ENS 52751
From kanterella
Jump to navigation
Jump to search
ENS Event | |
|---|---|
13:30 May 14, 2017 | |
| Title | Single Flow Barrier Access Point Found Unbolted |
| Event Description | On May 14, 2017, with the Unit in Mode 4, it was identified that a single flow barrier access point (Gate C) to the 46 ft. elevation of Containment was unbolted for access to the inner crane wall to perform surveillance testing. This single flow barrier access point is required to be bolted closed to ensure the Emergency Core Cooling System (ECCS) operability basis which requires the sump barrier system to be operable in Modes 1- 4. The sump barrier system is required to prevent the transport of debris to the recirculation and containment sumps. This event is a safety system functional failure as the condition could have prevented adequate post-accident core cooling due to Design Basis Accident debris blockage of the recirculation and/or the containment sump and is reportable under 10 CFR 50.72(b)(3)(v)(D).
The licensee notified the NRC Resident Inspector and the New York Public Service Commission. |
| Where | |
|---|---|
| Indian Point New York (NRC Region 1) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | |
| Time - Person (Reporting Time:+2.03 h0.0846 days <br />0.0121 weeks <br />0.00278 months <br />) | |
| Opened: | Michael Mccarthy 15:32 May 14, 2017 |
| NRC Officer: | Donald Norwood |
| Last Updated: | May 14, 2017 |
| 52751 - NRC Website
Loading map... | |
Unit 3 | |
|---|---|
| Reactor critical | Not Critical |
| Scram | No |
| Before | Hot Shutdown (0 %) |
| After | Hot Shutdown (0 %) |
Retrieved from "https://kanterella.com/w/index.php?title=ENS_52751&oldid=81940"