ENS 50413
From kanterella
Jump to navigation
Jump to search
ENS Event | |
|---|---|
17:27 Aug 28, 2014 | |
| Title | Auxiliary Electric Equipment Room Hvac Inoperable |
| Event Description | This report is being made pursuant to 10CFR50.72(b)(3)(v)(D), Event or Condition that could have prevented fulfillment of a Safety Function needed to Mitigate the Consequences of an Accident. While the 'B' train of Auxiliary Electric Equipment Room HVAC was inoperable and out of service for emergent repairs due to an oil leak, the 'A' train of Auxiliary Electric Equipment Room HVAC became inoperable due to a failure of the liquid line solenoid valve. The Main Control Room Envelope consists of the Main Control Room and the Auxiliary Electric Equipment Room. Both the Control Room HVAC and the Auxiliary Electric Equipment Room HVAC systems are required to be operable in the current mode.
This is a loss of safety function for a system that is intended to mitigate the consequences of an accident and is discussed in chapter 6 of the UFSAR and is Tech Spec required and is safety related. Also, the system, structure, or component (SSC) is inoperable in a required mode in the Tech Spec applicability and there is no redundant equipment in the same system that is operable. The required actions of Tech Spec 3.7.5 were entered for this event. Online Risk remains Green. The station is currently pursuing repairs to both trains. The licensee notified the NRC Resident Inspector. |
| Where | |
|---|---|
| LaSalle Illinois (NRC Region 3) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | |
| LER: | 05000373/LER-2014-004 Re Auxiliary Electric Equipment Room HVAC Inoperable Due to Compressor Trip |
| Time - Person (Reporting Time:+0.98 h0.0408 days <br />0.00583 weeks <br />0.00134 months <br />) | |
| Opened: | Jason Depriest 18:26 Aug 28, 2014 |
| NRC Officer: | Donald Norwood |
| Last Updated: | Aug 28, 2014 |
| 50413 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
Unit 2 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |