.g.
U.S. NUCLEAR REGULATORY COMMISSION
REGION III
Reports No. 50-358/82-09(DETP); 03011989/82-01(DETP)
Docket Nos. 50-358; 03011989 License No. CPPR-88; 34-07251-04 Licensee: Cincinnati Gas and Electric Company 139 East 4th Street Cincinnati, Oli 45201 Facility Name:
Wm. II. Zimmer Nuclear Power Station Inspection At: Zimmer Site, Moscow, OH Inspection Conducted: June 14-17, 1982 4. e Adv 7/R/fR Inspector:
D. E. Miller
!
l Il2f9b Approved By:
L. R. Greger, Chief Facilities Radiation Protection Section Inspection Summary:
Inspection on June 14-17, 1982 (Report No. 50-358/82-09(DETP);
03011989/82-01(DETP))
Areas Inspected: Routine, unannounced preoperational inspection of radiation protection program, including organization, training, procedures, instruments and equipment, and adherence to requirements of Byproduct Materials License No. 34-07251-04.
Also inspected were items identified during previous inspec-tions. The inspection involved 32 inspector-hours onsite by one NRC inspector.
Results: No items of noncompliance or deviations were identified.
i 8207190357 820702 PDR ADOCK 05000358 G
.
.
DETAILS 1.
Persons Contacted
- D.
Erickson, Superintendent, Radcontrol and Chemistry Division J. Wald, Director, Station Quality Engineering M. Niswander, Health Physics Engineer J. Stieritz, Radiation. Protection Specialist S. Scheidler, Rad / Chem Foreman, Chemistry F. Reck, Rad / Chem Foreman, Health Physics
- F.
Christianson, Senior Resident Inspector, NRC P. Gwynn, Resident Inspector, NRC The inspector also contacted other licensee personnel, including Rad / Chem Technicians, during the inspection.
- Denotes those present at the exit meeting.
2.
General This inspection, which began at about 11:00 a.m. on June 14, 1982, was conducted to review the radiation protection program including, organiza-tion, training, procedures, instruments and equipment; adherence to require-ments of Byproduct Materials License No. 34-07251-04; corrective actions of items identified during previous inspection; and progress made in preopera-tional testing. Tours were made of the reactor, radwaste, auxiliary, and turbine buildings to observe construction progress on selected systems and components.
3.
Open Items (Closed) Open Item (358/79-18-01):
Concerning the need to provide a method for monitoring airborne radioactive materials in the laundry. The licensee intends to install and operate a constant air monitor in the laundry.
(Closed) Open Item (358/79-18-02):
Concerning the need to provide effluent monitoring capability for the SBGT system. The licensee intends to monitor this effluent pathway in accordance with NUREG-0737.
(Closed) Open Item (358/80-02-01):
Concerning training of operators, and others permitted to do self-monitoring, in the use of portable survey in-struments. The licensee has developed procedure TR. SAD.05, " Radiological Self-Monitoring Training Program," and has begun training in accordance with the procedure. No significant problems were noted during the inspector's review of the procedure and training outline.
(Closed) Open Item (358/81-10-01):
Concerning the need to acquire addi-tional respiratory protection equipment before fuel load. The licensee has ordered additional quantities and expects delivery before fuel load.
.
. _ _.
-_
.
_
-
.
.
(0 pen) Open Item (358/81-10-02):
Concerning the need to revise two radia-tion protection procedures concerning the respiratory protection program.
No problems were noted during the inspector's review of revised procedure RC.RPP.7.101, "Use of Respiratory Protective Equipment." Revision of RC.RPP.2.160 " Bioassay" is in progress and will be reviewed during a future inspection.
4.
Radiation / Chemistry Organization Since previously reported (358/80-02), the following Rad / Chem related organi-zational changes have been made.
a.
As part of a station management reorganization, the title Rad / Chem
,
i Engineer has been changed to Superintendent, Radcontrol and Chemistry Division. This Superintendent, along with four other Division Superin-tendents, now reports directly to the Station Manager. The Radeontrol
and Chemistry Division now includes station chemistry, radiation pro-tection, radwaste, and building services.
b.
A Radiation Protection Specialist position has been added.
J. Stieritz, l
former Senior Rad / Chem Technician, has been promoted to the new posi-
'
tion.
c.
A Radwaste Engineer position has been added and filled.
There are currently 23 Rad / Chem Technicians (13 Senior Technicians, 7 Tech-nicians, and 3 Junior Technicians). Senior Rad / Chem Technicians are con-
,
sidered by the licensee to be ANSI N18.1-1971 qualified. The inspector will review qualifications during a future inspection.
5.
Rad / Chem Technicians (RCT) Training The RCT training program remains as previously reported (50-358/80-02).
l The licensee has sent, or is scheduled to send, all senior RCTs who have not had significant previous operational experience to an operating reactor facility to observe and participate in an operational Rad / Chem program.
i The operational experience is for about five weeks and usually at a BWR l
during refueling.
The RCT training program appears to be very good.
6.
Radiation Protection Procedures Review of the following selected new and revised radiation protection pro-cedures and station administrative directives was performed. No significant problems were noted during review of the following procedures.
R0. SAD.01 Revision 1 Radwaste Management Program TR. SAD.05 Revision 0 Radiological Self-Monitoring Training Program I
,
!
9 m
-
.-
_ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _
.
.
RC.RPP.1.030 Revision 3 Receipt of Raf'oactive Material RC.RPP.S.068 Revision 0 Calibration of the Eberline RM-16 Radiation Monitor RC.RPP.5.076 Revision 2 Calibration of Eberline R0-2 and R0-2A Ion Chambers RC.RPP.5.079 Revision 1 Calibration of Eberline E-520 RC.RPP.S.086 Revision 1 Calibration of Neutron Survey Instruments RC.RPP.5.262 Revision 0 Calibration of the Eberline Stabilized Assay Meter (SAM-2)
Minor problems were noted during review of the following procedures. The licensee agreed to make needed corrections.
R0. SAD.02 Revision 0 Dry Waste Segregation and Controls RP. SAD.05 Revision 0 Occupational Radiation Exposure Controls RC.RPP.S.110-4 Revision 2 Calibration of Eberline HFM-3 Hand and Foot Moni-tor RC.RPP.5.111 Revision 1 Calibration of Eberline PMP 42 Portal Monitor 7.
Solid Radwaste The inspector discussed with the licensee the desirability of performing a management controlled audit of radwaste packaging and shipping before power operation. The licensee stated that they would perform an audit, using IE Bulletin 79-19 " Packaging of Low-Level Radioactive Waste for Transport and Burial" as audit criteria, before power operation.
(358/82-09-01)
8.
Preoperational Testing None of the remaining liquid processing and monitoring, gaseous monitoring, or ventilation preoperational tests that are assigned to this inspector were ready for review.
9.
Byproduct Materials License No. 34-07251-04 Licensee adherence to regulatory requirements imposed pursuant to Byproduct Materials License No. 34-07251-04 was reviewed. The license permits pos-session and use of material in any form having an atomic number from 1 to 83 (not to exceed 2 millicuries per nuclide and 1 curie total) and also permits the possession and use of specified sealed sources.
The inspector observed licensee provisions for storage and use of licensed material and checked material on hand against possession limits.
Sources, except for sealed sources housed in the Eberline Model 1000 Gamma Calibra-tor, are stored in locked shielded cabinets or storage pigs, or are within the locked and posted instrument calibration facility. Records reviewed
_ _ _ _ _. _ _.
--
. -.
--
. -.. -
~
.
.
.
,
include receipt, inventory, Icak test of sealed sources, portable survey instruraent calibrations, and personal monitoring results.
On June 14, 1982, the licensee received a 47.4 millicurie Kr-85 source which was sent by Eberline Instrument Corporation, Santa Fe, New Mexico, for use in gaseous effluent monitor calibration. The licensee's byproduct materials license permits possession of ten mil 11 curies of Kr-85.
The 11-censee, who had not ordered the radioactive material, immediately reported the matter to NRC Region III; has requested, application dated June 14, 1982, a license amendment to authorize possession; and is keeping the material in locked storage. The inspector notified NRC Region IV of the shipment.
No items of noncompliance or deviations were identified.
10.
Exit Meeting The inspector met with licensee representatives (denoted in Section 1) at the conclusion of the inspection on June 17, 1982. The inspector summarized the scope and findings of the inspection.
In response to the inspector's comments, the licensee stated that a manage-l ment controlled audit, using IE Bulletin 79-19 as part of the audit criteria,
would be performed before power operation.