05000346/FIN-2014008-01
From kanterella
(Redirected from 5000346/FIN-2014008-01)
Finding | |
|---|---|
| Title | Departure from Method of Evaluation Required Prior NRC Approval Under 10 CFR 50.59 (c)(2) |
| Description | The inspectors identified a Severity Level IV NCV of Title 10, Code of Federal Regulations (CFR) Part 50.59(c)(2), and an associated finding of very-low safety significance for the licensees failure to request and obtain a license amendment pursuant to 10 CFR 50.90. Specifically, the licensees method of evaluation that accepted shield building laminar cracking represented a departure from the method of evaluation described in the Final Safety Analysis Report (as updated), and required prior NRC approval with respect to the design and licensing basis. The licensee entered this finding into its Corrective Action Program; the licensees immediate corrective action determined that shield building remained operable and capable to perform its design safety functions; the licensees planned corrective actions included revising 10 CFR 50.59 Evaluation 13-00918, and preparation of additional documents for inclusion in a license amendment request. The finding was determined to be more than minor because the finding was associated with the Barrier Integrity cornerstone attribute of Design Control, and affected the cornerstone objective to provide reasonable assurance that physical design barriers protect the public from radionuclide releases caused by accidents or events. The inspectors evaluated the finding using IMC 0609, Appendix A, The SDP for Findings At-Power. Using Exhibit 3, the inspectors determined that the finding screened as very-low safety significance because all the Reactor Containment screening questions for the Barrier Integrity Cornerstone were answered No. Specifically, the inspectors concluded that the shield building remained capable of performing its design safety functions despite the identified laminar cracking. The associated violation was categorized as Severity Level IV because the issue was determined to be of very-low safety significance under the SDP. This finding had a cross-cutting aspect in the area of Human Performance, Conservative Bias, because the licensee did not take a conservative approach to decision making for evaluation of shield building laminar cracking, particularly when information is incomplete or conditions are unusual. |
| Site: | Davis Besse |
|---|---|
| Report | IR 05000346/2014008 Section 4OA2 |
| Date counted | Jun 30, 2015 (2015Q2) |
| Type: | NCV: Green |
| cornerstone | Barrier Integrity |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71152 |
| Inspectors (proximate) | D Hills J Neurauter T Bilik |
| Violation of: | 10 CFR 50.59 10 CFR 50.90 |
| CCA | H.14, Conservative Bias |
| INPO aspect | DM.2 |
| ' | |
Finding - Davis Besse - IR 05000346/2014008 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Davis Besse) @ 2015Q2