County Station Biennial Problem Identification and Resolution Inspection Report 05000373/2021013 and 05000374/2021013
ML22019A284
Person / Time
Site: LaSalle  Constellation icon.png
Issue date: 01/20/2022
From: Kenneth Riemer
NRC/RGN-III/DRP/B1
To: Rhoades D
Exelon Generation Co, Exelon Nuclear
References
IR 2021013
Download: ML22019A284 (15)


Text

SUBJECT:

LASALLE COUNTY STATION - BIENNIAL PROBLEM IDENTIFICATION AND RESOLUTION INSPECTION REPORT 05000373/2021013 AND 05000374/2021013

Dear Mr. Rhoades:

On December 20, 2021, the U.S. Nuclear Regulatory Commission (NRC) completed a problem identification and resolution inspection at your LaSalle County Station and discussed the results of this inspection with Mr. Van Fleet, and other members of your staff. The results of this inspection are documented in the enclosed report.

The NRC inspection team reviewed the stations corrective action program and the stations implementation of the program to evaluate its effectiveness in identifying, prioritizing, evaluating, and correcting problems, and to confirm that the station was complying with NRC regulations and licensee standards for corrective action programs. Based on the samples reviewed, the team determined that your staffs performance in each of these areas adequately supported nuclear safety.

The team also evaluated the stations processes for use of industry and NRC operating experience information and the effectiveness of the stations audits and self-assessments.

Based on the samples reviewed, the team determined that your staffs performance in each of these areas adequately supported nuclear safety.

Finally, the team reviewed the stations programs to establish and maintain a safety-conscious work environment, and interviewed station personnel to evaluate the effectiveness of these programs. Based on the teams observations and the results of these interviews the team found no evidence of challenges to your organizations safety-conscious work environment. Your employees appeared willing to raise nuclear safety concerns through at least one of the several means available.

No findings or violations of more than minor significance were identified during this inspection.

January 20, 2022 This letter, its enclosure, and your response (if any) will be made available for public inspection and copying at http://www.nrc.gov/reading-rm/adams.html and at the NRC Public Document Room in accordance with Title 10 of the Code of Federal Regulations 2.390, Public Inspections, Exemptions, Requests for Withholding.

Sincerely, Kenneth R. Riemer, Chief Branch 1 Division of Reactor Projects Docket Nos. 05000373 and 05000374 License Nos. NPF-11 and NPF-18

Enclosure:

As stated

Inspection Report

Docket Numbers:

05000373 and 05000374

License Numbers:

NPF-11 and NPF-18

Report Numbers:

05000373/2021013 and 05000374/2021013

Enterprise Identifier:

I-2021-013-0017

Licensee:

Exelon Generation Company, LLC

Facility:

LaSalle County Station

Location:

Marseilles, IL

Inspection Dates:

November 29, 2021 to December 17, 2021

Inspectors:

J. Bozga, Senior Reactor Inspector

G. Hansen, Sr. Emergency Preparedness Inspector

G. Hausman, Senior Reactor Inspector

P. Smagacz, Resident Inspector

Approved By:

Kenneth R. Riemer, Chief

Branch 1

Division of Reactor Projects

SUMMARY

The U.S. Nuclear Regulatory Commission (NRC) continued monitoring the licensees performance by conducting a biennial problem identification and resolution inspection at LaSalle County Station, in accordance with the Reactor Oversight Process. The Reactor Oversight Process is the NRCs program for overseeing the safe operation of commercial nuclear power reactors. Refer to https://www.nrc.gov/reactors/operating/oversight.html for more information.

List of Findings and Violations

No findings or violations of more than minor significance were identified.

Additional Tracking Items

None.

INSPECTION SCOPES

Inspections were conducted using the appropriate portions of the inspection procedures (IPs) in effect at the beginning of the inspection unless otherwise noted. Currently approved IPs with their attached revision histories are located on the public website at http://www.nrc.gov/reading-rm/doc-collections/insp-manual/inspection-procedure/index.html. Samples were declared complete when the IP requirements most appropriate to the inspection activity were met consistent with Inspection Manual Chapter (IMC) 2515, Light-Water Reactor Inspection Program - Operations Phase. The inspectors reviewed selected procedures and records, observed activities, and interviewed personnel to assess licensee performance and compliance with Commission rules and regulations, license conditions, site procedures, and standards.

OTHER ACTIVITIES - BASELINE

71152B - Problem Identification and Resolution Biennial Team Inspection (IP Section 02.04)

(1) The inspectors performed a biennial assessment of the licensees corrective action program, use of operating experience, self-assessments and audits, and safety conscious work environment.

Corrective Action Program Effectiveness: The inspectors assessed the corrective action programs effectiveness in identifying, prioritizing, evaluating, and correcting problems. The inspectors also conducted a five-year review of the 125V DC systems and Core Standby Cooling systems.

Operating Experience, Self-Assessments and Audits: The inspectors assessed the effectiveness of the stations processes for use of operating experience, audits and self-assessments.

Safety Conscious Work Environment: The inspectors assessed the effectiveness of the stations programs to establish and maintain a safety-conscious work environment.

INSPECTION RESULTS

Assessment 71152B Based on the samples reviewed, the team determined that the licensees' performance in each of these areas adequately supported nuclear safety.

Effectiveness of Problem Identification:

Overall, the licensee was effective at identifying issues at a low threshold and was properly entering them into the Corrective Action Program (CAP) as required by procedures. The inspectors determined that the station was generally effective at identifying negative trends that could potentially impact nuclear safety, at an appropriate threshold and at a healthy rate, team interviewed personnel, reviewed documents, walked down portions of the plant, and assessed licensee problem identification. Staff were encouraged to identify issues and felt comfortable raising concerns with management. However, there were numerous descriptions of the workforce feeling that very low-level items never get fixed, even though numerous condition reports are entered year after year or every time certain surveillances are performed.

The inspectors reviewed root cause and apparent cause evaluations and determined those evaluations were adequate. The inspectors noted that adding more detail to the event timelines will aid in an independent reviewer understanding all known facts. For example, during the review of the root cause report for the refuel bridge mast foreign material issue (AR 4407109), a statement troubleshooting was performed, and fuel moves recommenced was made. This statement could have been expounded upon and detailed the troubleshooting efforts, what was or was not identified, and the criteria for recommencing with fuel moves. Also, detailed descriptions on the actual physical limitations of the refuel mast after each failure would have aided an independent reviewer.

Effectiveness of Prioritization and Evaluation of Issues:

In depth reviews of a risk-informed sampling of Action Requests (ARs), work orders (WOs),and cause evaluations were completed, including 5-year reviews of issues associated with the 125V DC Battery Systems and Core Standby Cooling Systems. The inspectors identified that the licensee generally, appropriately prioritized and evaluated issues for resolution.

The inspectors also noted that while issue evaluations were generally sound, there were several examples where additional research was needed to understand the technical basis, primarily due to a lack of clear documentation. This theme had previously been identified in earlier licensee self-assessments and CAP audits and continued to be a concern.

Effectiveness of Corrective Actions:

The inspectors concluded that the licensee was generally effective in developing Corrective Actions that were appropriately focused to correct the identified problem and correct conditions adverse to quality. For issues considered significant conditions adverse to quality, the licensee took action to address the root and contributing causes and to preclude repetition. Corrective actions were generally completed in a timely manner and in accordance with procedural requirements commensurate with the safety significance of the issue.

5-year Reviews of the 125V DC Systems and Core Standby Cooling Systems:

The inspectors performed an expanded 5-year review of the Units 1 and 2 125 Vdc system; specifically, by performing system walk-downs and evaluating condition reports, engineering changes, and work orders. The inspectors also interviewed the system engineer responsible for this system. Overall, the inspectors determined that the licensee was effectively managing issues associated with this system.

As part of the review of the Core Standby Cooling System, the team identified a condition report (AR 4406388) which was associated with the use of operability limits (ASME Section III Appendix F) for determination of pressure boundary integrity/continued operation of FAC component 2RA023, a 4" tee in the reactor bottom head drain line 2RR28B-4. The inspection of this condition report will continue as a Selected Issue for Follow-Up (71152 inspection procedure) during NRC inspections in 2022.

Operating Experience, Self-Assessment and Audits:

The inspectors reviewed operating experience captured in the CAP and sampled operating experience from NRC, industry, vendors, and third-party groups. Overall, for the samples selected, the licensee was generally performing the appropriate assessments for station applicability. Through interviews and observations at selected station meetings, the inspectors also concluded that operating experience was being appropriately used in daily plant activities.

The inspectors determined that the licensee was adequately performing self-assessments and audits in accordance with licensee procedures and implementing corrective actions as needed. The inspectors did note not all self-assessment templates developed included sufficient guidance to ensure consistent evaluations. This was specifically identified in security self-assessments where one assessment included a discussion on the quantity of records reviewed, but other assessments contained blanket statements of passing.

Safety Conscious Work Environment:

As part of the NRCs safety conscious work environment evaluation during the PI&R biennial inspection, NRC inspectors completed a limited scope inspection sample of an assessment performed by the licensee that evaluated human performance behaviors exhibited during the recent refueling outage, L1R18, and the potential impact on safety conscious work environment at the site. The inspectors performed an independent review that evaluated the licensees internal assessment of the sites SCWE program and the actions that were developed and implemented in response to the licensees identified areas for improvement to promote a healthy organizational safety conscious work environment. The NRC inspectors reviewed licensee evaluation records, internal organizational assessment survey results, training plans, and conducted interviews with the Employee Concerns Program Manager, Organizational Effectiveness Manager, and management staff from various departments.

No violations or findings were identified.

EXIT MEETINGS AND DEBRIEFS

The inspectors verified no proprietary information was retained or documented in this report.

On December 20, 2021, the inspectors presented the biennial problem identification and resolution inspection results to Mr. Van Fleet, and other members of the licensee staff.

DOCUMENTS REVIEWED

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

Calculations

L-003447

LaSalle Units 1 and 2, 125Vdc System Analysis Dated

June 11, 2020

2

04062322

Replace Battery 2DC18E Cell 44

10/12/2017

04114041

Replace or Retest 1DC07E

03/12/2018

04144731

Generate Forced Outage Work Order for Battery

Replacement

06/06/2018

203137

U2 Division 1 Battery Replacement

2/14/2018

04455972

Request WR to Replace 2DC16E K306 Relay

10/26/2021

04455973

Request WR to Replace 2DC23E K306 Relay

10/26/2021

1337255

TRM Appendix G, Table 2 Enhancements Needed

03/01/2012

141231

VR Supply Duct Access Repair Patch Not Installed Per

Design

01/27/2003

1518242

Ops Crew 6 4/17/13 LOOP Lessons Learned

04/17/2013

2387941

2E22-F369A Relief Valve Failed As-Found Test

09/29/2014

2530386

FAC Program - OE Review of Davis Besse Steam Rupture

05/19/2015

2618561

Degraded Condition Observed on CSCS Piping Line

2HP55A-4

01/28/2016

3990967

Degraded Condition Observed on CSCS Piping Line

2HP54A-4

03/29/2017

4048633

RM - 1C71A-K10C Failed to De-Energize During LOS-RP-Q2

09/03/2017

4099862

Limitation For 2HP55BB Per EC 403264 Flaw Evaluation

2/01/2018

4172339

Unit 2 LPCS Motor Cooler Inlet Pipe 2DG22A-1.5" is

Degraded

09/12/2018

4192778

2018 WANO AFI ER.2

11/06/2018

21635

VT-3 Exams Specified on Supports Exempted from

Examination

2/19/2019

25076

ACB 1414 Had a Lockout Trip While Performing LOS-AP-R2

03/01/2019

28241

Low Power TIP Set not Completed Due to TIPs OOS

03/10/2019

251021

Review Code Requirements for Replacement VY Cooling

Coils

05/22/2019

71152B

Corrective Action

Documents

252624

Code Non-Conformance Identified For VY Coolers

1(2)VY03A

05/29/2019

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

257366

4.0 Critique IR on Tendon Surveillances

06/17/2019

258604

Late Surveillance (LIS-OG-408)

06/21/2019

261844

Cardox Tank Compressor Tripped on Thermal Overloads

07/04/2019

262090

NRC ID - Dry Pipe FP Lines not Sloped Per NFPA13

07/05/2019

265814

1RE026 Closed Light Did Not Illuminate During LOS-PC-Q1

07/21/2019

265960

Large Steam Leak Found Downstream of 1G33-F040

07/22/2019

266264

Performance Level 3 OPEX Review of ICES 456532 for

Applicability to LaSalle

08/23/2019

267062

MSIV Pilot Solenoid Leads Crossed

07/25/2019

267121

PCE Level 1

07/25/2019

270252

Historical 2C51-J004C App J Leakage Evaluations not Found

08/07/2019

271342

Unexpected MCR Alarm: Unit 1 Hydrogen Panel Trouble

08/12/2019

273172

Part 21 Flowserve Unqualified NDE Performance of

Component

08/20/2019

273349

NER NC-19-010-Y OE Review-Potential LaSalle

Vulnerability

08/20/2019

276944

Part 21 Contactors Failing to Release/Open When

De-Energized

09/05/2019

277173

NRC IN 2019-05: Over Pressurization of Alpha Sources

09/06/2019

280047

AT 04257366-04 Needs to be Reevaluated

09/17/2019

281169

LOS-SY-SR1 Revision Needed

09/22/2019

284443

Through Wall Leak on ST Piping in U2 Div 1 CSCS Pump

Room

10/02/2019

286161

Unacceptable Trend Identified on MSIV Timing Per

LOS-PC-Q2

10/08/2019

288235

NRC IN 2019-08 OPEX Regarding FAC Causing RX Scrams

10/16/2019

288344

NRC ID: NRC Question on 1G33-F040

10/16/2019

288357

Replace Piping 1DG23B-6"

10/16/2019

294984

NRC IN 19-09: Spent Fuel Cask Movement Issues

10/30/2019

295415

Revise EC 363524 to Extend VY Fan SBM C\\S Replacement

PM's

11/07/2019

4305470

Biennial Safety Culture Self-Assessment

2/04/2020

4306254

Level 3 OPEX Review Requested #465166 Diablo Canyon

2/27/2019

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

Unit 2

4306904

1B RR Pump Lower Oil Reservoir Hi Level

2/30/2019

4307124

Level 3 OPEX Review Requested #464385 Salem Unit 2

2/31/2019

4307131

Level 3 OPEX Review Requested #458702 Hatch Unit 2

2/31/2019

4318198

L1R18 FAC; 1RH006 Low Wall Thickness

2/15/2020

4319242

L1R18 FAC; Component 1RH014 Low Wall Thickness

2/19/2020

22219

1ES010B Indicating Closed

2/28/2020

22221

1ES010C Indicating Closed

2/28/2020

28259

P21-Potential Deviation of Pressure Transmitters

03/20/2020

4330162

Rosemount Transmitters Part 21 for Changes in Heat Rise

03/27/2020

4343229

Flex Generator Issue at Quad: LaSalle has Similar Generator

05/14/2020

4357505

U1 EHC Pressure Low in Band with New Discharge Filter

07/18/2020

4362593

NRC Question on 2CW03A Piping Support

08/10/2020

4365890

RM - Step Change Reduction in U2 Jet Pump 15 Flow

08/27/2020

4366965

Degraded Piping Support

09/02/2020

4368035

LR Inspection of 2LP13B-3" Piping

09/08/2020

4368037

LR Inspection of 2LP23AA-1/2" Piping

09/08/2020

4368040

LR Inspection for 2LP19A-3" Piping

09/08/2020

4380329

SR 3.4.3.1 Jet Pump# 15 Curve No Conservative Change

10/28/2020

4382365

B DFP High Discharge Pressure

11/05/2020

4383488

2A RHR Seal Cooler Flow Low

11/10/2020

4389292

RM - JP 5/6 ACMP Flow Mismatch

2/10/2020

4391800

Loss of U2 Div 3 Water Leg Pump

2/23/2020

4391803

NRC IN 2020-04 - FP Mn Yard Buried Cast Iron Piping

Failures

2/17/2020

4404161

L2R18 FAC Component 2HJ016 Low Wall Thickness

2/23/2021

4404521

L2R18 FAC; 2RH004, Low Wall Thickness

2/24/2021

4404903

2DG01A Heat Exchanger Tubes Material Degradation

2/24/2021

4404903

2DG01A Heat Exchanger Tubes Material Degradation

2/26/2021

4405141

Unanticipated Does Rate Alarm in High Radiation Area

2/27/2021

4406388

FAC Inspection on 2RA023 not Performed

03/03/2021

4406519

NRC ID Failure to Write IR in Heat Exchanger Program

03/03/2021

4406519

NRC ID Failure to Write IR in Heat Exchanger Program

03/04/2021

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

4406544

NRC ID LR Selective Leaching Program Perf. Deficiencies

03/01/2021

4406555

L2R18 FAC; 2MS66B-RT-01, Low Wall Thickness

03/04/2021

4407109

Unit 2 Refuel Bridge Mast Issue During Fuel Moves

03/07/2021

4407109

Unit 2 Refuel Bridge Mast Issue During Fuel Moves

03/07/2021

4407388

"L" SRV Drop Test Failure

03/08/2021

4407915

"L" SRV Failed LOS-MS-R& Drop Test

03/10/2021

4407917

"R" SRV Failed Regulated Header Drop Test

03/10/2021

4409413

NRC Identified-NRC Questioned Weld Procedure

Qualification

03/15/2021

4417755

RM - Unit 2 Jet Pump #6 is not Within Jet Pump Curves

04/20/2021

22004

FAC RWCU Bottom Head Drain Lessons Learned

05/06/2021

23071

NRC IN 2021-01: Design Bases LLed Power Operated

Valves

05/11/2021

26705

RM - 2A RPS M/G Set Output Breaker Tripped

05/31/2021

27494

2A RPS MG Set Voltage Adjustment Pot Bad

06/04/2021

28890

L1R19 Class 1 Small Bore Pipe Socket Welds

06/11/2021

4433739

Tendon Grease Cap Area Unit 2 Concrete Inspections

07/07/2021

4441741

21 PI&R SA Gap: OBJ 3A

08/20/2021

44447160

No Flow Thru U1 EHC Fullers Earth Filters Via Hydraulic

Pump

09/17/2021

4448905

10CFR Part 21. Ametek Equalize Relay

09/27/2021

4465190

NRC ID-2HP54A-4" UT Inspection Results Per WO-4621240

2/07/2021

4466247

NRC Identified Issue With L-003447 Rev. 002

2/13/2021

4466816

NRC ID - 2DG22A-1.5" Min Wall Design Limit

2/15/2021

4467017

NRC Observation - 2021 PI&R - CR Type AR Generation

2/16/2021

4467039

NRC Observation - PI&R 2021 - Security Self-Assessments

2/16/2021

Corrective Action

Documents

Resulting from

Inspection

4467111

NRC Observation - PI&R 2021 - Enhancement Opportunity

for RCR

2/16/2021

403264

Minimum Wall Thickness for Unit 2 Division 3 VY Cooler

Piping for Extent of Condition

403264

Minimum Wall Thickness for Unit 2 Division 3 VY Cooler

Piping for Extent of Condition

Engineering

Changes

28380

L2R18 FAC Min Wall Evaluation

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

28380

L2R18 FAC Min Wall Evaluation

LAS-02121

Failure Analysis of Limit Switch from LaSalle Station

08/14/2018

LAS-24193

Failure Analysis of a Namco Limit Switch from LaSalle

Station

11/16/2018

LAS-62503

Failure Analysis of a Namco limit Switch from Lasalle Station

05/03/2019

Engineering

Evaluations

LAS-93383

Failure Analysis of a NAMCO Limit Switch Assembly

06/13/2012

4405141

Rad Worker Behaviors Root Cause

05/27/2021

4407109

Root Cause Investigation Report for Unit 2 Refuel Bridge

Mast Issue During Fuel Moves

06/25/2021

IEEE STD 485-

1997Property "IEEE" (as page type) with input value "IEEE 485-</br></br>1997" contains invalid characters or is incomplete and therefore can cause unexpected results during a query or annotation process.

IEEE Recommended Practice for Sizing Lead-Acid Batteries

for Stationary Applications

09/11/2003

IEEE STD 946-

1985Property "IEEE" (as page type) with input value "IEEE 946-</br></br>1985" contains invalid characters or is incomplete and therefore can cause unexpected results during a query or annotation process.

IEEE Recommended Practice for the Design of

Safety-Related DC Auxiliary Power Systems for Nuclear

Power Generating Stations

03/21/1985

NOSA-LAS-19-05

Engineering Design Control Audit Report

07/10/2019

NOSA-LAS-20-05

Engineering Programs Audit Report

07/15/2020

NOSA-LAS-21-05

LaSalle Corrective Action Program Audit Report

09/01/2021

OPEX Evaluation

2570259-02

ICES 318466, Pin Hole Leak at Residual Heat Removal

Service Water (RHRSW) Pipe Elbow

11/25/2015

OPEX Evaluation

4056244-02

LER 2017-003, Division 2 Residual Heat Removal Service

Water System (RHRSW) Inoperable Due to an Inoperable

RHRSW Flow Control Valve (FCV) (Fermi 2)

11/09/2017

Miscellaneous

OPEX Evaluation

430760

ESW Inop Due to Silt Buildup

04/29/2020

NDE Reports20-141

Ultrasonic Exam of 2DG22A-1 1/2

09/08/2020

EI-AA-101

Employee Concerns Program

ER-AA-320

Maintenance Rule Implementation Per NEI 18-10

NISP-PI-02

Conduct of Self-Assessments and Benchmarks

NO-AA-10

Quality Assurance Topical Report

PI-AA-101

Conduct of Performance Improvement

PI-AA-1012

Safety Culture Monitoring

PI-AA-115

Operating Experience Program

Procedures

PI-AA-120

Issue ID and Screening Process

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

PI-AA-120

Issue Identification and Screening Process

PI-AA-125-1001

Root Cause Analysis Manual

PI-AA-125-1003

Corrective Action Program Evaluation Manual

PI-AA-126-1001

Self-Assessments

4091749

RP Personnel Knowledge SA Report Assignment

07/02/2019

4113395

NRC SY Baseline Inspect-SA Report PASSPORT

Assignment

06/06/2019

4113396

NRC EP Baseline Inspect-SA Report PASSPORT

Assignment

09/05/2019

4192133

SA Report - M&TE Inventory Control, Access, & Handling

10/08/2019

4192133

Self-Assessment M&TE Inventory Control, Access, &

Handling

11/06/2018

4192145

SA Report Assignment - M&T Effectiveness of ACAD 17-01

10/02/2019

4192182

SA Report Assignment - NRC SY Baseline Inspection

2/18/2019

257452

Self-Assessment of SA/BM NISP-PI-02 Implementation

05/14/2020

4305470

Biennial Safety Culture Self-Assessment

2/04/2020

29347

LaSalle Pre-NRC Triennial Heat Sink

2/24/2021

29367

SA Report - Security Baseline Inspection

07/21/2021

29672

SA Report - RP Baseline Inspection

07/16/2021

29675

SA Report - EP Baseline Inspection/Performance Indicator

Verification

10/01/2021

4343239

Cyber Security Program Effectiveness Self-Assessment

05/14/2020

4362946

LaSalle M&T Comprehensive Self-Assessment Report

06/30/2021

4378794

20 INPO Performance Based Evaluation Results

09/23/2021

4430137

21 Preparation for NRC Problem Identification and

Resolution (PI&R) Inspection

08/23/2021

LaSalle Station

01/27-31/2020

Fleet Assessment Special Assessment Report

2/24/2020

LaSalle Station

03/23-27/2020

Fleet Assessment T-6 Assessment Report (Maintenance)

04/16/2020

LaSalle Station

05/17-21/2021

Fleet Assessment T-18 Assessment Report (Maintenance)

06/14/2021

Self-Assessments

LaSalle Station

Fleet Assessment Mid-Cycle Assessment Report

09/18/2019

Inspection

Procedure

Type

Designation

Description or Title

Revision or

Date

08/16-28/2019

(Maintenance)

LaSalle Station

Fleet Assessment Midcycle Assessment Debrief

11/15/2021

Work Orders

4866827

Unit 2 Refuel Bridge Contingency Repairs

03/07/2021