| Title | Part 21 - Interim Notification of a Potential Defect on a Printed Circuit Board |
| Event Description | Ametek Solidstate Controls began a 10 CFR Part 21 evaluation after receiving notification from NextEra Energy Seabrook Station that a 7.5kVA Inverter would prematurely transfer to alternate source at 27A load during commissioning. The X202 Crest factor board (80-9213516-90) was replaced and the unit operated normally.
Analysis of the failed X202 Crest Factor board identified an SCR on the printed circuit board was turning on prematurely and resulted in a transfer to alternate source or with the absence of the alternate source, to a dead bus. A capacitor was placed across the SCR on the X202 board to protect the SCR from dv/dt turn on. Subsequent testing determined the added capacitor corrected the anomaly. In addition to Seabrook, Ametek has recently experienced similar anomalies on two separate occasions. However, these occurrences were discovered during manufacturing and in-house testing phase for new product and were attributed to a SCR failure, excessive noise, and long leads. ACTION RECOMMENDED: Ametek Solidstate Controls recommends installing a 0.22 microfarad capacitor p/n 80-134734-90 across X202 terminals J1-11 to J1-12. This capacitor will have no effect on EMI or seismic qualifications. If you wish to acquire the 80-134734-90 capacitor, Ametek Solidstate Controls will work with you to provide spare parts. Please contact Mr. Mark Shreve of our Client Services group at 1-800-222-9079 or 1-614-846-7500 ext. 6332. mark.shreve@ametek.com
The following information was excerpted from an Ametek Solidstate Control email: Ametek Solidstate Controls began a 10 CFR Part 21 evaluation after receiving notification from NextEra Energy Seabrook Station that a 7.5kVA Inverter would prematurely transfer to alternate source at 27A load during commissioning. The X202 Crest factor board (80-9213516-90) was replaced and the unit operated normally. Analysis of the failed X202 Crest Factor board identified an SCR on the printed circuit board was turning on prematurely and resulted in a transfer to alternate source, or with the absence of the alternate source, to a dead bus. A capacitor was placed across the SCR on the X202 board to protect the SCR from dv/dt turn on. Subsequent testing determined the added capacitor corrected the anomaly. In addition to Seabrook, Ametek has recently experienced similar anomalies on two separate occasions. However, these occurrences were discovered during manufacturing and in-house testing phase for new product and were attributed to an SCR failure, excessive noise, and long leads. Ametek Solidstate Controls recommends installing a 0.22 microfarad capacitor, p/n 80-134734-90 across X202 terminals J1-11 to J1-12. This capacitor will have no effect on EMI, seismic, or aging qualifications. If you wish to acquire the 80-134734-90 capacitor, Ametek Solidstate Controls will work with you to provide spare parts. Please contact Mr. Mark Shreve of our Client Services group at 1-800-222-9079 or 1-614-846-7500 ext. 6332. mark.shreve@ametek.com Notified R1DO (Bower), R3DO (Daley) and Part 21 Group via email. |
| Where | |
|---|---|
| Ametek Solid State Controls Columbus, Ohio (NRC Region 3) | |
| Organization: | Ametek Solid State Controls |
| Reporting | |
| 10 CFR 21.21(a)(2), Interim Report for Comply or Defect in Component | |
| Time - Person (Reporting Time:+5.87 h0.245 days <br />0.0349 weeks <br />0.00804 months <br />) | |
| Opened: | Ethan Salsbury 09:52 May 8, 2017 |
| NRC Officer: | Jeff Herrera |
| Last Updated: | Jun 1, 2017 |
| 52736 - NRC Website | |
Ametek Solid State Controls with 10 CFR 21.21(a)(2), Interim Report for Comply or Defect in Component | |
WEEKMONTHYEARENS 527362017-05-08T04:00:0008 May 2017 04:00:00
[Table view]10 CFR 21.21(a)(2), Interim Report for Comply or Defect in Component Part 21 - Interim Notification of a Potential Defect on a Printed Circuit Board 2017-05-08T04:00:00 | |