ENS 48134
ENS Event | |
|---|---|
21:02 Jul 25, 2012 | |
| Title | Identification of a Degraded or Unanalyzed Condition |
| Event Description | At 1602 [CDT], Engineering personnel notified the control room that during review of a pipe stress calculation it was identified that non-conservative or incorrect methodologies were used in the calculation. This calculation was for a modification to install four; 3 [inch] drain lines between the Essential Service Water (ESW) (safety) and the Service Water (SW) (non-safety) in 1991. A preliminary ME101 stress analysis performed, which corrects the above-identified discrepancies, indicates that the pipe stresses at the drain line weldolet connection exceed the ASME code of record allowable stresses by approximately 50%, when the revised Stress Intensification Factor (SIF) is applied. This modification affected both trains (A & B) ESW trains.
The normal system alignment uses the SW water to supply the ESW, then during accident conditions the SW and ESW systems isolate from each other so that two redundant separate train isolation valves isolate the ESW system. These 3 [inch] drain lines are located in the section of piping that is isolated from the ESW and SW systems. At the time of notification 'A' ESW was isolated from SW and 'B' ESW was in normal system alignment. 'B' ESW was declared inoperable and action was taken to separate the SW and ESW and isolate the 3 [inch] drain valves. With this action complete the non-conforming components have been removed from service and OPERABILITY of the ESW has been restored. This condition is been reported per 10 CFR 50.72(b)(3)(ii)(B). The NRC Resident Inspector has been notified.
Further engineering evaluation determined that the four drain lines [3-inch] between the Essential Service Water (ESW) (safety) and the Service Water (SW) (non-safety) were found to be within the allowable limits for operability and are acceptable. As a result, the condition has been determined to not be reportable per 10 CFR 50.72(b)(3)(ii)(B). The NRC Resident Inspector has been notified. Notified R4DO (Miller). |
| Where | |
|---|---|
| Wolf Creek Kansas (NRC Region 4) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition | |
| Time - Person (Reporting Time:+1.2 h0.05 days <br />0.00714 weeks <br />0.00164 months <br />) | |
| Opened: | Mark Jenkins 22:14 Jul 25, 2012 |
| NRC Officer: | Vince Klco |
| Last Updated: | Sep 19, 2012 |
| 48134 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (100 %) |
| After | Power Operation (100 %) |
WEEKMONTHYEARENS 526662017-04-05T19:00:0005 April 2017 19:00:00
[Table view]10 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor, 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition for Both Edg Transfer Line Connections ENS 506282014-11-19T21:37:00019 November 2014 21:37:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Postulated Hot Short Fire Event That Could Adversely Impact Safe Shutdown Equipment ENS 504682014-09-18T16:55:00018 September 2014 16:55:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Postulated Hot Short Fire Event That Could Adversely Impact Safe Shutdown Equipment ENS 494232013-10-09T22:30:0009 October 2013 22:30:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Postulated Hot Short Fire Event That Could Adversely Impact Safe Shutdown Equipment ENS 481342012-07-25T21:02:00025 July 2012 21:02:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Identification of a Degraded or Unanalyzed Condition ENS 474122011-11-03T21:00:0003 November 2011 21:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition for a Postulated Control Room Fire ENS 470762011-07-20T18:15:00020 July 2011 18:15:00 10 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Fire Protection Program Concern ENS 469092011-06-01T18:15:0001 June 2011 18:15:00 10 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor, 10 CFR 50.72(b)(3)(v)(B), Loss of Safety Function - Remove Residual Heat, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Both Trains of Component Cooling Water Declared Inoperable Due to Voiding ENS 464882010-12-17T21:35:00017 December 2010 21:35:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition - Potential Equipment Actuations Due to Electrical Short Circuits ENS 464282010-11-18T22:26:00018 November 2010 22:26:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Potential Post Fire Safe Shutdown Unanalyzed Condition ENS 461962010-08-21T22:00:00021 August 2010 22:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition One Train Eccs Declared Inoperable Due to Void in "a" Rhr Heat Exchanger ENS 461362010-07-28T19:22:00028 July 2010 19:22:00 10 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor, 10 CFR 50.72(b)(3)(v)(B), Loss of Safety Function - Remove Residual Heat, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Three Auxiliary Feedwater (Afw) Trains Declared Inoperable ENS 458592010-04-20T18:07:00020 April 2010 18:07:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Five Potential Issues Discovered During Post-Fire Safe Shutdown Review ENS 456922010-02-10T00:00:00010 February 2010 00:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Potential Post Fire Safe Shutdown Unanalyzed Condition ENS 452772009-08-19T20:00:00019 August 2009 20:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Time to Establish Charging Flow Exceeded Thermal Hydraulic Analysis ENS 445862008-10-21T05:00:00021 October 2008 05:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition During Design Basis Fire in Area A-27 of Auxiliary Building ENS 441722008-04-26T18:18:00026 April 2008 18:18:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Discovered Due to Improperly Installed Fuse Wiring in Class 1E Air Conditioning Unit ENS 441312008-04-10T15:15:00010 April 2008 15:15:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition "Analysis Indicates Containment Coolers May Not Have Automatically Started in Slow Speed Following Postulated Main Steam Line Break ENS 426032006-05-24T15:38:00024 May 2006 15:38:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition Discovered During Post-Fire Safe Shutdown Area Review ENS 423272006-02-10T17:00:00010 February 2006 17:00:00 10 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Potential for Loss of Safe Shutdown Capability ENS 421822005-12-02T00:30:0002 December 2005 00:30:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Unanalyzed Condition - Emergency Diesel Capability ENS 421462005-11-16T21:30:00016 November 2005 21:30:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Potential Failure to Meet Required Response Times for Shutdown Outside Control Room ENS 420292005-09-30T14:45:00030 September 2005 14:45:00 10 CFR 50.72(b)(3)(v)(A), Loss of Safety Function - Shutdown the Reactor, 10 CFR 50.72(b)(3)(v)(B), Loss of Safety Function - Remove Residual Heat, 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Potential Vulnerabilities Discovered During Design Basis Fire Review ENS 417862005-05-10T21:55:00010 May 2005 21:55:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Emergency Safety System Actuation Dampers Inoperable ENS 413272005-01-13T01:45:00013 January 2005 01:45:00 Other Unspec Reqmnt, 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition 24 Hour Condition of License Report Regarding Halon System- Actuator Connection Error ENS 413172005-01-07T23:00:0007 January 2005 23:00:00 10 CFR 50.72(b)(3)(ii)(B), Unanalyzed Condition Loss of a Fire Safe Shutdown Success Path 2017-04-05T19:00:00 | |