ENS 48386
ENS Event | |
|---|---|
17:03 Oct 5, 2012 | |
| Title | Rps and Pciv Actuation Due to Loss of Offsite Power |
| Event Description | On October 5, 2012, at 1303 hrs. EDT James A. FitzPatrick Nuclear Power Plant (JAF) experienced a loss of offsite power during its planned refueling outage. This resulted in the Reactor Power System (RPS) receiving a valid actuation of containment isolation valves in more than one system. All control rods were fully inserted when the full scram signal occurred. In addition, the four Emergency Diesel Generators (EDG) started in response loss of power but the EDG 'A' output breaker did not automatically close. Investigations are underway.
The following systems were automatically isolated: - Reaction Water Clean-up (RWCU) - Drywell Floor Drain - Drywell Equipment Drain The following systems were automatically actuated: - 4 Emergency Diesel Generators (EDG) All systems functioned as required except as noted above. JAF remains in Mode 5. In addition, a major loss of Emergency Response communication capability has occurred. Some of the systems not available include: Emergency Notification System (ENS), Health Physics Network (HPN), and commercial phone communication. The licensee has notified the NRC Resident Inspector.
On October 5, 2012, at 2011 hrs. EDT, James A. FitzPatrick Nuclear Power Plant (JAF) restored 345 kv backfeed qualified offsite power line and restored non-vital power. One of the two newly installed 115 kv Reserve Station Transformers experienced a lockout signal for an unknown reason which caused an isolation signal disconnecting offsite power. The Emergency Diesel Generators (EDG) started in order to provide vital power to plant systems. Both 115 kv Reserve Station Transformers have been removed from service and corrective actions are resolving this issue and the failure of the EDG 'A' output breaker to close. The EDGs are in standby. The current state of JAF is normal, Refueling Outage mode 5. In addition, Emergency Notification System (ENS), Health Physics Network (HPN), and commercial phone communication have been restored and verified functional. The Emergency Plan is functional. The NRC Resident Inspector has been informed. Notified R1DO (Trapp). |
| Where | |
|---|---|
| FitzPatrick New York (NRC Region 1) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(iv)(A), System Actuation 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness | |
| LER: | 05000333/LER-2012-005 Regarding Transformer Installation Error Causes Loss of Off-Site Power |
| Time - Person (Reporting Time:+-0.17 h-0.00708 days <br />-0.00101 weeks <br />-2.32866e-4 months <br />) | |
| Opened: | Martin Newshan 16:53 Oct 5, 2012 |
| NRC Officer: | Charles Teal |
| Last Updated: | Oct 6, 2012 |
| 48386 - NRC Website
Loading map... | |
FitzPatrick | |
WEEKMONTHYEARENS 573332024-09-23T11:20:00023 September 2024 11:20:00
[Table view]10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Scram Due to Generator Trip ENS 563732023-02-19T06:05:00019 February 2023 06:05:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Specified System Actuation ENS 563622023-02-06T11:30:0006 February 2023 11:30:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Communications and Assessment Capabilities ENS 561192022-09-26T07:06:00026 September 2022 07:06:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Scram ENS 520422016-06-24T16:15:00024 June 2016 16:15:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Reactor Scram Due to Reactor Recirculation Pumps Degradation ENS 511512015-06-12T13:24:00012 June 2015 13:24:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Tone Alert Radio System ENS 511502015-06-12T00:56:00012 June 2015 00:56:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Tone Alert Radio System ENS 497942014-02-05T15:00:0005 February 2014 15:00:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Tone Alert System Out of Service ENS 495512013-11-18T10:12:00018 November 2013 10:12:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Communications Loss to New York State Watch Tower ENS 490702013-05-26T22:39:00026 May 2013 22:39:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Tone Alert Radios Out of Service ENS 489582013-04-23T07:30:00023 April 2013 07:30:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness State Notification Line Outage ENS 489072013-04-10T15:30:00010 April 2013 15:30:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Planned Technical Support Center Outage ENS 486762013-01-16T02:12:00016 January 2013 02:12:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Loss of a 4160 Volt Bus While Performing Testing ENS 486542013-01-08T09:00:0008 January 2013 09:00:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Technical Support Center Ventilation Will Be Rendered Non-Functional for Planned Maintenance ENS 483862012-10-05T17:03:0005 October 2012 17:03:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation, 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Rps and Pciv Actuation Due to Loss of Offsite Power ENS 481562012-08-03T16:05:0003 August 2012 16:05:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Communications Capability ENS 477892012-03-30T01:05:00030 March 2012 01:05:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Tone Alert System ENS 477422012-03-14T17:05:00014 March 2012 17:05:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Tone Alert Radios Out of Service ENS 477172012-03-05T16:36:0005 March 2012 16:36:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Tone Alert Radio System ENS 475962012-01-16T08:30:00016 January 2012 08:30:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Technical Support Center Ventilation Damper Failure ENS 473322011-10-07T17:20:0007 October 2011 17:20:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Communications Systems Due to Cut Fiber Optic Cable ENS 470422011-07-11T14:22:00011 July 2011 14:22:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Temporary Loss of Erds and Spds Due to Planned Maintenance ENS 468222011-05-05T08:00:0005 May 2011 08:00:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Technical Support System Ventilation Out of Service for Planned Maintenance ENS 466292011-02-20T13:53:00020 February 2011 13:53:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Tone Alert Radio Emergency Notification System Out of Service ENS 466132011-02-14T12:00:00014 February 2011 12:00:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Technical Support Center Ventilation Out of Service for Planned Maintenance ENS 464552010-12-04T16:28:0004 December 2010 16:28:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Tone Alert Emergency Notification System Inoperable ENS 458322010-04-12T09:00:00012 April 2010 09:00:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Planned Modifications Affecting Technical Support Center Ventilation ENS 455042009-11-17T22:40:00017 November 2009 22:40:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of National Weather Service Tone Alert Radio System ENS 451562009-06-24T04:00:00024 June 2009 04:00:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Tone Alert Radios ENS 450302009-04-29T23:38:00029 April 2009 23:38:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Tone Alert Radios Out of Service ENS 445462008-10-07T10:35:0007 October 2008 10:35:00 10 CFR 50.72(b)(3)(iv)(A), System Actuation Specified System Actuation Due to Loss of Power During Testing ENS 444902008-09-15T06:44:00015 September 2008 06:44:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Emergency Notification Sirens Due to High Winds ENS 444312008-08-19T02:37:00019 August 2008 02:37:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Communication with Erds ENS 437522007-10-28T04:59:00028 October 2007 04:59:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Manual Scram Due to Lowering Intake Level ENS 437122007-10-11T05:00:00011 October 2007 05:00:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Tone Alert System Oos for Planned Maintenance ENS 436352007-09-12T10:35:00012 September 2007 10:35:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Reactor Scram Following Intake Structure Traveling Screen Fouling ENS 434532007-06-27T14:15:00027 June 2007 14:15:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Communications Capability at Eof ENS 434022007-06-04T10:55:0004 June 2007 10:55:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Tone Alert System ENS 420792005-10-26T06:33:00026 October 2005 06:33:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of the Tone Alert Prompt Notification System for Greater than One Hour ENS 419872005-09-14T06:13:00014 September 2005 06:13:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Automatic Reactor Scram on Low Reactor Vessel Water Level During Planned Maintenance ENS 416782005-05-07T07:41:0007 May 2005 07:41:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Tone Alert Notification System Out of Service ENS 414332005-02-23T14:00:00023 February 2005 14:00:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Tone Alert Radio Notification System Out of Service ENS 412612004-12-14T23:43:00014 December 2004 23:43:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Oswego County Prompt Notification System Out of Service for Greater than One Hour ENS 410922004-10-05T17:53:0005 October 2004 17:53:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Tone Alert Radio System Out of Service Greater than One Hour. ENS 402892003-11-02T23:30:0002 November 2003 23:30:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Emergency Notification Tone Alert Radios Out of Service/Restored to Service ENS 402522003-10-16T03:02:00016 October 2003 03:02:00 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Prompt Notification System (Pns) Sirens Exceeded Allowable Out of Service Time. ENS 400722003-08-14T20:26:00014 August 2003 20:26:00 10 CFR 50.72(b)(2)(iv)(B), RPS System Actuation, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration, 10 CFR 50.72(b)(3)(iv)(A), System Actuation Unusual Event Declared Due to a Loss of Offsite Power. 2024-09-23T11:20:00 | |