ENS 54298
ENS Event | |
---|---|
19:15 Sep 27, 2019 | |
Title | Procedural Noncompliance with Administrative Item Relied on for Safety |
Event Description | On September 27, 2019 at 1515 EDT, the fire protection engineer's review of the daily corrective action report identified a procedural noncompliance which affected an administrative Item Relied on for Safety (IROFS). During the morning of September 26th, a fuel oil delivery truck, escorted by plant employees, drove along the road adjacent to the Uranium Hexafluoride (UF6) cylinder storage area, violating the minimum distance requirement within the procedure.
The IROFS designation is UF6FIRE-901, which requires escort and a 60-foot spacing distance that was not fully satisfied. Instead of 60 feet, the truck drove past the area over a period of a few minutes at a distance of 20 to 30 feet from the cylinder storage area. The other IROFS in this accident sequence remained reliable and available as required. The basis for this procedural control is to provide separation so that if a fire did occur involving the fuel oil delivery truck, there would be no significant fire exposure to the stored UF6 cylinders. This is a non-emergency event notification, and there was no release of hazardous or radiological materials. There were no health or safety consequences to the public, the employees or the environment from this procedure non-compliance. The delivery truck was escorted at all times, and the site has an on-site fire department, available to respond to any event. Immediate Corrective Actions: Prior to any fuel trucks being escorted inside the facility fence, both designated escorts shall receive a pre-job brief from a supervisor to ensure that designated escorts understand the proper delivery route specified in the procedure. The licensee will notify NRC R2 (Vukovinsky) and the State of South Carolina. |
Where | |
---|---|
Westinghouse Electric Corporation Columbia, South Carolina (NRC Region 2) | |
License number: | SNM-1107 |
Reporting | |
Part 70 App A (B)(2) | |
Time - Person (Reporting Time:+15.28 h0.637 days <br />0.091 weeks <br />0.0209 months <br />) | |
Opened: | Gerard Couture 10:32 Sep 28, 2019 |
NRC Officer: | Donald Norwood |
Last Updated: | Sep 28, 2019 |
54298 - NRC Website | |
Westinghouse Electric Corporation with Part 70 App A (B)(2) | |
WEEKMONTHYEARENS 542982019-09-27T19:15:00027 September 2019 19:15:00
[Table view]Part 70 App A (B)(2) Procedural Noncompliance with Administrative Item Relied on for Safety ENS 519742016-06-02T16:45:0002 June 2016 16:45:00 Part 70 App A (B)(2) Administrative Verifications of Ventilation Clean-Out Containers Were Not Performed ENS 510242015-04-29T14:00:00029 April 2015 14:00:00 Part 70 App A (B)(2) Valve Classified as Item Relied on for Safety Failed to Operate as Designed ENS 459262010-05-13T16:33:00013 May 2010 16:33:00 Part 70 App A (B)(2) a Valve Classified as an Item Relied on for Safety Found Closed While Position Indicator Showed Open ENS 458842010-04-29T17:04:00029 April 2010 17:04:00 Part 70 App A (B)(2) Hot Oil System Emergency Shutdown Fails Annual Preventative Maintenance Check ENS 449282009-03-23T11:30:00023 March 2009 11:30:00 Part 70 App A (B)(2) Degraded Item Required for Safety in the Pelleting Area ENS 438142007-11-30T16:00:00030 November 2007 16:00:00 Part 70 App A (B)(2) Potential Loss of Item Relied on for Safety (Irofs) ENS 414242005-02-19T21:04:00019 February 2005 21:04:00 Part 70 App A (B)(2) 24-Hour Criticality Control Report - Failure to Obtain Required Powder Samples 2019-09-27T19:15:00 | |