ENS 57117
ENS Event | |
|---|---|
04:00 Feb 22, 2024 | |
| Title | Part 21 - Emergency Diesel Generator Cylinder Liner Leak |
| Event Description | The following is a synopsis of information provided by Engine Systems, Inc. (ESI) via fax and email:
On February 22, 2024, an EMD brand cylinder liner developed a jacket water leak following installation on an emergency diesel generator set. The leak occurred at a brazed joint and was detected after post-installation engine testing. Had the leak gone undetected, jacket water may have accumulated in the combustion chamber or airbox and potentially contaminated the engines lubricating oil. Jacket water intrusion into any of these areas is undesirable and could lead to failure of the diesel engine and therefore failure of the emergency diesel generator set. The extent of condition is a single cylinder liner, P/N 9318833, S/N 20D6294 used in the power assembly shown below. Customer: Constellation - Fitzpatrick Customer PO: 703, release 13498 ESI Sales Order: 3021545 Part Number Ordered: 40124898 (Blade Power Pack) Serial Number: 20L0603 ESI C-of-C Date: April 1, 2021 The corrective action: For Fitzpatrick: No action required; the power assembly has been returned to ESI for replacement. For ESI: ESI will revise the dedication package to include additional verifications to prevent reoccurrence. The revision will be implemented within 30 days. Name and contact information: Dan Roberts, Quality Manager Engine Systems Inc. 175 Freight Rd. Rocky Mount, NC 27804 John Kriesel, Engineering Manager Engine Systems Inc. 175 Freight Rd. Rocky Mount, NC 27804 |
| Where | |
|---|---|
| FitzPatrick Rocky Mount, North Carolina (NRC Region 1) | |
| Organization: | Engine Systems, Inc. |
| Reporting | |
| 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect | |
| Time - Person (Reporting Time:+1859.7 h77.488 days <br />11.07 weeks <br />2.547 months <br />) | |
| Opened: | Dan Roberts 14:42 May 9, 2024 |
| NRC Officer: | Thomas Herrity |
| Last Updated: | May 9, 2024 |
| 57117 - NRC Website
Loading map... {"minzoom":false,"maxzoom":false,"mappingservice":"leaflet","width":"350px","height":"250px","centre":false,"title":"","label":"","icon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"zoom":6,"defzoom":14,"layers":["OpenStreetMap"],"image layers":[],"overlays":[],"resizable":false,"fullscreen":false,"scrollwheelzoom":true,"cluster":false,"clustermaxzoom":20,"clusterzoomonclick":true,"clustermaxradius":80,"clusterspiderfy":true,"geojson":"","clicktarget":"","imageLayers":[],"locations":[{"text":"\u003Cb\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003E\u003Ca class=\"mw-selflink selflink\"\u003EENS 57117\u003C/a\u003E - \u003Ca href=\"/FitzPatrick\" title=\"FitzPatrick\"\u003EFitzPatrick\u003C/a\u003E\n\u003C/p\u003E\u003C/div\u003E\u003C/b\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003EPart 21 - Emergency Diesel Generator Cylinder Liner Leak\n\u003C/p\u003E\u003C/div\u003E","title":"ENS 57117 - FitzPatrick\n","link":"","lat":43.52241111111111,"lon":-76.39899444444444,"icon":"/w/images/b/be/Constellation_icon.png"}],"imageoverlays":null} | |
WEEKMONTHYEARENS 576992025-03-07T04:00:0007 March 2025 04:00:00
[Table view]10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 - Circuit Breaker Defect ENS 571172024-02-22T04:00:00022 February 2024 04:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 - Emergency Diesel Generator Cylinder Liner Leak ENS 570722024-02-22T04:00:00022 February 2024 04:00:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part 21 - Leaking Cylinder Liner in Emergency Diesel Generator ENS 483532012-09-27T16:12:00027 September 2012 16:12:00 10 CFR 21.21(d)(3)(i), Failure to Comply or Defect Part-21 Report - Faulty Master Trip Units, Slave Units, and Resistance Temperature Detectors 2025-03-07T04:00:00 | |