05000387/FIN-2008006-04
From kanterella
Jump to navigation
Jump to search
Finding | |
---|---|
Title | |
Description | The NRC identified a Non-Cited Violation of 10 CFR 50, Appendix B, Criterion XVI, Corrective Action, for the failure to identify that a setpoint error in the operating procedures for safety-related systems was a condition adverse to quality (CAQ), resulting in the procedures not being corrected in a timely manner. The setpoint for the low pressure injection permissive interlock in the RHR and CS systems had been changed in 1999 as part of a modification. However, the setpoint was not changed in the system operating procedures and operator aids. When this issue was identified by Susquehanna staff in 2006, the setpoint error in the procedure was not screened as a CAQ, which resulted in the procedures not being revised for 17 months after the issue was identified in an Action Report. This performance deficiency has a cross-cutting aspect in the area of Problem Identification and Resolution, Corrective Action Program, because Susquehanna did not identify that a setpoint error in operating procedures for safety-related systems was a CAQ, commensurate with its safety significance. P.1(a) The performance deficiency is more than minor because it is associated with the Procedure Quality attribute of Mitigating Systems and affects the cornerstone objective to ensure the availability, reliability, and capability of systems that respond to initiating events to prevent undesirable consequences. Specifically, the incorrect setpoint reference in the procedure impacted the reliability of operator response to the event in that it could delay operator actions or result in misoperation of equipment. The finding screened out as having very low safety significance because it was not a design deficiency, did not result in an actual loss of safety function, and did not screen as potentially risk significant due to external initiating events. (Section 4OA2.a.3 (e) |
Site: | Susquehanna |
---|---|
Report | IR 05000387/2008006 Section 4OA2 |
Date counted | Mar 31, 2008 (2008Q1) |
Type: | NCV: Green |
cornerstone | Mitigating Systems |
Identified by: | NRC identified |
Inspection Procedure: | IP 71152 |
Inspectors (proximate) | F Arner G Ottenberg R Mckinley J Bream R Fuhrmeister M Gray |
CCA | P.1, Identification |
INPO aspect | PI.1 |
' | |
Finding - Susquehanna - IR 05000387/2008006 | ||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Finding List (Susquehanna) @ 2008Q1
Self-Identified List (Susquehanna)
| ||||||||||||||||||||||||||||||||||