05000382/FIN-2014008-04
From kanterella
(Redirected from 5000382/FIN-2014008-04)
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Failure to Evaluate Operating Experience as Directed in Station Procedure |
Description | The team identified a finding for the licensees failure to evaluate industry operating experience as directed in the station operating experience program procedure. Specifically, a vendor supplied Technical Bulletin TB-13-1 Steam Generator and Pressurizer Closure Gasket Replacement Frequency, which recommended that all Westinghouse-designed steam generator and pressurizer closure gaskets be replaced at a prescribed frequency, was not evaluated in accordance with station procedures. This resulted in the licensee failing to take action to periodically replace affected gaskets to preclude degradation of the pressure boundary. The licensee documented this performance deficiency in Condition Report CR-WF3-2014-03229 to determine what further actions were needed. The failure to evaluate operating experience information as required by licensee procedure EN-OP-100, Operating Experience Program, Revision 20, was a performance deficiency. The performance deficiency is more than minor because if left uncorrected it would have the potential to lead to a more safety-significant concern. Specifically, the failure of the licensee to take any action with regard to the technical bulletin recommendation to replace the steam generator gaskets would allow the gaskets to be installed longer than their useful life. The deterioration of gasket material could result in unplanned transients or shutdowns. The finding is therefore associated with the initiating events cornerstone. Using Inspection Manual Chapter 0609, Appendix A, the inspectors determined that the finding was of very low safety significance (Green) because it was not an actual degradation that could have resulted in exceeding a reactor system leak rate for a small LOCA; could not have affected other systems used to mitigate a LOCA; did not cause a reactor trip and the loss of mitigation equipment relied upon to transition the plant to a stable shutdown condition; and did not involve a complete or partial loss of a support system that contributes to the likelihood of, or causes, an initiating event and affected mitigation equipment. This finding has a conservative bias cross-cutting aspect in the human performance area (H.14). Specifically, the licensee assumed that the technical bulletin was not based on actual failures and because steam generators had just been replaced, opted not to take further actions to evaluate or initiate any preventative maintenance to replace gaskets. |
Site: | Waterford |
---|---|
Report | IR 05000382/2014008 Section 4OA2 |
Date counted | Jun 30, 2014 (2014Q2) |
Type: | Finding: Green |
cornerstone | Initiating Events |
Identified by: | NRC identified |
Inspection Procedure: | IP 71152 |
Inspectors (proximate) | G Miller P Jayroe S Crane A Sanchez C Speer E Ruesch |
CCA | H.14, Conservative Bias |
INPO aspect | DM.2 |
' | |
Finding - Waterford - IR 05000382/2014008 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Waterford) @ 2014Q2
Self-Identified List (Waterford)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||