Finding | |
---|---|
Title | Failure to follow procedures results in repetitive malfunction of electrical auxiliary building air handling unit 21B smoke purge inlet damper |
Description | The inspectors reviewed a self-revealing noncited violation of 10 CFR Part 50, Appendix B, Criterion V, for the failure to follow procedures and enter a malfunction of the Unit 2 smoke purge damper 21B into the corrective action program. Specifically, the licensee failed to write a condition report in accordance with Procedure 0PGP03-ZX-0002, Condition Reporting Process, when the damper failed to stroke open or closed as expected. Maintenance personnel were able to close the damper; however, the licensee missed the opportunity to identify and correct a material deficiency, which resulted in another failure during subsequent testing because the condition was not entered into the corrective action program. The finding was more than minor because, if left uncorrected, it could have led to a more significant safety concern because incomplete and inaccurate corrective actions failed to ensure the damper would have actuated to the correct position when required. Using the Significance Determination Process Phase 1 worksheets from Inspection Manual Chapter 0609, the finding had very low safety significance because it was not a design or qualification deficiency, it did not result in the loss of system safety function, it did not result in the loss of safety function of a single train greater than its technical specification allowed outage time, it did not represent an actual loss of safety function of one or more nontechnical specification trains of equipment designated as risk significant for greater than 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />, and it was not risk significant due to a seismic, flooding, or severe weather initiating event. In addition, the finding had Problem Identification and Resolution crosscutting aspects associated with the corrective action program, in that, the licensee failed to accurately identify the smoke purge damper material deficiency in a timely manner because maintenance personnel did not have a low threshold for entering this issue into the corrective action program (P.1(a)(Section 1R22). |
Site: | South Texas |
---|---|
Report | IR 05000498/2010002 Section 1R22 |
Date counted | Mar 31, 2010 (2010Q1) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | Self-revealing |
Inspection Procedure: | IP 71111.22 |
Inspectors (proximate) | L Ricketson J Dixon B Tharakan C Graves D Stearns W Walker |
CCA | P.1, Identification |
INPO aspect | PI.1 |
' | |
Finding - South Texas - IR 05000498/2010002 | |||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (South Texas) @ 2010Q1
Self-Identified List (South Texas)
| |||||||||||||||||||||||||||||||||||