[On February 20, 2020, at 1240 EST, the Licensee determined the following information:]
This notification is in reference to reports EN 54130 and LER 2019-002, which were retracted. James A. FitzPatrick Nuclear Power Plant received additional information on the technical basis for the retraction. Further review, including testing of the terminal blocks, demonstrated that the short circuit current would result in heat levels in excess of cable insulation ratings.
Unprotected DC control circuits for non-safety related DC motors are routed between separate fire areas. A postulated fire in one area can cause a short circuit and potentially result in secondary fires or cable fires in other fire areas where the cables are routed. The secondary fires or cable failures degrade the degree of separation for redundant safe shutdown trains and are outside the assumptions of the 10 CFR 50 Appendix R Safe Shutdown Analysis. This condition is reportable in accordance with 10 CFR 50.72(b)(3)(ii)(B).
Compensatory actions per the Technical Requirements Manual (TRM) for affected fire areas have been implemented. A modification to install fuses in the control circuits for 94P-2(M), 31P-7A(M), 31P-7B(M), and 94P-13(M) has been scheduled and shall correct this condition.
The NRC Resident Inspector has been notified.