| Title | High Pressure Core Spray Valve Breaker Overcurrent Trip Setpoint Out of Tolerance |
| Event Description | During testing of the High Pressure Core Spray [HPCS] system minimum flow valve breaker, it was discovered that the overcurrent trip setpoint was out of tolerance. This testing was being performed as a result of a breaker trip that occurred during a surveillance. The discovery occurred while the system was inoperable for maintenance and no TS [Technical Specification] limits or action times were exceeded.
The overcurrent trip setpoint was placed within tolerance and HPCS is in operable status. The licensee notified the NRC Resident Inspector. |
| Where | |
|---|---|
| Grand Gulf Mississippi (NRC Region 4) | |
| Reporting | |
| 10 CFR 50.72(b)(3)(v)(D), Loss of Safety Function - Mitigate the Consequences of an Accident | |
| Time - Person (Reporting Time:+3.53 h0.147 days <br />0.021 weeks <br />0.00484 months <br />) | |
| Opened: | Ricky Liddell 07:08 Mar 20, 2011 |
| NRC Officer: | Vince Klco |
| Last Updated: | Mar 20, 2011 |
| 46687 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (96 %) |
| After | Power Operation (96 %) |