ENS 52065
ENS Event | |
|---|---|
04:38 Jul 6, 2016 | |
| Title | Manual Reactor Trip and Unusual Event Declaration Due to Steam Leak in Turbine Building |
| Event Description | On July 6, 2016, at 0038 [EDT], DC Cook Unit 2 Reactor was manually tripped and at 0050 [EDT] an Unusual Event (N-7 'Unanticipated Explosion') Emergency Declaration was made due to steam leak and associated damage to the turbine building.
In accordance with Emergency Plan procedures, notifications of Berrien County and State of Michigan were completed. The licensee has notified the NRC Senior Resident Inspector. The Unusual Event was terminated at 0207 [EDT]. This notification is being made in accordance with 10 CFR 50.72 (a)(1)(i) due to declaration of an emergency class. Original notification to NRC made at 0100 EDT via ENS. This event is reportable under 10 CFR 50.72(b)(2)(iv)(B), Reactor Protection System (RPS) actuation and 10 CFR 50.72(b)(2)(xi) Offsite Notification, as a four (4) hour report, and under 10 CFR 50.72(b)(3)(iv)(A), specified system actuation of the Auxiliary Feedwater System, as an eight (8) hour report. The DC Cook NRC Resident Inspector has been notified. A press release is planned. Unit 2 is being supplied by offsite power. All control rods fully inserted. Decay heat is being removed via Steam Generator PORVs [Power Operated Relief Valve]. Preliminary evaluation indicates all plant systems functioned normally following the reactor trip. DC Cook Unit 2 remains stable in Mode 3 while conducting the Post Trip Review. No radioactive release is in progress as a result of this event. Notified DHS SWO, FEMA Ops Center, DHS NICC. Notified FEMA National Watch and Nuclear SSA via email. |
| Where | |
|---|---|
| Cook Michigan (NRC Region 3) | |
| Reporting | |
| Emergency class: | Unusual Event |
| 10 CFR 50.72(a) (1) (i), Emergency Class Declaration 10 CFR 50.72(b)(2)(iv)(B), RPS Actuation 10 CFR 50.72(b)(3)(iv)(A), System Actuation 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release | |
| Time - Person (Reporting Time:+-3.6 h-0.15 days <br />-0.0214 weeks <br />-0.00493 months <br />) | |
| Opened: | Brandy Wark 01:02 Jul 6, 2016 |
| NRC Officer: | Dong Park |
| Last Updated: | Jul 6, 2016 |
| 52065 - NRC Website
Loading map... {"minzoom":false,"maxzoom":false,"mappingservice":"leaflet","width":"350px","height":"250px","centre":false,"title":"","label":"","icon":"","lines":[],"polygons":[],"circles":[],"rectangles":[],"copycoords":false,"static":false,"zoom":6,"defzoom":14,"layers":["OpenStreetMap"],"image layers":[],"overlays":[],"resizable":false,"fullscreen":false,"scrollwheelzoom":true,"cluster":false,"clustermaxzoom":20,"clusterzoomonclick":true,"clustermaxradius":80,"clusterspiderfy":true,"geojson":"","clicktarget":"","imageLayers":[],"locations":[{"text":"\u003Cb\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003E\u003Ca class=\"mw-selflink selflink\"\u003EENS 52065\u003C/a\u003E - \u003Ca href=\"/Cook\" title=\"Cook\"\u003ECook\u003C/a\u003E\n\u003C/p\u003E\u003C/div\u003E\u003C/b\u003E\u003Cdiv class=\"mw-parser-output\"\u003E\u003Cp\u003EManual Reactor Trip and Unusual Event Declaration Due to Steam Leak in Turbine Building\n\u003C/p\u003E\u003C/div\u003E","title":"ENS 52065 - Cook\n","link":"","lat":41.97790555555556,"lon":-86.56431666666667,"icon":"/w/images/3/39/American_Electric_Power_icon.png"}],"imageoverlays":null} | |
Unit 2 | |
|---|---|
| Reactor critical | Critical |
| Scram | Yes, Manual Scram |
| Before | Power Operation (100 %) |
| After | Hot Standby (0 %) |
Cook | ||
WEEKMONTHYEARENS 574112024-11-04T04:12:0004 November 2024 04:12:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of Rapidly Terminated Unusual Event Due to Fire Alarm in Containment ENS 571952024-06-27T12:04:00027 June 2024 12:04:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Start of Turbine Driven Auxiliary Feedwater Pump ENS 571282024-05-15T08:27:00015 May 2024 08:27:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unit 2 Manual Reactor Trip ENS 562162022-11-10T12:44:00010 November 2022 12:44:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip and Auxiliary Feedwater System Actuation ENS 560762022-08-28T17:48:00028 August 2022 17:48:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Due to Reactor Coolant Pump Trip ENS 559102022-05-24T08:14:00024 May 2022 08:14:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Following Manual Turbine Trip from High Vibrations on Main Turbine ENS 556912022-01-06T15:44:0006 January 2022 15:44:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to a Fire in the Aux Cable Vault ENS 553222021-06-23T03:31:00023 June 2021 03:31:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation Manual Rx Trip Due to Steam Leak in Moisture Separator Re-Heater Crossover Pipe ENS 549442020-10-12T04:26:00012 October 2020 04:26:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation | Automatic Reactor Trip ENS 547292020-05-27T13:12:00027 May 2020 13:12:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Inadvertent Actuation of Sirens ENS 541762019-07-21T12:26:00021 July 2019 12:26:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Due Non-Essential Service Water System Degraded Condition ENS 540362019-04-30T00:29:00030 April 2019 00:29:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to a Spurious Actuation of an Emergency Siren ENS 533872018-05-07T07:36:0007 May 2018 07:36:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Rx Trip Due to High-High Level in Moisture Separator Drain Tank ENS 533342018-04-13T19:55:00013 April 2018 19:55:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Valid Emergency Diesel Generator Start During Testing ENS 529672017-09-13T04:47:00013 September 2017 04:47:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Due to Letdown Relief Valve Discharge to the Pressurizer Relief Tank ENS 526492017-03-30T07:10:00030 March 2017 07:10:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Loss of All Control Room Annunciators ENS 525852017-03-01T18:03:0001 March 2017 18:03:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Notification of Offsite Agencies Due to Sulfuric Acid Leak within the D.C. Cook Protected Area ENS 520652016-07-06T04:38:0006 July 2016 04:38:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip and Unusual Event Declaration Due to Steam Leak in Turbine Building ENS 518592016-04-08T22:20:0008 April 2016 22:20:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Oil Leak in a Switchyard Transformer Oil System ENS 510042015-04-23T06:10:00023 April 2015 06:10:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation, 10 CFR 50.72(b)(2)(i), Tech Spec Required Shutdown Manual Reactor Trip Due to a Secondary Plant Transient ENS 508222015-02-13T18:15:00013 February 2015 18:15:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification to Michigan Osha ENS 506972014-12-20T17:12:00020 December 2014 17:12:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Oil Leak from Main Turbine Lube Oil System ENS 505872014-11-01T06:48:0001 November 2014 06:48:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Dual Unit Manual Reactor Trips Due to Lowering Condenser Vacuum and Degraded Forebay ENS 504982014-09-28T12:30:00028 September 2014 12:30:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Inadvertent Activation of an Emergency Siren ENS 504622014-09-16T19:19:00016 September 2014 19:19:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notifications and Press Release Regarding Onsite Fatality ENS 503862014-08-21T06:10:00021 August 2014 06:10:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Suspected Fuel Oil Leak to the Environment ENS 501882014-06-11T03:27:00011 June 2014 03:27:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to an Inadvertent Activation of an Emergency Siren ENS 493642013-09-20T02:30:00020 September 2013 02:30:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to an Inadvertent Activation of an Emergency Siren ENS 492202013-07-28T14:18:00028 July 2013 14:18:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Following Secondary Plant Transient ENS 489642013-04-24T18:11:00024 April 2013 18:11:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Valid Actuation of an Emergency Diesel Generator Due to a Loss of Train a Reserve Feed to the Site ENS 489452013-04-19T03:12:00019 April 2013 03:12:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Inadvertent Activation of an Emergency Siren ENS 487472013-02-12T20:30:00012 February 2013 20:30:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Notification of Offsite Agencies Due to Discovery of Potential Human Remains ENS 487312013-02-07T22:35:0007 February 2013 22:35:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Related to Death of Contractor Onsite ENS 478812012-05-01T03:28:0001 May 2012 03:28:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Due to Main Turbine Trip ENS 478642012-04-26T02:46:00026 April 2012 02:46:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Notification to Offsite Agencies Due to Oil Spill ENS 474772011-11-25T10:23:00025 November 2011 10:23:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Aux Feedwater Pump Start After Main Feedwater Pump Trip ENS 472472011-09-07T12:54:0007 September 2011 12:54:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Following Main Turbine Trip from 100% Power ENS 471942011-08-23T18:24:00023 August 2011 18:24:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of an Unusual Event Due to a Seismic Event ENS 464772010-12-14T02:19:00014 December 2010 02:19:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Actuation of Auxiliary Feedwater System in Response to Loss of One Main Feedwater Pump ENS 463112010-10-06T04:08:0006 October 2010 04:08:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Valid Actuation of Auxiliary Feedwater System in Response to Valid Steam Generator Low-Low Level Signals ENS 462342010-09-08T11:47:0008 September 2010 11:47:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Body Discovered in the Owner Controlled Area ENS 460372010-06-23T18:28:00023 June 2010 18:28:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Declaration of Unusual Event Due to Seismic Event ENS 458932010-05-02T12:58:0002 May 2010 12:58:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Actuation of Auxiliary Feedwater System in Response to Loss of One Main Feedwater Pump ENS 452282009-07-26T19:06:00026 July 2009 19:06:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Due to a Reactor Coolant Pump Seal Malfunction ENS 445072008-09-21T00:18:00021 September 2008 00:18:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unit 1 Manual Reactor Trip from 100% Power Due to a Fire in the Main Turbine ENS 441472008-04-18T10:02:00018 April 2008 10:02:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Seismic Activity ENS 439562008-02-02T10:30:0002 February 2008 10:30:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Trip Due to High Turbine Vibrations ENS 436052007-08-28T17:54:00028 August 2007 17:54:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip After Digital Feedwater System Failure ENS 425312006-04-27T06:07:00027 April 2006 06:07:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Low Pressure Steam Line Pressure Safety Injection Signal Inadvertently Initiated ENS 421252005-11-08T08:58:0008 November 2005 08:58:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Reactor Trip Due to Reactor Coolant Pump Bus Undervoltage ENS 416392005-04-26T04:02:00026 April 2005 04:02:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip with Afw Actuation ENS 406602004-04-09T02:16:0009 April 2004 02:16:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip Due to a Feedwater Flow Transient ENS 406222004-03-29T19:04:00029 March 2004 19:04:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Trip During Reactor Trip Bypass Breaker Manipulation Test ENS 404192003-12-30T18:30:00030 December 2003 18:30:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Reactor Tripped from 100% Power Due to Low Steam Generator ENS 404022003-12-19T23:44:00019 December 2003 23:44:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event 2024-06-27T12:04:00 [Table view] | |