| | | Reporting criterion |
|---|
| 05000455/LER-1995-001-08, :on 950120,determined That TS Surveillance Following Change of Power Level of More than 15% in 1 H Not Performed in Required Time Limit After MFW Pump Trip Due to Personnel Error.Procedure Boa SEC-1 Revised |
- on 950120,determined That TS Surveillance Following Change of Power Level of More than 15% in 1 H Not Performed in Required Time Limit After MFW Pump Trip Due to Personnel Error.Procedure Boa SEC-1 Revised
| 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications |
| 05000454/LER-1995-001, Informs That SER Issued Using LER 95-001 & Will Not Be Deemed as Ler.Lers 95-007 & 95-009 Will Not Be Used for Docket 50-454.LERs 95-003 Will Not Be Used for Docket 50-455 | Informs That SER Issued Using LER 95-001 & Will Not Be Deemed as Ler.Lers 95-007 & 95-009 Will Not Be Used for Docket 50-454.LERs 95-003 Will Not Be Used for Docket 50-455 | |
| 05000455/LER-1995-002-09, :on 950331,extraction Steam Valve Was W/O Lcoar Entry Due to Personnel Error.Shift Supervisor Has Been Counseled on Responsibilities Re Work Request Authorization |
- on 950331,extraction Steam Valve Was W/O Lcoar Entry Due to Personnel Error.Shift Supervisor Has Been Counseled on Responsibilities Re Work Request Authorization
| 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications |
| 05000454/LER-1995-002-11, :on 950818,Unit 1 Train B H Monitor Was Found Inoperable Due to Isolated Water Trap.Removed Unit 1 Train B H Monitor Line Caps |
- on 950818,Unit 1 Train B H Monitor Was Found Inoperable Due to Isolated Water Trap.Removed Unit 1 Train B H Monitor Line Caps
| 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications |
| 05000455/LER-1995-002-03, :on 950331,TS LCO Action Requirement Not Entered Prior to Valve Work.Caused by Personnel Error.Shift Supervisor Counselled & Work Request Approval Page Revised |
- on 950331,TS LCO Action Requirement Not Entered Prior to Valve Work.Caused by Personnel Error.Shift Supervisor Counselled & Work Request Approval Page Revised
| 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2) |
| 05000454/LER-1995-003-10, :on 950913,containment Leak Detector Was Inoperable.Caused by Misinterpretation of TS Requirements by Shift Control Room Engineers Involved.Wrote Daily Order to Identify Correct Interpretation of TS 3.4.6.1 |
- on 950913,containment Leak Detector Was Inoperable.Caused by Misinterpretation of TS Requirements by Shift Control Room Engineers Involved.Wrote Daily Order to Identify Correct Interpretation of TS 3.4.6.1
| 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications |
| 05000455/LER-1995-004-09, :on 950815,DG Post Maint Was Inadequate Due to Mgt Deficiency.Developed Procedure Which Verified Performance of Voltage Regulator & Governor Under Accident Transient Loading Conditions |
- on 950815,DG Post Maint Was Inadequate Due to Mgt Deficiency.Developed Procedure Which Verified Performance of Voltage Regulator & Governor Under Accident Transient Loading Conditions
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function |
| 05000454/LER-1995-004-10, :on 950928,resistance for Intercel Connection of 125 Volt Batteries Had Not Been Measured Due to Procedural Deficiency.Revised Surveillance to Include Measurement of Resistance from Connection |
- on 950928,resistance for Intercel Connection of 125 Volt Batteries Had Not Been Measured Due to Procedural Deficiency.Revised Surveillance to Include Measurement of Resistance from Connection
| 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications |
| 05000454/LER-1995-005-01, :on 951010,identified Fire Protection Discrepancies.Caused by Inadequate Evaluations During Preparation of Original Analysis.Continued Hourly Fire Watches & Installed Darmatt KM 1 Fire Barrier |
- on 951010,identified Fire Protection Discrepancies.Caused by Inadequate Evaluations During Preparation of Original Analysis.Continued Hourly Fire Watches & Installed Darmatt KM 1 Fire Barrier
| 10 CFR 50.73(a)(1), Submit an LER 10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition |
| 05000454/LER-1995-005-10, :on 951010 & 13,identified Fire Protection Rept (FPR) Discrepancies Due to Inadequate Evaluations During Preparation of Original Safe Shutdown Analysis.Criteria for Reporting Deficiencies in FPR Established |
- on 951010 & 13,identified Fire Protection Rept (FPR) Discrepancies Due to Inadequate Evaluations During Preparation of Original Safe Shutdown Analysis.Criteria for Reporting Deficiencies in FPR Established
| 10 CFR 50.73(a)(1), Submit an LER 10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition |
| 05000454/LER-1995-005, :on 951010,discovered Fire Protection Rept Discrepancies.Caused by Inadequate Evaluations During Preparation of Original Analysis.Established Hourly Fire Watches & Installed Darmatt KM1 Fire Barrier |
- on 951010,discovered Fire Protection Rept Discrepancies.Caused by Inadequate Evaluations During Preparation of Original Analysis.Established Hourly Fire Watches & Installed Darmatt KM1 Fire Barrier
| 10 CFR 50.73(a)(1), Submit an LER 10 CFR 50.73(a)(2)(ii)(B), Unanalyzed Condition 10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded |
| 05000454/LER-1995-006-10, :on 951028,surveillance Was Missed During SG Tube Insp.Caused by Cognitive Personnel Error.Counselled Cognizant Engineer on Responsibilities Re SG Work |
- on 951028,surveillance Was Missed During SG Tube Insp.Caused by Cognitive Personnel Error.Counselled Cognizant Engineer on Responsibilities Re SG Work
| 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications |
| 05000454/LER-1995-008-07, :on 951109,discovered That Inadequate Tracking of Brass Plugs for Fuel Transfer Tube Flange Prevented Proper Llrt.Plugs Will Be Physically Inventoried After Installation of Flange |
- on 951109,discovered That Inadequate Tracking of Brass Plugs for Fuel Transfer Tube Flange Prevented Proper Llrt.Plugs Will Be Physically Inventoried After Installation of Flange
| 10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded 10 CFR 50.73(a)(2) |
| 05000454/LER-1995-008-01, :on 951109,inadequate Test for Compliance with Llrt.Caused by a Procedure That Did Not Adequately Identify That Plugs Were Removed.C/A:Procedure Revision Initiated and Maint Foreman Counseled |
- on 951109,inadequate Test for Compliance with Llrt.Caused by a Procedure That Did Not Adequately Identify That Plugs Were Removed.C/A:Procedure Revision Initiated and Maint Foreman Counseled
| 10 CFR 50.73(a)(2)(v), Loss of Safety Function 10 CFR 50.73(a)(2)(ii)(A), Seriously Degraded 10 CFR 50.73(a)(2) |
| 05000454/LER-1995-010-08, :on 951113,chemistry Sample for Lcoar Was Not Done within Specified Time Limit Due to de-energized Closed Valve.Closed Circuit Breaker & Sample Was Taken |
- on 951113,chemistry Sample for Lcoar Was Not Done within Specified Time Limit Due to de-energized Closed Valve.Closed Circuit Breaker & Sample Was Taken
| 10 CFR 50.73(a)(2)(i)(B), Prohibited by Technical Specifications 10 CFR 50.73(a)(2)(x) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition 10 CFR 50.73(a)(2) |
| 05000454/LER-1995-011-05, :on 951105,discovered Increased Tube Degradation in Sgs.Caused Not Determined.Defective Tubes Will Be Removed from Svc by Plugging or Sleeving & Suppl Rept on Root Cause Will Be Submitted |
- on 951105,discovered Increased Tube Degradation in Sgs.Caused Not Determined.Defective Tubes Will Be Removed from Svc by Plugging or Sleeving & Suppl Rept on Root Cause Will Be Submitted
| 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition |
| 05000454/LER-1995-011-01, :on 951107,current Insp Results Identified Increased Tube Degradation in Sgs.Cause Unknown.Defective Tubes Removed from Svc by Plugging or Sleeving |
- on 951107,current Insp Results Identified Increased Tube Degradation in Sgs.Cause Unknown.Defective Tubes Removed from Svc by Plugging or Sleeving
| 10 CFR 50.73(a)(2)(x) 10 CFR 50.73(a)(2)(iii) 10 CFR 50.72(b)(3)(ii), Degraded or Unanalyzed Condition |