLACE FUSE, 8
PT-102B BLOWING FUSES CALIBRATE PER IMP-4.5 870512 66
.050737 JIC FAULTY AGASTAT ACCU-1A-ITR BAD REPLACE FROM STOCK; 10 ACCU-1A DURING TESTING TEST, SET A 50s u
M
. NEW M POER AUINORITY J#ES A. FITZPATRICK NUCEAR POWER PIANT
. ~
SAFE 1Y RELATED ELECIRICAL & HECHANICAL MAIhTENANCE SGHARY MAY 1987 leEAIR W RK REQUEST f TDE DATE SYSTDi CCHPONENT HOW DEIECTED CAUSE OF MAUUNCTION -
ACTION TAKEN TO PRECLUDE RECURRENCE HOURS 5/13-00 54394 OPS
' Penetration not.
Sealed Penetration 18.5 T-37I sealed 5/1 23 53857 OPS Ioose Packing Adjusted Packing 2.0 HN I4 5/19 11 36937 OPS Worn Gasket
. Replaced Gasket 13.0 P 2K-I I
NEW YORK POWER AUTHORITY
. JAMES A. FITZPATRICK NUCLEAR POWER PLANT REFUELING INFORMATION
- 11. 'The date of'the next sche'duled refueling outage is August, 1988.
~2, The scheduled date for.. restart following refueling is November, 1988.
3.
Will refueling or resumption of operation thereafter require a technical specification change or other license amendment?
p YES X If yes, describe in general what these will be and go to question 5.
Changes'in MCPR values and possible ECCS fuel bundle enrichment changes. These reflect-typical refuel changes.
NO If no, answer question 4.
4..
ANSWER ONLY IF ANSWER TO 3 ABOVE IS NO.
Has the reload fuel design and core configuration been reviewed by the Plant Safety Review committee to determine whether any unreviewed safety questions are associated with the core reload (Ref. 10 CFR Section 50.59)?
5.
ANSWER ONLY IF ANSWER TO 3 ABOVE'IS YES.
4
'The scheduled date for submitting proposed licensing action and supporting information is July - August, 1988.
6.
Answer the following important licensing considerations:
YES NO i
a) New fuel design?
X b) New fuel supplier?
X c) Are there any new u'nreviewed design or performance analysis methods?
X d)~ Are there any new operating procedure?
X j
e) Other Specify:
7.
There are normally 560 fuel assemblies in the core during operation, presently there
-are 560 in the core.
8.
a) There are 1200 fuel' assemblies of the licensed allowable 2244 in the spent fuel'
.. pool.
-b)
An increase in the licensed storage capacity:
X 1s being contemplated as this time.
is planned at this time for an additional ~
fuel assemblies.
'has been requested for an additional fuel assemblies.
19.
October, 1992 is the last possible refueling date that can be projected at this time given the presently licensed spent fuel pool storage capacity.
e.
J:mes A. FitzP trick Nuclear Power Plant PO. Box 41 Lycoming, New York 13093 315 342.3840
- > NewYorkPower 4# Authority June 9, 1987 JAFP-87-0470 Director, Office of Inspection and Enforcement U.S.
Nuclear Regulatory Commission Washington, D.C.
20555 ATTENTION:
DOCUMENT CONTROL DESK
REFERENCE:
DOCKET NO. 50-333
Dear Sir:
Enclosed please find the J.
A.
FitzPatrick Operating Status Report for the month of May, 1987.
Refueling information has been updated and is attached to this transmittal.
If there are any questions concerning this report, please contact John Cook at (315) 349-6569.
l RA FORD CONVERSE RESIDENT MANAGER RJC:JPC:mac Enclosures cc:
Distribution
>{i
-