| Title | Unusual Event Declared Due to Small Fire Inside Protected Area |
| Event Description | Fire inside the Protected Area lasting greater than 10 minutes in an electrical conduit between the Ionic trailer and the Water Treatment Building. Power to the electrical feed through the conduit to the Ionic trailer has been secured. No offsite assistance has been requested. The licensee is verifying the status of the fire after securing the power.
The licensee notified the NRC Resident Inspector and the State and Local authorities.
Fire was declared out at 0842 CST. Fire was in the EE transformer supplying the Ionic trailer. Fire was extinguished by opening Breaker 48D. The licensee corporate office will be issuing a press release later today. The licensee notified the NRC Resident Inspector.
Licensee terminated the Unusual Event due to the fire being out and plant returned to normal operation with the exception of the Ionic trailer power. The licensee notified the NRC Resident Inspector. Notified R4DO (Clark), NRR EO (Benner), IRD Manager (McGinty), DHS (Everette) and FEMA (Liggett) |
| Where | |
|---|---|
| Cooper Nebraska (NRC Region 4) | |
| Reporting | |
| Emergency class: | Unusual Event |
| 10 CFR 50.72(a) (1) (i), Emergency Class Declaration 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release | |
| Time - Person (Reporting Time:+-4.63 h-0.193 days <br />-0.0276 weeks <br />-0.00634 months <br />) | |
| Opened: | Scott Coon 09:18 Mar 20, 2006 |
| NRC Officer: | Jeff Rotton |
| Last Updated: | Mar 20, 2006 |
| 42431 - NRC Website
Loading map... | |
Unit 1 | |
|---|---|
| Reactor critical | Critical |
| Scram | No |
| Before | Power Operation (82 %) |
| After | Power Operation (82 %) |
Cooper | |
WEEKMONTHYEARENS 567862023-10-10T20:53:00010 October 2023 20:53:00
[Table view]10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification - Spurious Alarm Actuation ENS 557032022-01-13T14:06:00013 January 2022 14:06:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Spurious Siren Actuation ENS 540992019-06-04T13:15:0004 June 2019 13:15:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Issuance of Press Release Due to Spurious Actuation of Emergency Sirens ENS 539342019-03-15T10:46:00015 March 2019 10:46:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration En Revision Imported Date 3/25/2019 ENS 538092018-12-29T06:00:00029 December 2018 06:00:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notice of Unusual Event Due to Toxic Gas and Fire ENS 534162018-05-22T14:00:00022 May 2018 14:00:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Unplanned Public Notification During a Drill ENS 530742017-11-16T02:07:00016 November 2017 02:07:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Public Prompt Notification System Capability ENS 530692017-11-14T17:18:00014 November 2017 17:18:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Hydrogen Line Leak ENS 527652017-05-19T13:05:00019 May 2017 13:05:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Nonfunctional Radio Transmission Tower Affects Tone Alert Radios ENS 522792016-10-04T20:30:0004 October 2016 20:30:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Cooper Nuclear Station Loss of Tone Alert Radios ENS 522622016-09-25T14:15:00025 September 2016 14:15:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Cooper Nuclear Station Loss of Tone Alert Radios ENS 522212016-09-03T12:10:0003 September 2016 12:10:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Seismic Event Alarm ENS 518872016-04-27T13:23:00027 April 2016 13:23:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Tone Alert Radio System Tower ENS 516172015-12-22T01:55:00022 December 2015 01:55:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(b)(3)(xiii), Loss of Emergency Preparedness Loss of Tone Alert Radio System Tower ENS 513472015-08-26T13:50:00026 August 2015 13:50:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Regarding Material Being Released and Recovered ENS 509242015-03-25T22:19:00025 March 2015 22:19:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Effluent Below National Pollutant Discharge Elimination System Ph Limits ENS 505302014-10-13T18:27:00013 October 2014 18:27:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification - Dropped Control Rod During Refueling Operations ENS 503382014-08-03T20:49:0003 August 2014 20:49:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Inadvertent Pager Notification System Message ENS 503052014-07-24T17:13:00024 July 2014 17:13:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Inadvertent Message Transmitted Via Emergency Response Siren ENS 497912014-02-04T13:38:0004 February 2014 13:38:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Due to Fatality on Site ENS 477602012-03-22T15:34:00022 March 2012 15:34:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notice of Unusual Event - Potentially Hazardous Atmosphere Due to Freon Leak ENS 469702011-06-20T00:40:00020 June 2011 00:40:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Release of Oil to the Missouri River ENS 469692011-06-19T09:02:00019 June 2011 09:02:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Missouri River Flooding ENS 469412011-06-09T14:20:0009 June 2011 14:20:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Concerning Inability to Meet Sludge Pond Discharge Permit Due to River Levels ENS 467562011-04-14T21:25:00014 April 2011 21:25:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification to Nebraska Department of Environmental Quality ENS 460332010-06-22T07:06:00022 June 2010 07:06:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration River Water Level Above 899 Feet ENS 460172010-06-16T17:33:00016 June 2010 17:33:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification to the Nebraska Department of Environmental Quality ENS 454282009-10-12T21:03:00012 October 2009 21:03:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Notification of Unusual Event Due to Small Fire Lasting Greater than 10 Minutes ENS 429852006-11-11T11:30:00011 November 2006 11:30:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to an Electrical Fire Involving Heat Trace ENS 427282006-07-25T20:41:00025 July 2006 20:41:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Fire Alarm ENS 424662006-04-02T19:04:0002 April 2006 19:04:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Adverse Weather Conditions ENS 424312006-03-20T13:56:00020 March 2006 13:56:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release, 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event Declared Due to Small Fire Inside Protected Area ENS 418282005-07-08T14:15:0008 July 2005 14:15:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification Related to Improperly Packaged Radioactive Waste Material Shipment ENS 402622003-10-20T20:26:00020 October 2003 20:26:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification to Nebraska Department of Environmental Quality ENS 402542003-10-16T17:30:00016 October 2003 17:30:00 10 CFR 50.72(a)(1)(i), Emergency Class Declaration Unusual Event at Cooper Due to Small Fire at a Turbine Bearing ENS 402142003-10-02T14:10:0002 October 2003 14:10:00 10 CFR 50.72(b)(2)(xi), Notification to Government Agency or News Release Offsite Notification to U.S. Fish and Wildlife Service and Nebraska Game and Parks Commission 2023-10-10T20:53:00 | |
Retrieved from "https://kanterella.com/w/index.php?title=ENS_42431&oldid=427479"