IR 05000821/2009020

From kanterella
Jump to navigation Jump to search
Notice of Deviation from Insp on 850821-0920
ML20138M730
Person / Time
Site: Mcguire, McGuire, 05000821  
Issue date: 10/21/1985
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML20138M724 List:
References
50-369-85-30, 50-370-85-23, NUDOCS 8511040262
Download: ML20138M730 (1)


Text

_._. _ _ _ _. _ _ _ _

__ --__

. _ _ _ _ _.. _ - -

. _.

___

.

__

i i

i

,

,

!

ENCLOSURE 2

'

NOTICE OF DEVIATION

The following deviation was identified during an inspection conducted August 21 -

September 20, 1985.

McGuire FSAR Section 9.4.2.3 and Table 9.4.2-3 stipulate that in-place testing of the Auxiliary Building Ventilation Systems (VA), had been conducted in accordance with Regulatory Guide 1.52 (Revision 2, March 1978)

which in turn obligates the licensee to ANSI N 510-1975.

Contrary to those comittments, a review of completed pre-operational tests performed on both McGuire units revealed that Regulatory Guide 1.52 and/or ANSI N 510-1975 were not adhered to in that the number of data sets taken with respect to charcoal adsorber efficiency were not in compliance with

,

those in the reference documents nor was filter air flow distribution testing performed as specified.

,

This is a deviation applicable to Units 1 and 2.

l

OCT 211985 Date:

1 J

l

,

8511040262 851021

I PDR ADOCK 05000369

G PDR

!

i l

l

- -.-

m.. -... -.,. - -. -.

- - - -...

...

... -. -...

....., - -. -. -,..

. -.. -. -.. - -. - - -