05000456/FIN-2015004-03
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | Failure to Establish Adequate Feedwater Pump Operational Guidance During a Normal Plant Shutdown |
Description | A finding of very low safety significance and an associated NCV of Technical Specification 5.4.1, Procedures, was self-revealed on October 5, 2015, due to the licensees failure to establish and maintain adequate guidance for operating the Unit 1 and Unit 2 motor driven main feedwater pump (MDFWP) during plant shutdown conditions. Specifically, on October 4, 2015, during a Unit 2 plant shutdown, the Unit 2 MDFWP was placed in service at low forward feedwater flow conditions and was manually tripped when the pumps main journal bearing temperature exceeded the procedural limit. Subsequent review, determined that the procedural limit was too low as previously recognized by historic station specific operating experience. This issue was entered into the licensees corrective action program (CAP) as Issue Report (IR) 2565486. The inspectors determined that the performance deficiency was more than minor because the issue was associated with the Procedural Quality attribute of the Initiating Event cornerstone and adversely affected the cornerstone objective to limit the likelihood of events that upset plant stability and challenge critical safety functions during shutdown as well as power operations. Specifically, the performance deficiency contributed to a loss of main feedwater event that upset plant stability and challenged the critical safety function of removing decay heat via the steam generators in Mode 3. For Unit 1, the increased potential for a loss of main feedwater event existed under similar conditions. The inspectors determined that the finding was of very low safety significance based upon a detailed risk evaluation. The inspectors concluded that this finding did not have a cross-cutting aspect because the performance deficiency was greater than 3 years old and, therefore, not indicative of recent performance. |
Site: | Braidwood |
---|---|
Report | IR 05000456/2015004 Section 1R20 |
Date counted | Dec 31, 2015 (2015Q4) |
Type: | NCV: Green |
cornerstone | Initiating Events |
Identified by: | NRC identified |
Inspection Procedure: | IP 71111.2 |
Inspectors (proximate) | B Bostn C Hunt D Betancourt D Mcneil D Reeser G Edwards J Benjamin J Bozga J Jandovitz M Garza T Bilik T Go |
Violation of: | Technical Specification - Procedures Technical Specification |
INPO aspect | |
' | |