Finding | |
|---|---|
| Title | Inadequate Scaffold Procedure to Ensure Nearby Equipment is Not Impacted |
| Description | The inspectors identified a non-cited violation of 10 CFR Part 50, Appendix B, Criterion V, Instructions, Procedures, and Drawings, for the licensees failure to provide an adequate procedure for construction and disassembly of scaffolding. Specifically, the licensee failed to ensure that nearby systems, structures, and components were not impacted during periods while scaffolding was being constructed and disassembled in their vicinity. The licensee documented this concern in Callaway Action Request 201400646 and immediately suspended any scaffold work until the procedure could be revised to ensure operability of adjacent equipment during construction and disassembly. Failure to ensure that nearby systems, structures, and components were not impacted during periods when scaffolding is being constructed or disassembled in their vicinity was a performance deficiency. This performance deficiency affected the Mitigating Systems Cornerstone and was more than minor because, if left uncorrected, it would have the potential to lead to a more significant safety concern because future scaffolds could impact the functionality of mitigating systems. The finding was determined to be of very low safety significance since the finding did not result in identifying any specific example of a loss of functionality of mitigating systems, structures, and components. This finding does not have a cross-cutting aspect because it did not represent current performance, since this procedure had been in effect since 2005. |
| Site: | Callaway |
|---|---|
| Report | IR 05000483/2014002 Section 1R15 |
| Date counted | Mar 31, 2014 (2014Q1) |
| Type: | NCV: Green |
| cornerstone | Mitigating Systems |
| Identified by: | NRC identified |
| Inspection Procedure: | IP 71111.15 |
| Inspectors (proximate) | N O'Keefe P Elkmann T Hartman Z Hollcraft |
| Violation of: | 10 CFR 50 Appendix B Criterion V |
| INPO aspect | |
| ' | |
Finding - Callaway - IR 05000483/2014002 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Callaway) @ 2014Q1
Self-Identified List (Callaway)
| ||||||||||||||||||||||||||||||||||||||||||||||||||||||||