IR 05000515/2006008
| ML18101A838 | |
| Person / Time | |
|---|---|
| Site: | Salem, 05000515 |
| Issue date: | 07/19/1995 |
| From: | NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I) |
| To: | |
| Shared Package | |
| ML18101A837 | List: |
| References | |
| 50-272-95-12, 50-311-95-12, NUDOCS 9507260109 | |
| Download: ML18101A838 (2) | |
Text
NOTICE OF VIOLATION Public Service Electric and Gas {PSE&G)
Docket Nos:
Salem Units 1 and 2 License Nos:
50-272 50-311 DPR-70 DPR-75 During an NRC inspection conducted from May 15 - June 8, 1995, a violation of.
NRC requirements was identifie In accordance with the "General Statement of Policy and Procedure for NRC Enforcement Actions," {60 FR 34381; June 30, 1995) the violation is listed below:
Ctiterion XVI, "Corrective Action," of Appendix B to 10 CFR 50, "Quality Assurance Criteria For Nuclear Power Plants and Fuel Reprocessing Plants," requires that, "In the case of signifitant conditions adverse to quality, the measures shall assure that the cause of the condition is determined and corrective action taken to preclude rep*etition."
Contrary to the above, corrective actions were not taken to preclude repetition of significant conditions adverse to quality in that, between December 4, 1989, and March 29, 1995, 13 failures of safety-related circuit breakers occurred.due to hardened grease and/or dirt in the breaker *operating mechanis PSE&G did not determine the cause of the condition and repetitive failures occurre This is a Severity Level IV violation {Supplement 1).
Pur$uant to the provisions of 10 CFR 2.201, Public Service* Electric and Gas Company is hereby required to submit a written statement or explanation to the U.S.. Nuclear* Regulatory Commission, ATTN:
Document Control Desk, Washington, D.C. 20555 with a copy to the Regional Administrator, Region I, and a copy to the NRC Resident Inspector at the facility that is the subject of this Notice, within 30 days of the date of the letter transmitting this Notice of Violation
{Notice). This reply should be clearly marked as a "Reply to a Notice of Violation" and should include for each violation: {l) the reason for the violation, or, if contested, the basis for disputing the violation, (2) the
. corrective steps that have been taken and the results achieved, (3) the corrective steps that will be taken to avoid further violations, and (4) the date when full compliance will be achieve Your response may reference or include previous docketed correspondence, if the correspondence adequately addresses the required respons If an adequate reply is not received within the time specified in this Notice, an order or a Demand for Information may be issued as to why the 1 i cense should not be modi.fi ed, suspended, or revoked, or.
why such other action as may be proper should not be take Where _good cause is shown, consideration will be given to extending the response time.
9507260109 950719 PDR ADOCK 05000272 G
Because the response will be placed in the NRC Public Document Room {PDR), to the extent possible, it should not include any personal privacy, proprietary, or safeguards information so that it can be' placed in the PDR without redaction. However, if it is necessary to include such information,.it should clearly indicate the specific information that should not be placed in the PDR, and provide the legal basis to support the request for withholding the information from the publi Dated at King of Prussia, Pennsylvania this 19th day of July, 1995