JAFP-86-1026, Monthly Operating Rept for Nov 1986

From kanterella
Jump to navigation Jump to search
Monthly Operating Rept for Nov 1986
ML20214X067
Person / Time
Site: FitzPatrick Constellation icon.png
Issue date: 11/30/1986
From: Radford Converse, Jackie Cook
POWER AUTHORITY OF THE STATE OF NEW YORK (NEW YORK
To:
NRC OFFICE OF ADMINISTRATION (ADM)
References
JAFP-86-1026, NUDOCS 8612100526
Download: ML20214X067 (8)


Text

s JAMES A. FITZPATRICK NUCLEAR POWER PIANT OPERATING DATA REPORT DOCKET NO. 50-333 UNIT NAME ruuAIRICK DATE DEC 1986 00MPIETED BY JOHN COOK TELEPIONE (315)342-3840 OPERATING STATUS
1. UNIT NAME: FITZPATRICK NOTES
2. . REPORTING PERIOD: 861101-861130
3. LICENSED 11IERMAL POWER (MWT): 2436
4. NAMEPIATE RATING (GROSS MWE): 883
5. DESIGN ELECTRICAL RATING (NET MWE): 816
6. MAXIMUM DEPENDABLE CAPACITY (GROSS MWE): 823
7. F%XIMlE DEPENDABLE CAPACITY (NET MWE): 796
8. IF CHANGES OCCUR IN CAPACITY RATINGS (ITms 3 - 7) SINCE IAST RttUKr, GIVE REASONS:

NONE

9. IWER IZVEL 10 WHICH Kr.mIUrt.U, IF ANY (Nr;f MWE): NONE
10. REASONS FOR RESTRICTIONS, IF ANY:

THIS 10 NTH YR-10-DATE CUMUIATIVE

11. IIOURS IN REPORTING PERIOD: 720 8016 99457
12. N1.NBER OF HOURS REACIOR WAS CRITICAL: 720 7331.8 72747.4
13. REACTOR RESERVE SHITfDOWN HOURS: 0 D'- 0
14. HOURS GENERATOR ON-LINE: 720 7188.2 70714.3
15. UNIT RESERVE SHIJrDOWN HOURS: 0 0 0
16. GROSS 111ERMAL ENERGY GENERATED (FHi): 1582056 16904304 152617978
17. GROSS ELECTRICAL ENERGY GENERATED (bMI): 535930 5718930 52312140
18. NET ELECTRICAL ENERGY GENERATED (FMI): 516870 5524850 50089375
19. UNIT SERVICE FACIOR: 100% 89.7I 71.lI
20. UNIT AVAIIABILITY FACIOR: 100I 89.7% 7G
21. UNIT CAPACITY FACIOR (USING MDC NET): 90.2% 86.6% 65.5%
22. UNIT CAPACITY FACIOR (USING DER NET): 88.0% 84.5% 61.7%
23. UNIT FORCED OUTAGE RATE: 0% 1.9% 12.3%

24 SHIJrDOWNS SCHEDULED OVER NEXT 6 FONI11S (TYPE, DATE AND DURATION OF EAQl):

Refuel outage to cmmence Jantury 15, 1987 and last approximately 88 days.

25. IF SHIJr DOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARIUP:
26. UNITS IN TEST STATUS (PRIOR TO C0bHERCIAL OPERATION): FORECAST A011EVED INITIAL CRITICALITY INITIAL ELECTRICITY C0bNERCIAL OPERATION 8612100S26 861130 PDR ADOCK 05000333 R PDR yj

(

' ~

JAMES A. FITZPATRICK NUCLEAR POWER FIANT AVERAGE DAILY UtTIT POWER LEVEL DOCKET NO. 50-333 UNIT m uAIRICK DATE DEC 1986 OCEPLETED BY JOHN COOK TELEPHONE (315)342-3840 FDNDI Novenber 1986 DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL We NET We NET 1 770 17 726 2 765 18 724 3 763 19 720 4 760 20 720 5 758 21 568 6 755 22 472 7 743 23 704 8 750 24 718 9 746 25 708 10 745 26 707 11 741 27 705 12 739 28 702 13 737 29 700 14 735 30 698 15 731 31 ---

16 728 SIFNARY: The FitzPatrick plant operated at reduced thermal power for this reporting period with a further power reduction on 861121 to repair "A" Reactor Feed pump.

JMES A. FITZPATRICK NUCLEAR POWER FIANT UNIT SHUIDOWNS AND POWER REDUCTIONS >

DOCKET No. 50-333 UhTT NAME TITZIT!RICIC-DATE uts 1986 REPORT M)NIH NOVEMBER 1986 00MPLEIED BY JUHN W UK TELEPHONE (315)342-3840 D C UH R MEIHOD S C RO E OF YC MC CAUSE AND CORRECTIVE ACTION AU A SHUITING LICENSEE SO PO 10 NO. DATE TYPE TR S DOWN EVENT TD 0D PREVENT RECURRENCE IS O THE REPORT EE NE O N RFACIOR M E N N T

6 861121 F 39.5 A N/A SK SEAL 861121 FEEDPLNP SEAL FAILURE REDUCED POWER, REPLACED SEALS AND RETURNED TO SERVICE 861123 1 2 3 4 F: FORCED REASON: MEIHOD: EXHIBIT G.- INSTRUCTIONS S: SCHEDULED A. EQUIPMENT FAILURE (EXPLAIN) 1-MANUAL FOR PREPARATION OF DATA B. MAINIENANCE OR TEST 2-MANUAL SCRAM ENIRY SHEEIS FOR LICENSEE C. REFUELING 3-AUIW ATIC. SCRAM EVENT REPORT (LER) FILE D. REGUIAIORY RESTRICTION 4-0IHER (EXPIAIN) (NUREG-0161)

E. OPERATOR TRAINING AND LICENSE EXAMINATION F. AININISTRATIVE G. OPERATIONAL ERROR (EXPIAIN)

H. OIHER (EXPIAIN)

NARRATIVE

SUMMARY

OF OPERATING EXPERIENCE NOVEMBER 1986 The FitzPatrick plant commenced a coastdown to refueling this reporting period. The unit was run at a reduced thermal power for the entire month with a further power reduction on 861121 to repair "A" Reactor feed pump seals.

At the end of the reporting period the plant is running at approximately 698 MWe, 1

1 1

t

NEW YORK POWER AUIHORITY I

JAMES A. FITZPATRICK NUCLEAR POWER FLANT ,

MAINTENANCE SlbEARY l FOR THE 10NIH OF: NOVEMBER 1986 NORK REQUEST NO. HOW CAUSE OF RESULTS OF ACTION TAKEN TO REPAIR DATE SYSTEM R EPONENT NO. DutLTw MAIRJNCTION MALFUNCTION PR N N RECURRENCE TIFE IOURS 861106 02 036309 OPS UNKNOWN MKLAm]RAL DAMAGE REFAIRED DAMAGE 2 VMS-071 DRAWER FRONT ON DRAWER 861103 10 046593 OPS CALIBRATION DOES 10f AUID CALIBRATE,. IMP-10.1; 16 10V-16A REQUIRED OPEN ARJUSTED ZERO, SPAN 861103 16 046566 OPS PENEFRATION FAILS ST-39G RECHARGED 10 30 PSIA 4 X-103A RECHARGE PRESSURE WITH N2 REQUIRED IND. SPSIG 861120 17 032543 OPS REMY ON PANEL ID FID AIARM CLEANED CONTACTS; 83 04-13A,B 04-13B FAULTY DOESN'T REG REPIACED REIAY ON CP 861125 17 045525 OPS FAULTY BULB BLINKING HV-ON REPIACED NEON BULB 21 RIS-458A LIGHT WITH NEW ONE 861125 67 045585 OPS SCNE0tE BLEPED BROKEN GAUGE FACE REPIACED AND CHECKED 1 TI-216B3 INIO GAUGE FACE CALIBRATION: WR 46596 861125 70 045571 OPS DIR1Y REIAY INDICATION IS CLEANED CONTACIS 1 TIC-100 CONTACIS TYB-100 ERRATIC ON REIAY 861102 71 045416 OPS REGUIATOR DRIFT OUTPUr VOLTAGE IS ADJUSTED AC OUTPUI FRoti 2 INV-3B READING 620 620 to 600 l I I l

NER YORK POWER AUI110RITY JAMES A. FITZPATRICK NUrrFAR POWER PIRTf ,

SAFELY RELATED ELECIRICAL & MEGANICAL PAINIENANCE S& NARY NOVEMBER 1986 REPAIR WRK REQUEST f TIME DATE SYSTEM CWPONENT HOR DratLTr.D CAUSE OF MAIRRKT, ION AC1' ION TAKEN 'IO PRECLUDE RECURRENCE HOURS 11/17 70 38405 OPS Cracked Stator Replaced Motor. 76 XHU~3B Housing 11/4 17 46589 OPS Broken Drive Replaced Belt. 4 F TOH Belt


__--_-_- ___==-------------------------------------------------------------------------------------------------

11/24 71 44067 PM Overload Heaters Replaced Overloads. 6 C253-OC1 11/24 01-125 44787 TEST Charcoal deterioration Replaced Charcoal. 60 F 2E-11/17 23 30935 OPS Erosion Repaired Irakoff Line. 16 FDV T4

e -

James A. Fit: Patrick Nucle:r Power Plant PO W= 41 Lycoming. New York 13093 315 342.3840 Radford J. Converse

  1. > NewYorkPbwer 4# Authority December 3, 1986 JAFP-86-1026 Director, Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, D.C. 20555 ATTENTION: DOCUMENT CONTROL DESK

REFERENCE:

DOCKET NO. 50-333

Dear Sir:

Enclosed please find the J. A. FitzPatrick Operating Status Report for the month of November, 1986.

Refueling information remains the same as previously submitted.

If there are any questions concerning this report, please contact p John Cook at (315) 342-3840, Ext. 3569.

7,/ /n . -

RADFORD J. CONVERSE RESIDENT MANAGER RJC:JPC:mac Enclosures cc: Distribution IG14

'In