05000528/LER-1998-004, :on 980304,safety Valves as-found Pressures Out of Tolerance.Cause of Event Is Under Investigation.Three MSSVs & Psv Will Be Replaced W/Refurbished & Recertified Valves During Refueling Outage U1R7

From kanterella
(Redirected from 05000528/LER-1998-004)
Jump to navigation Jump to search
:on 980304,safety Valves as-found Pressures Out of Tolerance.Cause of Event Is Under Investigation.Three MSSVs & Psv Will Be Replaced W/Refurbished & Recertified Valves During Refueling Outage U1R7
ML17313A325
Person / Time
Site: Palo Verde 
Issue date: 04/01/1998
From: Marks D
ARIZONA PUBLIC SERVICE CO. (FORMERLY ARIZONA NUCLEAR
To:
Shared Package
ML17313A324 List:
References
LER-98-004, LER-98-4, NUDOCS 9804100290
Download: ML17313A325 (10)


LER-1998-004, on 980304,safety Valves as-found Pressures Out of Tolerance.Cause of Event Is Under Investigation.Three MSSVs & Psv Will Be Replaced W/Refurbished & Recertified Valves During Refueling Outage U1R7
Event date:
Report date:
Reporting criterion: 10 CFR 50.73(a)(2)(vii), Common Cause Inoperability

10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications
5281998004R00 - NRC Website

text

c<

LlCENSEE EVENT REPORT (LER)

AGILITYNAME(1)

(4)

Palo Verde Unit 1 DOCKET NUMBER(2)

PAGE (3) 050005281oFO Safet Valves As-Found LiftPressures Out of Tolerance MONTH DAY REPORT DATE OTHER FACILfnES INVOLVED NUMBERS 0

3 0

4 9

8 9

8 0

0 4

0 0 0401 9

8 IS REPORT IS SUBMITTEDPURSUANT TO THE REQUIREMENTS OF 10 CFR t: (Check one or more ot the tollowinp) (1 1)

LEVEL(to) 1 P

P 2tk402(b) 20.45(aX1Xi) 20.405(aXtN 2IL45(aXt)(4r) 20.45(aXt)orr) 2(L405(aXt)(4 20.405(c)

RL36(cXI)

RL35(cX2)

RL73(aX2Qi RL73(aX2Xa) 50.73(aX2)re)

UCENSEE CONTACT FOR THIS LER (I2) 50.73(aX2)0rr)

R(73(aX2)N RL73(aX2)(rlr)

RL73(a~)(A) 5073(aX2)b4XB) 5'3(aX2)(rr) 73.71(b) 73,71(c)

X OTHER(~k Ab>>tmct below and In TerrL NRC Form 305A) Voruntary Report for PSV Dan Marks, Section Leader, Palo Verde Regulatory Affairs 802393-6492 COMPLETE ONE UNE FOR EACH COMPONENT FALURE DESCRIBED INTtaS REPORT (13)

REPORTABLE TO NPRDS MANUFAC-TURER REPORTABLE TO NPRDS SUPPLEMENTALREPORT EXPECTED (14)

X NO YES (tr Tea complete EXPECTED SUBMISSION DATE)

TRAOT(L'lto 1400 apacea Lepppncrrrlmatety rrtterm alngleeroce ew1tttan Tinea EXPECTED SUBMISSON DATE (1 5)

On March 4,

1998, Palo Verde Unit 1 was in Mode 1

(POWER OPERATION) operating at approximately 100 percent power when Control Room personnel declared Main Steam Safety Valve (MSSV)

SGE-PSV-578 inoperable because'he as-found lift pressure was found to be above the maximum allowed Technical Specification (TS) liftsetting tolerance during Trevitest activities.

The affected MSSV was satisfactorily retested and declared operable.

During subsequent MSSV

testing, SGE-PSV-579 and SGE-PSV-554 were also declared inoperable because their as-found liftpressures were found to be above the maximum allowed TS liftsetting tolerance.

The two additional MSSVs were satisfactorily

zetested, and declared operable.

Trevitest activities were completed on March 5,

1998.

On March 25, 1998, during, off-site Pressurizer Safety Valve (PSV)

testing, one PSV as-found liftpressure was found to be below. the minimum allowed TS liftsetting tolerance.

The out-of-tolerance PSV data was factored into the safety analysis that is being performed as a result of this event.

The PSV event is being voluntarily reported in this, LER.

Previous similar events

were reported in LERs 529/97-001 (a voluntary LER) and 530/97-003-01 in the past three years.

The investigation associated with this LER (528/98-004) is currently evaluating the cause of the MSSVs high out-of-tolerance liftpressure.

The preliminary safety analysis demonstrated that system was capable of performing its intended safety function with the out-of-tolerance MSSVs and PSV.

'7)8041002'7)0

'I)80401 PDR ADDCK 05000528 8

PDR

II f

LICENSEE EVENT REPORT (LER) TEXT CONTINUATION DOCKET NUMBER LER NUMBER PAGE Palo Verde Unit 1 1 ~

REPORTING REQUIREMENT:

05000528 9

8 0

0 4

0 0

0 2 of 0 5

This LER (528/98-004-00) is being submitted to report an event where a

single cause or condition may have caused at least one independent train or channel to become inoperable in multiple systems or two independent trains or channels to become inoperable in a single system designed to:

(A) Shut down the reactor and maintain it in a safe shutdown condition; (B)

Remove residual heat; (C) Control the release of radioactive material; or (D) Mitigate the consequences of an accident, as specified in 10 CFR 50.73(a) (2) (vii)

.'n addition, this LER is being submitted to report an operation or condition prohibited by the plant's Technical Specifications (TS) as specified by 10 CFR 50.73 (a)(2)(i)(B).

Because of the number of Main Steam Safety Valves (MSSV)

(RV)

(SB) found out-of-tolerance, APS has reason to believe the MSSVs became inoperable sometime prior to the time of discovery.

As such, the TS Limiting Condition for Operation (LCO) 3.7.1.1 may not have been 'met during the past operating cycle.

Specifically, on March 4,

1998, Palo Verde Unit 1 was in Mode 1

(POWER OPERATION) operating at approximately 100 percent power when Control Room personnel declared MSSV SGE-PSV-578 inoperable because the as-found lift pressure was found to be above the maximum allowed Technical Specification (TS) liftsetting tolerance during Trevitest activities.

The affected MSSV was satisfactorily retested and declared operable.

During subsequent MSSV testing, SGE-PSV-579 and SGE-PSV-554 were also declared inoperable because their as-found liftpressures were found to be above the maximum allowed TS lift setting tolerance.

The two additional MSSVs were satisfactorily retested and declared operable.

This LER 529/97-001-00 is also being submitted to report an operational event that does not meet the reporting criteria contained in 10 CFR 50.73 (i.e., voluntary report).

On March 25, 1998, during off-site Pressurizer Safety Valve (PSV)

(RV)

(AB) testing, one PSV as-found liftpressure was found to be below the minimum allowed TS lift setting tolerance.

2 ~

EVENT DESCRIPTION

On March 3,

1998, Palo Verde Unit 1 was in Mode 1

(POWER OPERATION) operating at approximately 100 percent power when APS Maintenance and Engineering personnel and Furmanite personnel began on-line testing of the Unit 1 MSSVs using the Furmanite Digital Trevitest method.

MSSVs aze required by TS Surveillance Requirement (SR) 4.7.1.1 and the ASME Code to be tested once per 5 years.

This testing has been conducted more frequently than the 5-year interval in accordance with the corrective

.Il 4k

LICENSEE EVENT REPORT (LER) TEXT CONTINUATION Palo Verde Unit 1 DOCKET NUMBER YEAR LER NUMBER PAGE 0500052898 0

0 4

0 0

0 3 of 0 5

action for previous out-of-tolerance relief settings in Palo Verde Units 1, 2, and 3.

The MSSVs aze tested in accordance with approved procedures under normal operating pressure and temperature conditions.

At approximately 1348 MST on March 4, 1998, Control Room personnel declared Steam Generator (AB) No. 1's (SG-1)

MSSV SGE-PSV-578 inoperable due to an as-found liftpressure of 0.6 percent greater than the maximum tolerance allowed by TS and entered TS 3.7.1.1 ACTION a.

The TS allowable tolerance foz MSSVs is +/- 3.0 percent.

SGE-PSV-578 was satisfactorily retested without any setpoint ad)ustments and declared operable at approximately 1419 MST on March 4, 1998.

TS 3.7.1.1 ACTION a was exited and MSSV testing continued.

At approximately 1436 MST on March 4, 1998, Control Room personnel declared SG-1's MSSV SGE-PSV-579 inoperable due to an as-found lift pressure of 3.5 percent greater than the maximum tolerance allowed by TS and entered TS 3.7.1.1 ACTION a.

SGE-PSV-579 was satisfactorily zetested without any setpoint ad)ustments and declared operable at approximately 1503 MST on March 4, 1998.

TS 3.7.1.1 ACTION a was exited and MSSV testing continued.

At approximately 0835 MST on March 5, 1998, Control Room personnel declared SG-2's MSSV SGE-PSV-554 inoperable due to an as-found lift pressure of 0.9 percent greater than the maximum tolerance allowed by TS and entered TS 3.7.1.1 ACTION a.

SGE-PSV-554 was satisfactorily retested without any setpoint ad)ustments and declared operable at approximately 0905 MST on March 5, 1998.

TS 3.7.1.1 ACTION a was exited and MSSV testing continued until approximately 1631 MST on March 5, 1998 when Trevitest activities were complete.

At approximately 0003 MST on March 14, 1998, Unit 1 shut down for its seventh refueling outage (UlR7).

On March 25, 1998, during off-site Pressurizer Safety Valve (PSV)

(RV)

(AB) testing, one PSV as-found lift pressure was found to be below the minimum allowed TS liftsetting tolerance.

Data associated with the failed PSV was forwarded to APS Nuclear Fuels personnel for use in the safety analysis being performed to assess the safety consequences of the out-of-tolerance MSSVs.

An investigation was initiated in accordance with the APS corrective action program to evaluate the cause of the MSSVs high out-of-tolerance liftpressures.

During the event, there were no safety system actuations and none were required.

.Il 41

.f

LICENSEE EVENT REPORT (LER) TEXT CONTINUATION AQUlYHAMS Palo Verde Unit 1 DOCKET NUMBER YEAR LER NUMBER PAGE 0

5 0

0 0

5 2

8 9

8 0

0 4

0 0

0 4 of 0 5

3.

ASSESSMENT OF THE SAFETY CONSEQUENCES AND IMPLICATIONS OF THIS EVENT:

A preliminary safety analysis, performed as part of the investigation/

demonstrated that the system was capab'le of performing its intended safety function with the out-of-tolerance MSSVs and PSV.

The analysis concluded that the condition would not have resulted in the secondary system peak pressure exceeding 110 percent of the design pressure limit. If the conclusions of the final safety analysis differ from preliminary safety

analysis, a supplement to this LER will be submitted.

The MSSV and PSV as-found out-of-tolerance conditions did not result in any challenges to the fission product barriers or result in any release of radioactive materials.

There were no adverse

safety consequences

or implications as a result of this event.

This event did not adversely affect the safe operation of the plant or health and safety of the public.

4.

CAUSE OF THE EVENT

An investigation of this event is being conducted in accordance with the APS Corrective Action Program to evaluate the cause of the event.

Three MSSVs had as-found liftpressures greater than the 3 percent of the maximum tolerance 'allowed by TS 3.7.1.1 and one PSV as-found liftpressure was found to be below the minimum liftsetting tolerance allowed by TS 3.4.2.2 (SALP Cause Code:

E Component Failure).

While the cause of the condition is not yet known, out-of-tolerance MSSV liftpressure phenomenon during pre-refueling outage testing is well documented in the industry..

No unusual characteristics of the work location (e.g.,

noise, heat, poor lighting) directly contributed to this event.

No personnel or procedural errors contributed to this event.

5.

STRUCTURES~

SYSTEMS, OR COMPONENTS INFORMATZON:

The MSSVs were manufactured by Dresser/Consolidated'nd are Consolidated 3700 series valves designed for nuclear service and certified under Section ZII, class 2, of the ASME Code for application in nuclear power systems.

Palo Verde's specific valves aze Maxiflow, spring-loaded, direct

acting, model No. 3707-R with 6" 1500 pound inlet,and a 10" 300 pound outlet.

The PSV was manufactured by Dresser/Consolidated and is Consolidated 31700 series valve designed for nuclear service and certified under Section ZII, Class 1, of the ASME code for application in nuclear power systems.

Palo Verde's specific PSVs are Crossed Bonnet Maxiflow, spring loaded, direct

0

LICENSEE EVENT REPORT (LER) TEXTCONTINuATION Palo Verde Unit 1 DOCKET NUMBER YEAR LER NUMBER PAGE 0

5 0

0 0

5 2

8 9

8 0

0 4

0 Q Q5of 0 5

acting, model No.

31709NA with 6" 2500 pound inlet and an B" 600 pound outlet.

There are no indications that any structures,

systems, or components were inoperable at the start of the event that contributed to this event.

No failures that rendered a train of a safety system inoperable were involved.

No failures of components with multiple functions were involved.

6.

CORRECTIVE ACTIONS TO PREVENT RECURRENCE:'n investigation of this event is being conducted in accordance with the APS Corrective Action Program to evaluate the cause of the event.

Actions to prevent recurrence developed as a result of the investigation will be implemented.

The three MSSVs and one PSV that had as-found liftpressures outside the allowable TS tolerance, will be replaced with refurbished and recertified valves during refueling outage U1R7.

7 ~

PREVIOUS SIMILAR EVENTS

Previous similar events

were reported in LERs 529/97-001 (a voluntary LER) and 530/97-003-01 that described conditions where MSSVs had as-found lift pressures.

outside the allowable TS tolerance within the past three years.

Previous corrective actions included resetting the lift setpoint on the out-of-tolerance MSSVs to +/- 1.0 percent of the TS set pressures, refurbishing the valves, and amending TS to allow for a higher as-found tolerance.

The corrective actions taken to date have not been completely effective in preventing the recurrence of out-of-tolerance MSSV conditions found during pre-outage testing.

Palo Verde continues to participate in industry-wide efforts to improve the performance of safety valves used in this application.

0

~!

I'